Cable calculation report

Schneider
Page 2/6

Information

Name:
First name:
Company:
Customer:

Project: Schneider 09/21/2023 09:53:40 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/6

Content

1 Cable schedule.......................................................................................................................... 4

2 Calculation notes ......................................................................................................................5

Project: Schneider 09/21/2023 09:53:40 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/6

1 Cable schedule
Incomer Feeder Load Load Type Insulation L Active PE/PEN Du
type conductor
3Ph 500 kW Multi-core PVC 700 m 4x150 Copper 4x150 3.633 %
Copper
3Ph 500 kW Multi-core PVC 700 m 2x150 Copper 2x150 7.265 %
Copper

NOTICE

RISK OF INACCURATE DATA RESULTS

• Make sure that you have provided all the required inputs for the
conductor sizing.
• It is recommended to refer to the cable manufacturer’s catalogue
before making the selection.

Failure to follow these instructions can result in incorrect bill of


material and loss of business.

Project: Schneider 09/21/2023 09:53:40 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 5/6

2 Calculation notes
Cable
Parameters
Length 700 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation PVC
Ambient temperature 30 °C
Load 500 kW
Sizing constraint VoltageDrop
Correction factors according to IEC 60364-5-52
Temperature factor 0.94
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Touching conductor factor 0.79
Standard table reference
User correction factor 1
Overall factor 0.7426
Selected active conductor
Cross section area 4 x 150 mm²
Core Copper
Iz under real conditions 947.5576 A
Selected PE
Cross section area 4 x 150 mm²
Core Copper

Cable
Parameters
Length 700 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits 0
Insulation PVC
Ambient temperature 30 °C
Load 500 kW
Sizing constraint Iz
Correction factors according to IEC 60364-5-52
Temperature factor 0.94
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Touching conductor factor 0.88
Standard table reference

Project: Schneider 09/21/2023 09:53:40 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 6/6

User correction factor 1


Overall factor 0.8272
Selected active conductor
Cross section area 2 x 150 mm²
Core Copper
Iz under real conditions 527.7536 A
Selected PE
Cross section area 2 x 150 mm²
Core Copper

Method of Installation and current carrying capacities according to IEC-60364-5-52.

Project: Schneider 09/21/2023 09:53:40 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.

You might also like