Value of Insulation U (W/m2K) 0.

221 Side 1 72
Length L (m) 16 Side 2 72
Width W (m) 11 Side 3 49.5
Height H (m) 4.5 Side 4 49.5
Ambient Tempreature Ta © 48 Floor 176
Required room Tempreature Tr © 26 Roof 176
Transient time tT (h) 24 Volume 792
People P 8
Rate of Heat Loss from a Person Qp (W/hr) 500
Length of Working Hours tW (hr) 8
No of Lights NL 10
Rating of Lamp RL (W) 45
Changes in air CA 5

Transient Cooling Load (KWh/d) 69.42936


People Cooling Load (KWh/d) 32
Lighting Cooling Load (KWh/d) 3.6
Infiltration Cooling Load (KWh/d) 24.2

Total Cooling Load (KWh/d) 129.22936


Factor of Safety 1.5
Total Cooling Capacity (kW) 24.230505
Total Cooling Capacity (Ton) 6.889537958