Professional Documents
Culture Documents
Generator Set Data Sheet Hsy 50 t5 Soundproof English
Generator Set Data Sheet Hsy 50 t5 Soundproof English
HS | STATIONARY RANGE
Powered by YANMAR
POWER kVA 42 50
POWER kW 33 40
230/115 · 380/220 ·
AVAILABLE VOLTAGES V 415/240
Continuous Power (COP): According to Standard ISO 8528-1:2018, this is the Himoinsa has the right to modify any feature without prior notice.
maximum power available for continuous loads for unlimited running hours a year
between the maintenance times recommended by the manufacturer under the Weights and dimensions based on standard products. Illustrations may
environmental conditions established by the same. include optional equipment.
G2 class load acceptance in accordance with ISO 8528-5:2018 Technical data described in this catalogue correspond to the available
information at the moment of printing.
HIMOINSA HEADQUARTERS: The illustrations and images are indicative and may not coincide in their
Fábrica: Ctra. Murcia - San Javier, Km. 23,6 | 30730 SAN JAVIER (Murcia) Spain entirety with the product.
Tel.+34 968 19 11 28 Fax +34 968 19 12 17 Fax +34 968 19 04 20 |
info@himoinsa.com | www.himoinsa.com Industrial design under patent.
Manufacture facilities:
SPAIN • FRANCE • INDIA • CHINA • USA • BRAZIL • ARGENTINA
Subsidiaries:
PORTUGAL | POLAND | GERMANY | UK | SINGAPORE | UAE | PANAMA |
DOMINICAN REPUBLIC | ARGENTINA | ANGOLA | SOUTH AFRICA
2023-OCT.-10 14:54
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSY-50 T5
Rated Engine Output (PRP) kW 37,7 Lube oil consumption with g/kWh 0,27
full load
Rated Engine Output (ESP) kW 45,5
Total oil capacity L 10,5
Manufacturer YANMAR
Total coolant capacity L 9
Model 4TNV98THSPU
Governor Type Mechanical
Engine Type 4-stroke diesel
Air Filter Type Dry
Injection Type Direct
Inner diameter exhaust pipe mm 45
Aspiration Type Turbocharged
Number of cylinders and 4-L
arrangement
Bore and Stroke mm 98 x 110
Displacement L 3,319
Cooling System Coolant
SAE 3 class 10W30
Lube Oil Specifications / API grade CD,CF
Compression Ratio 18,1
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSY-50 T5
SOUND PRESSURE
Sound pressure level dB(A)@7m 66 ± 2,4
Sound pressure level with attenuation system dB(A)@7m 63 ± 2,4
APPLICATION DATA
EXHAUST SYSTEM NECESSARY AMOUNT OF AIR
Exhaust Gas Flow m³/min 11,36 Cooling Air Flow m³/s 0,979
Maximum allowed back pressure mm H2o 1000 Alternator fan air flow m³/s 0,176
STARTING SYSTEM
Recommended battery Ah 92
Soundproofed version
2023-OCT.-10 14:54
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
• Steel chassis • Anti-vibration shock absorbers • Versatility to assemble a high capacity
chassis with a metallic fuel tank
• Lower power cable outlet with aluminum • Fuel tank
cover • IP Protection according to ISO
• Fuel level gauge 8528-13:2016
• Side auxiliary cable outlet with aluminum
• Manual oil extraction pump (Opcional).
cover • External emergency stop switch
• Modular tank and retention tray system. • Noise reduction kit (Opcional).
Allows easy removal and / or maintenance • Bodywork made from high quality steel
plate • Retention Tray (Opcional).
of the equipment
• Wide access to the engine compartment • High mechanical strength • Manual oil drain pump (Opcional).
because of a removable door • Epoxy polyester powder coating • Fuel transfer pump (Opcional).
• Fuel tank in retention tray
• Full access for maintenance (water, oil and
filters, no need to remove the canopy)
• Soundproofing with foam and polyurethane
film
• 4 side lifting points
HSY-50 T5
FEATURES OF THE
CONTROL UNITS
M7X CEM 7 CEA 7 CEC 7 M7X+CEC7
Voltage between phases • • • • •
Voltage between neutral and phase • • • • •
Current intensities • • • • •
Generator Readings
Frequency • • • • •
Apparent power (Kva) • • • • •
Active power (Kw) • • • • •
Reactive power (kVAr) • • • • •
Power factor • • • • •
Voltage between phases • • •
Voltage between phases and neutral • • •
Current intensities • • •
Frequency • • •
Mains Readings
Apparent power •
Active power •
Reactive power •
Power factor •
Coolant temperature • • • •
Oil pressure • • • •
Engine Readings
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSY-50 T5
Short-circuit • • • •
Asymmetry between phases • • • • •
Incorrect phase sequence • • • • •
Inverse power • • • •
Overload • • • •
Genset signal drop • • • • •
Total hour counter • • • • •
Partial hour counter • • • • •
Kilowatt meter • • • • •
Starts valid counters • • • • •
Counters
GSM/GPRS modem ⓪ ⓪ ⓪ ⓪
Remote screen ⓪ ⓪
Tele signal ⓪ (8 + 4) ⓪ (8 + 4)
J1939 ⓪ M7XJ ⓪ ⓪ ⓪ M7XJ
Alarm history • (100) • (100)
• (100)
• (100)
• (100)
External start • • • • •
Start inhibition • • • • •
Mains failure start • • •
Start under normative EJP • • • •
Pre-heating engine control • • • •
Genset contactor activation • • • • •
Mains & Genset contactor activation • • •
Fuel transfer control • • • •
Engine temperature control • • • •
Manual override • • • •
Programmable alarms • • • •
Genset start function in test mode • • • • •
Features
Programmable outputs • • • •
Multilingual • • • •
GPS Positioning ⓪ ⓪
Synchronisation
Special Functions
⓪ ⓪
Mains synchronization ⓪ ⓪
Second Zero elimination ⓪ ⓪
RAM7 ⓪ ⓪
Remote screen ⓪ ⓪
• Standard Optional
2023-OCT.-10 14:54
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com
HSY-50 T5
CONTROL
PANELS
AS5 AS7
Automatic panel Automatic control
WITHOUT transfer panel WITHOUT
switch and Transfer Switch and
WITHOUT mains WITHOUT mains
control with CEM7 control with M7X
unit. (*) AS5 as unit.
optional with CEA7
unit. Automatic panel Digital control unit
without transfer M7X
switch and WITH
mains control.
CC2 AS5 +
CC2
Himoinsa Switching
cabinet WITH display. Automatic panel
Digital control unit WITH transfer switch
CEC7 and with mains
control. The display
will be on the genset
and on the cabinet.
Digital control unit
CEM7+CEC7
AS7 + AC5
CC2
Automatic mains
Automatic control failure control panel.
panel WITH transfer Wall-mounted
switch and WITH cabinet WITH
mains control. The transfer switch and
display will be on the thermal magnetic
genset and on the protection
cabinet. (depending on
current and voltage).
Digital control unit
M7X+CEC7 Digital control unit
CEA7
Electrical system
• Electric control and power panel • Heating resistor (standard on • Battery Switch (Opcional).
with measurements devices sets with automatic control • Leakage detector (Opcional).
and control unit (according to panels)
necessity and configuration) • Optional Battery (Optima)
• Battery charger alternator with (Opcional).
• 4-pole thermal magnetic circuit ground connection
breaker
• Starter battery/ies installed
• Adjustable earth leakage (cables and bracket included)
protection
• Ground connection electrical
• Battery charger (standard on installation with connection
gensets with automatic control ready for ground spike (not
panels) supplied)
2023-OCT.-10 14:54
Ctra. Murcia - San Javier, km. 23,6 | 30730 San Javier (Murcia) SPAIN | Tel.: +34 902 19 11 28 / +34 968 19 11 28
Fax: +34 968 19 12 17 | Export Fax +34 968 19 04 20 | E-mail:info@himoinsa.com | www.himoinsa.com