Professional Documents
Culture Documents
Single Line Diagram
Single Line Diagram
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETER UNLESS
OTHERWISE NOTED.
2. ALL LEVELS ARE IN METERS UNLESS
OTHERWISE NOTED.
3. THIS SHOULD BE READ IN ACCORDANCE WITH
STRUCTURAL AND MEP DRAWINGS.
4. VERIFY ALL THE DIMENSIONS PRIOR TO
EXECUTION.
BUILDING (B+G+13+R)
KEY PLAN
SHOP DRAWING
W/P
W/P
W/P
SMDB-1F SMDB-1F SMDB-1F SPARE
71.60 KW 71.60 KW 71.60 KW 16.00 KW
W/P
4C,70 mm² Cu/XLPE/SWA/PVC+
1C,35mm² AS ECC.
W/P
4C 70mm2 XLPE/SWA/PVC
W/P
4C,10mm² Cu/XLPE/SWA/PVC+
4C,16mm² Cu/XLPE/SWA/PVC+
4C,16mm² Cu/XLPE/SWA/PVC+
4C,10mm² Cu/XLPE/SWA/PVC+
MCCB MCCB MCCB MCCB MCCB
25KA 25KA 25KA 25KA 25 kA
1C,10mm² AS ECC.
1C,16mm² AS ECC.
1C,16mm² AS ECC.
1C,10mm² AS ECC.
70 KVAR MULTI STEP AUTOMATIC
R Y B CAP. BANK
SWITCHING CAPACITOR BANK
WITH REACTIVE POWER
E-BAR
400A TP REGULATOR
FORM-2, TYPE-2
MCCB
REV DESCRIPTION DATE DRW BY CHKD
35KA
NON AUTO
BY DEWA
INCOMER
FROM DEWA
Karnafuly Electromechanical
Works L.L.C
P.O Box: 237788
KARNAFULY E-mail:karnafuly12@gmail.com
EP-201 REVISION
00
SHEET SIZE : A1
PERSPECTIVE :
NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETER UNLESS
OTHERWISE NOTED.
2. ALL LEVELS ARE IN METERS UNLESS
OTHERWISE NOTED.
3. THIS SHOULD BE READ IN ACCORDANCE WITH
STRUCTURAL AND MEP DRAWINGS.
4. VERIFY ALL THE DIMENSIONS PRIOR TO
EXECUTION.
DB-LL DB-SHOP-1 DB-SHOP-2 DB-GYM TRANSPER PUMP FIRE PUMP DISEL PUMP JOCKY PUMP SMDB-R DB-TELEPHONE DB-PH SPARE BUILDING (B+G+13+R)
28.88KW 17.00 KW 44.00 KW 17.00KW 4.50 KW 15.00 KW 1.50 KW 3..00 KW 41.95 KW 9.55 KW 16.59 KW 35.47 KW
KEY PLAN
4C,16mm² Cu/XLPE/SWA/PVC+
4C,10mm² Cu/XLPE/SWA/PVC+
4C,35mm² Cu/XLPE/SWA/PVC+
4C,10mm² Cu/XLPE/SWA/PVC+
4C,10mm² Cu/XLPE/SWA/PVC+
4C,50mm² Cu/XLPE/SWA/PVC+
4C,10mm² Cu/XLPE/SWA/PVC+
2C,10mm² Cu/XLPE/SWA/PVC+
4C,6mm² Cu/XLPE/SWA/PVC+
4C,4mm² Cu/XLPE/SWA/PVC+
4C,6mm² Cu/XLPE/SWA/PVC+
SHOP DRAWING
1C,16mm² AS ECC.
1C,10mm² AS ECC.
1C,16mm² AS ECC.
1C,10mm² AS ECC.
1C,10mm² AS ECC.
1C,25mm² AS ECC.
1C,10mm² AS ECC.
1C,10mm² AS ECC.
1C,6mm² AS ECC.
1C,4mm² AS ECC.
1C,6mm² AS ECC.
LEGEND & SYMBOL - ELECTRICAL
63A,TP 40A,TP 100A,TP 40A,TP 20A,TP 40A,TP 20A,TP 20A,TP 125A,TP 32A,TP 40A,TP 100A,TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA 25KA
W/P
W/P
W/P
W/P
160A TP 160A TP
W/P
MCCB
25 kA
4C,10mm² Cu/XLPE/SWA/PVC+
4C,16mm² Cu/XLPE/SWA/PVC+
4C,10mm² Cu/XLPE/SWA/PVC+
4C,10mm² Cu/XLPE/SWA/PVC+
4C.300 mm2 XLPE/SWA/PVC
1C.150mm2 PVC Y/G AS ECC
1C,10mm² AS ECC.
1C,16mm² AS ECC.
1C,10mm² AS ECC.
1C,10mm² AS ECC.
MDB-1
KWH METERS
CT 400/5A KWH ON NON-COMBUSTIBLE BLOCK: PLOT NO.:
WOODEN BOARD AS PER AL KARAMA
DEWA REQUIREMENT 3180133
400A TP 40A,TP 32A,TP 63A,TP 32A,TP AS-BUILT
MCCB MCCB MCCB MCCB
MCCB 25KA 25KA 25KA 25KA PROPOSED G+3 BUILDING ON
35 KA PLOT NO 3180133 (RC1_p_s/4) AT
W/P IP55 KWH
E-BAR
A SS
CABLE GLAND TO
BS 6121 (TYPICAL)
INCOMER
FROM DEWA SMDB-ROOF
4C,50mm² Cu/XLPE/SWA/PVC+
1C,25mm² AS ECC.
EP-202 REVISION
00
SHEET SIZE : A1