DERV - Equipment Schedule
DERV - Equipment Schedule
AIR ON AIR OFF DBT/WBT AIR ON DBT/WBT AIR OFF DBT(°C) DBT(°C) DBT(°C) DBT(°C) DBT(°C) DBT(°C)
(m³/s) (m³/s) (Pa) (Pa) DBT/WBT (°C) (°C) (°C) DBT/WBT (°C) /WBT(°C) /WBT(°C) /WBT(°C) /WBT(°C) KW KW /WBT(°C) /WBT(°C) KW V/PH/HZ (W) (Amps) (W) (Amps) (mm) kW (mm) NOS
DERV-01 ERV-500 (50mm) 0.500 0.500 190 200 25.0/18.7 29.9/20.3 35.0/32.0 31.1/31.1 31.1/31.1 30.3/30.3 30.3/30.3 15.0/15.0 36.58 9.37 15.0/15.0 19.1/16.6 2.5 230V / 1Ph / 50Hz 170 x 2 0.84 x 2 170 x 2 0.84 x 2 1910 x 1455 x 655 R410A Scroll SAGL 060NA x 2 4.7 x 2 803 x 803 x 913 - 2 Nos TXV 1
Note :
1. The DERV unit shall consist of Heat Recovery Heat Pipes for recovery of heat and wrap around heat pipe for enhancing the dehumidification of cooling coil.
2. The working fluid shall be refrigerant type classified as ASHRAE safety group A1. The refrigerant shall be R410a. The heat pipe circuits shall be factory charged and hermetically sealed with the calculated weight of refrigerant.
3. There shall be a multitude of loops in the height of the heat pipe and each loop shall be individually charged. Heat pipes with header assemblies containing a single circuit are not suitable as a single leak will render the entire heat pipe inoperative
4. Heat pipe performance shall be independently type tested and certified in line with the requirements of British Standards BS 5141 pt1 / European Standards EN 305 & 306 / American Standards ARI 410 for testing and rating of heat exchangers. All software used to predict the performance of heat pipes shall be based upon the results of these independent tests.
5. The Heat Pipe should have a third party independent test report conducted by a certified laboratory from USA/ Europe like BSRIA, UK or CETIAT, FRANCE.
6. The Cooling Coil shall be irradiated by UVC emitter on upstream. The lamps shall be with Anodised Auminium reflector with minimum reflectivity of 85%.
7. The condensing unit shall be matching the capacity of indoor unit.
8. The unit shall be Double Skin.
9. Cooling coil should be AHRI certified