Professional Documents
Culture Documents
Single Line Diagram - Mahagenco
Single Line Diagram - Mahagenco
Single Line Diagram - Mahagenco
LEGENDS
AND MUST NOT BE COPIED WITHOUT OUR CONSENT NOR
TWO WINDING INVERTER DUTY TRANSFORMER
MADE KNOWN TO A THIRD PARTY.
36KV VACUUM CIRCUIT BREAKER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
ISOLATOR WITH ES
SURGE ARRESTER
BAY ANNUNCIATOR
EXTENSION LA
AT GSS 198kV,10kA,CL:3 HOOTER
STATION HIGH
R,Y,B
220kV, 1600A, 0.5mH,
50kA/1 Sec.
FUSE
245kV,1200A
50kA/1 Sec. M
ISO.+ 1E/S.
PSS
METERING CT,
300/1A, CL : 0.2S,10VA
MAIN CHECK SYSTEM DESCRIPTION
METER METER
198KV, 10KA,CL:3 LA
METERING PT 220KV√3/110V√3,
CL : 0.2, 50VA
Sr.No VOLTAGE LEVEL -
220kV, 4400pF, 3 Core CVT
METERING CT,
300/1A, CL : 0.2S,10VA STANDBY METER
220kV, 1600A, 0.5mH,
50kA/1 Sec. 1 RATED VOLTAGE 33kV 220kV
METERING PT 220KV/110V√3,
CL : 0.2S :50VA
245kV, 1200A, 2 MAXIMUM VOLTAGE 36kV 245kV
50kA/1 Sec. ISO M 220kV, 4400pF, 3 Core CVT
WITHOUT E/S
245kV, 1200A,
3 FREQUENCY 50Hz 50Hz
50kA/1 Sec. ISO M
245kV CT WITHOUT E/S 4 BASIC INSULATION 170kV 1050kV
300/1-1-1-1-1A
5CORE
PS,PS,0,2S,PS,PS 5 CONTROL VOLTAGE AC SUPPLY
METERING CT, 230V 230V
300/1A, CL : 0.2S,10VA STANDBY METER
245kV,1250A, 86 6
50kA/1 Sec. SF6 CB METERING PT 220KV/110V√3,
CONTROL VOLTAGE DC SUPPLY 220V 220V
CL : 0.2S :50VA
7 MIN. CLEARANCE - BETWEEN PHASE 320mm 2100mm
MAIN BUS-I (EXTENSION) 40/50kA FOR 1 SEC. MAIN BUS-I
245kV, 1200A, M
50kA/1 Sec. ISO
560sq.mm, WITHOUT E/S 8 MIN. CLEARANCE - PHASE TO GROUND 320mm 2100mm
245kV, 1200A,
50kA/1 Sec. ISO M
WITHOUT E/S 245kV CT 9 CREEPAGE DISTANCE 25 MM / kV 25 MM / kV
300/1-1-1-1-1A
5CORE SAFETY CLEARANCE TO LOWEST
245kV, 1200A, PS,PS,0,2S,PS,PS 10 3700mm 5500mm
50kA/1 Sec. ISO M
TERMINAL TO GROUND
WITHOUT E/S
11
245kV,1250A, 86 FAULT LEVEL 25kA for 1 Sec 50kA for 1 Sec
50kA/1 Sec. SF6 CB
MAIN BUS-II (EXTENSION), 40/50kA FOR 1 SEC. MAIN BUS-II
245kV, 1200A,
12
560sq.mm, M
50kA/1 Sec. ISO
WITHOUT E/S
245kV, 1200A,
50kA/1 Sec. ISO M 27
WITHOUT E/S 198KV, 10KA,CL:3 LA 59 UNDERVOLTAGE & OVERVOLTAGE PROTECTION
94 ANTIPUMPING RELAY
TRIPCOIL 110V
CLOSECOIL DC
33kV CT: 2000/1-1-1A
CORE 1
MET.CL 0.2S, 10VA TVM SPRG CHAR
1Ø230V
CORE 2 A MOTOR AC
CL 5P20, 10VA 50 50N 60 86
51 51N FL
CORE 3
CL PS, 10VA 95 94
87T IEC 61850
R G A ON OFF TRIP R G A ON OFF TRIP R G A ON OFF TRIP R G A ON OFF TRIP R G A ON OFF TRIP R G A ON OFF TRIP
VCB BCS TNC ANN H VCB BCS TNC ANN H VCB BCS TNC ANN H VCB BCS TNC ANN H VCB BCS TNC ANN H VCB BCS TNC ANN H
36KV,630A,25kA/3s 36KV,630A,25kA/3s 36KV,630A,25kA/3s 36KV,630A,25kA/3s 36KV,630A,25kA/3s 36KV,630A,25kA/3s
33kV 33kV
CT: 50/5A CT: 50/5A
CL : 0.2S CL : 0.2S
TVM TVM
10VA 10VA
A A
33kV CT: 250/1 33kV CT: 250/1 33kV CT: 250/1 33kV CT: 250/1 33kV CT: 250/1 33kV CT: 150/1
CORE 1 CORE 1 CORE 1 CORE 1 CORE 1 CORE 1
MET.CL 0.5, 10VA MET.CL 0.5, 10VA MET.CL 0.5, 10VA MET.CL 0.5, 10VA MET.CL 0.5, 10VA MET.CL 0.5, 10VA
CORE 2
CL 5P20, 10VA 50 50N 60
51 51N FL
95
86
94
IEC 61850
CORE 2
CL 5P20, 10VA 50 50N 60
51 51N FL
95
86
94
IEC 61850
CORE 2
CL 5P20, 10VA 50 50N 60
51 51N FL
95
86
94
IEC 61850
CORE 2
CL 5P20, 10VA 50 50N 60
51 51N FL
95
86
94
IEC 61850
CORE 2
CL 5P20, 10VA 50 50N 60
51 51N FL
95
86
94
IEC 61850
CORE 2
CL 5P20, 10VA 50 50N 60
51 51N FL
95
86
94
IEC 61850
FOR TENDER PURPOSE ONLY
63T&A 49T&A 49T&A 63T&A 49T&A 49T&A 63T&A 49T&A 49T&A 63T&A 49T&A 49T&A 63T&A 49T&A 49T&A 63T&A 49T&A 49T&A
30KV LA, 10KA 30KV LA, 10KA 30KV LA, 10KA 30KV LA, 10KA 30KV LA, 10KA 30KV LA, 10KA
PRV MOG PRV MOG PRV MOG PRV MOG PRV MOG PRV MOG
12.5 MW BLOCK-1 12.5 MW BLOCK-2 12.5 MW BLOCK-3 12.5 MW BLOCK-4 12.5 MW BLOCK-5 6.25 MW BLOCK-6
AUX PANEL AUX PANEL
AT-Paras, Balapur, Akola, MH, India.