TEST REPORT

LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE2-TCP01


Project Number : Panel Name : CE2-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB01 TCP01 MSB01 (MCB01)

LVCTB1-1 -1XV1-1 PASS


-CONNECTED TO 415VAC LINE SIDE OF CB (XSB01) FOR
1 LVCTB1-2 -1XV1-2 PASS
SENSING VOLTAGE XFM01
LVCTB1-3 -1XV1-3 PASS

LVCTB1-5 -1XB1-4 PASS


2 CONNECTED TO CB MCB01 TRIP CKT (REMOTE TRIP)
LVCTB1-6 -1XB1-5 PASS

LVCTB1-7 -1XB1-1 PASS


3 CONNECTED TO CB MCB01 CLOSING CKT
LVCTB1-8 -1XB1-2 PASS

COMMON LVCTB1-9 -1XB3-8 PASS

4 CB MCB01 OPEN LVCTB1-10 -1XB3-7 PASS

MC MCB01 CLOSED LVCTB1-11 -1XB3-9 PASS

COMMON LVCTB1-12 -1XB3-13 PASS

CB MCB01 CLOSED LVCTB1-13 -1XB3-14 PASS


5
CB MCB01 IN LOCAL / MANUAL MODE LVCTB1-14 -1XB3-15 PASS

CB MCB01 TRIP / CLOSE VOLTAGE FAILURE LVCTB1-15 -1XB3-16 PASS

LVCTB1-16 -1XB3-12 PASS


6 CB MCB01 BELL ALARM
LVCTB1-17 -1XB3-11 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE2-TCP01


Project Number : Panel Name : CE2-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB02 TCP01 MSB01 (MCB02)

LVCTB2-1 -2XV2-1 PASS

1 -CONNECTED TO 415VAC LINE SIDE OF CB (GPC01-GEN01) LVCTB2-2 -2XV2-2 PASS

LVCTB2-3 -2XV2-3 PASS

LVCTB2-5 -2XB1-6 PASS


2 CONNECTED TO CB MCB02 TRIP CKT (REMOTE TRIP)
LVCTB2-6 -2XB1-7 PASS

LVCTB2-7 -2XB1-1 PASS


3 CONNECTED TO CB MCB02 CLOSING CKT
LVCTB2-8 -2XB1-2 PASS

COMMON LVCTB2-9 -2XB3-20 PASS

4 CB MCB02 OPEN LVCTB2-10 -2XB3-19 PASS

MC MCB02 CLOSED LVCTB2-11 -2XB3-21 PASS

COMMON LVCTB2-12 -2XB3-25 PASS

CB MCB02 CLOSED LVCTB2-13 -2XB3-26 PASS


5
CB MCB02 IN LOCAL / MANUAL MODE LVCTB2-14 -2XB3-29 PASS

CB MCB02 TRIP / CLOSE VOLTAGE FAILURE LVCTB2-15 -2XB3-30 PASS

LVCTB2-16 -2XB3-24 PASS


6 CB MCB02 BELL ALARM
LVCTB2-17 -2XB3-23 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE2-TCP01


Project Number : Panel Name : CE2-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT


230 VAC SUPPLY POWER FROM CUSTOMER TCP01 MSB01-PNL03
PSTB:1 -2XV2-1 PASS
1
-MSB SOURCE 230 VAC 50 HZ, 10A PSTB:2 -2XV2-2 PASS
PSTB:3 -2XV2-3 PASS
REMOTE START ENGINE AND EMERGENCY STOP TCP01 GPC-GEN 01
-CTB-1 XD200:1 PASS
REMOTE START ENGINE GENERATOR
2 -CTB-2 XD200:2 PASS
-CTB-3 X100:13 PASS
REMOTE EMERGENCY STOP GENERATOR
-CTB-4 X100:16 PASS
COMMON UPS01 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS01
-CTB-14 INPUT 1-NO PASS
COMMON UPS01 STATIC BYPASS
3 -CTB-15 INPUT 1-NO PASS
-CTB-16 INPUT 2-NC PASS
UPS01 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-17 INPUT2-NC PASS
MAINTENANCE BYPASS BREAKER - MBB01 TCP01 MBB01
4 -CTB-18 -XB1-8 PASS
CONNECTED TO CB MCB01 CLOSING CKT
-CTB-19 -XB1-9 PASS
COMMON UPS02 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS02
-CTB-20 INPUT 1-NO PASS
COMMON UPS02 STATIC BYPASS
5 -CTB-21 INPUT 1-NO PASS
-CTB-22 INPUT 2-NC PASS
UPS02 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-23 INPUT2-NC PASS
MCB01 LOCK OUT RELAY TCP01 MSB01-PNL03
6 -CTB-24 -XB1-61 PASS
MCB01 LOCK OUT RELAY
-CTB-25 -XB1-133 PASS
SYSTEM MANUAL MODE TCP01 MSB01-PNL03
7 -CTB-26 -XB1-62 PASS
SYSTEM MANUAL MODE
-CTB-27 -XB1-134 PASS
GENERATOR E STOP TCP01 MSB01-PNL03
8 -CTB-30 -XB1-63 PASS
GENERATOR E STOP
-CTB-31 -XB1-135 PASS
MCB02 LOCK OUT RELAY TCP01 MSB01-PNL03
9 -CTB-38 -XB1-64 PASS
MCB02 L;OCK OUT RELAY
-CTB-39 -XB1-136 PASS
LOAD BANK (LBB01) TCP01 LBB01
10 -CTB-46 -XB1-1 PASS
LOAD BANK DUMP SIGNAL
-CTB-47 -XB1-2 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :
Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE3-TCP01


Project Number : Panel Name : CE3-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB01 TCP01 MSB01 (MCB01)

LVCTB1-1 -1XV1-1 PASS


-CONNECTED TO 415VAC LINE SIDE OF CB (XSB01) FOR
1 LVCTB1-2 -1XV1-2 PASS
SENSING VOLTAGE XFM01
LVCTB1-3 -1XV1-3 PASS

LVCTB1-5 -1XB1-4 PASS


2 CONNECTED TO CB MCB01 TRIP CKT (REMOTE TRIP)
LVCTB1-6 -1XB1-5 PASS

LVCTB1-7 -1XB1-1 PASS


3 CONNECTED TO CB MCB01 CLOSING CKT
LVCTB1-8 -1XB1-2 PASS

COMMON LVCTB1-9 -1XB3-8 PASS

4 CB MCB01 OPEN LVCTB1-10 -1XB3-7 PASS

MC MCB01 CLOSED LVCTB1-11 -1XB3-9 PASS

COMMON LVCTB1-12 -1XB3-13 PASS

CB MCB01 CLOSED LVCTB1-13 -1XB3-14 PASS


5
CB MCB01 IN LOCAL / MANUAL MODE LVCTB1-14 -1XB3-15 PASS

CB MCB01 TRIP / CLOSE VOLTAGE FAILURE LVCTB1-15 -1XB3-16 PASS

LVCTB1-16 -1XB3-12 PASS


6 CB MCB01 BELL ALARM
LVCTB1-17 -1XB3-11 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE3-TCP01


Project Number : Panel Name : CE3-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB02 TCP01 MSB01 (MCB02)

LVCTB2-1 -2XV2-1 PASS

1 -CONNECTED TO 415VAC LINE SIDE OF CB (GPC01-GEN01) LVCTB2-2 -2XV2-2 PASS

LVCTB2-3 -2XV2-3 PASS

LVCTB2-5 -2XB1-6 PASS


2 CONNECTED TO CB MCB02 TRIP CKT (REMOTE TRIP)
LVCTB2-6 -2XB1-7 PASS

LVCTB2-7 -2XB1-1 PASS


3 CONNECTED TO CB MCB02 CLOSING CKT
LVCTB2-8 -2XB1-2 PASS

COMMON LVCTB2-9 -2XB3-20 PASS

4 CB MCB02 OPEN LVCTB2-10 -2XB3-19 PASS

MC MCB02 CLOSED LVCTB2-11 -2XB3-21 PASS

COMMON LVCTB2-12 -2XB3-25 PASS

CB MCB02 CLOSED LVCTB2-13 -2XB3-26 PASS


5
CB MCB02 IN LOCAL / MANUAL MODE LVCTB2-14 -2XB3-29 PASS

CB MCB02 TRIP / CLOSE VOLTAGE FAILURE LVCTB2-15 -2XB3-30 PASS

LVCTB2-16 -2XB3-24 PASS


6 CB MCB02 BELL ALARM
LVCTB2-17 -2XB3-23 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE3-TCP01


Project Number : Panel Name : CE3-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT


230 VAC SUPPLY POWER FROM CUSTOMER TCP01 MSB01-PNL03
PSTB:1 -2XV2-1 PASS
1
-MSB SOURCE 230 VAC 50 HZ, 10A PSTB:2 -2XV2-2 PASS
PSTB:3 -2XV2-3 PASS
REMOTE START ENGINE AND EMERGENCY STOP TCP01 GPC-GEN 01
-CTB-1 XD200:1 PASS
REMOTE START ENGINE GENERATOR
2 -CTB-2 XD200:2 PASS
-CTB-3 X100:13 PASS
REMOTE EMERGENCY STOP GENERATOR
-CTB-4 X100:16 PASS
COMMON UPS01 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS01
-CTB-14 INPUT 1-NO PASS
COMMON UPS01 STATIC BYPASS
3 -CTB-15 INPUT 1-NO PASS
-CTB-16 INPUT 2-NC PASS
UPS01 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-17 INPUT2-NC PASS
MAINTENANCE BYPASS BREAKER - MBB01 TCP01 MBB01
4 -CTB-18 -XB1-8 PASS
CONNECTED TO CB MCB01 CLOSING CKT
-CTB-19 -XB1-9 PASS
COMMON UPS02 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS02
-CTB-20 INPUT 1-NO PASS
COMMON UPS02 STATIC BYPASS
5 -CTB-21 INPUT 1-NO PASS
-CTB-22 INPUT 2-NC PASS
UPS02 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-23 INPUT2-NC PASS
MCB01 LOCK OUT RELAY TCP01 MSB01-PNL03
6 -CTB-24 -XB1-61 PASS
MCB01 LOCK OUT RELAY
-CTB-25 -XB1-133 PASS
SYSTEM MANUAL MODE TCP01 MSB01-PNL03
7 -CTB-26 -XB1-62 PASS
SYSTEM MANUAL MODE
-CTB-27 -XB1-134 PASS
GENERATOR E STOP TCP01 MSB01-PNL03
8 -CTB-30 -XB1-63 PASS
GENERATOR E STOP
-CTB-31 -XB1-135 PASS
MCB02 LOCK OUT RELAY TCP01 MSB01-PNL03
9 -CTB-38 -XB1-64 PASS
MCB02 L;OCK OUT RELAY
-CTB-39 -XB1-136 PASS
LOAD BANK (LBB01) TCP01 LBB01
10 -CTB-46 -XB1-1 PASS
LOAD BANK DUMP SIGNAL
-CTB-47 -XB1-2 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :
Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE4-TCP01


Project Number : Panel Name : CE4-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB01 TCP01 MSB01 (MCB01)

LVCTB1-1 -1XV1-1 PASS


-CONNECTED TO 415VAC LINE SIDE OF CB (XSB01) FOR
1 LVCTB1-2 -1XV1-2 PASS
SENSING VOLTAGE XFM01
LVCTB1-3 -1XV1-3 PASS

LVCTB1-5 -1XB1-4 PASS


2 CONNECTED TO CB MCB01 TRIP CKT (REMOTE TRIP)
LVCTB1-6 -1XB1-5 PASS

LVCTB1-7 -1XB1-1 PASS


3 CONNECTED TO CB MCB01 CLOSING CKT
LVCTB1-8 -1XB1-2 PASS

COMMON LVCTB1-9 -1XB3-8 PASS

4 CB MCB01 OPEN LVCTB1-10 -1XB3-7 PASS

MC MCB01 CLOSED LVCTB1-11 -1XB3-9 PASS

COMMON LVCTB1-12 -1XB3-13 PASS

CB MCB01 CLOSED LVCTB1-13 -1XB3-14 PASS


5
CB MCB01 IN LOCAL / MANUAL MODE LVCTB1-14 -1XB3-15 PASS

CB MCB01 TRIP / CLOSE VOLTAGE FAILURE LVCTB1-15 -1XB3-16 PASS

LVCTB1-16 -1XB3-12 PASS


6 CB MCB01 BELL ALARM
LVCTB1-17 -1XB3-11 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE4-TCP01


Project Number : Panel Name : CE4-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB02 TCP01 MSB01 (MCB02)

LVCTB2-1 -2XV2-1 PASS

1 -CONNECTED TO 415VAC LINE SIDE OF CB (GPC01-GEN01) LVCTB2-2 -2XV2-2 PASS

LVCTB2-3 -2XV2-3 PASS

LVCTB2-5 -2XB1-6 PASS


2 CONNECTED TO CB MCB02 TRIP CKT (REMOTE TRIP)
LVCTB2-6 -2XB1-7 PASS

LVCTB2-7 -2XB1-1 PASS


3 CONNECTED TO CB MCB02 CLOSING CKT
LVCTB2-8 -2XB1-2 PASS

COMMON LVCTB2-9 -2XB3-20 PASS

4 CB MCB02 OPEN LVCTB2-10 -2XB3-19 PASS

MC MCB02 CLOSED LVCTB2-11 -2XB3-21 PASS

COMMON LVCTB2-12 -2XB3-25 PASS

CB MCB02 CLOSED LVCTB2-13 -2XB3-26 PASS


5
CB MCB02 IN LOCAL / MANUAL MODE LVCTB2-14 -2XB3-29 PASS

CB MCB02 TRIP / CLOSE VOLTAGE FAILURE LVCTB2-15 -2XB3-30 PASS

LVCTB2-16 -2XB3-24 PASS


6 CB MCB02 BELL ALARM
LVCTB2-17 -2XB3-23 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE4-TCP01


Project Number : Panel Name : CE4-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT


230 VAC SUPPLY POWER FROM CUSTOMER TCP01 MSB01-PNL03
PSTB:1 -2XV2-1 PASS
1
-MSB SOURCE 230 VAC 50 HZ, 10A PSTB:2 -2XV2-2 PASS
PSTB:3 -2XV2-3 PASS
REMOTE START ENGINE AND EMERGENCY STOP TCP01 GPC-GEN 01
-CTB-1 XD200:1 PASS
REMOTE START ENGINE GENERATOR
2 -CTB-2 XD200:2 PASS
-CTB-3 X100:13 PASS
REMOTE EMERGENCY STOP GENERATOR
-CTB-4 X100:16 PASS
COMMON UPS01 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS01
-CTB-14 INPUT 1-NO PASS
COMMON UPS01 STATIC BYPASS
3 -CTB-15 INPUT 1-NO PASS
-CTB-16 INPUT 2-NC PASS
UPS01 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-17 INPUT2-NC PASS
MAINTENANCE BYPASS BREAKER - MBB01 TCP01 MBB01
4 -CTB-18 -XB1-8 PASS
CONNECTED TO CB MCB01 CLOSING CKT
-CTB-19 -XB1-9 PASS
COMMON UPS02 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS02
-CTB-20 INPUT 1-NO PASS
COMMON UPS02 STATIC BYPASS
5 -CTB-21 INPUT 1-NO PASS
-CTB-22 INPUT 2-NC PASS
UPS02 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-23 INPUT2-NC PASS
MCB01 LOCK OUT RELAY TCP01 MSB01-PNL03
6 -CTB-24 -XB1-61 PASS
MCB01 LOCK OUT RELAY
-CTB-25 -XB1-133 PASS
SYSTEM MANUAL MODE TCP01 MSB01-PNL03
7 -CTB-26 -XB1-62 PASS
SYSTEM MANUAL MODE
-CTB-27 -XB1-134 PASS
GENERATOR E STOP TCP01 MSB01-PNL03
8 -CTB-30 -XB1-63 PASS
GENERATOR E STOP
-CTB-31 -XB1-135 PASS
MCB02 LOCK OUT RELAY TCP01 MSB01-PNL03
9 -CTB-38 -XB1-64 PASS
MCB02 L;OCK OUT RELAY
-CTB-39 -XB1-136 PASS
LOAD BANK (LBB01) TCP01 LBB01
10 -CTB-46 -XB1-1 PASS
LOAD BANK DUMP SIGNAL
-CTB-47 -XB1-2 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :
Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE1-TCP01


Project Number : Panel Name : CE1-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB01 TCP01 MSB01 (MCB01)

LVCTB1-1 -1XV1-1 PASS


-CONNECTED TO 415VAC LINE SIDE OF CB (XSB01) FOR
1 LVCTB1-2 -1XV1-2 PASS
SENSING VOLTAGE XFM01
LVCTB1-3 -1XV1-3 PASS

LVCTB1-5 -1XB1-4 PASS


2 CONNECTED TO CB MCB01 TRIP CKT (REMOTE TRIP)
LVCTB1-6 -1XB1-5 PASS

LVCTB1-7 -1XB1-1 PASS


3 CONNECTED TO CB MCB01 CLOSING CKT
LVCTB1-8 -1XB1-2 PASS

COMMON LVCTB1-9 -1XB3-8 PASS

4 CB MCB01 OPEN LVCTB1-10 -1XB3-7 PASS

MC MCB01 CLOSED LVCTB1-11 -1XB3-9 PASS

COMMON LVCTB1-12 -1XB3-13 PASS

CB MCB01 CLOSED LVCTB1-13 -1XB3-14 PASS


5
CB MCB01 IN LOCAL / MANUAL MODE LVCTB1-14 -1XB3-15 PASS

CB MCB01 TRIP / CLOSE VOLTAGE FAILURE LVCTB1-15 -1XB3-16 PASS

LVCTB1-16 -1XB3-12 PASS


6 CB MCB01 BELL ALARM
LVCTB1-17 -1XB3-11 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE1-TCP01


Project Number : Panel Name : CE1-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB02 TCP01 MSB01 (MCB02)

LVCTB2-1 -2XV2-1 PASS

1 -CONNECTED TO 415VAC LINE SIDE OF CB (GPC01-GEN01) LVCTB2-2 -2XV2-2 PASS

LVCTB2-3 -2XV2-3 PASS

LVCTB2-5 -2XB1-6 PASS


2 CONNECTED TO CB MCB02 TRIP CKT (REMOTE TRIP)
LVCTB2-6 -2XB1-7 PASS

LVCTB2-7 -2XB1-1 PASS


3 CONNECTED TO CB MCB02 CLOSING CKT
LVCTB2-8 -2XB1-2 PASS

COMMON LVCTB2-9 -2XB3-20 PASS

4 CB MCB02 OPEN LVCTB2-10 -2XB3-19 PASS

MC MCB02 CLOSED LVCTB2-11 -2XB3-21 PASS

COMMON LVCTB2-12 -2XB3-25 PASS

CB MCB02 CLOSED LVCTB2-13 -2XB3-26 PASS


5
CB MCB02 IN LOCAL / MANUAL MODE LVCTB2-14 -2XB3-29 PASS

CB MCB02 TRIP / CLOSE VOLTAGE FAILURE LVCTB2-15 -2XB3-30 PASS

LVCTB2-16 -2XB3-24 PASS


6 CB MCB02 BELL ALARM
LVCTB2-17 -2XB3-23 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02-MICROSOFT Substation : JKT02-COLO1-CE1-TCP01


Project Number : Panel Name : CE1-TCP01
Test Object : CONTINUITY CABLE CONTROL TCP01 Location : COLO1
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT


230 VAC SUPPLY POWER FROM CUSTOMER TCP01 MSB01-PNL03
PSTB:1 -2XV2-1 PASS
1
-MSB SOURCE 230 VAC 50 HZ, 10A PSTB:2 -2XV2-2 PASS
PSTB:3 -2XV2-3 PASS
REMOTE START ENGINE AND EMERGENCY STOP TCP01 GPC-GEN 01
-CTB-1 XD200:1 PASS
REMOTE START ENGINE GENERATOR
2 -CTB-2 XD200:2 PASS
-CTB-3 X100:13 PASS
REMOTE EMERGENCY STOP GENERATOR
-CTB-4 X100:16 PASS
COMMON UPS01 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS01
-CTB-14 INPUT 1-NO PASS
COMMON UPS01 STATIC BYPASS
3 -CTB-15 INPUT 1-NO PASS
-CTB-16 INPUT 2-NC PASS
UPS01 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-17 INPUT2-NC PASS
MAINTENANCE BYPASS BREAKER - MBB01 TCP01 MBB01
4 -CTB-18 -XB1-8 PASS
CONNECTED TO CB MCB01 CLOSING CKT
-CTB-19 -XB1-9 PASS
COMMON UPS02 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS02
-CTB-20 INPUT 1-NO PASS
COMMON UPS02 STATIC BYPASS
5 -CTB-21 INPUT 1-NO PASS
-CTB-22 INPUT 2-NC PASS
UPS02 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-23 INPUT2-NC PASS
MCB01 LOCK OUT RELAY TCP01 MSB01-PNL03
6 -CTB-24 -XB1-61 PASS
MCB01 LOCK OUT RELAY
-CTB-25 -XB1-133 PASS
SYSTEM MANUAL MODE TCP01 MSB01-PNL03
7 -CTB-26 -XB1-62 PASS
SYSTEM MANUAL MODE
-CTB-27 -XB1-134 PASS
GENERATOR E STOP TCP01 MSB01-PNL03
8 -CTB-30 -XB1-63 PASS
GENERATOR E STOP
-CTB-31 -XB1-135 PASS
MCB02 LOCK OUT RELAY TCP01 MSB01-PNL03
9 -CTB-38 -XB1-64 PASS
MCB02 L;OCK OUT RELAY
-CTB-39 -XB1-136 PASS
LOAD BANK (LBB01) TCP01 LBB01
10 -CTB-46 -XB1-1 PASS
LOAD BANK DUMP SIGNAL
-CTB-47 -XB1-2 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :
Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02 Substation :


Project Number : Panel Name :
Test Object : Location :
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB01 TCP01 MSB01 (MCB01)

LVCTB1-1 -1XV1-1 PASS

1 -CONNECTED TO 415VAC LINE SIDE OF CB (XSB01) LVCTB1-2 -1XV1-2 PASS

LVCTB1-3 -1XV1-3 PASS

LVCTB1-5 -1XB1-4 PASS


CONNECTED TO CB MCB01 TRIP CKT (REMOTE TRIP) /
2
REMOTE OPEN COMMAND
LVCTB1-6 -1XB1-5 PASS

LVCTB1-7 -1XB1-1 PASS


CONNECTED TO CB MCB01 CLOSING CKT / REMOTE
3
CLOSE COMMAND
LVCTB1-8 -1XB1-2 PASS

COMMON LVCTB1-9 -1XB3-14 PASS

4 CB MCB01 OPEN / OPEN STATUS LVCTB1-10 -1XB3-13 PASS

MC MCB01 CLOSED / CLOSE STATUS LVCTB1-11 -1XB3-15 PASS

COMMON LVCTB1-12 -1XB3-19 PASS

CB MCB01 CLOSED STATUS LVCTB1-13 -1XB3-20 PASS


5
CB MCB01 IN LOCAL / MANUAL MODE STATUS LVCTB1-14 -1XB3-21 PASS

CB MCB01 TRIP / CLOSE VOLTAGE FAILURE STATUS LVCTB1-15 -1XB3-22 PASS

LVCTB1-16 -1XB3-18 PASS


6 CB MCB01 BELL ALARM
LVCTB1-17 -1XB3-17 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02 Substation :


Project Number : Panel Name :
Test Object : Location :
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT

LV CABLE CONTROL FROM TCP01 TO MSB02 TCP01 MSB01 (MCB02)

LVCTB2-1 -2XV2-1 PASS

1 -CONNECTED TO 415VAC LINE SIDE OF CB (GPC01-GEN01) LVCTB2-2 -2XV2-2 PASS

LVCTB2-3 -2XV2-3 PASS

LVCTB2-5 -2XB1-6 PASS


2 CONNECTED TO CB MCB02 TRIP CKT (REMOTE TRIP)
LVCTB2-6 -2XB1-7 PASS

LVCTB2-7 -2XB1-1 PASS


3 CONNECTED TO CB MCB02 CLOSING CKT
LVCTB2-8 -2XB1-2 PASS

COMMON LVCTB2-9 -2XB3-14 PASS

4 CB MCB02 OPEN STATUS LVCTB2-10 -2XB3-13 PASS

MC MCB02 CLOSED STATUS LVCTB2-11 -2XB3-15 PASS

COMMON LVCTB2-12 -2XB3-19 PASS

CB MCB02 CLOSED LVCTB2-13 -2XB3-20 PASS


5
CB MCB02 IN LOCAL / MANUAL MODE LVCTB2-14 -2XB3-23 PASS

CB MCB02 TRIP / CLOSE VOLTAGE FAILURE LVCTB2-15 -2XB3-24 PASS

LVCTB2-16 -2XB3-18 PASS


6 CB MCB02 BELL ALARM
LVCTB2-17 -2XB3-17 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02 Substation :


Project Number : Panel Name :
Test Object : Location :
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM TO RESULT


230 VAC SUPPLY POWER FROM CUSTOMER TCP01 MSB01-PNL03
PSTB:1 -X15-1 PASS
1
-MSB SOURCE 230 VAC 50 HZ, 10A PSTB:2 -X15-2 PASS
PSTB:3 -X15-3 PASS
REMOTE START ENGINE AND EMERGENCY STOP TCP01 GPC-GEN 01
-CTB-1 XD200:1 PASS
REMOTE START ENGINE GENERATOR
2 -CTB-2 XD200:2 PASS
-CTB-3 X100:13 PASS
REMOTE EMERGENCY STOP GENERATOR
-CTB-4 X100:16 PASS
COMMON UPS01 STATIS STATUS AND ON GENERATOR (EFFICENCY) TCP01 UPS01
-CTB-14 INPUT 1-NO PASS
COMMON UPS01 STATIC BYPASS
3 -CTB-15 INPUT 1-NO PASS
-CTB-16 INPUT 2-NC PASS
UPS01 ON GENERATOR (EFFICIENCY CHARGING)
-CTB-17 INPUT2-NC PASS
MAINTENANCE BYPASS BREAKER - MBB01 (UOP01) TCP01 MBB01 (UOP01)
4 -CTB-18 -XB1-8 PASS
CONNECTED TO CB MCB01 CLOSING CKT
-CTB-19 -XB1-9 PASS
MCB01 LOCK OUT RELAY TCP01 MSB01-PNL03
5 -CTB-24 -XB1-60 PASS
MCB01 LOCK OUT RELAY
-CTB-25 -XB1-115 PASS
SYSTEM MANUAL MODE TCP01 MSB01-PNL03
6 -CTB-26 -XB1-62 PASS
SYSTEM MANUAL MODE
-CTB-27 -XB1-117 PASS
GENERATOR E STOP TCP01 MSB01-PNL03
7 -CTB-30 -XB1-63 PASS
GENERATOR E STOP
-CTB-31 -XB1-118 PASS
MCB02 LOCK OUT RELAY TCP01 MSB01-PNL03
8 -CTB-38 -XB1-61 PASS
MCB02 L;OCK OUT RELAY
-CTB-39 -XB1-116 PASS
LOAD BANK (LBB01)_UOP01 TCP01 LBB01 (UOP01)
9 -CTB-46 -XB1-1 PASS
LOAD BANK DUMP SIGNAL
-CTB-47 -XB1-2 PASS

Remark :

PT.INDOKOMAS BP (T&C) Witness By


On Behalf of Tested By Approved By GC
SEI T&T NV5

Name :

Sign :

Date :
TEST REPORT
LV CONTROL CABLE CONTINUITY TEST for TCP01 PANEL

Customer/Client : JKT-02 Substation


Project Number : Panel Name
Test Object : Location
Rated Voltage : Date of Tested :

LV CONTROL CABLE CONTINUITY TEST

Testing Device Used :

No. DESCRIPTION FROM

LV CABLE CONTROL FROM TCP01 TO MSB01 TCP01

LVCTB1-1

1 -CONNECTED TO 415VAC LINE SIDE OF CB (XSB01) LVCTB1-2

LVCTB1-3

LVCTB1-5
2 CONNECTED TO CB MCB01 TRIP CKT (REMOTE TRIP)
LVCTB1-6

LVCTB1-7
3 CONNECTED TO CB MCB01 CLOSING CKT
LVCTB1-8

COMMON LVCTB1-9

4 CB MCB01 OPEN LVCTB1-10

MC MCB01 CLOSED LVCTB1-11

COMMON LVCTB1-12

CB MCB01 CLOSED LVCTB1-13


5
CB MCB01 IN LOCAL / MANUAL MODE LVCTB1-14

CB MCB01 TRIP / CLOSE VOLTAGE FAILURE LVCTB1-15

LVCTB1-16
6 CB MCB01 BELL ALARM
LVCTB1-17
Remark :

PT.INDOKOMAS BP (T&C) Wit


On Behalf of Tested By Approved By GC
SEI

Name :

Sign :

Date :
TCP01 PANEL

:
:
:
Tested :

TO RESULT

MSB01

-1XV1-1 PASS

-1XV1-2 PASS

-1XV1-3 PASS

-1XB1-4 PASS

-1XB1-5 PASS

-1XB1-1 PASS

-1XB1-2 PASS

-1XB3-8 PASS

-1XB3-7 PASS

-1XB3-9 PASS

-1XB3-13 PASS

-1XB3-14 PASS

-1XB3-15 PASS

-1XB3-16 PASS

-1XB3-12 PASS

-1XB3-11 PASS
Witness By