OPERATION MANUAL
HSU-09LTE18 HSU-22TFW1CN
HSU-12LTE18 HSU-09LTR18
HSU-18LTE18 HSU-24LTR18
HSU-09LTF17 HSU-12TCS2CN
HSU-12LTF17 HSU-19TCS2CN
HSU-18LTF17 HSU-12TCR2CN
HSU-24LTF17 HSU-19TCR2CN
HSU-09LTA17/18 HSU-12TCB2CN
HSU-12LTA18 HSU-19TCB2CN
HSU-18LTA18 HSU-18TCS2CN
HSU-24LTA18 HSU-18LTR18
HSU-09CTFW HSU-12LTR18
HSU-12CTFW HSU-12TFW3CN
HSU-18CTFW HSU-19TFW3CN
HSU-24CTFW HSU-12TCS3CN
HSU-09LTK17
HSU-19TCS3CN
HSU-12LTK17
HSU-12TCR3CN
HSU-18LTK17
HSU-09LFA18 HSU-19TCR3CN
HSU-12LFA18 HSU-12TCB3CN
HSU-18LFA18 HSU-19TCB3CN
HSU-24LFA18 HSU-22TFW1CN
HSU-18TCR2CN
Contents
PARTS AND FUNCTIONS 1
OPERATION 2-4
MAINTENANCE 5
CAUTIONS 6-7
TROUBLE SHOOTING 7
Please read this operation manual before using the air conditioner.
Keep this operation manual for future reference.
0010589123
Parts and Functions
Indoor Unit Remote controller
Inlet Air Purifying Filter
(inside)
1 6 6. TIMER OFF display
TIMER ON display
Inlet grille 2
7 7. TEMP display
3 8. Additional functions display
4 Operation mode QUIET SLEEP HEALTH TURBO
Outlet
Remote controller
5 8
Vertical blade 9 9. TURBO/QUIET button
Emergency
(adjust left and
Switch TURBO/QUIET 18 10. FAN button
Horizontal flap right air fl ow) 10 11. COOL button
(adjust up and down air flow 19
Don't adjust it manually)
Display board 11 12. SWING LEFT/RIGHT button
20 (Manual adjustment of some units)
12 13. FAN SPEED button
Display board SWING
21
14. HEALTH button
13
(Healthy function is not available
22
1 Remote signal receiver 14 HEALTH SLEEP for some units.)
23
(A beeping sound is generated when a signal from remote controller isreceived.) 15 TIME TIME
15. SLEEP button
16. LOCK button
ON OFF
Remote controller
21. SWING UP/DOWN button
1
Display board 2. Signal sending display 22. TIME OFF/ON button
2 3. SWING display 23.HEALTH AIR FLOW button
4. FAN SPEED display 24.CANCEL/CONFIRM button
3 Display Function: Setting and cancel to the
1 Signal receiver circulated timer and other additional functions.
3 Operation mode indicator LO MED HI AUTO
25. RESET button
2 Setting temp.display 5. LOCK display When the remote controller appears
abnormal, use a sharp pointed
article to press this button to reset
the remote.
1 2 3 4 5 Healthy function is not available for some units.
Display board
Actual inlet grille may vary from the one shown in the Note:
4 Load the battery,then put on the cover again.
manual according to the product purchased The distance between the signal transmission head and the rece-
iver hole should be within 7m without any obstacle as well.
When electronic-started type fluorescent lamp or change- over
Outdoor Unit type fluorescent lamp or wireless telephone is installed in the
room, the receiver is apt to be disturbed in receiving the signals,
so the distance to the indoor unit should be shorter.
Full display or unclear display during operation indicates the
OUTLET batteries have been used up. Please change batteries.
INLET If the remote controller can't run normally during operation, please
remove the batteries and reload several minutes later.
CONNECTING PIPING
AND ELECTRICAL WIRING
4
4 DRAIN HOSE
1
Operation
Base Operation Emergency operation and test operation
Emergency Operation:
Use this operation only when the remote controller is defective
or lost, and with function of emergency running, air conditoner
Remote controller can run automatically for a while.
TURBO/QUIET
When the emergency operation switch is pressed, the " Pi "
sound is heard once, which means the start of this operation.
11 When power switch is turning on for the first time and
emergency operation starts, the unit will run automatically in
the following modes: Pi
2
3 Room Designated Timer Fan Operation
temperature temperature mode speed mode
SWING
1. Unit start 4 o
Above 23 C 26 C
o
No AUTO COOL
2
Press ON/OFF HEALTH SLEEP
3 It is impossible to change the settings of temp. and fan speed,It
on the remote controller, is also not possible to operate in timer or dry mode.
unit starts.
TIMER TIMER
ON OFF
Test operation:
2. Select operation mode Test ope ration switch is the same as emergency switch.
Use this switch in the test operation when the room
COOL button:Cooling mode o
temperature is below 16 C, do not use it in the
FAN button: Faning mode Pi Pi
normal operation.
DRY button: Dehumidify mode
Continue to press the test operation
3.Select temp.setting switch for more than 5 seconds . After
you hear the "Pi" sound twice, release
Press / button
your finger from the switch: the cooling
Every time the button is pressed, temp.setting
operation starts with the air flow speed "Hi".
increase 1oC,if kept depressed, it will increase
rapidly Under this operation mode,the fan motor of indoor
unit will run in high speed.
Every time the button is pressed, temp.setting
decrease 1oC,if kept depressed, it will
decrease rapidly Air Flow Direction Adjustment
Select a desired temperature.
4.Fan speed selection
1.Status display of air flow
Press FAN button. For each press, fan speed Vertical flap
changes as follows: Pos.1 (Auto swing)
Remote controller: Initial state
Display
circulated Pos.2 No initial state disaplayed on remote controller, the
LOW MED HI AUTO vertical flap will be fixed on the current position
2.Left and right air flow adjustment
Air conditioner is running under displayed fan speed.
When FAN is set to AUTO, the air conditioner For each press of button, remote controller
automatically adjusts the fan speed according to room displays as follows :
temperature. remote controller:
Pos.1 Pos.2 Pos.3 Pos.4
Pos.5 Pos.6
Operation Remote Note: In some model: The remote has the button ,But the
Mode Note
Controller
AC doesn’t have the left and right air flow auto adjustment function.
In COOL mode, the AC unit will emit air in this condition, change the direction of vertical blades manually.
Cool according to the remote setting on the
COOL
Cautions:
temperature display
The unit will return to ambient temperature after
a moment ago.
In DRY mode , when room temperature becomes lower When adjusting the flap by hand,turn off the unit.
DRY than temp.setting+2 o C, unit will run intermittently at LOW
speed regardless of FAN setting.
When humidity is high,condensate water might occur
In FAN operation mode , the unit will not operate in COOL or
at air outlet if all vertical louvers are adjust to left or right.
FAN
HEAT mode but only in FAN mode, AUTO is not available in
FAN mode. And temp. setting is disabled. In FAN mode,
It is advisable not to keep horizontal flap at downward
sleep operation is not available. position for a long time in COOLor DRY mode ,
otherwise, condensate water might occur.
2
Operation
Sleep Operation Note
When TIMER ON is set, the sleeping function can’t be
Before going to bed,you can simply press the SLEEP set up. When TIMER OFF is set, the sleeping function
button and unit will operate in SLEEP mode and bring can be set up.
you a sound sleep.
TURBO/QUIET Operation
TURBO /QUIET
TURBO /QUIET
Operation Mode
When you need fast cool or fast dehumidification,you can
1. In COOL,DRY mode
choose the Turob function; when you sleep, read, you can
O
1 hours after SLEEP mode starts,temp.will become 1 C
higher than temp.setting.After another 1 hours,temp.rises
choose Quiet function
by 1OC futher.The unit will run for further 6 hours then stops
Temp. is higher than temp.setting so that room temperature
Press the TURBO /QUIET bu on, you can switch the “Turbo” and “Quiet”
won’t be too low for your sleep.
Rises 1OC
1 hr
When running in Turbo,the fan speed is the highest,
Temp.setting Unit stop
In COOL, DRY mode when running in Quiet, the fan speed is super slow
HEALTH Operation
3
Operation
Dry Operation
Press “DRY” Button, when the LCD displays , The sequence of ON or OFF does not related to the
Dry Mode is set. setting sequence. But, it related to period set.
In Dry mode, compressor will stop to operate when the room If set ON 4hr, OFF 5hr, the sequence will be
temperature is below the setting temperature. If the room ON -> OFF. Means, ON after 4hrs, OFF after 1hr.
temperature is higher than the setting temperature, the logic If set ON 7hr, OFF 3hr, the sequence will be
circuit will control the operation of compressor and indoor ON <- OFF. Means, OFF after 3hrs, ON after off 4hrs.
fan speed, in order to cause dew formation on cooling coil to
obtain the effect of dehumification. In dry mode ,it is normal
that the indoor fan speed is lower than other operation mode. BLANK
0.5h 1.5h 0.5h 1.5h
TIMER ON TIMER OFF TIMER ON-OFF TIMER OFF-ON
Fan Operation
Press “FAN” Button, when the LCD displays , Fan Mode
is set.
Health airflow Operation
In Fan mode, the Fan speed is pre-set at low speed, and
1.Press to starting
the compressor does not start.
Setting the comfort work conditions
.
In Fan mode, the LED displays 24 or 26.
2.The setting of healthy airflow function
Timer On/Off On-Off Operation Press button to select “ Healthy airflow”, the remote
Press “TIME ON” & set the duration. 2.In cooling, it is better to select the mode.
Press “CONFIRM/CANCEL”. 3.In cooling and dry, using the air conditioner for a long
Press “TIME OFF” & set the duration time under the high air humidity, condensate water
Press “CONFIRM/CANCEL”. may occur at the grille .
4
Maintenance
For Smart Use of The Air Conditioner
Setting of proper room Remote Controller Indoor Body
Do not block the air inlet
temperature or outlet
Proper
Wipe the air conditioner by using a soft and
temperature
dry cloth.For serious stains,use a neutral
Do not use water ,wipe the controller with a detergent diluted with water.Wring the water
dry cloth.Do not use glass cleaner or chemical out of the cloth before wiping.then wipe off
cloth. the detergent completely.
Replacement of Air Purifying Filter (NOTE: Air purifying filter is optional part)
NOTE:
The photocatalyst air purifying filter will be solarized in fixed
time. In normal family, it will be solarized every 6 months.
The bacteria-killing medium air purifying filter will be used
3.Attach Air Purifying Filter
Put air purifying filter appliances into the for a long time,no need for replacement. But in the period
right and left filter frames. of using them ,you should remove the dust frequently by
using vacuum cleaner or flaping them lightly,otherwise ,
its performance will be affected.
5
Cautions
WARNING
Please call Sales/Service Shop for the Installation.
Do not attempt to install the air conditioner by yourself because improper works
may cause electric shock, fire, water leakage.
WARNING
When abnormality such as burnt-small found, Use an exclusive Check proper
immediately stop the operation button and power source installation of the
contact sales shop. with a circuit drainage securely
breaker
Do not start or stop the Do not channel the air flow directly Do not try to repair or Connect the earth
operation by disconnecting at people, especially at infants or reconstruct by yourself.
the aged. cable.
the power supply cord
and so on.
earthing
PROHIBITION PROHIBITION
CAUTION
Do not use for the purpose of storage of Take fresh air occasionally especially Do not operate the switch with
food, art work, precise equipment, when gas appliance is running at the wet hand.
breeding, or cultivation. same time.
STRICT
PROHIBITION ENFORCEMENT PROHIBITION
Do not install the unit near a fireplace Check good condition of the Do not pour water onto the unit
or other heating apparatus. installation stand for cleaning
6
Trouble shooting
Before asking for service, check the following first. Cautions
Phenomenon Cause or check points The machine is adaptive in following situation
The system does not restart When unit is stopped, it won't restart 1.Applicable ambient temperature range:
immediately.
immediately until 3 minutes have For: T1 o o
elapsed to protect the system. Maximum: D.B / W.B 35 C/24 C
Indoor o o
When the electric plug is pulled out Minimum: D.B / W.B 18 C/14 C
and reinserted, the protection circuit Cooling o
will work for 3 minutes to protect the Maximum: D.B 46 C/--
air conditioner. Outdoor o
Minimum: D.B 18 C
During unit operation or at stop, Maximum: D.B
o
27 C
a swishing or gurgling noise may Indoor o
be heard.At first 2-3 minutes after
Minimum: D.B 15 C
Heating o o
unit start, this noise is more noticeable. Maximum: D.B / W.B 24 C/18 C
Noise is heard
(This noise is generated by Outdoor o o
Minimum: D.B / W.B -7 C/-8 C
refrigerant flowing in the system.)
For: T3 o o
During unit operation, a cracking Maximum: D.B / W.B 32 C/23 C
noise may be heard.This noise is Indoor o o
generated by the casing expanding Minimum: D.B / W.B 18 C/14 C
Normal Cooling
or shrinking because of o o
Performance temperature changes. Outdoor Maximum: D.B / W.B 52oC/31 C
inspection Should there be a big noise from Minimum: D.B 18 C
air flow in unit operation, air o
filter may be too dirty. Maximum: D.B 27 C
Indoor o
This is because the system Minimum: D.B 15 C
Heating o o
Smells are generated. circulates smells from the interior Maximum: D.B / W.B 24 C/18 C
air such as the smell of furniture, Outdoor Minimum: D.B / W.B -7oC/-8oC
paint, cigarettes.
Mist or steam are blown out. During COOL or DRY operation, 2. If the supply cord is damaged, it must be replaced by the
indoor unit may blow out mist. manufacturer or its service agent or a similar qualified person.
This is due to the sudden cooling
of indoor air. The type of connecting wire is H05RN-F or H07RN-F
3. If the fuse on PC board is broken please change it with a fuse
In DRY mode, when room
temperature becomeslower type T. 3.15A/250V.
o
In dry mode,fan than temp.setting+2 C,unit will If the fuse of outdoor unit on PC board is broken, please change
speed can’t be changed. run intermittently at LOW speed it with the type of T. 25A/250V.
regardless of FAN setting.
4.The distance between the indoor unit and the floor should be
Is power plug inserted? more than 2m.
Is there a power failure?
Is fuse blownout? 5.The wiring method should be in line with the local wiring standard.
Is the air filter dirty? 6. After installation, the power plug should be easily reached..
Normally it should be cleaned 7.The used batteries should be disposed of properly.
Poor cooling every 15 days.
Multiple Are there any obstacles before 8.The appliance is not intended to use by young children or infirm
check inlet and outlet? persons without supervision.
Is temperature set correctly?
Are there some doors or 9.Young children should be supervised ensure that they do not
windows left open? play with the appliance.
Is there any direct sunlight
through the window during the 10.The appliance must be installed on a strong enough support.
cooling operation?(Use curtain) 11.The wiring diagram is attached inside the machine.
Are there too much heat sources
or too many people in the room T1: Application temp. range of air conditioner18 oC~43oC.
during cooling operation?
T3: Application temp. range of air conditioner -7oC~54oC.