Professional Documents
Culture Documents
1 FF - Breathing - Apparatus
1 FF - Breathing - Apparatus
FIRE FIGHTING
FIRE SAFETY
1. Detach demand v/v from quick release coupling on medium pressure hose
3. Open cylinder v/v slowly and fully and check reading on test gauge.
4. At inlet pressure of >100 bar gauge should read between 6 - 9 bar. After one minute
it is
acceptable for pressure to rise to 9.7 bars
5. If set fails test then pressure reducer requires returning to Dragger on exchange basis
MARINE SOLUTIONS
Maritime leadership. All the way. ©2008
©2009 Teledata
Teledata Marine
Marine Solutions.
Solutions Ltd. All
All rights reser ved. 4
Breathing Apparatus Maintenance
FIRE FIGHTING
FIRE SAFETY
How to: - Remove sintered filter and replace along with O-ring - Explain required to be done on
a yearly basis.
FAULT DIAGNOSIS
• Pressure Reducer
• Demand Valve
• Face piece
MARINE SOLUTIONS
Maritime leadership. All the way. ©2008
©2009 Teledata
Teledata Marine
Marine Solutions.
Solutions Ltd. All
All rights reser ved. 5