Material Submittal Form Document Ref.

AMA-CN-FRM-0018
Policy Construction Revision 00

Material Submittal Form


General Information
1TB01005-005C17-
Contractor HASCO Submittal No.
HAH-MAT-ME-0002 C0

Contract No. 005C17 Date 04 FEB 2023


Approved Subcontractor
To the Engineer ATKINS
(as applicable)

Material Information
Material Description
Material Submittal for Life Support System – Skid 2
(One item only per Form)
As per Specification Alternative
1TB01005-005C17-HAH-XX-XX-SDW- ME-
10001
Drawing Reference BOQ Ref. No.
1TB01005-005C17-HAH-XX-XX-SDW- ME-
10002
Specification Reference 1TB01005-005C17- SPC-ME-0001 Standards, BS, DIN BIS

Manufacturer/Supplier
Company Name Advanced Aquarium Technologies Locally Manufactured
Address 14 Kerryl Street, Kunda Park Qld. Australia
Local Agent Other Details
Program Date 31 March 2023
Expected Arrival Date 31 March 2023
(Material Required on Site) (on Site)
Contractor’s

Irshad Ahmed 04 FEB 2023


Name Signature Date

Design Consultant - Comments


Comments:

Name Signature Date

Engineer’s - Comments
Comments:

Refer to the attached ATKINS comment sheet below

Hesham Gabr -SRE 07-Feb-2023


Name Signature Date

Status Code

☐ Accepted ☐ Accepted with Comments ☐ Revise and Resubmit

☐ Rejected ☐ Review not Required

Page 1 of 1
Project : 5216396 | AMAALA TB-RSMLI
Client : AMAALA
Contractor : HASCO

Atkins Comments
Date of comments : 07/02/2023
Submittal Type : Material Submittal
Workflow No. : WF-001042
Submittal Ref. No. : 1TB01005-005C17-HAH-MAT-ME-0002 C0
Subject : Material Submittal for Life Support System – Skid 2

Mechanical Comments:

1. The Material submittal is approved subject to the compliance of the below mentioned comments.
2. Contractor submitted the document as Material submittal. However, the submitted document is
only technical data copied from the Technical Specification.
3. Contractor is requested to submit the document as a Material submittal incorporating all the
sections required for a Material Submittal complying to the Project standard. (Including all
certificates such as system test certificate, ISO certification, SASO, company profile etc.)
4. Contractor shall ensure LSS, Skid-2 system comply to the required water filtration and
temperature controls to achieve the required level of functional performance complying to the
design intend as detailed in Employer’s Requirements.
5. The system shall ensure the required water extraction, treatment, re-circulation, and disposal.
6. It is Contractor’s responsibility to comply Coral farming raceway & lighting systems as per the
design intend.

Status Code: Code B – Approved with comments

Hesham Gabr -SRE


ATKINS
07-Feb-2023
ISSUE DATE: 24/01/2023 DOCUMENT TITLE: LSS SYSTEM SCHEDULE
ISSUED TO: HASCO, AMAALA DESIGN PHASE: Detail Design
REVISION NO: Rev.00

CHECKED BY: GA
APPROVED BY: JL Ch'd Remark In'
LSS ID 2
PIPE STANDARD: TBC LSS Description Indoor Coral Raceway System
ELECTRICAL STANDARD No. of Exhibits 4
Single Phase: (v) 230 Gross Volume (m3) 4.90
Three Phase: (v) 400 Net Volume (m3) 4.90
Hertz: (Hz) 60 Design Flow Rate (m3/hr) 12.00
Mins per turnover
Water Type Saltwater
Max (°C) 28
Min (°C) 26
AAT SKID UNIT AAT - SKID 2
Estimated Total Power (INC 20% BUFFER) (kW) 6.5

Filtration Loop SSLP


Piping (Pipe Size Nomination) N/A

Model (FF) FF-400


Foam Fractionator
QTY (FF) 1
(FF)
% Flow (FF) 80%
FFSP SubT D-FR (L/S) 2.76
FFSP QTY 1
Supply Pumps
FFSP FR (L/s) 3.30 CNP NST150 (1.1kW @3450rpm)
(FFSP)
Foam Fractionator FFSP TDH (m) 15.0
FFSP Est (kW) 1.10
FFVP SubT D-FR (L/S) 0.50 Duty added to FFSP duty
FFVP QTY 0
Venturi Pumps
FFVP FR (L/s) 0.00
(FFVP)
FFVP TDH (m) 0.0
FFVP Est (kW) -

Model (BF-S) T2-100µm-PE/PP


QTY (BF-S)
Bag Filter
Model(BF-H)
(BF)
QTY (BF-H)
% Flow (BF) 100%
Sand Filter / Bag
SFSP SubT D-FR (L/S) -
Filter
BFSP SubT D-FR (L/S) 3.33
Supply Pumps S{B}FSP QTY 1
(S{B}FSP) S{B}FSP FR (L/s) 3.33 CNP NST150 (1.1kW @2850rpm)
S{B}FSP TDH (m) 12.0
S{B}FSP Est (kW) 1.10

Model (UV) AAT-LPUV-PVC-160- PLC SKID


Ultraviolet Steriliser QTY (UV) 1
Primary UV Est (kW) 0.16
Equipment Model (HP/HEX) ENV-HP-85HC [8.5 kW]
Heat
QTY (HP/HEX) 1
Pump/Exchanger
HP Est (kW) 2.88

Bio-Media Q (l/s) 2.67


% Flow (Bio/Degas) 80%
Bio-Media Bio-media Type Salt Water - BBall
Model (Bio-Media) ENV-BBall-300 (stand-alone)
Bio-media (m3) 0

AUX1 QTY 4
Auxiliary Pumps 1 AUX1 FR (L/s) 2.5 PANTA RHEI HYDRO WIZARD ECM42 (0.033kW, 100-240 V~, 50/60Hz)
Auxiliary Pumps
(AUX1) AUX1 TDH (m) 0.6
AUX1 Est (kW) 0.04

TS Opt' YES
Temp Sensor
Model (TS) SIN-P202
ORP ORP Opt' NO
PS Opt' NO
Pressure Sensor
Pump PS QTY -
FM Opt' NO
Flow Meter
FM QTY -
Secondary
FS Opt' YES
Equipment Flow Switch
FS QTY 2
pH Probe pH Opt' YES
Ultrasonic Level ULS Opt' YES
Sensor ULS QTY 1
FLS Opt' YES
Float Level Switch
FLS QTY 2
Ozone Gas Detection O3D Opt' NO

966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx


O:\966-002-KSA AMAALA-MLOF\Working\002-Design&Drawing\000-Design Book\966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx
Page 2 of 4 LSS System Schedule
ISSUE DATE: 24/01/2023 DOCUMENT TITLE: LSS SYSTEM SCHEDULE
ISSUED TO: HASCO, AMAALA DESIGN PHASE: Detail Design
REVISION NO: Rev.00

CHECKED BY: GA
APPROVED BY: JL Ch'd Remark In'
LSS ID 3
PIPE STANDARD: TBC LSS Description Animal Rescue System - Indoor
ELECTRICAL STANDARD No. of Exhibits 3
Single Phase: (v) 230 Gross Volume (m3) 4.16
Three Phase: (v) 400 Net Volume (m3) 4.16
Hertz: (Hz) 60 Design Flow Rate (m3/hr) 17.10
Mins per turnover
Water Type Saltwater
Max (°C) 28
Min (°C) 26
AAT SKID UNIT AAT - SKID 3
Estimated Total Power (INC 20% BUFFER) (kW) 8.1

Filtration Loop SSLP


Piping (Pipe Size Nomination) N/A

Model (FF) FF-400


Foam Fractionator
QTY (FF) 2
(FF)
% Flow (FF) 110%
FFSP SubT D-FR (L/S) 5.53
FFSP QTY 1
Supply Pumps
FFSP FR (L/s) 6.50 CNP NST300 (2.2kW @ 3450rpm)
(FFSP)
Foam Fractionator FFSP TDH (m) 15.0
FFSP Est (kW) 2.20
FFVP SubT D-FR (L/S) 1.00 Duty added to FFSP duty
FFVP QTY 0
Venturi Pumps
FFVP FR (L/s) 0.00
(FFVP)
FFVP TDH (m) 0.0
FFVP Est (kW) -

Model (BF-S) T2-100µm-PE/PP


QTY (BF-S)
Bag Filter
Model(BF-H)
(BF)
QTY (BF-H)
% Flow (BF) 100%
Sand Filter / Bag
SFSP SubT D-FR (L/S) -
Filter
BFSP SubT D-FR (L/S) 4.75
Supply Pumps S{B}FSP QTY 1
(S{B}FSP) S{B}FSP FR (L/s) 4.75 CNP NST200 (1.5kW @ 2900/3450)
S{B}FSP TDH (m) 12.0
S{B}FSP Est (kW) 1.50

Model (UV) AAT-LPUV-PVC-160- PLC SKID


Ultraviolet Steriliser QTY (UV) 1
Primary UV Est (kW) 0.16
Equipment Model (HP/HEX) ENV-HP-85HC [8.5 kW]
Heat
QTY (HP/HEX) 1
Pump/Exchanger
HP Est (kW) 2.88

Bio-Media Q (l/s) 5.23


% Flow (Bio/Degas) 110%
Bio-Media Bio-media Type Salt Water - BBall
Model (Bio-Media) ENV-BBall-300 (stand-alone)
Bio-media (m3) 0

AUX1 QTY 0.00


Auxiliary Pumps 1 AUX1 FR (L/s) 0.0
Auxiliary Pumps
(AUX1) AUX1 TDH (m) 0.0
AUX1 Est (kW) -

TS Opt' YES
Temp Sensor
Model (TS) SIN-P202
ORP ORP Opt' NO
PS Opt' NO
Pressure Sensor
Pump PS QTY -
FM Opt' NO
Flow Meter
FM QTY -
Secondary
FS Opt' YES
Equipment Flow Switch
FS QTY 2
pH Probe pH Opt' YES
Ultrasonic Level ULS Opt' YES
Sensor ULS QTY 1
FLS Opt' YES
Float Level Switch
FLS QTY 2
Ozone Gas Detection O3D Opt' NO

966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx


O:\966-002-KSA AMAALA-MLOF\Working\002-Design&Drawing\000-Design Book\966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx
Page 3 of 4 LSS System Schedule
ISSUE DATE: 24/01/2023 DOCUMENT TITLE: LSS SYSTEM SCHEDULE
ISSUED TO: HASCO, AMAALA DESIGN PHASE: Detail Design
REVISION NO: Rev.00

CHECKED BY: GA
APPROVED BY: JL Ch'd Remark In'
LSS ID CS
PIPE STANDARD: TBC LSS Description New SW Treatment/Transfer system.
ELECTRICAL STANDARD No. of Exhibits 1
Single Phase: (v) 230 Gross Volume (m3) 25.13
Three Phase: (v) 400 Net Volume (m3) 25.13
Hertz: (Hz) 60 Design Flow Rate (m3/hr) 23.50
Mins per turnover N/A
Water Type Saltwater
Max (°C) 28
Min (°C) 26
AAT SKID UNIT N/A
Estimated Total Power (INC 20% BUFFER) (kW) 11.3

Filtration Loop SSLP


Piping (Pipe Size Nomination) N/A

Model (FF) FF-600


Foam Fractionator
QTY (FF) 1
(FF)
% Flow (FF) 95%
FFSP SubT D-FR (L/S) 6.22
FFSP QTY 1
Supply Pumps
FFSP FR (L/s) 6.22 CNP NST200 (1.5kW @ 2850rpm)
(FFSP)
Foam Fractionator FFSP TDH (m) 8.0
FFSP Est (kW) 1.50
FFVP SubT D-FR (L/S) 1.50
FFVP QTY 1
Venturi Pumps
FFVP FR (L/s) 1.50 CNP NST200 (1.5kW @ 3450rpm)
(FFVP)
FFVP TDH (m) 16.0
FFVP Est (kW) 1.50

Model (BF-S) T2-100µm-PE/PP


QTY (BF-S)
Bag Filter
Model(BF-H)
(BF)
QTY (BF-H)
% Flow (BF) 100%
Sand Filter / Bag
SFSP SubT D-FR (L/S) -
Filter
BFSP SubT D-FR (L/S) 6.53
Supply Pumps S{B}FSP QTY 1
(S{B}FSP) S{B}FSP FR (L/s) 6.50 CNP NST200 (1.5kW @ 1800/2850/3450)
S{B}FSP TDH (m) 12.0
S{B}FSP Est (kW) 1.50

Model (UV) AAT-LPUV-PVC-240- PLC SKID


Ultraviolet Steriliser QTY (UV) 1
Primary UV Est (kW) 0.24
Equipment Model (HP/HEX) ENV-HP-145HC [14.5kW]
Heat
QTY (HP/HEX) 1
Pump/Exchanger
HP Est (kW) 4.66

Bio-Media Q (l/s) 0.00


% Flow (Bio/Degas) 0%
Bio-Media Bio-media Type 0
Model (Bio-Media) 0
Bio-media (m3) -

AUX1 QTY 0.00


Auxiliary Pumps 1 AUX1 FR (L/s) 0.0
Auxiliary Pumps
(AUX1) AUX1 TDH (m) 0.0
AUX1 Est (kW) -

TS Opt' YES
Temp Sensor
Model (TS) SIN-P202
ORP ORP Opt' NO
PS Opt' YES
Pressure Sensor
Pump PS QTY 3
FM Opt' YES
Flow Meter
FM QTY 1
Secondary
FS Opt' YES
Equipment Flow Switch
FS QTY 3
pH Probe pH Opt' YES
Ultrasonic Level ULS Opt' YES
Sensor ULS QTY 1
FLS Opt' YES
Float Level Switch
FLS QTY 2
Ozone Gas Detection O3D Opt' NO

966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx


O:\966-002-KSA AMAALA-MLOF\Working\002-Design&Drawing\000-Design Book\966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx
Page 4 of 4 LSS System Schedule
ISSUE DATE: 25/01/2023 DOCUMENT TITLE: LSS DESIGN COORDINATION SCHEDULE
ISSUED TO: CLIENT, STAKEHOLDERS
DESIGN PHASE: Detail Design
REVISION NO: Rev.02

Total of Exhibits Weights Freshwater Potable water Supply Model (HP/HEX) Estimated Total Power
No. of Design Flow mins per AAT SKID
LSS ID LSS Description Technical Net Volume Water Type Min (°C) Max (°C) Dry Operational Supply (post Saltwater Supply (Fractionator (INC 20% BUFFER) (kW)
Exhibits 2 3 Rate (m3/hr) turnover UNIT HP Size
Area (m ) (m ) (kg) (kg) treatment) washdown) Excl' lighting
1 Outdoor Coral Raceway System 4 11.5 4.9 12.0 24.5 Saltwater 26 28 AAT - SKID 2 600 1400 1l/s @ 1-2bar 1.5l/s (DN40 branch) 1l/s @ 1-2bar ENV-HP-85HC [8.5 kW] 6.47
2 Indoor Coral Raceway System 4 11.5 4.9 12.0 24.5 Saltwater 26 28 AAT - SKID 2 600 1400 1l/s @ 1-2bar 1.5l/s (DN40 branch) 1l/s @ 1-2bar ENV-HP-85HC [8.5 kW] 6.47
3 Animal Rescue System - Indoor 3 4.6 4.2 17.1 14.6 Saltwater 26 28 AAT - SKID 3 660 1800 1l/s @ 1-2bar 1.5l/s (DN40 branch) 1l/s @ 1-2bar ENV-HP-85HC [8.5 kW] 8.09
CS New SW Treatment/Transfer system. 1 12.6 25.1 23.5 N/A Saltwater 26 28 N/A 1000 1700 2-3l/s 40m3/day to 170m3/day 1l/s @ 1-2bar ENV-HP-145HC [14.5kW] 11.28

Each of the provisions above:


- FW Supply (post treatment)
- SW Supply
- Potable Supply
Are required local to the respective LSS. Typical of historic projects, is to terminate at
highlevel on wall adjacent to the LSS Skids. LSS installer completes final connection from
provision to the skid. (As the design is detailed, AAT will include Builders Works Drawings
identifying termination locations/elevations.)
Recommended the FW Supply (post treatment) reticulation is minimum of 1.5" line @ appx
3l/s.
The potable water required for the washdowns is minimal, i.e. max of 30sec duration every
20min, assume demand of up to 3 systems may be simulataneous.

End-User requested inclusion of flow through operation for Exh.3.1 thru 3.3 (LSS-3_Animal
Rescue). Given each of these tanks has a demand of 1.6l/s, provision of this flow rate (in full)
requires dedicated saltwater supply line to each tank (revised on Central Services system).
Aditionally increases the daily Saltwater demand from 40m3/day to 170m3/day.

PROJECT ID: 966-002 AMAALA-MLOF - KSA


966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx LEAD DESIGNER: Gerard Adam
O:\966-002-KSA AMAALA-MLOF\Working\002-Design&Drawing\000-Design Book\966-002_LSS Design Book_V1.59_Rev1.2_GA_2023.01.24.xlsx Page 1 of 1