1. Dry-bulb temperature - 𝒕𝒅𝒃 𝒐𝒓 𝑫𝑩𝑻 (°𝑪)
2. Humidity ratio (absolute humidity) - 𝝎 (𝒈 𝒐𝒇 𝒘𝒂𝒕𝒆𝒓 𝒗𝒂𝒑𝒐𝒓 𝒑𝒆𝒓 𝒌𝒈 𝒐𝒇 𝒅𝒓𝒚 𝒂𝒊𝒓, 𝒈/𝒌𝒈)
3. Relative humidity - 𝐑𝐇 𝐨𝐫 ∅ (%)
4. Specific enthalpy -h (𝒌𝑱/𝒌𝒈 𝒐𝒇 𝒅𝒓𝒚 𝒂𝒊𝒓)
5. Wet-bulb temperature -𝒕𝒘𝒃 𝒐𝒓 𝑾𝑩𝑻 (°𝑪)
6. Dew-point temperature -𝒕𝒅𝒑 𝒐𝒓 𝑫𝑷𝑻 (°𝑪)
7. Specific volume - 𝑣 (𝒎3 /𝒌𝒈 𝒐𝒇 𝒅𝒓𝒚 𝒂𝒊𝒓)
8. Density of air - 𝜌 (𝒌𝒈/𝒎3 )
5/18/2023 4
5/18/2023 5
5/18/2023 6
5/18/2023 7
5/18/2023 8
𝟏
𝝆(𝒂𝒊𝒓 𝒅𝒆𝒏𝒔𝒊𝒕𝒚) =
𝒗
5/18/2023 9
Air conditioning processes
5/18/2023 10
Simple (sensible) Heating and Cooling (𝝎 = constant)
𝒕𝑨𝑫𝑷 > 𝒕𝒅𝒑𝟏
(𝒕𝒐 𝒂𝒗𝒐𝒊𝒅 𝒄𝒐𝒏𝒅𝒆𝒏𝒔𝒂𝒕𝒊𝒐𝒏)
𝟏𝐓𝐑 = 𝟑. 𝟓𝐤𝐖
5/18/2023 11
Humidification
Steam humidifier 𝒕𝒅𝒃 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝝎𝟐 > 𝝎𝟏
Humdifier Capacity
(amount of humidification/moisture content)
(kW)
Heating & Humidification
= 𝐦ሶ 𝐬𝐭𝐞𝐚𝐦 𝒉𝒔𝒕𝒆𝒂𝒎
Steam injection 𝒕𝒅𝒃 ≠ 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝝎𝟐 > 𝝎𝟏
𝐱≠𝟏 𝐱=𝟏
𝒉𝒔𝒕𝒆𝒂𝒎 = 𝒉𝒇𝒈 𝒉𝒔𝒕𝒆𝒂𝒎 = 𝒉𝒈
5/18/2023 12
Cooling & Humidification
WBT & h lines are almost
Air washer/Adiabatic saturation/Adiabatic humidification [h=constant] parallel to each other
Evaporative cooling/Desert conditioner [WBT=constant] therefore error is not
significant in the answer
• Process across air washer is (h=constant) unless extra information given such as: Air washed with
recirculated spray water (WBT=constant)
• Process across evaporative cooling is (WBT=constant) unless told otherwise in problem
(amount of humidification/moisture content/make up water)
𝐦ሶ 𝐰 = 𝐦ሶ 𝐚 𝛚𝟐 − 𝛚𝟏 (𝐤𝐠 𝐰 /𝐬)
5/18/2023 13
Cooling & Dehumidification
Coil surface temperature/Apparatus dew point (ADP)
is less than air dew point
5/18/2023 14
Cooling & Dehumidification
Bypass factor (BPF)
𝒉𝟏
𝑨𝒊𝒓 𝒕𝒉𝒂𝒕 𝒃𝒚𝒑𝒂𝒔𝒔𝒆𝒅 𝒄𝒐𝒊𝒍 𝒕𝒅𝒃𝟐 − 𝒕𝑨𝑫𝑷
𝑩𝑷𝑭 = =
𝑨𝒍𝒍 𝒂𝒊𝒓 𝒕𝒅𝒃𝟏 − 𝒕𝑨𝑫𝑷 𝒉𝒙
𝝎𝟐 − 𝝎𝑨𝑫𝑷
= 𝒉𝟐 𝝎𝟏
𝝎𝟏 − 𝝎𝑨𝑫𝑷
𝒉𝟐 − 𝒉𝑨𝑫𝑷
= 𝝎𝟐
𝒉𝟏 − 𝒉𝑨𝑫𝑷
𝟐𝑨𝑫𝑷 𝑹𝑯𝟐 = 𝟗𝟎%
=
𝟏𝑨𝑫𝑷
Contact factor (CF)/[efficiency of coil] 𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏
𝑪𝑭 = 𝟏 − 𝑩𝑷𝑭
For chilled water spray BPF = 0 (CF = 1)
Mass of bypassed air (𝒎ሶ 𝒃𝒚𝒑𝒂𝒔𝒔)
(𝒕𝒅𝒃𝟐 = 𝒕𝑨𝑫𝑷 )
𝒎ሶ 𝒃𝒚𝒑𝒂𝒔𝒔 = 𝒎ሶ 𝒂 𝑩𝑷𝑭
5/18/2023 15
Cooling & Dehumidification
Recall sensible change (heating/cooling)
𝒉𝟏
𝝎 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝒕𝒅𝒃 ≠ 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕 𝒉𝒙
5/18/2023 16
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)
𝒉𝟏
𝒉𝒙
𝒉𝟐 𝝎𝟏
𝝎𝟐
𝑹𝑯𝟐 = 𝟗𝟎%
𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏
𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏
5/18/2023 17
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)
𝒉𝟏
𝒉𝒙
𝒉𝟐 𝝎𝟏
𝝎𝟐
𝑹𝑯𝟐 = 𝟗𝟎%
𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏
𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏
5/18/2023 18
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)
𝒉𝟏
𝒉𝒙
𝒉𝟐 𝝎𝟏
summer winter
𝝎𝟐
𝑹𝑯𝟐 = 𝟗𝟎%
𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏
𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏
5/18/2023 19
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)
𝐜𝐨𝐦𝐟𝐨𝐫𝐭 (𝐫𝐞𝐟𝐞𝐫𝐞𝐧𝐜𝐞) 𝐩𝐨𝐢𝐧𝐭/𝐳𝐨𝐧𝐞
𝒉𝟏
𝑫𝑩𝑻 = 𝟐𝟒℃
𝑹𝑯 = 𝟓𝟎% 𝒉𝒙
𝒉𝟐 𝝎𝟏
𝝎𝟐
𝑹𝑯𝟐 = 𝟗𝟎%
𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏
𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏
5/18/2023 20
Dehumidification
𝒕𝒅𝒃 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
5/18/2023 21
Heating & Dehumidification
Adiabatic chemical dehumidification/Adiabatic drier [h=constant]
𝐦ሶ 𝐰 = 𝐦ሶ 𝐚 𝛚𝟏 − 𝛚𝟐 (𝐤𝐠 𝐰 /𝐬)
5/18/2023 22
Adiabatic mixing of two air streams
𝒎ሶ 𝟏
𝒎ሶ 𝟐
𝒎ሶ 𝒘𝟏
𝝎𝟏 =
𝒎ሶ 𝒂𝟏
5/18/2023 23
Adiabatic mixing of two air streams
𝒎ሶ 𝟏
𝒕𝒅𝒃𝟑 − 𝒕𝒅𝒃𝟐 32
= = 𝒎ሶ 𝟐
𝒕𝒅𝒃𝟏 − 𝒕𝒅𝒃𝟑 13
𝑚ሶ 1 23
= Distance 23 can be calculated
𝑚ሶ 3 21
𝑚ሶ 1 𝑚ሶ 2
+ =1
𝑚ሶ 3 𝑚ሶ 3
5/18/2023 24