SUB U - T2-Protection Relay Report - Updated
SUB U - T2-Protection Relay Report - Updated
REF 615
TEST REPORT
1. DETAILS
GENERAL CHARACTERISTICS
Relay Manufacturer ABB Rated Aux. Voltage 24/60 VDC
Relay Type REF 615 CT Ratio 150/1 A
Serial No. 1VHR91546800 VT Ratio 20kV/200 V
Model No. HBFFAEAGNDC1BNA21G Ground CT Ratio 100/1
Setting Group 1 Software Version PCM 2.11
2. PROTECTION SETTINGS
3. METERING
VOLTAGE METERING
Injected Voltage (V) Expected Voltage (kV) Displayed Prim. Voltage on Relay (kV) Remarks
R-N W-N B-N R W B R W B
115.5 115.5 115.5 20 20 20 19.89 19.87 19.89 Pass
TEST REPORT
DPHLPDOC1:1 0.72 0.73 0.73 0.73 ±5% of Setting plus ±0.02 • INOM A
Secondary
DPHLPDOC2:2 0.33 0.35 0.35 0.35
DIRECTIONAL TEST
Phase Expected Angle Operating Angle
ELEMENT Direction Remarks
Deg Deg
DPHLPDOC2:2 L2 100 deg to 260 deg 102 deg to 258 deg Reverse Pass
L3 340 deg to 140 deg 342 deg to 138 deg Reverse Pass
Calculated
ELEMENT CURRENT INJECTED (A) MEASURED TRIP TIMES (s) Trip Times TOLERANCE
(s)
±1.5 Cycles, plus ±4%
EFHPTOC1:1 1 0.461 0.450 (Between 2 and 30
multiples of Pick Up)
TEST REPORT
5. FINAL CHECKS
FINAL CHECKS
Relay final setting applied ☒ CT Links Closed ☒
Relay Settings read back ☒ CT Shorts removed ☒
All test equipment removed ☒ VT Supply restored ☒
As tested stickers applied to relay ☒ All Trip links closed ☒
Reset all flags/latches ☒ All Wiring and Contacts in good condition ☒
6. COMMENTS
TEST REPORT
7. VISUAL INSPECTION
Visual Photos