S/N DESCRIPTION

7.5 MVA 7.5 MVA


1 Description of Transformer Step down Step down
2 Indoor oroutdoor installation Outdoor Outdoor
3 Site conditions:-
a)Altitude m 1000 1000
4 b)Cooling mediumtemperature -m
5 Air: referenceambient .... Co 45 45
6 Continuous maximum ratings irrespective of tapping position
when operating undersite Conditions.
a) H.V.terminal rating MVA 7.5 7.5
7 MaximumONANratings,irrespectiveoftapping position when
operating under siteconditions:-
8 a)H.V.terminalrating MVA 7.5 7.5
9 Rated frequency HZ 50 50
Rated voltage:-
10 a)H.V. KV 33 33
11 b)L.V. KV 11 11
12 Systemhighestvoltage:-
a)H.V. KV 36.3 36.3
13 b)L.V. KV 12.1 12.1
14 Method of system earthings:
15 a) H.V.system Impedance Impedance
b)L.V. system Solid Solid
16 Method of transformer earthing Impedance Impedance
17 a)H.V.winding solid solid
18 b)L.V.winding
Type of cooling ONAN ONAN
19 Impedance voltageat 75OCat CMR and normalandratioonbase of CMR 8 8

20 Impulsewithstandlevel(fullwave1.2/50micro second) under


site conditions
21 a)H.V. 170 170
b)L.V. 75 75
22 Switching surgewithstand level:-
23 a)H.V.winding 140 140
24 b)L.V.winding 62 62
PhaseConnections:-
25 a)IEC vector group referenceb) Dyn1 Dyn1
26 Whether linksare required for alternative IEC vector group NO NO
27 a) Whetherstarconnectedwindings(ifany) shall be Full insulation Full insulation
fullyinsulated or graded
b)IEC categoryof grading only N/A N/A
b)lfso,whetherthewindingistobebroughtout
toseparatebushinginsulator(s)orcablebox
terminalfortestpurpose(forearthing-seeitem 10)
28 Whether'on-load'or'off-circuit'tapchanging equipment or On load On load
linksare required
29 Approximatetotalrangeofvariationofturns ratio:- +5% to -15% @2.5% +5% to -15% @2.5%
i.HV/LV- Increasing ratioplus%NDecreasing ratio minus %
Thesevaluesarecalculatedonthebasisofthe
tapchangerbeingsituatedonthewinding preferred in item22.
30 Approximate sizeofsteps % 1.25% 2.50%
Excessofcontinuouslyappliedvoltageabove NIL NIL
105%ratedvoltageofanytapping thatisallowed bylEC76

Page 1 of 3
31 Whethertappingsarepreferredonanyparticular winding a)On YES
Hvwinding b)On YES NO C.F.V.V
Lvwinding NO
c)Categoryof regulation
C.F.V.V
32 Whether on-loadtapchanging equipment shall be suitablefor NO NO
supervisory control and indication
33 Whether remote tap change control panelis required YES YES
Automatic voltagecontrol equipment YES YES
a)Whether required
34 b)Whether to be suitable for current compounding c)Rangeof YES YES
compound required % 10 10
35 Whetherequipmentshallbeprovidedtopermit YES YES
automaticsynchronizedoperationofon-loadtap equipment
inparallelwith similar transformers
36 Bushing insulator sor cable boxe sorsealingend chambersfor line Bushing Cable Air Bushing Cable Air
terminals: -a)H.V.
b)L.V.
c)Filling mediumfor cable boxes
Whether disconnecting chambers are required No No
37 Bushinginsulatororcableboxforneutral terminals ifany a)H.V. b)L.V. N/A N/A
c)Filling mediumfor cable boxes Cable box Air Cable box Air

38 *Thesevaluesarecalculatedonthebasisofthe
tapchangerbeingsituatedonthewinding preferred in Item22.
39 Whether accommodation forcurrent transformers shall beprovidedon Yes Yes
a)H.V.Terminals b)L.V. Yes Yes
Bushings

Whethertappingshallbebroughtoutfromeach condenser type


bushing insulator to a
separate/areaforpowerfactortestingonsite, on:-
40 a)H.V. Bushings N/A N/A
41 b)L.V. Bushings N/A N/A
42 Whether pressure releasedeviceis tobe fitted Yes Yes
Whetherfirstfillingoilshallbesuppliedforthe
transformer and its associated oil-filled equipment Yes Yes
43 Whethertransformershallbetransportedfilled with oil orwith a Gas/Oil Gas/Oil
suitable gas
44 Whether marshalling unit shallbe provided, ifso
45 a)Whether kioskor cabinet Kiosk Kiosk
b)Whether metalcladheater to be provided Yes Yes
46 Type ofbreather
47 a)Silica gel Yes Yes
48 b)Automatic ofthe repetitive cycle type No No
Whether wheels are required
49 If so
50 a)Whether plain of flanged No No
51 b)Whether required to turn through90O
c)Gaugeof track
52 Whetheroil orwindingtemperatureindicatorsare required Yes Yes
53 Whetherwindingtemperatureindicatorremote repeatersare No No
required
54 Whethertheforcedcoolingequipmentistobe No No
operatedautomaticallyfromcontactsonthe winding temperature
indicator
Whether electrical energy will be provided on site for erection
55 a) If so Yes Yes

Page 2 of 3
56 b)Maximumavailable power tobe discussed Not in our scope
57 Supply voltage for transformer auxiliaries 415V,3phase 415V, 3-phase
Whethercontrolandinstrumentwiringshall conformto Yes Yes
specifiedcolourcode
58 Impulse type tests
59 a)Whether RSO tests are tobe carried out No No
60 b)i.Whether H.V. windingtobedirectly impulse tested Yes Yes
ii.Whether choppedwaves tobeincluded
61 c)iWhetherL.V.windingtobedirectlyimpulse tested
62 ii.Whether choppedwaves tobeincluded Yes Yes
63 FaultMVA:-
a)SystemfaultlevelavailableatH.V.terminals with
64 L.V.windings open circulated. 1500MVA 1500MVA
65 b)SystemfaultlevelavailableatL.V.terminals with
66 H.V.winding open circuited but energized 500MVA 500MVA
Losses:-
67 Forthepurposesofcomparingtenders,the
transformercapitalizedcostindicatedinthe specifications shall
be adopted.
68 Capitalisedcostsofeachtransformershallbe
enteredinthescheduleofparticularsand guarantee.
69 C.T.'s on Transformer Bushings
Burden(VA) 30 30
70 Class CT CL 1.0,5P20 CL 1.0,5P20
71 Ratio 4x400/1/1A 4x400/1/1A
72 Losses:
No Load (kW)max. 9.4 9.4
73 Load(kW)max. 3.8 54 54

Page 3 of 3