Professional Documents
Culture Documents
GTP 7.5 Mva - Rakson
GTP 7.5 Mva - Rakson
Page 1 of 3
31 Whethertappingsarepreferredonanyparticular winding a)On YES
Hvwinding b)On YES NO C.F.V.V
Lvwinding NO
c)Categoryof regulation
C.F.V.V
32 Whether on-loadtapchanging equipment shall be suitablefor NO NO
supervisory control and indication
33 Whether remote tap change control panelis required YES YES
Automatic voltagecontrol equipment YES YES
a)Whether required
34 b)Whether to be suitable for current compounding c)Rangeof YES YES
compound required % 10 10
35 Whetherequipmentshallbeprovidedtopermit YES YES
automaticsynchronizedoperationofon-loadtap equipment
inparallelwith similar transformers
36 Bushing insulator sor cable boxe sorsealingend chambersfor line Bushing Cable Air Bushing Cable Air
terminals: -a)H.V.
b)L.V.
c)Filling mediumfor cable boxes
Whether disconnecting chambers are required No No
37 Bushinginsulatororcableboxforneutral terminals ifany a)H.V. b)L.V. N/A N/A
c)Filling mediumfor cable boxes Cable box Air Cable box Air
38 *Thesevaluesarecalculatedonthebasisofthe
tapchangerbeingsituatedonthewinding preferred in Item22.
39 Whether accommodation forcurrent transformers shall beprovidedon Yes Yes
a)H.V.Terminals b)L.V. Yes Yes
Bushings
Page 2 of 3
56 b)Maximumavailable power tobe discussed Not in our scope
57 Supply voltage for transformer auxiliaries 415V,3phase 415V, 3-phase
Whethercontrolandinstrumentwiringshall conformto Yes Yes
specifiedcolourcode
58 Impulse type tests
59 a)Whether RSO tests are tobe carried out No No
60 b)i.Whether H.V. windingtobedirectly impulse tested Yes Yes
ii.Whether choppedwaves tobeincluded
61 c)iWhetherL.V.windingtobedirectlyimpulse tested
62 ii.Whether choppedwaves tobeincluded Yes Yes
63 FaultMVA:-
a)SystemfaultlevelavailableatH.V.terminals with
64 L.V.windings open circulated. 1500MVA 1500MVA
65 b)SystemfaultlevelavailableatL.V.terminals with
66 H.V.winding open circuited but energized 500MVA 500MVA
Losses:-
67 Forthepurposesofcomparingtenders,the
transformercapitalizedcostindicatedinthe specifications shall
be adopted.
68 Capitalisedcostsofeachtransformershallbe
enteredinthescheduleofparticularsand guarantee.
69 C.T.'s on Transformer Bushings
Burden(VA) 30 30
70 Class CT CL 1.0,5P20 CL 1.0,5P20
71 Ratio 4x400/1/1A 4x400/1/1A
72 Losses:
No Load (kW)max. 9.4 9.4
73 Load(kW)max. 3.8 54 54
Page 3 of 3