HMS Medium Voltage Air-Insulated

Metal-Clad Switchgear
Internal Arc-Resistant
ANSI/IEEE C37.20.2 and C37.20.7
HMS series, HYUNDAI Medium Voltage
Air-Insulated Metal-Clad Switchgear, provides various
benefits with its safe, reliable features, and compact design.
ANSI/IEEE C37.20.2 and C37.20.7
Metal-Clad Switchgear

Characteristics

HMS series, Built by Hyundai Electric & Energy Systems Co.,Ltd


ISO90001 facilities.
Designed in accordance with ANSI/IEEE C37.20.2.

Features
• Functional compartments separated by metal grounded partitions

• Draw-out circuit breaker construction

•Integral breaker racking mechanism with self-aligning and self-coupling primary and secondary disconnecting device

•MOC (Mechanism operated cell) and TOC (Truck operated cell)

• All parts easily accessible, minimum of maintenance


• Simple and flexible design

• Easy installation

• Breakers interlocked to prevent sliding into service position from test position, and vice versa while in the closed position

• Low voltage compartment to accommodate instruments, meters, and relays

• Main busbar system, fully insulated, housed in isolated compartment

• Dedicate voltage transformer section mounted on withdrawable truck

Application
Utility and Power Plants Marine
• Transforming stations • Drilling rigs

• Switching stations • Offshore flatforms and FPSO

• Power generation stations • Container ships

• Main and auxiliary switchgear • Passenger ships

• Tanker ships

Industry • Bulk ships

• Chemical industry

• Petroleum industry Services and Transport


• Iron and steel works • Shopping malls

• Automobile industry • Hospitals

• Oil and gas pipelines • Large infrastructure and civil works

• Textile, paper and food industries • Airports, ports

• Rolling mills

4 / HYUNDAI ELECTRIC
Construction

Typical Section Views

Arc Relief Ducts (Option) Arc Relief Ducts (Option)

1,200 A or
2,000 A

3,000 A
1,200 A or
2,000 A

91" (Standard) 91" (Standard)


101" (Extended) 101" (Extended)

Typical Compartment Arrangements

1,200 A 1,200 A 1,200 A 2,000 A


Circuit Circuit VT or CPT Circuit Circuit
Breaker Breaker Breaker Breaker

Low Voltage Low Voltage Low Voltage Low Voltage Low Voltage
Panel Panel Panel Panel Panel

1,200 A 1,200 A 2,000 A 1,200 A


Circuit VT or CPT Circuit Circuit Circuit
Breaker Breaker Breaker Breaker

2,000 A 2,000 A 3,000 A (4,000 A)


Circuit VT or CPT Circuit VT or CPT Circuit VT or CPT
Breaker Breaker Breaker

Low Voltage Low Voltage Low Voltage Low Voltage Low Voltage Low Voltage
Panel Panel Panel Panel Panel Panel

1,200 A 2,000 A 3,000 A (4,000 A)


Circuit Circuit VT or CPT Circuit VT or CPT VT or CPT
Breaker Breaker Breaker

HYUNDAI ELECTRIC /5
Metal-Clad Switchgear

Construction

Electrical Characteristics

Power frequency Impulse Short-time Momentary Internal arc


Voltage Rated current
withstand, 1 min. withstand withstand current withstand current withstand
(kV) (A)
(kV rms) (kV peak) 3 sec. (kA rms) (kA peak) current

1,200, 2,000
4.76 19 60 50 130 50 kA/0.5 sec.
3,000, 4,000 (FC)

1,200, 2,000
15 36 95 40 104 40 kA/0.5 sec.
3,000

1,200, 2,000
38 80 150 40 104 40 kA/0.5 sec.
3,000

※ The (FC) means that the fan cooling is used in the switchgear and 4,000 A fan cooled rating is achieved using a 3,000 A circuit breaker.

Cubicle Dimensions

Rated voltage Width Depth Height Approximate weight


(kV) (inches) (inches) (inches) (lbs.)

4.76, 15 36 91 95 4,000
38 42 129 95 5,000

Special Tools Accessories and Options


Special tools are supplied All switchgear can be customized for specific applications and
• Hand crank for breaker trucks requirements. Some of the available options are:
• Manual charging handle for circuit breakers • Voltage transformers

• Trolley for breaker truck removal • Current transformers

• Zero sequence current transformers

• Protective relaying

Operating Conditions • Space heaters

Switchgear is intended for use under normal indoor • Meters

conditions: • Controls and control indicators

• Ambient temperature 40 ˚C max. • Remote control and mimic panels

• Altitude 3,000 ft above sea level max. • Surge absorber

• Relative humidity 95 % max.

Switchgear for special operating conditions is


available - Please consult with factory

6 / HYUNDAI ELECTRIC
Vacuum Circuit Breakers

ANSI/IEEE C37.06 and C37.09

Vacuum circuit breaker Breaker cradle and shutters


in switchgear breaker cell

Electrical Characteristics

Low Short-time
MVA Continuous Max. Impulse Interrupting Close and Interrupting
Voltage frequency withstand
three current voltage withstand symmetrical latch time
(kV rms) withstand current
phase (A) (kV rms) (kV peak) (kA) (kA rms) (Cycles)
(kV rms) 3 sec.

1,200,
2,000,
4.16 350 4.76 19 60 50 50 78 3
3,000, 4,000A
(FC)

1,200,
13.8 1,000 2,000, 15.0 36 95 40 40 62 3
3,000

1,200,
33 2,000 2,000, 38.0 80 150 40 40 62 5
3,000

Operating Voltage Range

Nominal control Spring charge Closing Tripping


voltage motor coil coil

48 V DC 36-56 36-56 28-56


125 V DC 100-140 100-140 70-140
250 V DC 200-280 200-280 140-280
120 V AC 104-127 104-127 104-127
240 V AC 208-254 208-254 208-254

HYUNDAI ELECTRIC /7
HEES-SE-B42-01, 2018.1 Designed by designwat
www.hyundai-electric.com

Bundang Office 5F, 55, Bundang-ro, Bundang-gu, Seongnam-si, Gyeonggi-do, Korea


(Sales & Marketing) Tel: 82-31-8006-6640 Fax: 82-31-8006-6897
Ulsan 700 Bangeojinsunhwan-doro, Dong-gu, Ulsan, Korea
(Factory) Tel: 82-52-202-8114 Fax: 82-52-202-8100
Atlanta 6100 Atlantic Boulevard, Norcross, GA 30071, USA
Tel: 1-678-823-7839 Fax: 1-678-823-7553
Frankfurt Mendelssohn Strabe 55-59 Frankfurt 60325, Germany
Tel: 49-69-4699-4988
Moscow World Trade Center, Ent. 3# 703, Krasnopresnenskaya Nab. 12, Moscow, 123610, Russia
Tel: 7-495-258-1381 Fax: 7-495-258-1382
Osaka I-Room 5th Floor Nagahori Plaza Bldg. 2-4-8 Minami Senba, Chuo-ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766~7 Fax: 81-6-6261-5818
Bangkok 19th Floor, Unit 1908, Sathorn Square Office Tower, 98 North Sathorn Road, Silom, Bangrak, Bangkok, 10500 Thailand
Tel: 66-2-115-7920
Riyadh Office No. 230, 2nd Floor, 4th Akariya Plaza, Olaya Street, PO Box 8072, Riyadh 11485, Saudi Arabia
Tel: 966-11-464-4696 Fax: 966-11-462-2352
Al Khobar 7th Floor, Al Khobar Business Gate Building PO Box 20753, Al Khobar-31952, Kingdom of Saudi Arabia
Tel: 966-013-849-3876~7
Dubai Unit 205, Building 4, Emaar Square, Sheikh Zayed Road, Pobox 252458, Dubai, UAE
Tel: 971-4-425-7995 Fax: 971-4-425-7996
Sofia 1271 Sofia 41, Rojen Blvd., Bulgaria
Tel: 359-2-803-3200, 3220 Fax: 359-2-803-3203
Alabama 215 Folmar Parkway, Montgomery, AL 36105, USA
Tel: 1-334-481-2000 Fax: 1-334-481-2098
Yangzhong No.9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0500 Fax: 86-511-8842-0668, 0231

You might also like