TemPower 97-I51E

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

TERASAKI

Terasaki (Europe) Ltd

Terasaki Europe Ltd. was established in 1971


and is located near Glasgow, Scotland U.K.
From head office at our 7,500 square metre
facility, Terasaki Europe controls an Interna-
tional Sales network that serves the whole of
Europe and the Middle East.

The British managed facility manufacturers


the TemPower series of Air Circuit Breakers
(ACB's), TemBreak Moulded Case Circuit
Breakers (MCCB's) and a complete range of
Final Distribution Products.

These superbly engineered products are sold


in the U.K. Europe and the Middle East.

The success of the Glasgow based operation


has helped Terasaki become one of Europe's
leading suppliers of circuit breaker technology,
a fact reflected in our accreditation to the BS
EN ISO 9002 quality management standard.

Terasaki Europe Facility

Standards and Approvals

Based Standards Approvals Applications

IEC 947-2 ASTA/U.K.


International Electrotechnical Commission The Association of Short Circuit Testing
Authorities (Inc.)
BS EN 60947 Part 2
British Standard
NK/Japan
VDE 0660 Part 101 Nippon Kaiji Kyokai
Verband Deutscher Elektrotechniker
LR/U.K.
AS 3858-1990/Australia Lloyds Register of Shipping
Australian Standard
AB/U.S.A.
NEMA PUB NO. SG3/U.S.A. American Bureau of Shipping
National Electrical Manufacturers Association
GL/Germany
ANSI C37.13/U.S.A. Germanischer Lloyd
American National Standard Institute
BV/France
JIS C8372/Japan Bureau Veritas
Japanese Industrial Standard
DNV/NORWAY
JEC 160/Japan Det Norske Veritas
Japanese Electrical Commitee

2
Section Contents Page

1 Air circuit breaker and overcurrent relay features 4-7

2 Ratings and specifications

3 Air circuit breaker specification and accessories

4 Overcurrent relay specification and accessories

5 Outline dimensions

6 Electrical connection diagrams

7 Order forms & Preventive Maintenance Service 56-59

3
1 Features
AOR-1B : Multi-function r.m.s. sensing protection

Enhanced overload protection

Conventional electronic devices incorporating


peak current detection are prone to nuisance
tripping if harmonic distortion exists. Micro-
processor controlled overcurrent relays elimi-
nate “nuisance” tripping by responding to the
true r.m.s. value of the waveform.

True r.m.s. reading utilizing sampling and


integrating techniques.

Thermal memory
The hot start characteristic takes account of
the accumulated heating effect caused by pre-
vious loads. Hot or cold start characteristics
are set by means of a selector switch.
Note: For AOR-1BM only cold start is avail-
able.

Improved co-ordinated protection

Neutral phase protection Inverse time/current characteristics Ramp characteristic for short time-delay
If harmonic distortion exists in a 3-phase, In addition to the overload protection charac- The short time-delay tripping characteristic
4-wire distribution system, 3rd harmonic cur- teristics for general feeder circuits (L type) and provides co-ordination between upstream or
rents can accumulate in the neutral conductor. generators (S type), other inverse time/current downstream circuit breakers or fuses. For
Overcurrent protection of the neutral pole elim- characteristics (M type) are available for closer closer co-ordination with thermal magnetic cir-
inates possible damage to the neutral conduc- co-ordination: Very Inverse (proportional to cuit breakers or fuses, a selector switch is
tor insulation caused by large harmonic cur- I3t) and Extremely Inverse (proportional to I4t). used to set “definite-time delay characteristic”
rents. Full or half rated neutral protection is These characteristics are set by a selector or “ramp characteristic.”
available. (Please specify at time of order- switch.
ing).

MCR function Time


The MCR (Making Current Release) is an Time
instantaneous tripping element that is in oper- Upstream
ation only during the closing cycle of the ACB. H.V. fuse
After the ACB has completely closed, the
MCR function is disabled. The MCR function
Ramp characteristic
is set by INST/MCR switch. AOR-1BL
Standard
inverse Definite time-delay
AOR-1BM curve characteristic

Extremely
inverse
curve
Downstream L.V. fuse
Current Current
Selectivity can be achieved with up to six ACBs in series.

4
Features
AOR-1B : Multi-function r.m.s. sensing protection
1
Multi-protective characteristics Increased reliability

4
3 Self-diagnostic function
LTD current setting range
2
This function continually interrogates the
hour

N-phase current setting range


1 PRE-TRIP current setting range internal circuitry of the OCR for normal opera-
50
40 tion. If an abnormal condition is detected,
STD current setting range
30 GFT current setting range indication is provided via an LED and a volt-
20
age-free contact.
10
INST current setting range
minute

8
6 Click-step adjustment dials
5
4 All adjustment dials are of the click-step type
3
to ensure easy, accurate adjustment of all
2
PRE-TRIP time functions.
setting range
1
50
40
30
Customised IC
20 The customised IC used by Terasaki is a
Operating time

double sided, high density package, thus min-


10 N-phase time
8
setting range LTD time imising the size and increasing the reliability
6
5 setting range of the OCR.
4
3
2

1 1000ms
0.8 1000ms
second

0.6
0.5
0.4 400ms 400ms
0.3 STD time
0.2 GFT time
setting range Fault indication
setting range
0.1
0.08
0.06
80ms 80ms
Individual LEDs and volt free contacts, pro-
0.05
0.04 vide unique fault identification, locally and by
0.03
0.02
remote.

0.01
0.008
0.006
0.005
400
7
8
9
10

15

20

30

40

50
60
70
80
90
100
125
150

200
60
70
80
90
100
125

150

200
250
300

500
600
700
800
900
1000

1500

2000
2500
3000

Field test functions


Percent rated current of OCR CT primary current [ICT] Percent rated current of base current [IO]

A built in test facility enables a calibration


check of overcurrent settings on site. A 'Non
trip' setting allows the testing to be carried out
User friendly features while the ACB is on line.

Control voltage Pre-trip alarm function


The overcurrent and ground fault functions are The Pre-trip Alarm function gives prior warning
self-powered by the ACB current transformers of an impending trip due to overload. Indica-
and do not require an external power supply. tion is by L.E.D. and voltage free contact. This
A power supply is required for all other func- can be used to trip circuit breakers feeding
tions. Control voltages from 24V DC to 250V non-essential loads or, in the case of marine
AC are available on one OCR. applications, to start emergency generators).

Dielectric withstand voltage


2000VAC for 1 minute between all control cir-
cuit terminals and ground. OVERCURRENT &
GROUND FAULT TRI P

Extensive range of rated current settings 1600A


The base current [I0] can be adjusted in 4
stages: 50%, 63%, 80% or 100% of the pri-
mary current rating of the CT [ICT]. The 10 metres (max.)
800A 3200A
Long Time-delay pick-up current setting [I1] is
adjustable between 80 to 100% of [I0], thus
giving a total adjustment range for the ACB
rated current of 40 to 100%.

Current measuring facility


External current monitoring of the phase carry-
ing the largest load is possible by connection AOR-1BL-GI
of a meter to the current monitoring terminals.
(5VDC full scale deflection; 5VDC=200% of Utilizes existing current transformers of ACBs
rated current).

5
1 TemPower
Features

• AT06 - AT40 seven frame sizes covering 630 to 4000 Amps • AT20L & AT25L Current limiting ACBs •

• ACB height and depth is unified throughout


the TemPower series.

• Fixed type height 500mm, depth 343mm.

• Draw-out type: depth 458mm (D).


Up to 2000A frame, height 492mm (H).
Up to 4000A frame, height 526mm (H).

TemPower - Compact, high performance circuit breakers


1 Double segregated arc chamber for maxi-
mum fault interruption performance.
2 Spring charging handle stored flush in the
front panel.
3 Operating mechanism. A simple cam
system for lightweight, narrow construction,
1 mechanically reliable parts, such as ball
bearings are used at all key points.
4 Two tip contact system. Arc damage to the
main contacts during opening and closing
operations is substantially reduced by the
arcing contacts which close before the
4 main contacts (during closing operations)
and which open after the main contacts
6 (during opening operations).
5 U-shaped current path. This design utilises
the electromagnetic repulsive force between
the arms of the “U” conductor to provide
additional contact pressure in the closed
5
position. During current interruption, this
magnetic force drives the arc into the arc
2 chamber and increases contact opening
speed.
6 Early make/late break, neutral pole contact.
3
The neutral pole contact closes earlier,
and opens later than the 3 main pole
contacts. This feature prevents abnormal
transient voltages occurring between
the phase and neutral lines during open-
ing and closing operations. The neutral
contact is mechanically linked to the main
pole contacts making it impossible to
leave the neutral pole open or to acciden-
tally open or close the neutral pole only.

6
TemPower
Features
1
Uniformity in switchboard appearance

4
7

6 2

14
1

12

11

13

10

1 Name Plate 8 Position Padlock (Draw-out type only)

2 Spring Charging Handle 9 OPEN button

3 Dust Plate (Optional) 10 CLOSE button

4 Close-Open Cycle Counter (Optional) 11 Lock-in Open Padlock

5 Position Indicator (Draw-out type only) 12 Draw-out handle Insertion Hole

6 Spring Charge Indicator 13 Keylock location (optional)

7 CLOSED-OPEN Indicator 14 Position Stop Release Lever

ACB positions indicated:


CONNECTED, TEST or ISOLATED
The draw-out handle insertion hole, 12, is
covered by a shutter which is opened by
the position stop release lever, 14. When
the ACB is closed, the position stop release
lever cannot be operated to open the shutter
and so the ACB cannot be removed from the
chassis

7
2 TemPower
Ratings & specifications

Rating and specifications

Ampere Frame 630 1250 1600 2000 2500 3200 4000


Type AT06 AT12 AT16 AT20 AT25 AT32 AT40
Number of poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4
RATED CURRENT (A) [In] 1 IEC, BS, VDE, AS 630 1250 1600 2000 2500 3200 4000
Neutral pole ampere frame (A) 630 1250 1600 2000 2000 6 2000 6 2000 6
RATED PRIMARY CURRENT OF OVERCURRENT TRIP 80 320 320 320 250 1600 4000
DEVICES [ICT] (A) 160 630 630 630 500 3200
(For general feeder circuit use) 320 1250 1250 1250 1000
630 1600 1600 2000
2000 2500
RATED CURRENT OF OVERCURRENT TRIP DEVICES [Io] (A) 40≤Io≤80 160≤Io≤320 160≤Io≤320 160≤Io≤320 125≤Io≤250 800≤Io≤1600 2000≤Io≤4000
(For generator protection use) 80<Io≤160 320<Io≤630 320<Io≤630 320<Io≤630 250<Io≤500 1600<Io≤3200
[Io] is the generator rated current 160<Io≤320 630<Io≤1250 630<Io≤1250 630<Io≤1250 500<Io≤1000
320<Io≤630 800≤Io≤1600 800≤Io≤1600 1000<Io≤2000
1000≤Io≤2000 1250≤Io≤2500
RATED IMPULSE WITHSTAND VOLTAGE [Uimp] (kV) 8 8 8 8 8 8 8
AC RATED INSULATION VOLTAGE [Ui] (V) 10 1000 1000 1000 1000 1000 1000 1000
RATED OPERATIONAL VOLTAGE [Ue] (V) 8 690 690 690 690 690 690 690
AC RATED BREAK. CAP. (kA r.m.s.)/MAKE CAP. (kA peak)
IEC 947-2 with Inst. 12 690V 22/46.2 50/105 50/105 50/105 50/105 50/105 50/105
BS EN 60947-2 [Ics] =100% [Icu] 12 600V 30/63 50/105 50/105 50/105 50/105 65/143 65/143
CEI EN 60947-2 500V 35/73.5 65/143 65/143 65/143 65/143 85/187 85/187
up to 415V 35/73.5 65/143 65/143 65/143 65/143 85/187 85/187
without Inst. 12 690V 22/46.2 50/105 50/105 50/105 50/105 50/105 50/105
12 600V 30/63 50/105 50/105 50/105 50/105 65/143 65/143
up to 500V 35/73.5 50/105 50/105 50/105 65/143 80/176 80/176
DC RATED BREAKING CAPACITY DC 3 250V 40/40 40/40 40/40 40/40 40/40 40/40 40/40
DNV with Inst. 660V – – – – – – –
9 600V – – – – – – –
480V 35/73.5 65/143 65/143 65/143 65/143 91/215 85/187
without Inst. up to 480V – – – – – – –
LR with Inst. 660V 22.2/59.4 35.2/81 35.1/81 – 45.3/106 45.4/106 –
9 without Inst. 600V 30.4/76 50.5/126 50.6/126 – 50.2/126 66.1/168 –
with Inst. 480V 37/90.2 72.6/190.5 72.4/190.5 67.2/144.3 72.4/190.5 91/215.1 –
without Inst. up to 480V 35/81.1 50/114.6 50/114.2 50/122.5 5 50/126 65/157.1 –
AB with Inst. 660V – – – – – – –
9 600V – – – – – – –
480V 35/77.2 65/145 65/145 65/145 65/145 85/203 –
without Inst. up to 480V 35/77.2 50/111 50/111 50/111 50/111 65/145 –
GL with Inst. 660V 22/59.4 35/81 35/81 35/81 45/106 45/106 –
9 600V 30/76 50/126 50/126 50/126 50/126 65/168 –
480V 35/90.2 65/190.5 65/190.5 65/190.5 65/190.5 65/190.5 –
without Inst. up to 480V – – – – – – –
BV with Inst. 660V – – – – – – –
9 600V – – – – – – –
500V 35/85.4 65/148.5 65/148.5 65/148.5 65/148.5 85/220.6 –
without Inst. up to 500V 35/85.4 50/122.23 50/119.95 50/116.2 50/130.95 65/162.37 –
SHORT TIME WITHSTAND 1 sec 35 50 50 50 65 80 80
CURRENT [ICW] (kA) 3 sec 30 45 45 50 50 65 65
Latching current [kA] 35 50 50 50 50 65 65
UTILIZATION CATEGORY B B B B B B B
OPERATION TIMES
Total breaking time (s) 0.05 0.05 0.05 0.05 0.05 0.05 0.05
Spring charging time (s) max. 10 10 10 10 10 10 10
Closing time (s) max. 0.06 0.06 0.06 0.06 0.06 0.06 0.06
OUTLINE DIMENSIONS (mm)
Fixed type a 380 465 380 465 380 465 380 465 470 585 530 665 530 665
b b 500 500 500 500 500 500 500
c 343 343 343 343 343 343 343
a 20 c d d 79 79 79 79 79 79 79
Draw-out type a 368 453 368 453 368 453 368 453 458 573 518 653 518 653
b b 492 492 492 492 526 526 526
c 458 458 458 458 458 458 458
a 20 c d d 82 7 82 7 82 7 92 82 82 82
Weight (kg) draw-out type 82 98 85 106 90 113 91 115 137 165 152 188 175 211

NOTES:
1 : Values in open air at 40°C (45°C for marine applications). 7 : For vertical terminals, d = 92 mm.
3 : DC rating is for special application. For further details, contact Terasaki. 8 : Rated operational voltage depends on applied standard: 690V according to IEC947-2
5 : Approval pending. 9 : Only applied to 3 pole ACBs.
6 : Full rated neutral pole available on request. 10 : Rated insulation voltage depends on applied standard: 1000VAC according to IEC947-2
12 : The application of I.T. systems at this voltage is not permissible

8
TemPower
Ratings & specifications
2
Rating and specifications - Current limiting range

Ampere Frame 2000 2500


Type AT20L 11
AT25L 11
Maxmum let-through peak current [kA]
Number of poles 1
3 4 3 4
RATED CURRENT (A) [In] IEC, BS, VDE, AS 2000 2500
Neutral pole ampere frame (A) 2000 2000
RATED PRIMARY CURRENT OF OVERCURRENT TRIP 320 2500
DEVICES [ICT] (A) 630 325kA
(For general feeder circuit use)
300
1250
1600 Current
2000
200 limiting

it
RATED CURRENT OF OVERCURRENT TRIP DEVICES [Io] (A)

e) cu
– –
effect

lu cir
(For generator protection use)

va ort
[Io] is the generator rated current

ak sh
pe ve
RATED IMPULSE WITHSTAND VOLTAGE [Uimp] (kV) 8 8 130kA
100

i
um ct
AC RATED INSULATION VOLTAGE [Ui] (V) 690 690

im pe
RATED OPERATIONAL VOLTAGE [Ue] (V) 460 460

ax ros
AC RATED BREAK. CAP. (kA r.m.s.)/MAKE CAP. (kA peak)

(m p
em
IEC 947-2 with Inst. 690V – –
BS EN 60947-2 600V

st
– –

Sy
CEI EN 60947-2 [Ics] =100% [Icu] 500V – – 50
up to 415V 130/286 130/286
DC RATED BREAKING CAPACITY DC 250V
3 – –
DNV with Inst. 660V – –
9
600V – –
480V – –
without Inst. up to 480V – –
LR with Inst. 660V – –
Maximum let-through energy I2t [x107A2sec]
9
without Inst. 600V – –
with Inst. 480V – –
without Inst. up to 480V – –
AB with Inst. 660V – –
9
600V – – 10
480V – –
without Inst. up to 480V – –
GL with Inst. 660V – –
9 600V – –
480V – –
without Inst. up to 480V – –
5
BV with Inst. 660V – – 4
9 600V – –
500V – –
without Inst. up to 500V – – 3
SHORT TIME WITHSTAND 1 sec 17 17
CURRENT [ICW] (kA) 3 sec 17 17 2
Latching current [kA] 17 17
UTILIZATION CATEGORY A A
OPERATION TIMES
Total breaking time (s) 0.02 0.02
Spring charging time (s) max. 10 10
Closing time (s) max. 0.06 0.06
OUTLINE DIMENSIONS (mm) 1 10 20 30 40 50 100 130 200
Fixed type a – – – –
b – –
Short circuit current sym. r.m.s. value (kA)
b
c – – at 460 V AC r.m.s.
a 20 c d d – –
Draw-out type a 368 453 518 653
b b 492 526
Note: Max. peak let-through current / I2t energy let-through. Example for AT20L
c 458 458
a 20 c d d 92 82
Weight (kg) draw-out type 91 115 152 188

NOTES:
1 : Values in open air at 40°C (45°C for marine applications).
3 : DC rating is for special application. For further details, contact Terasaki.
9 : Only applied to 3-pole ACBs.
11 : Current limiting ACBs are fitted with an electromagnetic instantaneous trip device set at
20kA as standard.

9
2 AH / AP Range
Ratings & specifications

Rating and specifications - AH and AP type ACBs

Ampere Frame 1600 2000 3200 4000 5000 6300


Type AP-16 AP-20 AH-30CH AH-40C AH-50C AH-60C
Number of poles 3 4 3 4 3 4 3 4 3 4 3 4
1
RATED CURRENT [In] (A) IEC, BS, VDE, AS 1600 2000 3200 4000 5000 6300
Neutral pole ampere frame (A) 1600 2000 3200 4000 5000 6300
RATED PRIMARY CURRENT OF OVERCURRENT TRIP 250 630 800 3200 4000 5000 6300
DEVICES [ICT] (A) (For general feeder circuit use) 1600 2000
RATED CURRENT OF OVERCURRENT TRIP DEVICES [Io] 100≤Io≤250 320≤Io≤800 1250<Io<3200 1600≤Io≤4000 2000≤Io≤5000 2500≤Io≤6300
(For generator protection use) 250<Io<630 800<Io<2000
Note: [Io] is the generator rated current 630<Io<1600
RATED IMPULSE WITHSTAND VOLTAGE [Uimp] (kV) 8 8 8 8 8 8
AC RATED INSULATION VOLTAGE [Ui] (V) 4
1000 1000 1000 1000 1000 1000
RATED OPERATIONAL VOLTAGE [Ue] 5
690 690 690 690 690 690
AC RATED BREAK. CAP. (kA r.m.s.)/MAKE CAP. (kA peak)
IEC 947-2 with Inst. 690V 65/143 65/143 65/143 85/187 85/187 85/187
BS EN 60947-2 [ICS] =100% [ICU] 600V 85/187 85/187 85/187 85/187 85/187 85/187
CEI EN 60947-2 500V 100/220 120/264 100/220 120/264 120/264 120/264
up to 415V 100/220 120/264 100/220 120/264 120/264 120/264
with MCR 690V 50/105 65/143 65/143 85/187 85/187 85/187
600V 50/105 70/154 85/187 85/187 85/187 85/187
up to 500V 50/105 70/154 85/187 100/220 100/220 120/234
without Inst. 690V – – 42/88.2 60/132 70/154 70/154
up to 600V – – 42/88.2 60/132 70/154 70/154
DC RATED BREAKING CAPACITY 3 DC 250V 40/40 40/40 40/40 40/40 40/40 40/40
LR with Inst. 660V 68.2/151 66.7/151 – 86.1/203 – 87.6/203
with Inst. 500V 106/253 129.6/294 86.9/203.9 6
124/280 124/280 124/280
with MCR 500V 50/124 74/161 86.9/203.9 6 106/239 108/239 124/280
SHORT TIME WITHSTAND 1 sec 50 70 85 100 100 120
CURRENT [ICW] (kA) 3 sec – – 65 70 70 70
Latching current r.m.s. [kA] 30 35 42 60 70 70
UTILIZATION CATEGORY B B B B B B
OPERATION TIMES
Total breaking time (s) 0.02 0.03 0.05 0.03 0.03 0.03
Spring charging time (s) max. 10 10 10 10 10 10
Closing time (m. sec). 40 40 40 40 40 40
OUTLINE DIMENSIONS (mm)
Fixed type a – – 578 738 – – –
b b – – 577 – – –
c – – 388 – – –
a 50 c d d – – 119 – – –
Draw-out type a 350 435 580 710 622 782 622 782 747 937 747 937
b b 505 645 655 655 685 685
c 478 537 566 566 589 589
a 50 c d d 47 60 106 106 146 146
Weight (kg) (draw-out type, motor charging) 83 101 150 178 215 271 240 280 350 450 380 480
Spring charged operation (optional)
Motor charging • • • • • •
Manual charging • • • • • •
Overcurrent trip (optional)
Solid state over- For general feeder circuit use • • • • • •
current trip device For generator protection use • • • • • •
Electrical tripping devices (optional)
Shunt trip, Capacitor trip • • • • • •
Undervoltage trip • • • • • •
OTHER ACCESSORIES (optional)
Key lock, key interlock • • • • • •
Safety shutters • • • • • •
Mechanical interlock – • • • • •
Trip indication switch • • • • • •
Close-open cycle counter • • • • • •

NOTES:
• : Yes or available. 3 : DC rating is for special application.
– : No or not available. 4 : Rated insulation voltage depends on the applied standard: 1000V AC according to IEC 947-2.
1 : Values in open air at 40°C (45°C for marine applications). 5 : Rated operational voltage depends on applied standard: 690V AC according to IEC 947-2.
6 : Values at 460VAC.

Ratings and specifications of AH / AP ACBs only, are contained in this catalogue, for further information, contact TERASAKI for details.

10
TemPower
Technical Data
2
Internal resistance, reactance, power consumption

Type AT06 AT12 AT16 AT20 AT25 AT32 AT40


DC Internal (mΩ) Draw-out type 0.050 0.040 0.034 0.028 0.020 0.015 0.011
resistance (per pole) Fixed type 0.040 0.025 0.021 0.015 0.013 0.010 0.007
Reactance (mΩ) Draw-out type 0.150 0.098 0.085 0.078 0.063 0.055 0.050
(per pole) Fixed type 0.150 0.098 0.085 0.078 0.063 0.055 0.050
AC Power (W) Draw-out type 110 280 380 540 690 900 1370
consumption Fixed Type 70 160 240 340 440 730 860

Note: The power consumption shown above is measure on the basis of internal AC resistance for 3 poles

De-rating

Based Ambient temp. Type AT06 AT12 AT16 AT20 AT25 AT32 AT40
standards (°C)
IEC947-2 40 (Standard ambient temperature) 630 1250 1600 2000 2500 3200 4000
BS EN 60947-2 45 630 1250 1600 2000 2500 3200 4000
VDE 0660 Part 50 630 1250 1600 2000 2380 3080 3890
101 55 630 1250 1600 1920 2300 2970 3740
AS 3858 1990 60 630 1230 1600 1840 2200 2850 3590

Dielectric withstand voltage

Circuit 50/60 Hz
Main circuit Between terminals all terminals to earth AC3500V 1 minute
Auxiliary switch all terminals to earth AC2500V 1 minute
Undervoltage trip AC Rating terminals 9 - 10 to earth AC2500V 1 minute
terminals 11 - 12 to earth AC1500V 1 minute
Accessories

DC Rating all terminals to earth AC1500V 1 minute


Shunt trip all terminals to earth AC2000V 1 minute
Overcurrent trip all terminals to earth AC2000V 1 minute

Motor charging closing AC100-250V all terminals to earth AC2000V 1 minute


control circuit DC100-220V
DC24-48V all terminals to earth AC500V 1 minute
Other Accessories all terminals to earth AC2000V 1 minute
Note: The values shown above are those measured on new parts and cannot
be applied to components' terminals in the ACB.

11
3 ACB Specification
Types of mounting

Draw-out type Fixed type

The draw-out type consists of a circuit breaker and a draw-out cradle. This consists only of the circuit breaker with fixings to allow it to be
The circuit breaker can be removed from the cradle. There are mounted permanently inside the switchboard.
four circuit breaker positions CONNECTED, TEST, ISOLATED and
REMOVE. The switchboard panel door can be kept closed in CON-
NECTED, TEST and ISOLATED positions (“shut-in three positions”).

1 Connected position Main circuit terminals

Standard terminal arrangements are either horizontal or vertical type.


(Horizontal and vertical types are available for AT06, AT12, AT16 and
Indication Control circuits
AT20). Front connections are also available.
CONN. Please refer to the table below and specify the required connection
Main circuits
method at time of ordering.

Terminal Arrangement
Type Type Of Horizontal Vertical Front
Mounting Terminals Terminals Connections

Draw-out
Both main and control circuits are connected for normal AT06
service. Fixed –

2 Test position Draw-out


AT12
Indication Fixed –
TEST
Draw-out
AT16
Fixed –

Draw-out
AT20
Fixed –

AT20L Drawout – –
The main circuit is isolated and the control circuits are connected.
Draw-out
This position permits operation tests with the switchboard panel shut.
AT25
Fixed –
3 Isolated position
AT25L Draw-out – –
Indication
ISOLATED Draw-out
AT32
Fixed –

Draw-out – –
AT40
Fixed – –

Note:- : Standard : Optional – : No or not available

Both main and control circuits are isolated. The switchboard


panel door can be shut. Earth circuit still connected.

4 Remove position

Horizontal Terminals Vertical Terminals

The ACB is completely removed from the cradle.

12
ACB Specification
Accessories
3
Door interlock
The door interlock prevents the switchboard
(Front view) (Plan view)
door from being opened when the breaker ø10
is CLOSED. The door can be opened only ø7 Breaker
when the breaker is OPEN. It is also fitted Panel door mounting

12.5
with a lock release. Installation of the door 250 hole
interlock requires simple drilling of the switch-
board panel door.

200
270
Hinge can only be fitted on the RIGHT HAND Dust

301.5
SIDE as shown in the opposite diagram. plate

130
Hinge

50

15
A Breaker A B
(min.) (min.) (min.)
20
A B (3P) B (4P) Panel door
AT-06,12,16,20,20L 163 280 365
AT-25 208 330 445 Door interlock
AT-25L,32,40 238 330 465

Lifter loader

Breaker mounting position Lifter D W H Weight (kg)


AWT-2B 1310 840 95 120 AWT-2B
*150 max
Dimensions (mm)
ACB front panel The loader is a variable size type to suit all
frame sizes of TemPower ACBs (3 and 4
pole).
Size change is readily done by adjusting the 2300 mm
loader.
Maximum safe working load (SWL) : 250kg
Maximum lifting height : 1850mm
Minimum passage width : 1800mm

Panel door
Note: * If distance exceeds 150mm, contact D
TERASAKI

H
Carrying rollers W

The carrying rollers are necessary when the


lifter is used. The rollers can also be used for
moving the breaker on the floor.

Arc gas barrier

The Arc Gas Barrier reduces the air gap


requirement between the top of the ACB and
other electrical equipment or earthed metal.
See outline dimension drawings for details.
The barrier can be installed with the cradle, for
the draw-out type breaker. The arc gas barrier
is a heat proof, flame-resistant insulating plate.

Metal-clad type

The metal-clad type consists of a draw-out


breaker, housed in a steel enclosure. A load
centre is readily constructed by simply placing
metal-clad units one upon another.

13
3 ACB Specification
Accessories for draw-out type

Main circuit safety shutters Position switches

When the breaker is drawn out the shutters The Position switches operate when the • Position switch, operating sequence
automatically conceal and insulate the main breaker is in CONNECTED position, TEST
(Isolated) (Test) (Connected)
circuit disconnect contacts on the cradle. position, ISOLATED position or in the INSERT
Each shutter can be padlocked in the closed position, to electrically indicate the breaker a-contacts
Connected position
position. For safety during inspection and position. These switches are divided into units "ON"
indicator switch
maintenance, up to three padlocks may be (1) and (2) as shown below, and one switch Test position
a-contacts
"ON"
applied to each of the top and bottom shutters can be selected from each unit. A max of 2 indicator switch
(padlocks not supplied). units can be fitted on ACBs AT06~20, 3 Pole. a-contacts
Isolated position "ON"
A max of 4 units fitted on any other ACB size. indicator switch
UNITS (1) UNITS (2)
The top shutter and bottom shutter can be Insert position a-contacts
indicator switch "ON"
opened or closed independently by manual (1) CONNECTED (1) ISOLATED position • Position switch ratings
operation. Maintenance can be done in the position, indicator indicator switches Load Resistive Lamp Inductive Motor
open position. (The mechanism is released switches (2 max) (2 max) AC250V 10A 1.5A 6A 2A
automatically by inserting the circuit breaker). DC30V 6A 3A 6A 3A
The top shutter and bottom shutter can both (2) TEST position, (2) INSERT position, DC125V 0.6A 0.1A 0.6A 0.1A
be moved individually. indicator switches indicator switches DC250V 0.3A 0.05A 0.3A 0.05A
(2 max) (2 max)

(3) CONNECTED (3) ISOLATED and


and TEST position. INSERT position,
indicator switches indicator switches Mal-insertion prevention device
(one each) (one each)
Interchangeability exists within the TemPower
Range of Air Circuit Breakers. Because of this
Test jumper feature there is a possibility for a breaker of
a different specification being placed into the
The test jumper allows open-close tests on the cradle. This is effectively prevented by the use
removed breaker of the Mal-insertion Device.
(The standard length of the cable is 5m)

Control circuit safety shutter Breaker fixing blocks Draw-out position padlock

The control circuit disconnect contacts have These provide reinforcement for the breaker The breaker can be padlocked in three posi-
independent shutters for increased safety. mounting where vibration occurs. They are tions, CONNECTED, TEST and ISOLATED.
They are not padlockable. always fitted when the breaker is subject to The padlocking device is fitted as standard.
marine classification society rules. Padlocks not supplied (hasp diameter 8 or
6mm dia).

14
ACB Specification
Accessories
3
Open padlock Push-button padlock cover Carrying handle

Permits the ACB to be padlocked in the OPEN Prevents unauthorised operation of the For use with hooks, ropes etc when lifting the
position, this is fitted as standard. manual CLOSE and OPEN buttons. Padlock breaker.
Max. 3 padlocks (hasp size ø6 to ø8mm) can hasp size ø6 to ø8mm (not supplied).
be fitted (not supplied).

Dustplate Special environment specification

Provides a dust proof seal between the ACB Cold Climate Treatment Tropicalization
front panel and the cut-out on the switchboard Specify this treatment when the breaker is used (Fungus and Moisture Treatment)
panel when the breaker is located between the in cold areas. Specify this treatment when the breaker is used
CONNECTED and ISOLATED position. Specification :– 40°C storage temperature under high temperature and high humidity con-
-25°C operating temperature (no condensation ditions:
or freezing). Up to 60°C ambient temperature and up to 95%
relative humidity (no condensation).
Anti-Corrosion Treatment
Anti-corrosion treatment permits the use of the
breaker in a corrosive atmosphere. Contact
TERASAKI for further information.

Door flange Earthing device

Covers the panel cut-out on the switchboard. There is a growing demand in L.V. distribution for greater protection against electric shock
The panel cut-out should be greater than the particularly during periods when maintenance work is being carried out on the main busbars or
standard size shown in the outline dimensions cables. A safe and economical way to meet this requirement is to apply system earthing via the
section of 250mm x 270mm. We would recom- normal service breaker. Earthing devices (optional) on TemPower ACBs comprises; Permanent
mend to use a cut out of 260mm x 280mm. parts which are factory fitted by Terasaki (Europe) and are mounted on the ACB chassis and
The option is not available with the TemTrip body to enable the ACB to receive the portable parts. Portable parts are supplied in loose kit
relay. form and are fitted on to the ACB body by the customer's engineer. This converts the ACB
from a normal service device to an earthing device. For further information contact TERASAKI
for details.

15
3 ACB Specification
Accessories

Key interlock

The key interlock is a system of interlocking Utilising the lock-in-open type key lock feature In the latter case, use Lock Type FS 2 (angular
between breakers, each fitted with a lock-in- and using keys less than the number of the movement 65o clockwise to trap key) Castell
open type key lock key-locked breakers, an effective and reliable Locks Ltd.
*The key must be inserted to release the lock interlock system is formed.
before the breaker can be closed Breakers can be supplied with a cylinder lock EXAMPLE: Prevention of parallel connection of
* The breaker must be opened and locked in the fitted or with a provision for Castell lock. two sources with a bus tie breaker.
open position before the key can be removed

SOURCE 1 SOURCE 2 SOURCE 1 SOURCE 2 SOURCE 1 SOURCE 2


Breaker 1 Breaker 2 Breaker 1 Breaker 2 Breaker 1 Breaker 2

Bus-tie Bus-tie Bus-tie


Breaker 3 Breaker 3 Breaker 3

Loads 1 Loads 2 Loads 1 Loads 2 Loads 1 Loads 2

Breaker 3 cannot be closed Breaker 2 cannot be closed Breaker 1 cannot be closed

IP cover Mechanical interlock

Mounted on the switchboard panel door to


provide IP54 degree of protection as defined
Horizontal type Vertical type
in IEC529. Contact TERASAKI for the details of vertical
type with 3 ACBs.
Wire

60

P P P
C C C

Rod

N N N

P P
N
*Min
575mm
Select the required pitch from the table below:

Pitch of ACB P(mm)


Interlock
(PC line to PC line)
between
600 700 800 900 1000
AT06 * Minimum pitch (575mm) is pos-
AT12 sible if the proper insulating dis-
If you require to drawout the ACB with AT16 • • • tance is obtained. For larger pitch
AOR-1B to the isolated position, an additional AT20 (max. 1200mm) contact TERASAKI
depth frame is required with the IP54 cover. AT20L for details.
Please specify at the time of ordering. AT25
Note that the IP54 cover used with the Tem- AT25L
Trip is not hinged. AT32 • • •
AT40

16
ACB Specification
Accessories
3
Auxiliary switch assembly Close-Open cycle counter

Auxiliary switches electrically indicate the open- This device counts and indicates the number of
closed status of the breaker. For Draw-out close-open cycles
Type, the auxiliary switches operate in the
CONNECTED and TEST positions only. How-
ever, where marine classification society’s rules
apply, they operate in the CONNECTED posi- Key lock
tion only. Options include; 2A 2B, 5A 5B, 10A
10B. The key lock is available in two types: lock-in-
open type to lock the breaker in the OPEN posi-
tion, or lock-in-closed type to lock the breaker in
the CLOSED position.

Auxiliary Switch Ratings


Rated Voltage Resistive Lamp **Inductive Motor
AC125-500V 7A 5A 7A 7A
DC30V 7A 5A 7A 7A
DC125V 7A 5A 5A 5A
DC250V 7A 5A 2.5A 2.5A
Note: *minute current limit is Min. 10mA at 24V. DC
** (AC cos ø over 0.4 DC L/R below 0.007)

Trip indication switch

Operation of the trip indication switch varies depending on which device trips the breaker and whether or not the closing spring Ģ

Rating
Load Resistive Lamp Inductive Motor Operation of trip indication switch
Breaker tripped by
AC125- Closing springs charged Closing springs discharged
250V 7A 1.5A 6A 2A Overcurrent trip (OCR)
DC30V 6A 3A 6A 3A Switch is ON for 40ms, then reset to Switch remains ON until closing
Shunt trip
DC125V 0.6A 0.1A 0.6A 0.1A OFF springs are charged
DC250V 0.3A 0.05A 0.3A 0.05A Undervoltage Remote opening
trip
Switch remains ON until undervoltage Switch remains ON until closing springs
Undervoltage condition is restored to normal. are charged after undervoltage condition
Condition has restored to normal

Note: * Optional. The trip indication switch can be made * Manual opening by Switch remains ON until PUSH-TO- Switch remains ON until closing springs
inoperative for a manual OFF operation. Please specify at PUSH-TO-OPEN button OPEN button is released are charged after PUSH-TO-OPEN button
time of ordering. is released

TemTronic automatic changeover controller

An automatic mains/generator changeover Specifications


system can be achieved by utilizing TemTronic (Ue) System voltage level 110 ~ 440 V AC
with a pair of mechanically interlocked ACBs, (Um) Mains fail voltage 75 ~ 95% Ue
each fitted with a motor operator, shunt trip (Tf) Mains fail delay 0.5 ~ 8.0 sec.
and auxiliary switch. (Tr) Mains return delay 15 ~ 1200 sec.
If one or more phases fail on mains supply, (Tg) Generator cool down time 30 ~ 1200 sec.
TemTronic will trip the mains circuit breaker
and start the generator. Once up and running Dimensions
(85% of Ue) the generator circuit breaker will (W) 95 mm, (H) 143 mm, (D) 138 mm
close. If mains voltage should return the gen-
erator circuit breaker will trip, mains circuit Power supply
breaker will close and the generator will con- 150mA @ 24V DC
tinue to run on 'No load' for a preset cool down 5% Maximum ripple
period. An optional UPS backup supply is available
for this unit. It contains rechargeable batteries
Contact TERASAKI for further details. which can supply enough power to energise a
shunt trip and keep the unit powered for up to
1 hour. Refer to page 53 for details.

17
3 ACB Specification
Spring charged operation

Manual charging type Rating of motor charging type

The closing springs are manually charged Breaker Rated voltage Min & max Inrush Steady-State Charging Closing
by pumping the charging handle. When the operation current current time command
PUSH TO CLOSE button is pressed, the clos- voltage (peak value) (AC, A, current
ing springs are released, quickly closing the r.m.s. value) (peak value)
breaker.
(An electrical latch release can be provided (V) (V) (A) (A) (s) (A)
for remote closing applications. The closing
springs must be charged manually prior to AC240 - 250 204 - 275 2.9 (240V) 0.5 2.8 1.6 (240V)
remote close operation). AC200 - 230 170 - 253 3.4 (220V) 0.5 2.4 1.5 (220V)
AT06 AC100 - 120 85 - 132 6.3 (110V) 1.2 2.4 3.1 (110V)
AT12 DC200 - 220 150 - 242 2.8 (220V) 0.5 2.7 1.3 (220V)
AT16 DC125 94 - 138 2.2 (125V) 0.8 3.0 3.4 (125V)
Motor charging type AT20 DC100 - 110 75 - 121 6.5 (100V) 0.9 2.8 2.7 (100V)
AT20L DC48 36 - 53 11.0 (48V) 1.7 3.0 4.9 (48V)
The motor automatically charges the closing DC24 18 - 26 16.9 (24V) 3.4 2.7 8.8 (24V)
springs. The latch release coil is energised
by a remote push button, releasing the springs AC240 - 250 204 - 275 2.8 (240V) 0.8 3.4 1.7 (240V)
and quickly closing the circuit breaker. With the AC200 - 230 170 - 253 3.4 (220V) 0.6 2.5 1.6 (220V)
breaker closed, the motor automatically starts AC100 - 120 85 - 132 6.1 (110V) 1.1 2.5 3.2 (110V)
to charge the springs again for the next closing DC200 - 220 150 - 242 2.8 (220V) 0.5 3.1 1.4 (220V)
operation. AT25 DC125 94 - 138 2.4 (125V) 1.0 3.0 3.5 (125V)
Manual charging is also possible. DC100 - 110 75 - 121 6.5 (100V) 1.2 3.5 2.8 (100V)
Separate charging and closing circuits are DC48 36 - 53 11.0 (48V) 1.7 3.0 4.9 (48V)
available on request. DC24 18 - 26 16.9 (24V) 3.7 3.5 8.8 (24V)

AC240 - 250 204 - 275 2.8 (240V) 0.8 4.0 1.9 (240V)
AC200 - 230 170 - 253 3.2 (220V) 0.6 3.0 1.7 (220V)
AC100 - 120 85 - 132 6.0 (110V) 1.2 3.0 3.2 (110V)
AT25L DC200 - 220 150 - 242 2.8 (220V) 0.5 3.1 1.5 (220V)
AT32 DC125 94 - 138 2.5 (125V) 1.0 3.0 3.5 (125V)
AT40 DC100 - 110 75 - 121 6.0 (100V) 1.9 5.5 2.9 (100V)
DC48 36 - 53 11.0 (48V) 1.7 3.0 4.9 (48V)
DC24 18 - 26 15.5 (24V) 3.8 4.2 8.9 (24V)

Motor charging and closing operation

CHARGING OF CLOSING SPRINGS *CLOSING THE ACB *ANTI-PUMPING FUNCTION


1 When the closing springs are “DIS- 1 When the springs are charged, the 1 Once the closing springs have been
CHARGED”, the spring charged OFF “spring charged ON switch” in series with released, the “spring discharged OFF
switch in series with the motor is closed. the LRC is closed. switch” is closed. If a close signal is
2 Control voltage is applied to terminals 1 2 Apply voltage across terminals 3 and 2, continually applied across terminals 2 and
and 2 and the motor starts to charge the through PB (close). The latch release 3, the holding relay (HC) is energized and
springs. coil (LRC) is energized and the closing self holds when the HC a-contact closes.
3 When the closing springs are fully springs are released to close the ACB. The HC b-contact opens, cutting the
charged, the “spring charged OFF switch” 3 Open the spring charged ON SW. by 2 supply to the LRC. ACB can not re-close
in series with the motor opens and cuts release the closing spring and cuts the without opening the PB (close).
the supply to the motor. supply to the LRC by AUX SW. b-contact.

Note :* Refers to standard circuit

18
ACB Specification
Spring charged operation
3
Motor circuit

Source Source Source


for for
motor L.R.C.
Interlock switch Interlock switch
Ry Ry etc
For spring charge Ry Ry etc
PB (Close) For spring charge PB (Close)
indication
indication

15 1 3 15 1 3

101 101
1 3 31 1 3 31
AXT-1C

AXT-1C
Spring C C Spring C C
R
charged R charged
switch switch HC
HC
OFF OFF

A A
R R
41 41
HC HC
M M AMT-1C
AMT-1C
B B D D D B B D D D
205 205
204 204

AXT-1BA
AXT-1BA

AXT-1C
AXT-1C

AXT-1C
AXT-1C

Aux.Sw.
Aux.Sw.

Spring Spring
charged LRC charged LRC
switch switch
ON ON
203 203
202
Spring Spring
202 charged
4 charged 2 4
2 switch switch
OFF OFF

2 4 2 4
Standard circuit Split supply circuit

Power transformer (external)

The maximum rated control power voltage Rated


applicable to the motor charging type is 250V Transformer
Control
AC. If a higher voltage than this value Voltage Type Cap. Volt ratio
is applied, a power transformer is required.
AC350-395V TSE -30M 300VA 380 / 220V
TERASAKI can offer the following transform-
AC410-470V TSE -30M 300VA 450 / 220V
ers.
(please specify on order).

Automatic closing spring release Spring charged switch Jig for slow-closing
The closing springs are automatically released This switch electrically indicates the charged Jigs can be supplied with the breaker for
when the breaker is drawn out from the TEST condition of the closing springs. inspection and maintenance purposes (they are
position to the ISOLATED position. required when changing the arcing contacts of
the ACB). Slow-closing operation can be made
Ratings Resistive Motor by the charging handle when the slow-close jigs
AC125V-250V 7A 4A are installed.
DC125V-250V 0.4A 0.05A

19
3 ACB Specification
Electrical tripping devices

Shunt trip (SHT)

The shunt trip device allows the ACB to be Shunt Trip Ratings (instantaneous operating type)
remotely opened. Instantaneous operating
and continuously rated versions are available. Shunt Trip Rated Voltage Operational Voltage Peak Excitation Opening Time
(Contact Terasaki for details of continuous (V) (V) Current (max)
rated type). (A) (ms)
TemPower ACB can be fitted with shunt trip AVT-1 AC421-480 252-528 1.3 (450V) 30
and UVT. AC380-420 228-462 1.4 (380V) 30
AC180-250 108-275 1.7 (220V) 30
AC100-150 60-165 3.2 (110V) 30
DC150-230 90-276 1.5 (220V) 30
DC90 -125 54-150 2.9 (100V) 30
DC48 29-57 4.9 (48V) 30
DC24 14-28 8.9 (24V) 30

Capacitor trip

Combined with the shunt trip device, the capac- Type AQT-1A AQT-1B
itance trip device enables the ACB to be Rated Voltage AC 100-120V 220~240V
remotely tripped after a voltage (ac) drop due Operational Voltage 70 to 110% 70-110%
to a power failure, short circuit, etc, provided Rated frequency 50/60Hz 50/60Hz
that the remote trip operation occurs within 30 Rated Voltage of Shunt Trip used DC90-125V DC150~230
seconds after the voltage drop. Power Consumption (Inrush) 100VA 200VA

Outline Dimensions (mm)


173.0 64.0
161.0 51.0
151.0 28.0
4.0
SWITCH RED NEON

ON

OFF CAPACITOR
CHARGE
OUTPUT
3

1
INPUT

48.0
80.0
2
4

CAPACITOR TRIP DEVICE

FRONT VIEW SIDE VIEW


4 - ø4.5 CSK mtg. holes

Control Circuit

PB
(OPEN)
Power or
ACB OCR
Source
etc.
AUX
SW
8 SHT 7

3 4 2 – + 1

ON OFF C
NL
R

Power
Switch
Di Di R Di

20
3
ACB Specification
Electrical tripping devices

Undervoltage trip (UVT)

The undervoltage trip (UVT) automatically trips


the ACB when the control power voltage drops
PB (OPEN) OR OCRy etc.
below a pre-determined value. When the con- AC SOURCE
trol voltage is restored to a value equal to or 9 11
greater than the pick-up value, the ACB can
be closed. The UVT consists of a trip control AUX
SW
device and a tripping mechanism. AUT-1BD. AUT-1BS
Two types of UVT are available: AUT-1BS A
UVT CONTROL DEVICE
C
(instantaneous trip type: AC and DC control
voltages available) and AUT-1BD (500ms or
1sec time delay type. D1
R R

The DC versions of the AUT-1BS require an C C R


R

external current limiting resistor to be used


Rec Ry
(supplied with the ACB). R

Remote opening of the circuit breaker by the * UVT


C UVT
UVT is possible by connection of a normally ENERGIZED
open push button across terminals 11 and 12. "OFF"

Note: Not available for AT20L and AT25L B D

10 12
* AUT-1BD only

Current limiting resistor DC SOURCE


PB (OPEN) OR OCRy etc.

9 + 11
54

AUX
SW
Current limiting Resistor

*2
AUT-1BS
217 6 A UVT CONTROL DEVICE C
SR
*1
236 26 R

D1

(For D.C. control device type AUT-1BS) R


R
1.5kΩ 150W...DC100-110V, 200-220V
150 Ω 150W...DC48V Ry
50 Ω 150W...DC24V UVT UVT
ENERGIZED
"OFF"
B D

10 12 –

Note: *1 Fitted on the circuit of rated control voltage 200-220V DC


*2 When the rated control voltage is 200-220V DC, two switches in series are used

Ratings

Type of UVT Rated Control Opening Voltage (V) Coil Excitation Power Consumption (VA)
Control Device Voltage (V), 50/60Hz [Pick-up Voltage (V)] Current (A)
Normal Reset

AUT-1BS AC 430 – 470 164.5 – 256.5 [365] 0.1 (450V)


401 – 429 150.5 – 236.5 [330] 0.1 (415V)
360 – 400 140 – 216.5 [305] 0.1 (380V) 5 50
200 – 240 84 – 125.5 [170] 0.1 (220V)
100 – 120 42 – 62.5 [85] 0.1 (110V)
AUT-1BS DC 200 – 220 77 – 114 [170] 0.1 (200V) 24 140
AUT-1BD 1 100 – 110 38.5 – 57 [85] 0.1 (100V) 12 70
48 17 – 27.5 [40.5] 0.3 15 110
24 8 – 13.5 [20] 0.8 20 120
1 Note: Time delay available for 100-110 VDC only.

1
4 OCR Specification
AOR-1B Multi-function protection device

Protection functions

1 Adjustable Long Time-delay LTD 2 Adjustable Short Time-delay STD 4 Adjustable Pre-Trip Alarm PRE-TRIP
The LTD fuction protects against overload. The STD function is intended to give dis- The PRE-TRIP alarm gives warning (via a volt-
Select HOT or COLD start. crimination with other devices during short cir- age free contact) of impending trip due to
The HOT start characteristic takes account cuits. The STD characteristic is user-selecta- overload. On L and M type OCRs, it has a
of accumulated heating caused by previous ble between 'definite time-delay' and 'I2t ramp' definite time delay and on S type OCRs, it has
loads. characteristics. The 'definite time-delay' is an inverse time delay.
(HOT start characteristics are not available on suitable for co-ordination with other definite PRE-TRIP signal automatically resets when
M type) time delay devices. The 'ramp' characteristic the current drops below pick-up current (IP).
allows closer co-ordination with thermal-mag-
netic MCCBs. When the STD is set to 'I2t 5 Adjustable Ground Fault GFT
ON', the 'ramp' characteristic is in operation The GFT pick-up current can be set between
current

up to 1000% of the base current for L & M 10% to 40% of the CT rated primary current
(general feeder protection) type OCRs and and the definite time delay between 80 to
Pick-up current of LTD up to 500% for S (generator protection) type 1000ms.
OCRs. Above these levels the definite time-
time delay comes into operation. The STD is set to 6 Neutral Phase Protection N-phase
Fluctuating current load profile 'I2t OFF' at the time of manufacture. Available on 3 & 4 pole ACBs for use on
3-phase, 4 wire systems. The N-phase cur-
tripping

3 Adjustable Instantaneous Trip INST.


time

rent setting is 20% to 100% of the CT rated


time The INST. function protects against short cir- primary current. Please specify at time of
Conventional electronic relay without thermal memory cuits, without a built-in time-delay, It is user- ordering.
tripping

selectable between 'INST.' or 'MCR'. The


time

MCR (Making Current Release) function oper- OCR Sealing Facility


time ates only during the closing cycle of the ACB Unauthorised access to the OCR adjustment
Microprocessor based relay with thermal memory. and is disabled once the ACB has fully closed. dials can be prevented by use of an optional
Simulates true heating effect of conductor.
sealing cover. This is placed over the dials
and secured by two screws. The screw heads
have holes drilled in them for a sealing wire to
be fitted. (Wire and seal are not provided).

NON setting and FAIL-SAFE

1 Each of the overcurrent protection func- 2 If the STD and INST functions are both 3 If the STD and MCR functions are both set
tions (LTD, STD, INST/MCR) can be disa- set to 'NON' (thereby removing all short- to 'NON', the in-built FAIL-SAFE function
bled by setting the respective pick up dial circuit protection), the in-built FAIL-SAFE will trip the ACB on fault currents exceed-
to 'NON' position. (For example, the INST function will trip the ACB on fault currents ing 10 times the base current, [Io], (on L
setting is often set to 'NON' to improve exceeding 16 times the base current [Io], and M type OCRs) and 5 times the base
selectivity levels.) instantaneously. current, [Io] (on S type OCRs). Trip time is
the STD time setting.

Base current [Io]

The base current, [I0], is used as the reference 1 For General Feeder Circuits 2 For Generator Protection
for deciding the current and time settings of 1 Calculate the maximum full load current, 1 Check the generator full load current, [IGEN].
the LTD, STD, INST. and PRE-TRIP functions. [ILOAD], through the ACB. The base current, [I0], will be equal to [IGEN]
On AOR-1BL and AOR-1BM type OCRs, it 2 Select the required rated primary current, 2 and should be used as a reference for the
can be set by means of a dial on the front to [ICT], of the OCR, (note that [ILOAD] must pick-up current settings of the other protec-
50, 63, 80 or 100%, of the rated CT primary not be greater than [ICT]. tion characteristics.
current (ICT). On AOR-1BS, it is factory set 3 Decide what the base current, [I0] should Select the OCR with the protection and
according to the full load current of the gen- be and use this as a reference for the LTD, 3 indication functions required for the par-
erator (which should be specified at time of STD, INST and PRE-TRIP current settings. ticular application.
order). Select the OCR with the protection and
Base current selection procedures are as fol- 4 indication functions required for the par-
lows: (Refer to tables on P.26, 28, 30 for avail- ticular application.
able values of [ICT] and [I0].

Note: The ground fault pick-up current, [IG] is


a factor of [ICT], not [I0].

2
OCR Specification
AOR-1B Multi-function protection device 4
Local and remote trip indication

AOR-1B type OCRs are available with trip Trip Indicator Contact Ratings
indications. Two types of trip indication func-
tion are available: single contact type and indi- Single Rated Voltage AC250V AC100V DC30V DC125V DC250V
vidual contact and LED type. Contact Rated Current (Resistive) 7A 7A 5A 0.5A 0.3A
Type Rated Current (inductive) 3A 3A 3A 0.25A 0.15A
1 Individual Rated Voltage AC250V AC100V DC30V DC125V DC220V
Single contact type
This is a voltage-free contact which closes for Contact Rated Current (Resistive) 0.5A 0.25A 2A 0.5A 0.27A
40ms and then resets when the ACB is tripped Type Rated Current (Inductive) 0.2A 0.2A 0.7A 0.2A 0.04A
by any one of the LTD, STD, INST/MCR or
GFT functions. Output is on terminals 22 and
23. 1) All contacts are voltage-free and operate as following table
2
Individual contact and LED type Type of OCR Auto. Reset Contacts *1 Hold Contacts *2
This type has an individual contact and LED For general
for LTD, STD and INST/MCR., and GFT over- feeder PRE-TRIP LTD, STD, INST/MCR, GFT
current functions. The PRE-TRIP function is (L, M char.) System Alarm
incorporated on OCRs with these type of indi- For generator
cators and a corresponding contact and LED protection LTD, STD, INST/MCR System Alarm
are fitted. Additionally a SYSTEM ALARM (S char.) PRE-TRIP
contact and LED are provided to give warning
of abnormality in the OCR unit.
A separate control supply is required for these Notes:
indicators. (A) Contacts
*1:The contacts for LTD, STD, INST/MCR close for 40ms and then reset.
The contact for PRE-TRIP resets when the current level drops below pick-up setting
*2:The contacts remain until the RESET button on the front of the OCR is operated. (Remote
resetting can be achieved by disconnection of the control supply)
**: STD and INST/MCR is common terminal.

(B) LEDs
LEDs (except for PRE-TRIP) remain until the RESET button is operated or the control supply
is disconnected.
LED for PRE-TRIP goes out when the current level drops below pick-up setting.

UPS Backup power supply

This unit provides a constant supply for the display indicators (LEDs & volt free contacts) in
the event of a power failure for up to 1 hour. It contains rechargeable batteries which will be
maintained at full charge through the AC supply voltage.

Spec Unit 1 Unit 2


Input voltage 230 ~ 240V AC 220 ~ 230V
Output 24V DC 24V DC

Outline dimensions on page 53.


For further information contact Terasaki for details.

DC Power supply

Systems utilizing a control voltage of 30, 48 or 60V D.C. must use the D.C. power supply module
for the O.C.R. to work effectively. See page 53 for more information.

MHT Manual reset

The option of a manual MHT reset button is available upon request.


This button protrudes through the ACB label and must be depressed following an overcurrent
trip in order to close the ACB.

3
4
OCR Specification
Multi-function protection device

OCR specifications

The multi-function protection device for Tem- The OCR range is divided into three groups: Optional protection functions, indication and a
Power is an 8-bit microprocessor controlled , •AOR-1BL (standard inverse characteristic) current monitoring facility are available.
r.m.s. sensing overcurrent relay (OCR). •AOR-1BM (very/extremely inverse
characteristic)
•AOR-1BS (generator protection).

Protection functions Trip indicators


3
Protection Type LTD
1
Single Individual Current Field Control voltage
characteristic STD PRE-TRIP GFT N-phase contact contact and monitoring test
INST type LED type function facility

AOR-1BL-AL 2 Not required


AOR-1BL-GL Not required
AOR-1BL-AS Required
L-characteristic

AOR-1BL-GS 4 Required
AOR-1BL-NS Required
AOR-1BL-ES Required
AOR-1BL-AI Required
AOR-1BL-GI 4 Required
General feeder

AOR-1BL-NI Required
AOR-1BL-EI Required
AOR-1BM-AL2 Not required
AOR-1BM-GL Not required
AOR-1BM-AS Required
M-characteristic

AOR-1BM-GS 4 Required
AOR-1BM-NS Required
AOR-1BM-ES Required
AOR-1BM-AI Required
AOR-1BM-GI 4 Required
AOR-1BM-NI Required
AOR-1BM-EI Required
AOR-1BS-AL 2 Not required
S-characteristic

AOR-1BS-AS Required
Generator
Protection

4
AOR-1BS-NS Required
AOR-1BS-AI Required
4
AOR-1BS-NI Required

Notes:
1 : Not available when [ICT] is 80, 160 or 250A

2 : ANR-1 OCR checker required to meet NK standard.

3 : Long time-delay, short time-delay, instantaneous and ground fault will still operate even if the control voltage is lost.

4 : With MCR function

Type code

AOR-1B L – A L

L-characteristic A with LTD, STD, INST. L Single contact type


M-characteristic G A+Ground fault protection S Individual contact and LED type and pre-trip alarm
S-characteristic N A+Neutral pole protection I features of S and Current monitoring
E N+Ground fault protection

Field test facility

Field test-facility is included on versions of AOR-1B that have indication LEDs and contacts. This
function permits a simple field check to be performed on the LTD, STD and INST characteristics.
TRIP or NON-TRIP tests of the circuit breaker are possible. To operate push button on OCR (trip
indication is by the LEDs on the front of the AOR-1B).

4
OCR Specification
Accessories 4
OCR checker (external) Electromagnetic inst. trip

ANH-1B ANR-1 Portable checker This is a direct-acting non-adjustable, instanta-


neous trip device. (Not available for AT40).
Type ANH-1B OCR checker operates on The ANR-1 portable checker permits field
100-110V AC and permits overcurrent release checking of the tripping functions of the Pick-up current settings
tests without requiring any special skill. Ideal AOR-1B range of OCRs.
for inspection, testing and maintenance pur- AT06 AT25 AT32
poses. AT12
AT16
AT20
3kA 7.5kA 10kA
5 10 15
7.5 15 20
10 20 25
15 25 30
20 30 40
25

OCR alarm switch

Rated Voltage 100-110V AC 50/60Hz The OCR Alarm switch (normally open con-
Power Consumption 500VA tact) indicates the operation of the electro-
Overcurrent trip device magnetic instantaneous trip device only. ON
calibration tests: for 40 ms, then OFF.
•Long time-delay trip
•Short time-delay trip Rated Voltage 100/110V AC 50/60Hz Rating of contact
Test Functions •Instantaneous trip or 9V DC battery
•Pre-trip Alarm Power Consump'n 10VA Load Resistive Lamp Inductive Motor
•Ground fault trip Long time-delay trip check AC 125V 5A 0.7A 3A 0.7A
Continuity check of Test Functions Short time-delay trip AC 250V 3A 0.5A 2A 0.5A
current transformers Instantaneous trip check DC 30V 5A 3A 4A 3A
Outline Dimensions W365xH257xD300(mm) Outline Dim. W92 x H146 x D37(mm) DC 125V 0.4A 0.05A 0.4A 0.05A
Weight 15kg Weight 700g DC 250V 0.2A 0.03A 0.2A 0.03A

Current transformer for neutral line

Ground fault protection in a 3-phase, 4-wire •Outline dimensions of CT for neutral line
system is possible with a 3-pole breaker using M5 50 AT06, AT12, AT16, AT20, AT20L
the ground fault trip function, In this application
a neutral line current transformer that matches k l Type CW80 - 40LS
the breaker’s ground fault protection charac- L L K Rated 320 1600
teristic should be used. Primary 630
TERASAKI can provide CT for Neutral line. Current (A) 1250
A neutral line CT is built into the 4-pole type
150
80
30

when the breaker ground fault protection is Rated secondary current is 5A


used.
70

If line fed ‘K’ should face towards the line side.


4-ø7
If load fed ‘K’ should face towards the load
side. 30 80
70 100
80
•Neutral CT connection diagram 125

60 M5
N-Line AT20, AT20L, AT25, AT25L, AT32, AT40
Type CW160 - 40LS
K k l L Rated 500 2000
K k 30 29 K 4-M5 Tap
k for fixing Primary 1000 2500
L l k
Neutral CT
l
l k secondary Current 1600 3200
l
wiring (A) 4000
255

n kc kb ka g
0
ø16
Rated secondary current is 5A
OCR
125

4-ø10

160 120
ACB (3 pole) 235 150
Example: for AT25-AT40 types

5
4 OCR Specification - General feeder circuits
L-Type standard inverse characteristic curve

Setting range of protection functions

Protection Functions Setting Range


Characteristics
LTD
Pick-up current [I1] (A) [I0] x (0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05 – 1.1 – NON) 8 graduations
Non-tripping at [I1] setting x 105% and below. Tripping at 120% and above.
Time-delay [T1] (s) (0.5 – 1.25 – 2.5 – 5 – 10 – 15 – 20 – 25 – 30) at [I1] x 600% current. 9 graduations
Setting tolerance (%) ±15% (±20% when [ICT] of type AT06 is 80A or 160A)
STD
Pick-up current [I2] (A) [I0] x (1 – 1.5 – 2 – 2.5 – 3 – 4 – 6 – 8 – 10 – NON) 10 graduations
Setting tolerance (%) ±15%
Time-delay [T2] (ms)
Relay-time (ms) 10 graduations 80 160 240 320 400 480 560 640 800 1000
Opening time (ms) 100 180 260 340 420 500 580 660 820 1020
Resettable time (ms) 55 135 215 295 375 455 535 615 775 975
Max. total clearing time (ms) 150 230 310 390 470 550 630 710 870 1070
INST or MCR
Pick-up current [I3] (A) [I0] x (2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) 9 graduations
Setting tolerance (%) ±20%
PRE-TRIP
Pick-up current [IP] (A) [I0] x (0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05 – 1.1) 8 graduations
Setting tolerance (%) ±7.5% (±10% when [ICT] of type AT06 is 80A or 160A)
Time-delay [TP] (s) (60 – 80 – 100 – 120 – 140 – 160 – 180 – 200) at over [IP] setting. 8 graduations
Setting tolerance (%) ±15%
GFT
Note: Ground fault current setting [IG] should be below 1200A.
Pick-up current [IG] (A) [ICT] x (0.1 – 0.15 – 0.2 – 0.25 – 0.3 – 0.35 – 0.4) 7 graduations
Setting tolerance (%) ±20%
Time-delay [TG] (ms)
Relay-time (ms) 10 graduations 80 160 240 320 400 480 560 640 800 1000
Opening time (ms) 100 180 260 340 420 500 580 660 820 1020
Resettable time (ms) 55 135 215 295 375 455 535 615 775 975
Max. total clearing time (ms) 150 230 310 390 470 550 630 710 870 1070
N-phase Protection
Pick-up current [IN] (A) [ICT] x (0.2 – 0.25 – 0.32 – 0.4 – 0.5 – 0.63 – 0.8 – 1.0) Fixed setting. Specify at time of order.
Non-tripping at [IN] setting x 105% and below. Tripping at 120% and above.
Time-delay [TN] (s) [TN = T1] 9 graduations using [T1] setting dial at [IN] x 600% current
Setting tolerance (%) ±15% (±20% when [ICT] of type AT06 is 80A or 160A)

Control Power AC, DC 100-250V or DC24V / 5VA

[ICT] and Base current


[I0] Values
Type Applicable Base current [I0] (A) Type Applicable Base current [IO] (A)
[ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT]
(A) x 0.5 x 0.63 x 0.8 x 1.0 (A) x 0.5 x 0.63 x 0.8 x 1.0
AT06 80 40 50 63 80 AT20 320 160 200 250 320
160 80 100 125 160 AT20L 630 320 400 500 630
320 160 200 250 320 1250 630 800 1000 1250
630 320 400 500 630 1600 800 1000 1250 1600
AT12 320 160 200 250 320 2000 1000 1250 1600 2000
630 320 400 500 630 AT25 250 125 160 200 250
1250 630 800 1000 1250 500 250 320 400 500
AT16 320 160 200 250 320 1000 500 630 800 1000
630 320 400 500 630 2000 1000 1250 1600 2000
1250 630 800 1000 1250 2500 1250 1600 2000 2500
1600 800 1000 1250 1600 AT25L 2500 1250 1600 2000 2500
AT32 1600 800 1000 1250 1600
3200 1600 2000 2500 3200
AT40 4000 2000 2500 3200 4000
Note: Standard settings are underlined

6
OCR Specification
Multi-function protection device 4
Front face of multi-function protective device

Type: AOR-1BL-GS
6 5 1 2 3 4
1. Base current setting dial
2. LTD pick-up current setting dial
LTD time-delay setting dial
3. STD pick-up current setting dial
STD time-delay setting dial
4. INST pick-up current setting dial 7
5. PRE-TRIP pick up current setting dial
PRE-TRIP time-delay setting dial 9
6. GFT pick-up current setting dial 8
GFT time-delay setting dial
14
7. HOT/COLD select switch
8. INST/MCR select switch 10
9. Ramp characteristic select switch
10. LED for trip indicator
11. LED for system alarm indicator
11 13
12. Field test facility
13. Reset button
14. Test terminals (for ANR-1)
15. Trip indicator contact terminals
16. Control power terminals. 15 12 16

Multi-function protection c haracteristics

4
3
2 LTD current setting range
hour

N-phase current setting range


1 PRE-TRIP current setting range
50
40
30 GFT current setting range STD current setting range
20

10
INST current setting range
minute

8
6
5
4
3
2
PRE-TRIP time
setting range
1
50
40
30

20
Operating time

10 N-phase time
8
setting range LTD time
6
5 setting range
4
3
2

1
0.8 1000ms 1000ms
second

0.6
0.5
0.4 400ms
400ms
0.3 STD time
0.2 GFT time
setting range
setting range
0.1
0.08 80ms 80ms
0.06
0.05
0.04
0.03
0.02

0.01
0.008
0.006
0.005
400
7
8
9
10

15

20

30

40

50
60
70
80
90
100
125
150

200
60
70
80
90
100
125

150

200
250
300

500
600
700
800
900
1000

1500

2000
2500
3000

Percent rated current of OCR CT primary current [ICT] Percent rated current of base current [IO]

7
4 OCR Specification - General feeder circuits
M-Type very/extremely inverse characteristic curve

Setting range of protection functions

Protection functions Setting range


Characteristics
LTD
Pick-up current [I1] (A) [I0] x (0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05 – 1.1 – NON) 8 graduations
Non-tripping at [I1] setting x 105% and below. Tripping at 120% and above.
Time-delay [T1] (S) (1 – 2 – 3 – 4 – 5) at [I1] x 300% current. 5 graduations
Setting tolerance (%) ±20% (±30% when [ICT] of type AT06 is 80A or 160A)

STD
Pick-up current [I2] (A) [I0] x (1 – 1.5 – 2 – 2.5 – 3 – 4 – 6 – 8 – 10 – NON) 10 graduations
Setting tolerance (%) ±15%
Time-delay [T2] (ms)
Relay-time (ms) 10 graduations 80 160 240 320 400 480 560 640 800 1000
Opening time (ms) 100 180 260 340 420 500 580 660 820 1020
Resettable time (ms) 55 135 215 295 375 455 535 615 775 975
Max. total clearing time (ms) 150 230 310 390 470 550 630 710 870 1070

INST or MCR
Pick-up current [I3] (A) [I0] x (2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) 9 graduations
Setting tolerance (%) ±20%

PRE-TRIP
Pick-up current [IP] (A) [I0] x (0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05 – 1.1) 8 graduations
Setting tolerance (%) ±7.5% (±10% when [ICT] of type AT06 is 80A or 160A)
Time-delay [TP] (s) (60 – 80 – 100 – 120 – 140 – 160 – 180 – 200) at over [IP] setting. 8 graduations
Setting tolerance (%) ±15%

GFT Note: Ground fault current setting [IG] should be below 1200A.
Pick-up current [IP] (A) [ICT] x (0.1 – 0.15 – 0.2 – 0.25 – 0.3 – 0.35 – 0.4) 7 graduations
Setting tolerance (%) ±20%
Time-delay [TG] (ms)
Relay-time (ms) 10 graduations 80 160 240 320 400 480 560 640 800 1000
Opening time (ms) 100 180 260 340 420 500 580 660 820 1020
Resettable time (ms) 55 135 215 295 375 455 535 615 775 975
Max. total clearing time (ms) 150 230 310 390 470 550 630 710 870 1070
N-phase Protection
Pick-up current [IN] (A) [ICT] x (0.2 – 0.25 – 0.32 – 0.4 – 0.5 – 0.63 – 0.8 – 1.0) Fixed setting. Specify at time of order.
Non-tripping at [IN] setting x 105% and below. Tripping at 120% and above.
Time-delay [TN] (s) [TN=T1] 5 graduations using [T1] setting dial at [IN] x 300% current
Setting tolerance (%) ±20% (±30% when [ICT] of type AT06 is 80A or 160A)

Control Power AC, DC 100-250V or DC24V / 5VA

[ICT] and Base current


[I0] Values
Type Applicable Base current [I0] (A) Type Applicable Base current [I0] (A)
[ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT] [ICT]
(A) x 0.5 x 0.63 x 0.8 x 1.0 (A) x 0.5 x 0.63 x 0.8 x 1.0
AT06 80 40 50 63 80 AT20 320 160 200 250 320
160 80 100 125 160 AT20L 630 320 400 500 630
320 160 200 250 320 1250 630 800 1000 1250
630 320 400 500 630 1600 800 1000 1250 1600
AT12 320 160 200 250 320 2000 1000 1250 1600 2000
630 320 400 500 630 AT25 250 125 160 200 250
1250 630 800 1000 1250 500 250 320 400 500
AT16 320 160 200 250 320 1000 500 630 800 1000
630 320 400 500 630 2000 1000 1250 1600 2000
1250 630 800 1000 1250 2500 1250 1600 2000 2500
1600 800 1000 1250 1600 AT25L 2500 1250 1600 2000 2500
AT32 1600 800 1000 1250 1600
3200 1600 2000 2500 3200
AT40 4000 2000 2500 3200 4000

Note: Standard settings are underlined.


With I3t (very inverse) / I4t (extremely inverse) please specify at time of order.

8
OCR Specification-General feeder circuits
M-Type very/extremely inverse characteristic curve 4
Front face of multi-function protective device

Type: AOR-1BM-GS
1. Base current setting dial
2. LTD pick-up current setting dial
LTD time-delay setting dial 6 5 1 2 3 4
3. STD pick-up current setting dial
STD time-delay setting dial
4. INST pick-up current setting dial
5. PRE-TRIP pick up current setting dial
PRE-TRIP time-delay setting dial
6. GFT pick-up current setting dial 7
GFT time-delay setting dial
7. HOT/COLD select switch 9
8. INST/MCR select switch 8
9. Ramp characteristic select switch 14
10. LED for trip indicator
11. LED for system alarm indicator 10
12. Field test facility
13. Reset button
14. Test terminals (for ANR-1) 11 13
15. Trip indicator contact terminals
16. Control power terminals.

15 12 16

Multi-function protection characteristics

4
3
N-phase current setting range LTD current setting range
2
hour

PRE-TRIP current setting range


1
50
40 STD current setting range
30

20 GFT current setting range

10 INST current setting range


minute

8
6
[I4t] extremely 5
4
inverse 3
PRE-TRIP time
2
setting range
[I3t] very inverse
1
50
40
[I4t] extremely
30 inverse
20
Operating time

[I3t] very inverse


10
8
6
5
4
3
N-phase time
2
setting range
1000ms 1000ms
1
0.8
second

0.6
0.5
400ms 400ms
0.4 STD time
0.3 setting range
GFT time
0.2 setting range

0.1
80ms 80ms
0.08
0.06
0.05
0.04
0.03
0.02

0.01
0.008
0.006
0.005
400
7
8
9
10

15

20

30

40

50
60
70
80
90
100
125
150

200
60
70
80
90
100
125

150

200
250
300

500
600
700
800
900
1000

1500

2000
2500
3000

Percent rated current of OCR CT primary current [ICT] Percent rated current of base current [IO]

9
4 OCR Specification
S-Type : Generator protection

Setting range of protection functions

Protection functions Setting range


Characteristics
LTD
Pick-up current [I1] (A) [I0] x (0.8 – 1.0 – 1.05 – 1.1 – 1.15 – 1.2 – 1.25 – NON) 8 graduations
Setting tolerance (%) ±5% (±10% when [ICT] of type AT06 is 80A or 160A)
Time-delay [T1] (S) (15 – 20 – 25 – 30 – 40 – 50 – 60) at [I1] x120% current. 7 graduations
Setting tolerance (%) ±15% (±20% when [ICT] of type AT06 is 80A or 160A)
STD
Pick-up current [I2] (A) [I0] x (2 – 2.5 – 2.7 – 3 – 3.5 – 4 – 4.5 – 5 – NON) 9 graduations
Setting tolerance (%) ±10% (±15%when [ICT] of type AT06 is 80A or 160A)
Time-delay [T2] (ms)
Relay-time (ms) 10 graduations 80 160 240 320 400 480 560 640 800 1000
Opening time (ms) 100 180 260 340 420 500 580 660 820 1020
Resettable time (ms) 55 135 215 295 375 455 535 615 775 975
Max. total clearing time (ms) 150 230 310 390 470 550 630 710 870 1070
INST or MCR
Pick-up current [I3] (A) [I0] x (2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) 9 graduations
Setting tolerance (%) ±20%.
PRE-TRIP
Pick-up current [IP] (A) [I0] x (0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05 – 1.1) 8 graduations
Setting tolerance (%) ±5% (±10% when [ICT] of type AT06 is 80A or 160A).
Time-delay [TP] (s) (5 – 10 – 15 – 20 – 25 – 30 – 35 – 40 – 45) at [IP] x 120% current 9 graduations
Setting tolerance (%) ±15% (±20% when [ICT] of type AT06 is 160A or 80A)
N-phase Protection
Pick-up current [IN] (A) [I0] x (0.2 – 0.25 – 0.32 – 0.4 – 0.5 – 0.63 – 0.8 – 1.0) Fixed setting. Specify at time of order.
Setting tolerance (%) ±7.5%
Time-delay [TN] (s) [TN] = [T1] 7 graduations using [T1] setting dial at [IN] x 120% current
Setting tolerance (%) ±15% (±20% when [ICT] of type AT06 is 80A or 160A)

Control Power AC, DC 100-250V or DC24V / 5VA

Acceptable range of base current [I0]


for the rated generator current [IGEN]
Type Rated primary [IGEN] = [I0]
current [ICT] (A) range (A)
AT06 80 40 ≤ [I0] ≤ 80
160 80 < [I0] ≤ 160
320 160 < [I0] ≤ 320
630 320 < [I0] ≤ 630
AT12 320 160 ≤ [I0] ≤ 320
630 320 < [I0] ≤ 630
1250 630 < [I0] ≤ 1250
AT16 320 160 ≤ [I0] ≤ 320
630 320 < [I0] ≤ 630
1250 630 < [I0] ≤ 1250
1600 800 ≤ [I0] ≤ 1600
AT20 320 160 ≤ [I0] ≤ 320
630 320 < [I0] ≤ 630
1250 630 < [I0] ≤ 1250
1600 800 ≤ [I0] ≤ 1600
2000 1000 ≤ [I0] ≤ 2000
AT25 250 125 ≤ [I0] ≤ 250
500 250 < [I0] ≤ 500
1000 500 < [I0] ≤ 1000
2000 1000 < [I0] ≤ 2000
2500 1250 < [I0] ≤ 2500
AT32 1600 800 ≤ [I0] ≤ 1600
3200 1600 < [I0] ≤ 3200
AT40 4000 2000 ≤ [I0] ≤ 4000

Note : Standard settings are underlined.

10
OCR Specification
S-Type : Generator protection 4
Front face of multi-function protective device

Type: AOR-1BS-AS
1. LTD pick-up current setting dial
LTD time-delay setting dial
2. STD pick-up current setting dial 4 1 2 3
STD time-delay setting dial
3. INST pick-up current setting dial
4. PRE-TRIP pick up current setting dial
PRE-TRIP time-delay setting dial
5. HOT/COLD select switch
6. INST/MCR select switch 5
7. Ramp characteristic select switch
8. LED for trip indicator 7
9. LED for system alarm indicator
6
10. Field test facility 12
11. Reset button 8
12. Test terminals (for ANR-1)
13. Trip indicator contact terminals
14. Control power terminals.
9 11

13 10 14

Multi-function protection characteristics

4
3

2
PRE-TRIP current setting range
hour

1
50 LTD current setting range
40
30
STD current setting range
20
N-phase current setting range
10
8
minute

6 INST current setting range


5
4
3

1
50
40
30
N-phase time LTD time
20
setting range setting range
PRE-TRIP time
Operating time

10 setting range
8
6
5
4
3
2

1
0.8 1000ms
second

0.6
0.5
0.4
400ms
0.3 STD time
0.2 setting range

0.1
0.08
80ms
0.06
0.05
0.04
0.03
0.02

0.01
0.008
0.006
0.005
1500
7
8
9
10

15

20

30

40

50
60
70
80
90
100
125

150

200

250
300

400

800
900
1000

2000

2500
3000
500
600
700

Percent rated current of generator [IO]

11
4 TemTrip
Intelligent protection relay

Specifications

TemTrip is a multi-function microprocessor based protection relay. The standard model provides
3 phase overcurrent & earth fault protection. However, options of undervoltage and reverse
power protection can be incorporated.
It can be fitted integral with the TemPower ACB (PRQ-2) or can be supplied separately, panel
mounted (PRQ-1). Refer to TemTrip catalogue I73Ea for further information.

• True r.m.s. monitoring eliminates nuisance


tripping on overloads due to harmonic
distortion.

• Built in O.C.R. checker to enable full


calibration check on site. Can also check on-
line.

• Integral L.E.D display provides information


on phase currents, fault magnitude and
tripping time.

• Optional communication to Trends' building


management systems.

COMPATIBLE

True r.m.s. sensing

Ground Fault Pre-operation Overcurrent protective Reverse power Undervoltage


protective alarm characteristic protective protective
characteristic characteristic characteristic characteristic
hour

Standard inverse
Very inverse
Extremely inverse
Definite
minute
Operating time

Ramped

Ramped Definite

Definite
second

Inverse

Generator
protection

% in reference to rated cur- % in reference to % in reference to rated % in reference to rated


rent (ICT) transformer current base current (IO) % in reference to base current (IO) power (PR) voltage (UR)

12
TemTrip
Intelligent protection relay 4
Protection functions

AL AS AI. AP AG PRQ-1LA PRQ-2LA

AL AS AI. AP AG PRQ-1MA PRQ-2MA

AL AS AI. AP AG PRQ-1NA PRQ-2NA


General feeder

AL AS AI. AP AG AU PRQ-1LU PRQ-2LU


protection

AL AS AI. AP AG AU PRQ-1MU PRQ-2MU

AL AS AI. AP AG AU PRQ-1NU PRQ-2NU

AL AS AI. AP AG AR AU PRQ-1LR PRQ-2LR

AL AS AI. AP AG AR AU PRQ-1MR PRQ-2MR

AL AS AI. AP AG AR AU PRQ-1NR PRQ-2NR

AL AS AI. AP PRQ-1SA PRQ-2SA


Generator
protection

AL AS AI. AP AU PRQ-1SU PRQ-2SU

AL AS AI. AP AR AU PRQ-1SR PRQ-2SR

AL Long time-delay AS Short time-delay AU Undervoltage trip


Stand.Inverse (L)
AL Long time-delay AI. Instantaneous trip AR Reverse power trip
Very Inverse (M)
AL Long time-delay AG Ground fault trip
Extrem. Inverse (N)
AL Long time-delay AP Pre-trip alarm
Gen. Protection (S)

Note : PRQ-2, the user can select between INST. or MCR (making current release).

TemCurve - Selectivity analysis software

To compliment the flexibility of the TemTrip multi-function protection


relay we have available a selectivity software program called
TemCurve.
This software program takes full advantage of the number of time
current characteristic curves on offer by the mircroprocessor protection
relay. Ground fault studies can also be carried out.
Enabling selectivity levels to be checked in minutes rather than
hours, TemCurve is a time saving breakthrough in the production of
accurate selectivity studies.
For further information please contact Terasaki's projects division.

Extensive database comprises


• MCBs
• Thermal magnetic & microprocessor MCCBs
• Overcurrent relays for ACBs
• LV & HV fuses
• MCGG & CDG relays

13
4 TemTrip
Intelligent protection relay

PRQ-2 Settings

Protective functions Pick-up setting range Time setting range


Pre-ope. alarm For general feeder Base current [IO] X 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 60, 80, 100, 120, 140, 160, 180, 200s
AP
circuit use IP 1.1 (Tolerance ± 3%) TP (Tolerance ± 10%)
For generator protection Base current [IO] X 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 10, 15, 20, 25, 30, 35, 40, 45s
use IP 1.1 (Tolerance ± 3%) TP (Tolerance ± 10%)
Long time-delay Standard inverse Base current [IO] X NON, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 5, 10, 15, 20, 25, 30s
AL
trip (LTD) characteristic (L) I1 1.1 (Tolerance * 1) T1 (Tolerance ± 10%)
Very inverse Base current [IO] X NON, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5s
AL
characteristic (M) I1 1.1 (Tolerance * 1) T1 (Tolerance ± 15%)
Extremely inverse Base current [IO] X NON, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1, 1.5, 2, 2.5, 3, 3.5, 4, 4.5, 5s
AL
characteristic (N) I1 1.1 (Tolerance * 1) T1 (Tolerance ± 15%)
For generator protection Base current [IO] X NON, 0.8, 1.0, 1.05, 1.1, 1.15, 1.2, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60s
AL
use (S) I1 1.25 (Tolerance ± 3%) T1 (Tolerance ± 10%)
Short time-delay For general feeder Base current [IO] X NON, 4, 5, 6, 7, 8, 9, 10 50,100,150, 200, 250, 300, 350, 400ms
trip (STD) circuit use I2 (Tolerance ± 10%) T2 (Tolerance (T2 ± 20ms) ± 10%)
AS
For generator protection Base current [IO] X NON, 2, 2.5, 3, 3.5, 4, 4.5, 5 50,100,150, 200, 250, 300, 350, 400ms
use I2 (Tolerance ± 10%) T2 (Tolerance (T2 ± 20ms) ± 10%)
I2t ramp characteristic *2
Instantaneous Base current [IO] X NON, 4, 6, 8, 10, 12, 14, 16
AI
trip (INST) I3 (Tolerance ± 15%)
Ground fault AS definite CT rated current [ICT] X NON, 0.1, 0.15, 0.2, 0.25, 0.3 50,100,150, 200, 250, 300, 350, 400ms
trip (GFT) characteristic IG 0.35,0.4 (Tolerance ± 15%) TG (Tolerance (TG ± 20ms) ± 10%)
AG
I2t ramp characteristic *2
Reverse power For generator protection Rated power [PO] X NON, 0.02, 0.05, 0.08, 0.11, 0.14 2.5, 5, 7.5, 10, 12.5, 15, 17.5, 20
AR
trip (RPT) use 0.17, 0.2 (Tolerance ± 10%) TR (Tolerance ± 20%)
Undervoltage Rated voltage [UR] X NON, 0.8, 0.825, 0.85, 0.875, 0.9 0,0.1,0.2,0.3,0.4,0.5,0.6,0.7,0.8,1.0s
AU
trip (UVT) 0.925, 0.95 (Tolerance ± 5%) TU (Tolerance (TU ± 70ms) ± 5%)

Note :*1: Non-tripping at [I1] setting X 105% and below. Tripping at 120% and above.
*2 [I2t] Ramp characteristic Base Current [I0]
Characteristic change-over switches
Use these switches to change • Base current [IO] is the reference current
the AS and AG characteristics. value used to set operation values.
Change-over IN OUT • Base current [IO] can be adjusted in three
AS I2t ramp characteristic definite characteristic
steps; 0.63, 0.8, or 1.0 times CT rated cur-
AG I t ramp characteristic
2
definite characteristic
rent [ICT]. (For general feeder circuit use)

The following features on TemTrip can be supplied as an option.

Breaker A
Over temperature detection Zone interlocking TemTrip

By monitoring the temperature of the contacts This new technique of selectivity was devel-
Fault Point
it is possible to inform the user if contacts oped to overcome the drawbacks of long
Zone 3
require 'dressing' thus providing maintenance time delays associated with time discrimina-
information, other applications could be detec- tion. Zone interlocking can be applied to both
tion of inadequate ventilation or de-rating serial and parallel networks to obtain full selec-
within the switchboard. tivity whilst still maintaining instantaneous trip- Breaker B
TemTrip
ping. For further information please consult
TemTrip I73E catalogue.
Fault Point
Zone 4
Arcing fault detection

An arcing fault can be very destructive due to Breaker C TemTrip


its high energy content. Using fibre optic sen-
sors it is possible to detect the initial build up
of the arcing fault and extinguish it instantane- Fault Point
ously thus preventing severe damage to the Zone 5
switchboard.

14
TemTrip
Intelligent protection relay 4
Data communication Functions of the remote monitor

Information gathered by the TemTrip intelligent 1 Breaker status indication 4 Setting zone selective interlock
relay can be displayed on a PMQ-1B remote (open/closed/tripped) • Zone setting can be changed or cleared
monitor. Using fibre optic cable to obtain high • Phase A current on the LCD screen.
information reliability, one PMQ-1B monitor • Phase B current
can be connected to eight TemTrips. Up to five • Phase C current 5 Fault type, trip current and
PMQs may then be connected via an RS485 • Ground fault current operation time indication.
connection which would enable 40 TemTrips to All current is indicated in Amps
be viewed on a building management system Transmitting data to PC
6
(B.M.S.) or supervisory control and data 2 Power indication (via RS-232C)
acquisition system (S.C.A.D.A.)
3 Line voltage indication

Function of the Remote Monitor

TemTrip No.1 TemTrip No.8

B.M.S. supervisor

PMQ-1B monitor

1 fibre optic cable


2 RS 232C serial interface

The information viewed on the Remote Monitor can be further transmitted to a Trend Building Management System utilising
COMPATIBLE a device known as a Terasaki Node Controller (T.N.C.). Standard user software can be supplied for viewing on a Trend 945
Supervisor. For further information please contact Terasaki.

Schematic single line diagram providing status Unique user pages showing breaker location, Graphical display of current, voltage, & power
overview settings, electrical parameters and fault trend logs
information

15
5 Outline Dimensions (mm)
• Type AT06,12,16 & 20 (with horizontal terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type FIXED TYPE
* The required distance is 625 mm.
Panel cut-out P P
C : front panel centre line C 207 (3P)
207 292 (4P)
P 175 (3P) 195 (3P)
C
175 260 (4P) 195 280 (4P)
142.5 (3P) 187.5 (3P)
142.5 227.5 (4P) 187.5 272.5 (4P) control circuit terminals
auxiliary switch 28-M3.5 screws
arc barrier 2
terminal
2-ø 12 screw,M3.5
250
Fixing blocks
with ø12 holes.
Blocks are fitted

25
when the
breaker is sub-
ject to marine

*545 (min.)
N classification
society rules.
R116 1 Secure these
380

260
332.5
270
301

blocks to the
switchboard
frame.
145
20

50

55
30

90 (3P)

153 (3P) 230


rear panel cut 4-ø14
238 (4P) draw-out handle 260
130 (3P) mtg. holes
3 front panel cut 130 215 (4P)
1-ø9
184 (3P)
Note : 1 N is neutral pole of 4-pole breaker. 184 269 (4P)
2 Use arc barrier of a heat and flame resistant insulating material. (max.) (max.)
Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)

Fixed type P P
C 187.5 (3P) C : front panel centre line
187.5 272.5 (4P)

P 200 (3P)
C 162.5 285 (4P)
maintenance space
auxiliary switch
arc barrier 2
terminal screw, M3.5

(3P) (4P) control circuit


250 terminals 28-M3.5
screws
panel cut-out
600

*520 (min.)

N
1
260
270

30
25
100

230
260
4-ø14
255 (3P) 162.5 (3P)
255 340 (4P) 162.5 247.5 (4P) Mtg. holes

Note : 1 N is neutral pole of 4-pole breaker. 180 (3P)


2 Use arc barrier of a heat and flame resistant insulating material. 180 265 (4P)

16
Outline Dimensions (mm)
• Type AT06,12,16 & 20 (with horizontal terminals) 5
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 600 x (D) 456.5 AT06 AT12 AT16 AT20
a 25 30 30 30
t 8 10 15 20
dust plate 2-ø11 45 conductor overlap max. w 45 55 55 55
5
10

b 145.5 145.5 145.5 148.5


c 132 132 132 126
front panel

w
a
CONNECTED position
225 90 20
TEST position P
142.5 (3P) C
ISOLATED position arc barrier 2 227.5 (4P) 142.5
rear panel
15 30 (not supplied) 2-M10 tapped
A
Mtg. holes

t
461

6 306.2

380
b

85 85 85

20
25 116 153 (3P)
126 200 127.2 238 (4P)
draw-out position
333 81.8 M8 screw earth terminal
453.2

dust plate surface 4-ø14 Mtg. holes


A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules.
•Mounting angle steel not supplied.

32 conductor overlap max. AT06 AT12 AT16 AT20


2-ø11
dust a 25 30 30 30
406
5 plate
10

w
a

front 137 225 t 8 10 15 20


panel
arc barrier 2 21 w 45 55 55 55
55
b 120.5 120.5 120.5 123.5
237 23
c 132 132 132 126

P
N C
t
440

500
c
b

126 230 85 85 85

417
dust plate surface 4-ø14 Mtg. holes

•Mounting angle steel not supplied.


17
5 Outline Dimensions (mm)
• Type AT06,12,16 & 20 (with vertical terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type P
C : front panel centre line P 207 (3P)
207 C 292 (4P)
Fixing blocks with ø12
Panel cut-out 195 (3P) holes. Blocks are fitted
195 280 (4P) when the breaker is
P 187.5 (3P) subject to marine clas-
C 175 (3P) sification society rules.
187.5 272.5 (4P)
175 260 (4P) Secure these blocks to
auxiliary switch control circuit terminals the switchboard frame.
142.5 (3P) terminal screw, 28-M3.5 screws
142.5 227.5 (4P) M3.5
arc barrier 2

2-ø 12 250

25

*545 (min.)
N
R116
332.5
380

1
301

270

260
145
50

55
30

20

90 (3P)
P 153 (3P)
C 238 (4P) 1-ø9 230
rear panel cut 260 4-ø14 mtg. holes
130 (3P)
3 front panel cut 130 215 (4P)
draw-out handle 184 (3P)
Note : 1 N is neutral pole of 4-pole breaker. 184 269 (4P)
2 Use arc barrier of a heat and flame resistant insulating material. (max.) (max.)
Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)

18
Outline Dimensions (mm)
• Type AT06,12,16 & 20 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 600 x (D) 456.5
5
AT06 AT12 AT16 AT20
a 25 30 30 50
dust plate b 12.5 12.5 17.5 15
5
10

t 8 10 15 15
w 50 55 65 80
front panel øD 2-ø11 2-ø11 2-ø11 3-ø12
c 120.5 115.5 105.5 100.5
225 90 d 82 82 82 62
CONNECTED position
TEST position 2-M10 tapped
rear panel mtg holes
ISOLATED position arc barrier 2 142.5 (3P) P
(not supplied) C
15 30 227.5 (4P) 142.5
conductor overlap max.
A

b
N

w
a
45

b
b
øD

w
a
6 306.2
b
461

380
Terminal
dimensions of

w
types AT06 to
AT16
t

20
c
85 85 85

25
116 øD 153 (3P)
20
126 200 127.2 238 (4P)
draw-out position
333 453.2 91.8 M8 screw earth
4-ø14 Mtg. holes terminal
dust plate surface
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules.
•Mounting angle steel not supplied.

19
5 Outline Dimensions (mm)
• Type AT25 (with vertical terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
FIXED TYPE P 252 (3P) Fixing blocks with
Draw-out type C
* The required distance is 625 mm. 252 367 (4P) ø12 holes. Blocks
Panel cut-out are fitted when the
P : front panel centre line 240 (3P)
P C breaker is subject
C 223 (3P) 240 355 (4P) to marine classifi-
223 338 (4P) cation society rules.
232.5 (3P)
232.5 347.5 (4P) Secure these blocks
187.5 (3P) to the switchboard
187.5 302.5 (4P) auxiliary switch control circuit terminals frame.
terminal screw, 28-M3.5 screws
2-ø 12 250 M3.5
arc barrier 2

25
*545 (min.)
R116
N
500
440

1
270

332.5

260
145

55
50
20
30

90 (3P)
198 (3P) 230
rear panel cut 313 (4P) draw-out 260 4-ø14 mtg. holes
handle 175 (3P)
3 front panel cut
1-ø9 175 290 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 229 (3P)
2 Use arc barrier of a heat and flame resistant insulating material. 229 344 (4P)
Cradle with arc barrier available on request. (max.) (max.)
3 If door flange is used, a large cut out is required. (260 x 280 mm)

P
C P
Fixed type 232.5 (3P) C : front panel centre line
232.5 347.5 (4P)
245 (3P)
207.5 360 (4P)

maintenance space auxiliary switch


P terminal
C screw, M3.5 arc barrier 2

panel cut-out
250 (3P) (4P) control circuit
terminals
28-M3.5 screws
*520 (min)
600

N
260

1
270
25

30
100

230
260 4-ø14 Mtg. holes
300 300 (3P)
415 (4P) 207.5 (3P)
207.5 322.5 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 225 (3P)
2 Use arc barrier of a heat and flame resistant insulating material. 225 340 (4P)
20
Outline Dimensions (mm)
• Type AT25 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 600 x (D) 456.5
5
Note:* 3.2 mm spacer required (not supplied)

dust plate
5
10

front panel
225 93 3.2* rear panel P
C
CONNECTED position (not supplied) 187.5 (3P) 2-M10 tapped mtg. holes
TEST position 302.5 (4P) 187.5
conductor
2
ISOLATED position arc barrier overlap max.
A N
15 30
3-ø12
45

20 30 30 20 20 30 30 20
15 25 2515 15 25 25 15

100
80
461

525

80

80
500
80
6 306.2

100
130

110
15 15
20

25
M8 screw
116 20 earth terminal 115 115 115 3-ø14
draw-out position 126 200 127.2 198 (3P)
333 453.2 81.8 313 (4P)
dust plate surface 4-ø14 Mtg. holes

A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.

N Neutral rated current 2000A

dust 406 conductor overlap max.


5 plate
10

137 225
front
panel 55

arc barrier 2

237 23
35 N
P
C
20 30 30 20 20 30 30 20
15 25 25 1515 25 25 15
140

100
80
500
440

80
10

80
80

80

100
105
185

85

15 15

3-ø12
126 230 21 115 115 115 3-ø14
417
dust plate surface
4-ø14 Mtg. holes
•Mounting angle steel not supplied.

1
5 Outline Dimensions (mm)
• Type AT25 (with horizontal terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
FIXED TYPE P 252 (3P) Fixing blocks with
Draw-out type C
* The required distance is 625 mm. 252 367 (4P) ø12 holes. Blocks
Panel cut-out are fitted when the
P : front panel centre line 240 (3P)
P C breaker is subject
C 223 (3P) 240 355 (4P) to marine classifi-
223 338 (4P) cation society rules.
232.5 (3P)
232.5 347.5 (4P) Secure these blocks
187.5 (3P) to the switchboard
187.5 302.5 (4P) auxiliary switch control circuit terminals frame.
terminal screw, 28-M3.5 screws
2-ø 12 250 M3.5
arc barrier 2

25
*545 (min.)
R116
N
500
440

1
270

332.5

260
145

55
50
20
30

90 (3P)
198 (3P) 230
rear panel cut 313 (4P) draw-out 260 4-ø14 mtg. holes
handle 175 (3P)
3 front panel cut
1-ø9 175 290 (4P)
Note : 1 N is neutral pole of 4-pole breaker.
2 Use arc barrier of a heat and flame resistant insulating material. 229 (3P)
Cradle with arc barrier available on request. 229 344 (4P)
3 If door flange is used, a large cut out is required. (260 x 280 mm) (max.) (max.)

2
Outline Dimensions (mm)
• Type AT25 (with horizontal terminals) 5
Note:* 3.2 mm spacer required (not supplied) N Neutral rated current 2000A

dust plate
5
10

front panel
225 93 3.2* rear panel P 2-M10 tapped
C
CONNECTED position (not supplied) 187.5 (3P) mtg. holes
TEST position 302.5 (4P) 187.5
2
ISOLATED position arc barrier A
N
15 30 45
80 80
50 50

15

60 50

60 50
525

500
80

80
461

15

50 60

50 60
6 306.2

20
100

100
20
25 10
3-ø14
M8 screw
116 earth terminal 115 115 115
draw-out position 126 200 127.2 198 (3P)
3-ø14
25 313 (4P)
333 453.2 32.8
dust plate surface 4-ø14 Mtg. holes
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.

3
5 Outline dimensions (mm)
• Type AT32 (with vertical terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 700 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type FIXED TYPE P 282 (3P) Fixing blocks
* The required distance is 675 mm. C
282 417 (4P) with ø12 holes,
P
Panel cut-out C : front panel centre line 270 (3P) blocks are fitted
when the
P 270 405 (4P)
C breaker is sub-
253 (3P)
262.5 (3P) ject to marine
253 388 (4P) classification
262.5 397.5 (4P)
society rules.
217.5 (3P)
auxiliary switch control circuit terminals Secure these
217.5 352.5 (4P) blocks to the
terminal screw, 28-M3.5 screws
250 switchboard
2-ø 12 M3.5
arc barrier 2 frame.

*545 (min.)
R116

25
N
500
440

260
270

332.5
145

55
50

20

90 (3P)
30

228 (3P) 230


rear panel cut 363 (4P) 260 4-ø14
205 (3P) mtg. holes
3 front panel cut 1-ø9 205 340 (4P)
Note: 1 N is neutral pole of 4-pole breaker. 259 (3P)
2 Use arc barrier of a heat and flame draw-out 259 394 (4P)
resistant insulating material. handle (max.) (max.)
Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)
P
P
C
262.5 (3P) C : front panel centre line
Fixed type 262.5 397.5 (4P)
275 (3P)
237.5 410 (4P)

maintenance space auxiliary switch


terminal screw
P 2
C M3.5 arc barrier
panel cut-out
(3P) (4P)

250
*520 (min)
600

N
1 control
260
270

circuit
terminals
28-M3.5
screws
25

30
100

230
330 (3P) 260 4-ø14
330 465 (4P)
237.5 (3P) Mtg. holes
237.5 372.5 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 255 (3P)
2 Use arc barrier of a heat and flame resistant insulating material. 255 390 (4P)

4
Outline dimensions (mm)
• Type AT32 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 700 x (D) 456.5
5
Note: *3.2mm spacer required (not supplied) N Neutral rated current 2000A

dust plate
5
10

front panel rear panel (not supplied)


conductor overlap max. 2-M10 tapped
93 P mtg holes
225 C
217.5 (3P)
CONNECTED position 3.2* 352.5 (4P) 217.5
TEST position
ISOLATED position 2
arc barrier N
A

15 30
45

15 30 30 30 15 15 30 30 30 15
15 25 25 15 15 25 25 15

120
80
461

80

80
500
306.2 525

80
6

120
130

90
15 18
20

25
M8 screw
116 earth terminal 4-ø14
135 135 135
126 200 127.2 20
draw-out position 228 (3P)
333 453.2 81.8 3-ø12 363 (4P)
dust plate surface 4-ø14 Mtg. holes
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.

N Neutral rated current 2000A

dust 406 conductor overlap max.


plate
5 225
10

137
front P
55 C
panel
arc barrier 2
N
237 23 35
15 30 30 30 15 15 30 30 30 15
15 25 2515 15 25 25 15
140

120
80
500
440

80
10

80
80

120
105

15 18
65

126 230 21 3-ø12 135 135 135 4-ø14


417
dust plate surface
•Mounting angle steel not supplied.

5
5
Outline dimensions (mm)
• Type AT32 (with horizontal terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 700 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type FIXED TYPE P 282 (3P)
* The required distance is 675 mm. C
282 417 (4P)
P
Panel cut-out C : front panel centre line 270 (3P) Fixing blocks with
ø12 holes, blocks
P 270 405 (4P) are fitted when
C 253 (3P) the breaker is
262.5 (3P)
253 388 (4P) subject to marine
262.5 397.5 (4P) classification
217.5 (3P) society rules.
auxiliary switch control circuit terminals Secure these
217.5 352.5 (4P) blocks to the
terminal screw, 28-M3.5 screws
switchboard
250 2-ø 12 M3.5 frame.
arc barrier 2

*545 (min.)
R116

25
N
500
440

260
270

332.5
145

55
50

20

90 (3P)
30

228 (3P) 230


rear panel cut 363 (4P) 260 4-ø14
205 (3P) mtg. holes
3 front panel cut 1-ø9 205 340 (4P)
Note: 1 N is neutral pole of 4-pole breaker. 259 (3P)
2 Use arc barrier of a heat and flame draw-out 259 394 (4P)
resistant insulating material. handle (max.) (max.)
Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)

6
5
Outline dimensions (mm)
• Type AT32 (with horizontal terminals)

Note: *3.2mm spacer required (not supplied) N Neutral rated current 2000A

dust plate
5
10

front panel rear panel (not supplied)


2-M10 tapped
93 P mtg holes
225 C
217.5 (3P)
CONNECTED position 3.2* 352.5 (4P) 217.5
TEST position
ISOLATED position 2
arc barrier N
A

15 30 55 80 100
45 50 70

15 (N)

60 50

60 60
20
461

80
525

80
500
20
306.2

100 50 60
6

60 60
20

90
25
20

M8 screw
116 earth terminal 3-ø14
135 135 135
draw-out position 126 200 127.2 10 228 (3P)
333 453.2 32.8 25 3-ø14 363 (4P)
dust plate surface 4-ø14 Mtg. holes
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.

7
5 Outline dimensions (mm)
• Type AT40 (with vertical terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 700 mm with respect to electrical devices,
grounded metal parts etc, located above.
FIXED TYPE
Draw-out type * The required distance is 675 mm. P 282 (3P)
C
282 417 (4P)
P
Panel cut-out C : front panel centre line 270 (3P)
P 270 405 (4P)
C 253 (3P) Fixing blocks with
253 388 (4P) 262.5 (3P) ø12 holes, blocks
are fitted when the
262.5 397.5 (4P) breaker is subject
217.5 (3P) to marine

217.5 352.5 (4P) auxiliary switch control circuit terminals classification society
rules. Secure these
terminal screw, 28-M3.5 screws blocks to the
250 M3.5 switchboard frame.
2-ø 12 arc barrier 2

*545 (min.)
25
R116
N
500
440

260
270

332.5
145

55
50

(3P)
30

20

90
228 (3P) 230
rear panel cut 363 (4P) 260 4-ø14 mtg.
205 (3P) holes
3 front panel cut 1-ø9 205 340 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 259 (3P)
draw-out handle 259 394 (4P)
2 Use arc barrier of a heat and flame resistant
insulating material. Cradle with arc barrier available on request. (max.) (max.)
3 If door flange is used, a large cut out is required. (260 x 280 mm)
P
C
Fixed type 262.5 (3P)
262.5 397.5 (4P)
275 (3P)
237.5 410 (4P)

maintenance space auxiliary switch


terminal screw
2
M3.5
P arc barrier
C panel cut-out
250 (3P) (4P)
600

*520 (min)

N control cir-
1 cuit
270

260

terminals
28-M3.5
screws
30
100

25

230
260 4-ø14 Mtg
330 330 (3P) . holes
237.5 (3P)
465 (4P) 237.5 372.5 (4P)
255 (3P)
Note : 1 N is neutral pole of 4-pole breaker. 255 390 (4P)
2 Use arc barrier of a heat and flame resistant insulating material.
8
5
Outline dimensions (mm)
• Type AT40 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 700 x (D) 456.5

Note: *3.2mm spacer required (not supplied) N Neutral pole rated current 2000A

dust plate
10

front panel rear panel (not supplied)


conductor overlap max. 2-M10 tapped
P
225 93 C mtg. holes
3.2* 217.5 (3P)
CONNECTED position 352.5 (4P) 217.5
TEST position
2
ISOLATED position arc barrier N
A

15 30
45

17.5
15 25 25 15 15 25 25 15

35 35 35

140
80

17.5
525

60
80
461

17.5

500
35 35 35
80
6 306.2

140
130

17.5
15 22

80
20

25
116 M8 screw
126 200 127.2 earth terminal 4-ø15
draw-out position 20 135 135 135
333 453.2 81.8
228 (3P)
4-ø14 mtg. holes 3-ø12 363 (4P)
dust plate surface
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.

N Neutral pole rated current 2000A

dust
406 conductor overlap max.
5 plate
10

137 225
front P
panel C
55
arc barrier 2
N
237 23

35
15 303030 1515 303030 15
15 2525 15 15 25 25 15
140

120
80
500
440

10

80
80
80

120
105

15 18
65

126 230 21 3-ø12 135 135 135 4-ø14


417
dust plate surface
•Mounting angle steel not supplied.

9
5 Outline dimensions (mm)
• Type AT06, 12, 16 & 20 (with front terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above. AT06 AT12 AT16 AT20
Draw-out type a 25 30 30 30
P
C : front panel centre line w 45 55 55 55
t 8 10 15 25
Panel cut-out d 11 11 11 12
207 207 (3P)
P 175 (3P) 292 (4P)
C
175 260 (4P) 195 195 (3P)
280 (4P)
142.5 (3P)
142.5 227.5 (4P) 187.5 187.5 (3P) control circuit terminals
auxiliary switch 272.5 (4P) 28-M3.5 screws
arc barrier 2
terminal
screw,M3.5
2-ø 12 250
Fixing blocks
with ø12 holes.
Blocks are fitted
when the

25
breaker is sub-

*545 (min.)
ject to marine
classification
N society rules.
Secure these
380

R116 1

260
301

blocks to the
270

332.5

switchboard
* frame.
145
50

55
20

90 (3P)
30

153 (3P) 230


rear panel cut 238 (4P) draw-out handle 260 4-ø14
130 (3P) mtg. holes
3 front panel cut 1-ø9 130 215 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 184 (3P)
2 Use arc barrier of a heat and flame resistant insulating material. 184 269 (4P)
Cradle with arc barrier available on request. (max.) (max.)
3 If door flange is used, a large cut out is required. (260 x 280 mm)
225 90
Dust plate
5
10

Connected

Front cover
Isolated

N
Test

arc barrier 2 P
15 30 C
20
*545

493
461
260

6 306.2
20
20

20

25
116
a 2-øD
126 200 127.2 w
t
Draw-out position
453.2 M8
333 32.8 85 85 85
Earth terminal
153 (3P)
Dustplate surface 238 (4P)
10
Outline dimensions (mm)
• Type AT25 (with front terminals)
Note: DRAW-OUT TYPE
5
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type P P Fixing blocks with
C : front panel centre line C 252 (3P)
367 (4P) ø12 holes. Blocks
252
Panel cut-out are fitted when the
240 (3P) breaker is subject to
P
C 223 (3P) 240 355 (4P) marine classification
223 338 (4P) society rules.
232.5 (3P)
232.5 347.5 (4P) Secure these blocks
187.5 (3P)
to the switchboard
187.5 302.5 (4P) auxiliary switch control circuit terminals frame.
terminal screw, 28-M3.5 screws
2-ø 12 250 M3.5
arc barrier 2

25
*545 (min.)
R116
N
500
440

1
332.5

260
270

145

55
50
20
30

90 (3P)
198 (3P) 230
rear panel cut
313 (4P) draw-out 260 4-ø14 mtg. holes
handle 175 (3P)
3 front panel cut 1-ø9 175 290 (4P)
229 (3P)
Note : 1 N is neutral pole of 4-pole breaker. 229 344 (4P)
2 Use arc barrier of a heat and flame resistant insulating material. (max.) (max.)
Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)

Connected P
5
Dust plate
225 93 C
10

Front
cover Test 302.5 187.5 2-M10
3.2 N tapped mtg.
20

holes
Isolated
arc barrier 2
15 30
30

600
*545

500
461

260

6 306.2
20

30

100

25
20

116 10 50
M8
80
Earth 4-ø12
126 200 127.2 terminal 115 115 115
t
Draw-out position
main pole N pole
333 453.2 32.8 198 (3P)
t 25 20
Dust plate surface 313 (4P)
11
5
Outline dimensions (mm)
• Type AT32 (with front terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
Front connected type P
C : front panel centre line P 282 (3P) Fixing blocks
C
282 417 (4P) with ø12 holes,
blocks are
Panel cut-out 270 (3P)
fitted when the
P 270 405 (4P) breaker is sub-
C 253 (3P)
262.5 (3P) ject to marine
253 388 (4P) classification
262.5 397.5 (4P)
society rules.
217.5 (3P) Secure these
auxiliary switch control circuit terminals
217.5 352.5 (4P) blocks to the
terminal screw, 28-M3.5 screws
250 switchboard
M3.5
2-ø 12 arc barrier 2 frame.

*545 (min.)
R116

25
N
500
440

1
270

260
332.5
145

55
50

(3P)
30

20

90
rear panel cut 228 (3P) 230
363 (4P) 260 4-ø14
3 front panel cut mtg. holes
205 (3P)
1-ø9 205 340 (4P)
259 (3P)
Note : 1 N is neutral pole of 4-pole breaker. draw-out 259 394 (4P)
2 Use arc barrier of a heat and flame resistant handle (max.)
(max.)
insulating material. Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)
Dust plate
5
10

Front cover
225 93 P 2-M10
352.5 C
217.5 tapped mtg
Connected 3.2 holes
N
20

Test
arc barrier 2
Isolated
30

15 30
*545

600
461

500
260

6 306.2
30

100
20

116
25 50 60
20

10
80 100
126 200 127.2 t
Draw-out position 135 135 135 4-ø14
32.8 M8 228 (3P)
333 453.2 Earth 363 (4P)
Dust plate surface terminal main pole N pole
Side View t 25 20
Back View
12
Outline dimensions (mm)
• OCR Options 5
PRQ-1 (Panel mounting type) PRQ-2 (Intregal with TemPower ACB)
C
L
Note: For further infor-
mation refer to TemTrip
catalogue I73Ea

164
220
395

C
L

Panel Cut out

132.5

145.5
4–ø6

250
140
Panel cut out
210

UPS Power supply module


130.0
62.0 120.0 4 - ø5.1
MTG. HOLES
This is used to provide a back-up power 60.0 110.0

supply to the display indication functions of the


AOR-1B or TemTronic. Refer to page 54 for

26
wiring diagrams.
Connection Description
1 A Gen N
( B Gen L ) 16.0

C Mains N
F BATTERY LED MAINS NEON
D Mains L E

E DC 24V output –VE D

190.0
F DC 24V output +VE C

A
1 Note: The main terminals used are C &
D for the AC Supply voltage and E & F
5.0
for the 24V DC output. If standby genera-
tion is available this may be connected to
terminals A & B. 26

SIDE VIEW TOP VIEW

AOR-1B DC Power supply module


105.0
95.0
This must be used in conjunction with the AOR-1B when the following DC CL

control voltages are used.


CODE No:

Rated DC input 30V 48V 60V


+ +
Power consumption 7VA 11VA 13VA INPUT DC
– –
CL
72.0

19 + 19 2 - ø5.5
Refer to page 54 for wiring OCR SUPPLY MTG. HOLES
diagram.
50.0

20 – 2024V DC
9
4.7

1 - ø3.4
SIDE VIEW MTG. HOLE
TOP VIEW

13
6 TemPower
Connection diagrams

Main circuit Overcurrent trip (OCR) Undervoltage trip Motor charging/closing control Spring
(UVT) circuits charged
switch
+ 19
Customers Power suuply
supply SW1 option – 20 Source

Control power Source


Interlock switch
PB
(open)
PB (closed) X

– 20 19 + 9 11 1 3 15

k AUX Spring
L SW charged
CT4 k switch
CT5 L ON
L SW
CT6
n g kC kB kA S0 S1 SP Undervoltage
Overcurrent relay (OCR) trip controller
(for general feeder circuits)
k ->T0 kB (example AOR-1BL-GI)
CT2
L
UVT Motor
Operator
From
motor
circuit

->T0 kA AC AP AL AS AG AA a c TN TP
Interlock switch

L ->T0 kC TP
L
CT1 CT3
k ->T0 n MIT
k

TN

22 28 25 26 27 24 + 17 18 – 10 12 2 4

Note : Do not use these output contacts in circuits exceeding 250V Note : When control power is DC Note : Spring charged switch arrangement differs from the above
AC or 220V DC. refer to the circuit diagram on when control power is DC see circuit diagram on page 19.
page 21.
For the control power source
CT1-3 : CT for overcurrent trip for types AT06-AT20
AC rated voltage operating range is 85% to 110%
DC rated voltage operating range is 75% to 110%.
CT4-6 : CT for overcurrent trip for types AT25-AT40

If required switch SW1 is to be provided & installed by the customer


for the purpose of circuit isolation.

Main circuit Motor charging/closing circuits OCR alarm switch

C T : Current transformer for OCR 1 2


(For magnetic inst. trip)
Source 17 18
3 4 OCR alarm switch (also used for
Closing circuit
ammeter output when available).
P B : Push-button switch
Overcurrent trip (OCR) X2 : Auxiliary switch (not supplied)

17 18
Current measuring function terminals
19 20
Control power terminals Shunt trip (SHT) Auxiliary switch
22
Common line for ind. contact
23
Trip indication (single contact type) SHT 31
24
System alarm indication contact Shunt trip device Auxiliary switch
7 8 to
25
LTD ind. contact SHT Circuit 50
26 AUX.SW Auxiliary switch
STD / INST ind. contact
27
GFT ind. contact P B : Push-button switch
28
PRE-TRIP alarm contact
MHT
Magnetic hold trigger (tripping coil)

Undervoltage trip (UVT) Capacitor trip Power Supply Option


9 10
Source 3 4 Source This is necessary if either the UPS or AOR-1B
11 12
Remote electrical tripping 1 7 Remote electrical tripping Power supply module is utilized.
UVT
Undervoltage trip device UPS option
AUX. Sw Auxiliary switch Supply voltage is unit 1 :- AC 240V
unit 2 :- AC 220 ~ 230V
Spring charged switch Trip indication switch AOR-1B DC Supply
Supply voltage is either 30, 48 or 60VDC
15
Spring charged switch 13 14 Trip indication Switch depending on module .
X1 : Auxiliary switch (not supplied) Refer to page 53 for more information.
14
TemPower
Connection diagrams 6
Shunt trip Capacitor trip Trip OCR alarm Auxiliary switch Position switch
(SHT) indication switch Draw-out type, the auxiliary switches operate in the
SERVICE and Test positions only. Test position 61-62 ON

Source
switch For indication of tripping by elec-
Marine classification society's rules apply, they
Connected position
61-63 OFF
71-72 ON
operate in the SERVICE position only.
tromagnetic instantaneous trip 71-73 OFF
device only. Isolated position 81-82 ON
4 3
Source Source 81-83 OFF
Insert position 91-92 ON
Capacitor trip 91-93 OFF
Source
1 2

PB PB X1 X2
(open) (open)
Test Connected Isolated Insert
position position position position
7 7 13 17 31 33 35 37 39 41 43 45 47 49 61 71 81 91

Connected position switch

Isolated position switch

Insert position switch


Test position switch
*1 *1

AUX AUX
SW SW

*2

SHT SHT

8 8 14 18 32 34 36 38 40 42 44 46 48 50 62 63 72 73 82 83 92 93

Note : Customer’s wiring shown dashed (- - - - -)


Note :* 1 When the shunt trip rated voltage is DC200-230V, two
switches in series are used.

Note : *2 Momentary action contact ON for 40ms. Requires self-sealing


circuit for tripped indication.

Terminal arrangement of control circuit OCR with trip indication

(Single contact type)


1
31 33 35 37 39 41 43 45 47 49 1 3 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2
B1 A1 B2 A2 B3 A3 B4 A4 B5 A5 B1 A1 B2 A2 B3 A3 B4 A4 B5 A5 3
4
32 34 36 38 40 42 44 46 48 50 2 4 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 7
8
9 Example: AOR-1BL-AL
10
11
12 CT
13
14
15
16 g n kC kB kA
17
OCR
18
19
Fixed type 20
Momentary
21 closing : 40ms
22
Control
Auxiliary switch Control circuits Auxiliary switch 23
circuit
24
25 AAL1 AAL2 TN TP
26
27 TP
Draw-out type Crade 73 72 71
28
29 MHT
Connected position sw.
Test position sw. 63 62 61 30
TN
Isolated position sw.
Insert position sw. 83 82 81

93 92 91 22 23

Trip indicator contact maximum rated voltage : 250VAC, 250VDC

15
7 TemPower Order Form
For general feeder use

Company Name Order No. __________

Quantity Delivery time required

Specifications
1 Type AT06 AT12 AT16 AT20 AT20L AT25 AT25L AT32 AT40

2 Number of poles 2-Pole 3-Pole 4-Pole


2-Pole type is identical with 3-Pole type except that the centre pole is omitted

3 System voltage AC_________V __________Hz DC___________V.

4 Applied standard and Applied standard IEC 947-2


ambient temperature 45°C Other __________°C please specify

5 Type of mounting Fixed type - horizontal terminals vertical terminals front connection
Drawout type - horizontal terminals vertical terminals front connection
Main circuit safety shutters
Control circuit safety shutter Position switch- Connected Test Isolated Insert
Test jumper (lead wire 5m) __________ sets Mal-insertion prevention device
Door interlock Carrying roller
Arc gas barrier (draw-out type only) Breaker fixing blocks (draw-out type only)

6 Type of spring charged Manual charging type


operation Motor charging type 50/60 Hz ______VAC ______VDC
Closing latch release coil 50/60 Hz ______VAC ______VDC (specify if different from motor voltage)
Split circuit required

7 Multi-function protection device AOR-1BL-AL AOR-1BL-GL AOR-1BL-AS AOR-1BL-GS AOR-1BL-NS


(Overcurrent trip) AOR-1BL-ES AOR-1BL-AI AOR-1BL-GI AOR-1BL-NI AOR-1BL-EI
AOR-1BM-AL AOR-1BM-GL AOR-1BM-AS AOR-1BM-GS AOR-1BM-NS
AOR-1BM-ES AOR-1BM-AI AOR-1BM-GI AOR-1BM-NI AOR-1BM-EI

OCR rated primary current [ICT] __________ A I0 __________


Other (please specify) : – I1 __________ T1 __________ IG __________ TG __________
I3t very inverse I2 __________ T2 __________ IN __________ TN __________
I4t extremely inverse I3 __________ IP __________ TP __________
Terasaki standard settings Control voltage - AC, DC100-250V DC24V * DC30V
* DC48V * DC60V
*Note: For these voltages you must use the DC power suppy module shown on page 53

8 Electromagnetic instantaneous __________kA OCR Alarm switch


trip

9 Accessories for overcurrent CT for neutral line UPS Power supply module Supply voltage AC _______
trip

10 Other trips Shunt trip- AC______ DC______ Instantaneous operating Continuously rated
Capacitor trip
Undervoltage trip- AC______ DC______ Instantaneous Required (time-delay STD)

11 Other accessories Trip indication switch IP54 Cover IP54 Cover & depth frame Door flange
Key lock ( lock in open lock in close) Carrying handle Slow close jigs
Castell lock (facility only) Castell lock ______ symbol Close-open cycle counter
Mechanical interlock Vertical Horizontal Breakers pitch ______ mm
Dust plate Push-button lock Auxiliary switch 2A2B 5A5B 10A10B

12 Special environment Not required Tropicalization Anti-chemical treatment Cold climate treatment
specification

13 Spare parts Not required Required (please state individual spare parts required)

14 Documentation Test report ______ copies ACB Instruction manual ______ copies

15 Other Lifter type AWT-2B ______ sets


OCR checker (ANH-1B) OCR checker (ANR-1)

16
TemPower Order Form
For generator protection use 7
Company Name Order No. __________

Quantity Delivery time required

Specifications
1 Type AT06 AT12 AT16 AT20 AT20L AT25 AT25L AT32 AT40

2 Number of poles 2-Pole 3-Pole 4-Pole


2-Pole type is identical with 3-Pole type except that the centre pole is omitted

3 Circuit voltage AC_________V __________Hz DC___________V.

4 Applied standard and Applied standard IEC 947-2


ambient temperature 45°C Other __________°C please specify

5 Type of mounting Fixed type - horizontal terminals vertical terminals front connection
Drawout type - horizontal terminals vertical terminals front connection
Main circuit safety shutters
Control circuit safety shutter Position switch- Connected Test Isolated Insert
Test jumper (lead wire 5m) __________ sets Mal-insertion prevention device
Door interlock Carrying roller
Arc gas barrier (draw-out type only) Breaker fixing blocks (draw-out type only)

6 Type of spring charged Manual charging type


operation Motor charging type 50/60 Hz ______VAC ______VDC
Closing latch release coil 50/60 Hz ______VAC ______VDC (specify if different from motor voltage)
Split circuit required

7 Multi-function protection device AOR-1BS-AL AOR-1BS-AS AOR-1BS-NS AOR-1BS-AI AOR-1BS-NI


(Overcurrent trip) Control voltage
OCR rated primary current [ICT] __________ A
Generator base current [I0] ___________ A (rated generator current)
Other (please specify) I1 __________ T1 __________
I2 __________ T2 __________ IN __________ TN __________
I3 __________ IP __________ TP __________
Terasaki standard settings Control voltage - AC, DC100-250V DC24V * DC30V
* DC48V * DC60V
*Note: For these voltages you must use the DC power suppy module shown on page 53

8 Electromagnetic instantaneous __________kA OCR Alarm switch


trip

9 Accessories for overcurrent CT for neutral line UPS Power supply module Supply voltage AC _______
trip

10 Other trips Shunt trip- AC______ DC______ Instantaneous operating Continuously rated
Capacitor trip
Undervoltage trip- AC______ DC______ Instantaneous Required (time-delay STD)

11 Other accessories Trip indication switch IP54 Cover IP54 Cover & depth frame Door flange
Key lock ( lock in open lock in close) Carrying handle Slow close jigs
Castell lock (facility only) Castell lock ______ symbol Close-open cycle counter
Mechanical interlock Vertical Horizontal Breakers pitch ______ mm
Dust plate Push-button lock Auxiliary switch 2A2B 5A5B 10A10B

12 Special environment Not required Tropicalisation Anti-chemical treatment Cold climate treatment
specification

13 Spare parts Not required Required (please state individual spare parts required)

14 Documentation Test report ______ copies ACB Instruction manual ______ copies

15 Other Lifter type AWT-2B ______ sets


OCR checker (ANH-1B) OCR checker (ANR-1)

17
7 TemPower Order Form
Spares listings

Company Name Order No. __________

Quantity Delivery time required

Specifications AH06B AH10B AH12B AH16B AH20C AH30C


1 Type AP16 AP20 AH40C AH50C AH60C
AT06 AT12 AT16 AT20 AT20L AT25 AT25L AT32 AT40

2 Number of poles 2-Pole 3-Pole 4-Pole


2-Pole type is identical with 3-Pole type except that the centre pole is omitted

3 Serial No.

4 Type of mounting Fixed type


Drawout type
Main circuit safety shutters
Control circuit safety shutter Position switch- Connected Test Isolated Insert
Test jumper (lead wire 5m) __________ sets Mal-insertion prevention device
Door interlock Carrying roller
Arc gas barrier (draw-out type only) Breaker fixing blocks (draw-out type only)

5 Type of spring charged Manual charging type


operation Motor charging type 50/60 Hz ______VAC ______VDC
Closing latch release coil 50/60 Hz ______VAC ______VDC (specify if different from motor voltage)
Split circuit required

AOR-1BL-AL AOR-1BL-GL AOR-1BL-AS AOR-1BL-GS AOR-1BL-NS Other


6 Multi-function protection device AOR-1BL-ES AOR-1BL-AI AOR-1BL-GI AOR-1BL-NI AOR-1BL-EI
(Overcurrent trip) –––––––
General AOR-1BM-AL AOR-1BM-GL AOR-1BM-AS AOR-1BM-GS AOR-1BM-NS –––––––
AOR-1BM-ES AOR-1BM-AI AOR-1BM-GI AOR-1BM-NI AOR-1BM-EI
–––––––
OCR rated primary current [ICT] __________ A I0 __________
Other (please specify) : – I1 __________ T1 __________ IG __________ TG __________
I3t very inverse I2 __________ T2 __________ IN __________ TN __________
I4t extremely inverse I3 __________ IP __________ TP __________
Terasaki standard settings Control voltage - AC, DC100-250V DC24V * DC30V
* DC48V * DC60V
*Note: For these voltages you must use the DC power suppy module shown on page 53

7 Multi-function protection device AOR-1BS-AL AOR-1BS-AS AOR-1BS-NS AOR-1BS-AI AOR-1BS-NI


(Overcurrent trip) Control voltage
Generator AC, DC100-250V DC24V
OCR rated primary current [ICT] __________ A
Generator base current [I0] ___________ A (rated generator current)
Other (please specify) I1 __________ T1 __________
I2 __________ T2 __________ IN __________ TN __________
I3 __________ IP __________ TP __________
Terasaki standard settings Control voltage - AC, DC100-250V DC24V * DC30V
* DC48V * DC60V
*Note: For these voltages you must use the DC power suppy module shown on page 53

8 Other trips Shunt trip- AC______ DC______ Instantaneous operating Continuously rated
Capacitor trip
Undervoltage trip- AC______ DC______ Instantaneous required (time-delay STD)

9 Other accessories Trip indication switch IP54 Cover IP54 Cover & depth frame Door flange
Key lock ( lock in open lock in close) Carrying handle Slow close jigs
Castell lock (facility only) Castell lock ______ symbol Close-opening cycle counter
Mechanical interlock Vertical Horizontal Breakers pitch ______ mm
Dust plate Push-button lock Auxiliary switch 2A2B 5A5B 10A10B

10 RECOMMENDED SPARES: Although unlikely, should spare parts be stocked we would recommend to keep only the arc chutes and
arcing contacts.

Arc chute Fixed arcing contact Moving arcing contact

18
Direct Response Prevents Costly Down Time.

IEE regulations (BS 7671)

It is a requirement of IEE regulations

(BS 7671) that switchboards and circuit

breakers are inspected, tested and

serviced regularly. It is with this in

mind that Terasaki initiated the Direct

Response Preventive Maintenance


Service, to support our customers and

their needs.

One of our service teams We customise service arrangements to

meet your requirements.

Did you know...?

Terasaki (Europe) Ltd is the largest circuit breaker manufacturer in the United Kingdom and the

main Terasaki service centre for Europe.

Our customers include: On-site service


Motorola - Sealink UK Ltd - BBC - Heathrow Operations Centre -

Channel 4 TV - Nissan Motor Plant - IBM (UK) Ltd - Shell - P & O Containers

- NEC Semiconductors - Scottish & Newcastle Brewers....

Our engineers provide a wide range of professional services:

Testing - Modifications - Upgrading - Discrimination studies - Repairs -

Site surveys - Spare parts - Product exchange - Marine maintenance -

Safety audits - Inspections - Training and documentation available from

our qualified safety team. Our engineers qualifications include Offshore

and HV certifications.

For free advice and catalogue contact: Stuart Smith - Service Manager at

Tel: 0141 941 1940 Fax: 0141 952 9246


19