TemPower 97-I51E
TemPower 97-I51E
TemPower 97-I51E
2
Section Contents Page
5 Outline dimensions
3
1 Features
AOR-1B : Multi-function r.m.s. sensing protection
Thermal memory
The hot start characteristic takes account of
the accumulated heating effect caused by pre-
vious loads. Hot or cold start characteristics
are set by means of a selector switch.
Note: For AOR-1BM only cold start is avail-
able.
Neutral phase protection Inverse time/current characteristics Ramp characteristic for short time-delay
If harmonic distortion exists in a 3-phase, In addition to the overload protection charac- The short time-delay tripping characteristic
4-wire distribution system, 3rd harmonic cur- teristics for general feeder circuits (L type) and provides co-ordination between upstream or
rents can accumulate in the neutral conductor. generators (S type), other inverse time/current downstream circuit breakers or fuses. For
Overcurrent protection of the neutral pole elim- characteristics (M type) are available for closer closer co-ordination with thermal magnetic cir-
inates possible damage to the neutral conduc- co-ordination: Very Inverse (proportional to cuit breakers or fuses, a selector switch is
tor insulation caused by large harmonic cur- I3t) and Extremely Inverse (proportional to I4t). used to set “definite-time delay characteristic”
rents. Full or half rated neutral protection is These characteristics are set by a selector or “ramp characteristic.”
available. (Please specify at time of order- switch.
ing).
Extremely
inverse
curve
Downstream L.V. fuse
Current Current
Selectivity can be achieved with up to six ACBs in series.
4
Features
AOR-1B : Multi-function r.m.s. sensing protection
1
Multi-protective characteristics Increased reliability
4
3 Self-diagnostic function
LTD current setting range
2
This function continually interrogates the
hour
8
6 Click-step adjustment dials
5
4 All adjustment dials are of the click-step type
3
to ensure easy, accurate adjustment of all
2
PRE-TRIP time functions.
setting range
1
50
40
30
Customised IC
20 The customised IC used by Terasaki is a
Operating time
1 1000ms
0.8 1000ms
second
0.6
0.5
0.4 400ms 400ms
0.3 STD time
0.2 GFT time
setting range Fault indication
setting range
0.1
0.08
0.06
80ms 80ms
Individual LEDs and volt free contacts, pro-
0.05
0.04 vide unique fault identification, locally and by
0.03
0.02
remote.
0.01
0.008
0.006
0.005
400
7
8
9
10
15
20
30
40
50
60
70
80
90
100
125
150
200
60
70
80
90
100
125
150
200
250
300
500
600
700
800
900
1000
1500
2000
2500
3000
5
1 TemPower
Features
• AT06 - AT40 seven frame sizes covering 630 to 4000 Amps • AT20L & AT25L Current limiting ACBs •
6
TemPower
Features
1
Uniformity in switchboard appearance
4
7
6 2
14
1
12
11
13
10
7
2 TemPower
Ratings & specifications
NOTES:
1 : Values in open air at 40°C (45°C for marine applications). 7 : For vertical terminals, d = 92 mm.
3 : DC rating is for special application. For further details, contact Terasaki. 8 : Rated operational voltage depends on applied standard: 690V according to IEC947-2
5 : Approval pending. 9 : Only applied to 3 pole ACBs.
6 : Full rated neutral pole available on request. 10 : Rated insulation voltage depends on applied standard: 1000VAC according to IEC947-2
12 : The application of I.T. systems at this voltage is not permissible
8
TemPower
Ratings & specifications
2
Rating and specifications - Current limiting range
it
RATED CURRENT OF OVERCURRENT TRIP DEVICES [Io] (A)
e) cu
– –
effect
lu cir
(For generator protection use)
va ort
[Io] is the generator rated current
ak sh
pe ve
RATED IMPULSE WITHSTAND VOLTAGE [Uimp] (kV) 8 8 130kA
100
i
um ct
AC RATED INSULATION VOLTAGE [Ui] (V) 690 690
im pe
RATED OPERATIONAL VOLTAGE [Ue] (V) 460 460
ax ros
AC RATED BREAK. CAP. (kA r.m.s.)/MAKE CAP. (kA peak)
(m p
em
IEC 947-2 with Inst. 690V – –
BS EN 60947-2 600V
st
– –
Sy
CEI EN 60947-2 [Ics] =100% [Icu] 500V – – 50
up to 415V 130/286 130/286
DC RATED BREAKING CAPACITY DC 250V
3 – –
DNV with Inst. 660V – –
9
600V – –
480V – –
without Inst. up to 480V – –
LR with Inst. 660V – –
Maximum let-through energy I2t [x107A2sec]
9
without Inst. 600V – –
with Inst. 480V – –
without Inst. up to 480V – –
AB with Inst. 660V – –
9
600V – – 10
480V – –
without Inst. up to 480V – –
GL with Inst. 660V – –
9 600V – –
480V – –
without Inst. up to 480V – –
5
BV with Inst. 660V – – 4
9 600V – –
500V – –
without Inst. up to 500V – – 3
SHORT TIME WITHSTAND 1 sec 17 17
CURRENT [ICW] (kA) 3 sec 17 17 2
Latching current [kA] 17 17
UTILIZATION CATEGORY A A
OPERATION TIMES
Total breaking time (s) 0.02 0.02
Spring charging time (s) max. 10 10
Closing time (s) max. 0.06 0.06
OUTLINE DIMENSIONS (mm) 1 10 20 30 40 50 100 130 200
Fixed type a – – – –
b – –
Short circuit current sym. r.m.s. value (kA)
b
c – – at 460 V AC r.m.s.
a 20 c d d – –
Draw-out type a 368 453 518 653
b b 492 526
Note: Max. peak let-through current / I2t energy let-through. Example for AT20L
c 458 458
a 20 c d d 92 82
Weight (kg) draw-out type 91 115 152 188
NOTES:
1 : Values in open air at 40°C (45°C for marine applications).
3 : DC rating is for special application. For further details, contact Terasaki.
9 : Only applied to 3-pole ACBs.
11 : Current limiting ACBs are fitted with an electromagnetic instantaneous trip device set at
20kA as standard.
9
2 AH / AP Range
Ratings & specifications
NOTES:
• : Yes or available. 3 : DC rating is for special application.
– : No or not available. 4 : Rated insulation voltage depends on the applied standard: 1000V AC according to IEC 947-2.
1 : Values in open air at 40°C (45°C for marine applications). 5 : Rated operational voltage depends on applied standard: 690V AC according to IEC 947-2.
6 : Values at 460VAC.
Ratings and specifications of AH / AP ACBs only, are contained in this catalogue, for further information, contact TERASAKI for details.
10
TemPower
Technical Data
2
Internal resistance, reactance, power consumption
Note: The power consumption shown above is measure on the basis of internal AC resistance for 3 poles
De-rating
Based Ambient temp. Type AT06 AT12 AT16 AT20 AT25 AT32 AT40
standards (°C)
IEC947-2 40 (Standard ambient temperature) 630 1250 1600 2000 2500 3200 4000
BS EN 60947-2 45 630 1250 1600 2000 2500 3200 4000
VDE 0660 Part 50 630 1250 1600 2000 2380 3080 3890
101 55 630 1250 1600 1920 2300 2970 3740
AS 3858 1990 60 630 1230 1600 1840 2200 2850 3590
Circuit 50/60 Hz
Main circuit Between terminals all terminals to earth AC3500V 1 minute
Auxiliary switch all terminals to earth AC2500V 1 minute
Undervoltage trip AC Rating terminals 9 - 10 to earth AC2500V 1 minute
terminals 11 - 12 to earth AC1500V 1 minute
Accessories
11
3 ACB Specification
Types of mounting
The draw-out type consists of a circuit breaker and a draw-out cradle. This consists only of the circuit breaker with fixings to allow it to be
The circuit breaker can be removed from the cradle. There are mounted permanently inside the switchboard.
four circuit breaker positions CONNECTED, TEST, ISOLATED and
REMOVE. The switchboard panel door can be kept closed in CON-
NECTED, TEST and ISOLATED positions (“shut-in three positions”).
Terminal Arrangement
Type Type Of Horizontal Vertical Front
Mounting Terminals Terminals Connections
Draw-out
Both main and control circuits are connected for normal AT06
service. Fixed –
Draw-out
AT20
Fixed –
AT20L Drawout – –
The main circuit is isolated and the control circuits are connected.
Draw-out
This position permits operation tests with the switchboard panel shut.
AT25
Fixed –
3 Isolated position
AT25L Draw-out – –
Indication
ISOLATED Draw-out
AT32
Fixed –
Draw-out – –
AT40
Fixed – –
4 Remove position
12
ACB Specification
Accessories
3
Door interlock
The door interlock prevents the switchboard
(Front view) (Plan view)
door from being opened when the breaker ø10
is CLOSED. The door can be opened only ø7 Breaker
when the breaker is OPEN. It is also fitted Panel door mounting
12.5
with a lock release. Installation of the door 250 hole
interlock requires simple drilling of the switch-
board panel door.
200
270
Hinge can only be fitted on the RIGHT HAND Dust
301.5
SIDE as shown in the opposite diagram. plate
130
Hinge
50
15
A Breaker A B
(min.) (min.) (min.)
20
A B (3P) B (4P) Panel door
AT-06,12,16,20,20L 163 280 365
AT-25 208 330 445 Door interlock
AT-25L,32,40 238 330 465
Lifter loader
Panel door
Note: * If distance exceeds 150mm, contact D
TERASAKI
H
Carrying rollers W
Metal-clad type
13
3 ACB Specification
Accessories for draw-out type
When the breaker is drawn out the shutters The Position switches operate when the • Position switch, operating sequence
automatically conceal and insulate the main breaker is in CONNECTED position, TEST
(Isolated) (Test) (Connected)
circuit disconnect contacts on the cradle. position, ISOLATED position or in the INSERT
Each shutter can be padlocked in the closed position, to electrically indicate the breaker a-contacts
Connected position
position. For safety during inspection and position. These switches are divided into units "ON"
indicator switch
maintenance, up to three padlocks may be (1) and (2) as shown below, and one switch Test position
a-contacts
"ON"
applied to each of the top and bottom shutters can be selected from each unit. A max of 2 indicator switch
(padlocks not supplied). units can be fitted on ACBs AT06~20, 3 Pole. a-contacts
Isolated position "ON"
A max of 4 units fitted on any other ACB size. indicator switch
UNITS (1) UNITS (2)
The top shutter and bottom shutter can be Insert position a-contacts
indicator switch "ON"
opened or closed independently by manual (1) CONNECTED (1) ISOLATED position • Position switch ratings
operation. Maintenance can be done in the position, indicator indicator switches Load Resistive Lamp Inductive Motor
open position. (The mechanism is released switches (2 max) (2 max) AC250V 10A 1.5A 6A 2A
automatically by inserting the circuit breaker). DC30V 6A 3A 6A 3A
The top shutter and bottom shutter can both (2) TEST position, (2) INSERT position, DC125V 0.6A 0.1A 0.6A 0.1A
be moved individually. indicator switches indicator switches DC250V 0.3A 0.05A 0.3A 0.05A
(2 max) (2 max)
Control circuit safety shutter Breaker fixing blocks Draw-out position padlock
The control circuit disconnect contacts have These provide reinforcement for the breaker The breaker can be padlocked in three posi-
independent shutters for increased safety. mounting where vibration occurs. They are tions, CONNECTED, TEST and ISOLATED.
They are not padlockable. always fitted when the breaker is subject to The padlocking device is fitted as standard.
marine classification society rules. Padlocks not supplied (hasp diameter 8 or
6mm dia).
14
ACB Specification
Accessories
3
Open padlock Push-button padlock cover Carrying handle
Permits the ACB to be padlocked in the OPEN Prevents unauthorised operation of the For use with hooks, ropes etc when lifting the
position, this is fitted as standard. manual CLOSE and OPEN buttons. Padlock breaker.
Max. 3 padlocks (hasp size ø6 to ø8mm) can hasp size ø6 to ø8mm (not supplied).
be fitted (not supplied).
Provides a dust proof seal between the ACB Cold Climate Treatment Tropicalization
front panel and the cut-out on the switchboard Specify this treatment when the breaker is used (Fungus and Moisture Treatment)
panel when the breaker is located between the in cold areas. Specify this treatment when the breaker is used
CONNECTED and ISOLATED position. Specification :– 40°C storage temperature under high temperature and high humidity con-
-25°C operating temperature (no condensation ditions:
or freezing). Up to 60°C ambient temperature and up to 95%
relative humidity (no condensation).
Anti-Corrosion Treatment
Anti-corrosion treatment permits the use of the
breaker in a corrosive atmosphere. Contact
TERASAKI for further information.
Covers the panel cut-out on the switchboard. There is a growing demand in L.V. distribution for greater protection against electric shock
The panel cut-out should be greater than the particularly during periods when maintenance work is being carried out on the main busbars or
standard size shown in the outline dimensions cables. A safe and economical way to meet this requirement is to apply system earthing via the
section of 250mm x 270mm. We would recom- normal service breaker. Earthing devices (optional) on TemPower ACBs comprises; Permanent
mend to use a cut out of 260mm x 280mm. parts which are factory fitted by Terasaki (Europe) and are mounted on the ACB chassis and
The option is not available with the TemTrip body to enable the ACB to receive the portable parts. Portable parts are supplied in loose kit
relay. form and are fitted on to the ACB body by the customer's engineer. This converts the ACB
from a normal service device to an earthing device. For further information contact TERASAKI
for details.
15
3 ACB Specification
Accessories
Key interlock
The key interlock is a system of interlocking Utilising the lock-in-open type key lock feature In the latter case, use Lock Type FS 2 (angular
between breakers, each fitted with a lock-in- and using keys less than the number of the movement 65o clockwise to trap key) Castell
open type key lock key-locked breakers, an effective and reliable Locks Ltd.
*The key must be inserted to release the lock interlock system is formed.
before the breaker can be closed Breakers can be supplied with a cylinder lock EXAMPLE: Prevention of parallel connection of
* The breaker must be opened and locked in the fitted or with a provision for Castell lock. two sources with a bus tie breaker.
open position before the key can be removed
60
P P P
C C C
Rod
N N N
P P
N
*Min
575mm
Select the required pitch from the table below:
16
ACB Specification
Accessories
3
Auxiliary switch assembly Close-Open cycle counter
Auxiliary switches electrically indicate the open- This device counts and indicates the number of
closed status of the breaker. For Draw-out close-open cycles
Type, the auxiliary switches operate in the
CONNECTED and TEST positions only. How-
ever, where marine classification society’s rules
apply, they operate in the CONNECTED posi- Key lock
tion only. Options include; 2A 2B, 5A 5B, 10A
10B. The key lock is available in two types: lock-in-
open type to lock the breaker in the OPEN posi-
tion, or lock-in-closed type to lock the breaker in
the CLOSED position.
Operation of the trip indication switch varies depending on which device trips the breaker and whether or not the closing spring Ģ
Rating
Load Resistive Lamp Inductive Motor Operation of trip indication switch
Breaker tripped by
AC125- Closing springs charged Closing springs discharged
250V 7A 1.5A 6A 2A Overcurrent trip (OCR)
DC30V 6A 3A 6A 3A Switch is ON for 40ms, then reset to Switch remains ON until closing
Shunt trip
DC125V 0.6A 0.1A 0.6A 0.1A OFF springs are charged
DC250V 0.3A 0.05A 0.3A 0.05A Undervoltage Remote opening
trip
Switch remains ON until undervoltage Switch remains ON until closing springs
Undervoltage condition is restored to normal. are charged after undervoltage condition
Condition has restored to normal
Note: * Optional. The trip indication switch can be made * Manual opening by Switch remains ON until PUSH-TO- Switch remains ON until closing springs
inoperative for a manual OFF operation. Please specify at PUSH-TO-OPEN button OPEN button is released are charged after PUSH-TO-OPEN button
time of ordering. is released
17
3 ACB Specification
Spring charged operation
The closing springs are manually charged Breaker Rated voltage Min & max Inrush Steady-State Charging Closing
by pumping the charging handle. When the operation current current time command
PUSH TO CLOSE button is pressed, the clos- voltage (peak value) (AC, A, current
ing springs are released, quickly closing the r.m.s. value) (peak value)
breaker.
(An electrical latch release can be provided (V) (V) (A) (A) (s) (A)
for remote closing applications. The closing
springs must be charged manually prior to AC240 - 250 204 - 275 2.9 (240V) 0.5 2.8 1.6 (240V)
remote close operation). AC200 - 230 170 - 253 3.4 (220V) 0.5 2.4 1.5 (220V)
AT06 AC100 - 120 85 - 132 6.3 (110V) 1.2 2.4 3.1 (110V)
AT12 DC200 - 220 150 - 242 2.8 (220V) 0.5 2.7 1.3 (220V)
AT16 DC125 94 - 138 2.2 (125V) 0.8 3.0 3.4 (125V)
Motor charging type AT20 DC100 - 110 75 - 121 6.5 (100V) 0.9 2.8 2.7 (100V)
AT20L DC48 36 - 53 11.0 (48V) 1.7 3.0 4.9 (48V)
The motor automatically charges the closing DC24 18 - 26 16.9 (24V) 3.4 2.7 8.8 (24V)
springs. The latch release coil is energised
by a remote push button, releasing the springs AC240 - 250 204 - 275 2.8 (240V) 0.8 3.4 1.7 (240V)
and quickly closing the circuit breaker. With the AC200 - 230 170 - 253 3.4 (220V) 0.6 2.5 1.6 (220V)
breaker closed, the motor automatically starts AC100 - 120 85 - 132 6.1 (110V) 1.1 2.5 3.2 (110V)
to charge the springs again for the next closing DC200 - 220 150 - 242 2.8 (220V) 0.5 3.1 1.4 (220V)
operation. AT25 DC125 94 - 138 2.4 (125V) 1.0 3.0 3.5 (125V)
Manual charging is also possible. DC100 - 110 75 - 121 6.5 (100V) 1.2 3.5 2.8 (100V)
Separate charging and closing circuits are DC48 36 - 53 11.0 (48V) 1.7 3.0 4.9 (48V)
available on request. DC24 18 - 26 16.9 (24V) 3.7 3.5 8.8 (24V)
AC240 - 250 204 - 275 2.8 (240V) 0.8 4.0 1.9 (240V)
AC200 - 230 170 - 253 3.2 (220V) 0.6 3.0 1.7 (220V)
AC100 - 120 85 - 132 6.0 (110V) 1.2 3.0 3.2 (110V)
AT25L DC200 - 220 150 - 242 2.8 (220V) 0.5 3.1 1.5 (220V)
AT32 DC125 94 - 138 2.5 (125V) 1.0 3.0 3.5 (125V)
AT40 DC100 - 110 75 - 121 6.0 (100V) 1.9 5.5 2.9 (100V)
DC48 36 - 53 11.0 (48V) 1.7 3.0 4.9 (48V)
DC24 18 - 26 15.5 (24V) 3.8 4.2 8.9 (24V)
18
ACB Specification
Spring charged operation
3
Motor circuit
15 1 3 15 1 3
101 101
1 3 31 1 3 31
AXT-1C
AXT-1C
Spring C C Spring C C
R
charged R charged
switch switch HC
HC
OFF OFF
A A
R R
41 41
HC HC
M M AMT-1C
AMT-1C
B B D D D B B D D D
205 205
204 204
AXT-1BA
AXT-1BA
AXT-1C
AXT-1C
AXT-1C
AXT-1C
Aux.Sw.
Aux.Sw.
Spring Spring
charged LRC charged LRC
switch switch
ON ON
203 203
202
Spring Spring
202 charged
4 charged 2 4
2 switch switch
OFF OFF
2 4 2 4
Standard circuit Split supply circuit
Automatic closing spring release Spring charged switch Jig for slow-closing
The closing springs are automatically released This switch electrically indicates the charged Jigs can be supplied with the breaker for
when the breaker is drawn out from the TEST condition of the closing springs. inspection and maintenance purposes (they are
position to the ISOLATED position. required when changing the arcing contacts of
the ACB). Slow-closing operation can be made
Ratings Resistive Motor by the charging handle when the slow-close jigs
AC125V-250V 7A 4A are installed.
DC125V-250V 0.4A 0.05A
19
3 ACB Specification
Electrical tripping devices
The shunt trip device allows the ACB to be Shunt Trip Ratings (instantaneous operating type)
remotely opened. Instantaneous operating
and continuously rated versions are available. Shunt Trip Rated Voltage Operational Voltage Peak Excitation Opening Time
(Contact Terasaki for details of continuous (V) (V) Current (max)
rated type). (A) (ms)
TemPower ACB can be fitted with shunt trip AVT-1 AC421-480 252-528 1.3 (450V) 30
and UVT. AC380-420 228-462 1.4 (380V) 30
AC180-250 108-275 1.7 (220V) 30
AC100-150 60-165 3.2 (110V) 30
DC150-230 90-276 1.5 (220V) 30
DC90 -125 54-150 2.9 (100V) 30
DC48 29-57 4.9 (48V) 30
DC24 14-28 8.9 (24V) 30
Capacitor trip
Combined with the shunt trip device, the capac- Type AQT-1A AQT-1B
itance trip device enables the ACB to be Rated Voltage AC 100-120V 220~240V
remotely tripped after a voltage (ac) drop due Operational Voltage 70 to 110% 70-110%
to a power failure, short circuit, etc, provided Rated frequency 50/60Hz 50/60Hz
that the remote trip operation occurs within 30 Rated Voltage of Shunt Trip used DC90-125V DC150~230
seconds after the voltage drop. Power Consumption (Inrush) 100VA 200VA
ON
OFF CAPACITOR
CHARGE
OUTPUT
3
1
INPUT
48.0
80.0
2
4
Control Circuit
PB
(OPEN)
Power or
ACB OCR
Source
etc.
AUX
SW
8 SHT 7
3 4 2 – + 1
ON OFF C
NL
R
Power
Switch
Di Di R Di
20
3
ACB Specification
Electrical tripping devices
10 12
* AUT-1BD only
9 + 11
54
AUX
SW
Current limiting Resistor
*2
AUT-1BS
217 6 A UVT CONTROL DEVICE C
SR
*1
236 26 R
D1
10 12 –
Ratings
Type of UVT Rated Control Opening Voltage (V) Coil Excitation Power Consumption (VA)
Control Device Voltage (V), 50/60Hz [Pick-up Voltage (V)] Current (A)
Normal Reset
1
4 OCR Specification
AOR-1B Multi-function protection device
Protection functions
1 Adjustable Long Time-delay LTD 2 Adjustable Short Time-delay STD 4 Adjustable Pre-Trip Alarm PRE-TRIP
The LTD fuction protects against overload. The STD function is intended to give dis- The PRE-TRIP alarm gives warning (via a volt-
Select HOT or COLD start. crimination with other devices during short cir- age free contact) of impending trip due to
The HOT start characteristic takes account cuits. The STD characteristic is user-selecta- overload. On L and M type OCRs, it has a
of accumulated heating caused by previous ble between 'definite time-delay' and 'I2t ramp' definite time delay and on S type OCRs, it has
loads. characteristics. The 'definite time-delay' is an inverse time delay.
(HOT start characteristics are not available on suitable for co-ordination with other definite PRE-TRIP signal automatically resets when
M type) time delay devices. The 'ramp' characteristic the current drops below pick-up current (IP).
allows closer co-ordination with thermal-mag-
netic MCCBs. When the STD is set to 'I2t 5 Adjustable Ground Fault GFT
ON', the 'ramp' characteristic is in operation The GFT pick-up current can be set between
current
up to 1000% of the base current for L & M 10% to 40% of the CT rated primary current
(general feeder protection) type OCRs and and the definite time delay between 80 to
Pick-up current of LTD up to 500% for S (generator protection) type 1000ms.
OCRs. Above these levels the definite time-
time delay comes into operation. The STD is set to 6 Neutral Phase Protection N-phase
Fluctuating current load profile 'I2t OFF' at the time of manufacture. Available on 3 & 4 pole ACBs for use on
3-phase, 4 wire systems. The N-phase cur-
tripping
1 Each of the overcurrent protection func- 2 If the STD and INST functions are both 3 If the STD and MCR functions are both set
tions (LTD, STD, INST/MCR) can be disa- set to 'NON' (thereby removing all short- to 'NON', the in-built FAIL-SAFE function
bled by setting the respective pick up dial circuit protection), the in-built FAIL-SAFE will trip the ACB on fault currents exceed-
to 'NON' position. (For example, the INST function will trip the ACB on fault currents ing 10 times the base current, [Io], (on L
setting is often set to 'NON' to improve exceeding 16 times the base current [Io], and M type OCRs) and 5 times the base
selectivity levels.) instantaneously. current, [Io] (on S type OCRs). Trip time is
the STD time setting.
The base current, [I0], is used as the reference 1 For General Feeder Circuits 2 For Generator Protection
for deciding the current and time settings of 1 Calculate the maximum full load current, 1 Check the generator full load current, [IGEN].
the LTD, STD, INST. and PRE-TRIP functions. [ILOAD], through the ACB. The base current, [I0], will be equal to [IGEN]
On AOR-1BL and AOR-1BM type OCRs, it 2 Select the required rated primary current, 2 and should be used as a reference for the
can be set by means of a dial on the front to [ICT], of the OCR, (note that [ILOAD] must pick-up current settings of the other protec-
50, 63, 80 or 100%, of the rated CT primary not be greater than [ICT]. tion characteristics.
current (ICT). On AOR-1BS, it is factory set 3 Decide what the base current, [I0] should Select the OCR with the protection and
according to the full load current of the gen- be and use this as a reference for the LTD, 3 indication functions required for the par-
erator (which should be specified at time of STD, INST and PRE-TRIP current settings. ticular application.
order). Select the OCR with the protection and
Base current selection procedures are as fol- 4 indication functions required for the par-
lows: (Refer to tables on P.26, 28, 30 for avail- ticular application.
able values of [ICT] and [I0].
2
OCR Specification
AOR-1B Multi-function protection device 4
Local and remote trip indication
AOR-1B type OCRs are available with trip Trip Indicator Contact Ratings
indications. Two types of trip indication func-
tion are available: single contact type and indi- Single Rated Voltage AC250V AC100V DC30V DC125V DC250V
vidual contact and LED type. Contact Rated Current (Resistive) 7A 7A 5A 0.5A 0.3A
Type Rated Current (inductive) 3A 3A 3A 0.25A 0.15A
1 Individual Rated Voltage AC250V AC100V DC30V DC125V DC220V
Single contact type
This is a voltage-free contact which closes for Contact Rated Current (Resistive) 0.5A 0.25A 2A 0.5A 0.27A
40ms and then resets when the ACB is tripped Type Rated Current (Inductive) 0.2A 0.2A 0.7A 0.2A 0.04A
by any one of the LTD, STD, INST/MCR or
GFT functions. Output is on terminals 22 and
23. 1) All contacts are voltage-free and operate as following table
2
Individual contact and LED type Type of OCR Auto. Reset Contacts *1 Hold Contacts *2
This type has an individual contact and LED For general
for LTD, STD and INST/MCR., and GFT over- feeder PRE-TRIP LTD, STD, INST/MCR, GFT
current functions. The PRE-TRIP function is (L, M char.) System Alarm
incorporated on OCRs with these type of indi- For generator
cators and a corresponding contact and LED protection LTD, STD, INST/MCR System Alarm
are fitted. Additionally a SYSTEM ALARM (S char.) PRE-TRIP
contact and LED are provided to give warning
of abnormality in the OCR unit.
A separate control supply is required for these Notes:
indicators. (A) Contacts
*1:The contacts for LTD, STD, INST/MCR close for 40ms and then reset.
The contact for PRE-TRIP resets when the current level drops below pick-up setting
*2:The contacts remain until the RESET button on the front of the OCR is operated. (Remote
resetting can be achieved by disconnection of the control supply)
**: STD and INST/MCR is common terminal.
(B) LEDs
LEDs (except for PRE-TRIP) remain until the RESET button is operated or the control supply
is disconnected.
LED for PRE-TRIP goes out when the current level drops below pick-up setting.
This unit provides a constant supply for the display indicators (LEDs & volt free contacts) in
the event of a power failure for up to 1 hour. It contains rechargeable batteries which will be
maintained at full charge through the AC supply voltage.
DC Power supply
Systems utilizing a control voltage of 30, 48 or 60V D.C. must use the D.C. power supply module
for the O.C.R. to work effectively. See page 53 for more information.
3
4
OCR Specification
Multi-function protection device
OCR specifications
The multi-function protection device for Tem- The OCR range is divided into three groups: Optional protection functions, indication and a
Power is an 8-bit microprocessor controlled , •AOR-1BL (standard inverse characteristic) current monitoring facility are available.
r.m.s. sensing overcurrent relay (OCR). •AOR-1BM (very/extremely inverse
characteristic)
•AOR-1BS (generator protection).
AOR-1BL-GS 4 Required
AOR-1BL-NS Required
AOR-1BL-ES Required
AOR-1BL-AI Required
AOR-1BL-GI 4 Required
General feeder
AOR-1BL-NI Required
AOR-1BL-EI Required
AOR-1BM-AL2 Not required
AOR-1BM-GL Not required
AOR-1BM-AS Required
M-characteristic
AOR-1BM-GS 4 Required
AOR-1BM-NS Required
AOR-1BM-ES Required
AOR-1BM-AI Required
AOR-1BM-GI 4 Required
AOR-1BM-NI Required
AOR-1BM-EI Required
AOR-1BS-AL 2 Not required
S-characteristic
AOR-1BS-AS Required
Generator
Protection
4
AOR-1BS-NS Required
AOR-1BS-AI Required
4
AOR-1BS-NI Required
Notes:
1 : Not available when [ICT] is 80, 160 or 250A
3 : Long time-delay, short time-delay, instantaneous and ground fault will still operate even if the control voltage is lost.
Type code
AOR-1B L – A L
Field test-facility is included on versions of AOR-1B that have indication LEDs and contacts. This
function permits a simple field check to be performed on the LTD, STD and INST characteristics.
TRIP or NON-TRIP tests of the circuit breaker are possible. To operate push button on OCR (trip
indication is by the LEDs on the front of the AOR-1B).
4
OCR Specification
Accessories 4
OCR checker (external) Electromagnetic inst. trip
Rated Voltage 100-110V AC 50/60Hz The OCR Alarm switch (normally open con-
Power Consumption 500VA tact) indicates the operation of the electro-
Overcurrent trip device magnetic instantaneous trip device only. ON
calibration tests: for 40 ms, then OFF.
•Long time-delay trip
•Short time-delay trip Rated Voltage 100/110V AC 50/60Hz Rating of contact
Test Functions •Instantaneous trip or 9V DC battery
•Pre-trip Alarm Power Consump'n 10VA Load Resistive Lamp Inductive Motor
•Ground fault trip Long time-delay trip check AC 125V 5A 0.7A 3A 0.7A
Continuity check of Test Functions Short time-delay trip AC 250V 3A 0.5A 2A 0.5A
current transformers Instantaneous trip check DC 30V 5A 3A 4A 3A
Outline Dimensions W365xH257xD300(mm) Outline Dim. W92 x H146 x D37(mm) DC 125V 0.4A 0.05A 0.4A 0.05A
Weight 15kg Weight 700g DC 250V 0.2A 0.03A 0.2A 0.03A
Ground fault protection in a 3-phase, 4-wire •Outline dimensions of CT for neutral line
system is possible with a 3-pole breaker using M5 50 AT06, AT12, AT16, AT20, AT20L
the ground fault trip function, In this application
a neutral line current transformer that matches k l Type CW80 - 40LS
the breaker’s ground fault protection charac- L L K Rated 320 1600
teristic should be used. Primary 630
TERASAKI can provide CT for Neutral line. Current (A) 1250
A neutral line CT is built into the 4-pole type
150
80
30
60 M5
N-Line AT20, AT20L, AT25, AT25L, AT32, AT40
Type CW160 - 40LS
K k l L Rated 500 2000
K k 30 29 K 4-M5 Tap
k for fixing Primary 1000 2500
L l k
Neutral CT
l
l k secondary Current 1600 3200
l
wiring (A) 4000
255
n kc kb ka g
0
ø16
Rated secondary current is 5A
OCR
125
4-ø10
160 120
ACB (3 pole) 235 150
Example: for AT25-AT40 types
5
4 OCR Specification - General feeder circuits
L-Type standard inverse characteristic curve
6
OCR Specification
Multi-function protection device 4
Front face of multi-function protective device
Type: AOR-1BL-GS
6 5 1 2 3 4
1. Base current setting dial
2. LTD pick-up current setting dial
LTD time-delay setting dial
3. STD pick-up current setting dial
STD time-delay setting dial
4. INST pick-up current setting dial 7
5. PRE-TRIP pick up current setting dial
PRE-TRIP time-delay setting dial 9
6. GFT pick-up current setting dial 8
GFT time-delay setting dial
14
7. HOT/COLD select switch
8. INST/MCR select switch 10
9. Ramp characteristic select switch
10. LED for trip indicator
11. LED for system alarm indicator
11 13
12. Field test facility
13. Reset button
14. Test terminals (for ANR-1)
15. Trip indicator contact terminals
16. Control power terminals. 15 12 16
4
3
2 LTD current setting range
hour
10
INST current setting range
minute
8
6
5
4
3
2
PRE-TRIP time
setting range
1
50
40
30
20
Operating time
10 N-phase time
8
setting range LTD time
6
5 setting range
4
3
2
1
0.8 1000ms 1000ms
second
0.6
0.5
0.4 400ms
400ms
0.3 STD time
0.2 GFT time
setting range
setting range
0.1
0.08 80ms 80ms
0.06
0.05
0.04
0.03
0.02
0.01
0.008
0.006
0.005
400
7
8
9
10
15
20
30
40
50
60
70
80
90
100
125
150
200
60
70
80
90
100
125
150
200
250
300
500
600
700
800
900
1000
1500
2000
2500
3000
Percent rated current of OCR CT primary current [ICT] Percent rated current of base current [IO]
7
4 OCR Specification - General feeder circuits
M-Type very/extremely inverse characteristic curve
STD
Pick-up current [I2] (A) [I0] x (1 – 1.5 – 2 – 2.5 – 3 – 4 – 6 – 8 – 10 – NON) 10 graduations
Setting tolerance (%) ±15%
Time-delay [T2] (ms)
Relay-time (ms) 10 graduations 80 160 240 320 400 480 560 640 800 1000
Opening time (ms) 100 180 260 340 420 500 580 660 820 1020
Resettable time (ms) 55 135 215 295 375 455 535 615 775 975
Max. total clearing time (ms) 150 230 310 390 470 550 630 710 870 1070
INST or MCR
Pick-up current [I3] (A) [I0] x (2 – 4 – 6 – 8 – 10 – 12 – 14 – 16 – NON) 9 graduations
Setting tolerance (%) ±20%
PRE-TRIP
Pick-up current [IP] (A) [I0] x (0.75 – 0.8 – 0.85 – 0.9 – 0.95 – 1.0 – 1.05 – 1.1) 8 graduations
Setting tolerance (%) ±7.5% (±10% when [ICT] of type AT06 is 80A or 160A)
Time-delay [TP] (s) (60 – 80 – 100 – 120 – 140 – 160 – 180 – 200) at over [IP] setting. 8 graduations
Setting tolerance (%) ±15%
GFT Note: Ground fault current setting [IG] should be below 1200A.
Pick-up current [IP] (A) [ICT] x (0.1 – 0.15 – 0.2 – 0.25 – 0.3 – 0.35 – 0.4) 7 graduations
Setting tolerance (%) ±20%
Time-delay [TG] (ms)
Relay-time (ms) 10 graduations 80 160 240 320 400 480 560 640 800 1000
Opening time (ms) 100 180 260 340 420 500 580 660 820 1020
Resettable time (ms) 55 135 215 295 375 455 535 615 775 975
Max. total clearing time (ms) 150 230 310 390 470 550 630 710 870 1070
N-phase Protection
Pick-up current [IN] (A) [ICT] x (0.2 – 0.25 – 0.32 – 0.4 – 0.5 – 0.63 – 0.8 – 1.0) Fixed setting. Specify at time of order.
Non-tripping at [IN] setting x 105% and below. Tripping at 120% and above.
Time-delay [TN] (s) [TN=T1] 5 graduations using [T1] setting dial at [IN] x 300% current
Setting tolerance (%) ±20% (±30% when [ICT] of type AT06 is 80A or 160A)
8
OCR Specification-General feeder circuits
M-Type very/extremely inverse characteristic curve 4
Front face of multi-function protective device
Type: AOR-1BM-GS
1. Base current setting dial
2. LTD pick-up current setting dial
LTD time-delay setting dial 6 5 1 2 3 4
3. STD pick-up current setting dial
STD time-delay setting dial
4. INST pick-up current setting dial
5. PRE-TRIP pick up current setting dial
PRE-TRIP time-delay setting dial
6. GFT pick-up current setting dial 7
GFT time-delay setting dial
7. HOT/COLD select switch 9
8. INST/MCR select switch 8
9. Ramp characteristic select switch 14
10. LED for trip indicator
11. LED for system alarm indicator 10
12. Field test facility
13. Reset button
14. Test terminals (for ANR-1) 11 13
15. Trip indicator contact terminals
16. Control power terminals.
15 12 16
4
3
N-phase current setting range LTD current setting range
2
hour
8
6
[I4t] extremely 5
4
inverse 3
PRE-TRIP time
2
setting range
[I3t] very inverse
1
50
40
[I4t] extremely
30 inverse
20
Operating time
0.6
0.5
400ms 400ms
0.4 STD time
0.3 setting range
GFT time
0.2 setting range
0.1
80ms 80ms
0.08
0.06
0.05
0.04
0.03
0.02
0.01
0.008
0.006
0.005
400
7
8
9
10
15
20
30
40
50
60
70
80
90
100
125
150
200
60
70
80
90
100
125
150
200
250
300
500
600
700
800
900
1000
1500
2000
2500
3000
Percent rated current of OCR CT primary current [ICT] Percent rated current of base current [IO]
9
4 OCR Specification
S-Type : Generator protection
10
OCR Specification
S-Type : Generator protection 4
Front face of multi-function protective device
Type: AOR-1BS-AS
1. LTD pick-up current setting dial
LTD time-delay setting dial
2. STD pick-up current setting dial 4 1 2 3
STD time-delay setting dial
3. INST pick-up current setting dial
4. PRE-TRIP pick up current setting dial
PRE-TRIP time-delay setting dial
5. HOT/COLD select switch
6. INST/MCR select switch 5
7. Ramp characteristic select switch
8. LED for trip indicator 7
9. LED for system alarm indicator
6
10. Field test facility 12
11. Reset button 8
12. Test terminals (for ANR-1)
13. Trip indicator contact terminals
14. Control power terminals.
9 11
13 10 14
4
3
2
PRE-TRIP current setting range
hour
1
50 LTD current setting range
40
30
STD current setting range
20
N-phase current setting range
10
8
minute
1
50
40
30
N-phase time LTD time
20
setting range setting range
PRE-TRIP time
Operating time
10 setting range
8
6
5
4
3
2
1
0.8 1000ms
second
0.6
0.5
0.4
400ms
0.3 STD time
0.2 setting range
0.1
0.08
80ms
0.06
0.05
0.04
0.03
0.02
0.01
0.008
0.006
0.005
1500
7
8
9
10
15
20
30
40
50
60
70
80
90
100
125
150
200
250
300
400
800
900
1000
2000
2500
3000
500
600
700
11
4 TemTrip
Intelligent protection relay
Specifications
TemTrip is a multi-function microprocessor based protection relay. The standard model provides
3 phase overcurrent & earth fault protection. However, options of undervoltage and reverse
power protection can be incorporated.
It can be fitted integral with the TemPower ACB (PRQ-2) or can be supplied separately, panel
mounted (PRQ-1). Refer to TemTrip catalogue I73Ea for further information.
COMPATIBLE
Standard inverse
Very inverse
Extremely inverse
Definite
minute
Operating time
Ramped
Ramped Definite
Definite
second
Inverse
Generator
protection
12
TemTrip
Intelligent protection relay 4
Protection functions
Note : PRQ-2, the user can select between INST. or MCR (making current release).
13
4 TemTrip
Intelligent protection relay
PRQ-2 Settings
Note :*1: Non-tripping at [I1] setting X 105% and below. Tripping at 120% and above.
*2 [I2t] Ramp characteristic Base Current [I0]
Characteristic change-over switches
Use these switches to change • Base current [IO] is the reference current
the AS and AG characteristics. value used to set operation values.
Change-over IN OUT • Base current [IO] can be adjusted in three
AS I2t ramp characteristic definite characteristic
steps; 0.63, 0.8, or 1.0 times CT rated cur-
AG I t ramp characteristic
2
definite characteristic
rent [ICT]. (For general feeder circuit use)
Breaker A
Over temperature detection Zone interlocking TemTrip
By monitoring the temperature of the contacts This new technique of selectivity was devel-
Fault Point
it is possible to inform the user if contacts oped to overcome the drawbacks of long
Zone 3
require 'dressing' thus providing maintenance time delays associated with time discrimina-
information, other applications could be detec- tion. Zone interlocking can be applied to both
tion of inadequate ventilation or de-rating serial and parallel networks to obtain full selec-
within the switchboard. tivity whilst still maintaining instantaneous trip- Breaker B
TemTrip
ping. For further information please consult
TemTrip I73E catalogue.
Fault Point
Zone 4
Arcing fault detection
14
TemTrip
Intelligent protection relay 4
Data communication Functions of the remote monitor
Information gathered by the TemTrip intelligent 1 Breaker status indication 4 Setting zone selective interlock
relay can be displayed on a PMQ-1B remote (open/closed/tripped) • Zone setting can be changed or cleared
monitor. Using fibre optic cable to obtain high • Phase A current on the LCD screen.
information reliability, one PMQ-1B monitor • Phase B current
can be connected to eight TemTrips. Up to five • Phase C current 5 Fault type, trip current and
PMQs may then be connected via an RS485 • Ground fault current operation time indication.
connection which would enable 40 TemTrips to All current is indicated in Amps
be viewed on a building management system Transmitting data to PC
6
(B.M.S.) or supervisory control and data 2 Power indication (via RS-232C)
acquisition system (S.C.A.D.A.)
3 Line voltage indication
B.M.S. supervisor
PMQ-1B monitor
The information viewed on the Remote Monitor can be further transmitted to a Trend Building Management System utilising
COMPATIBLE a device known as a Terasaki Node Controller (T.N.C.). Standard user software can be supplied for viewing on a Trend 945
Supervisor. For further information please contact Terasaki.
Schematic single line diagram providing status Unique user pages showing breaker location, Graphical display of current, voltage, & power
overview settings, electrical parameters and fault trend logs
information
15
5 Outline Dimensions (mm)
• Type AT06,12,16 & 20 (with horizontal terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type FIXED TYPE
* The required distance is 625 mm.
Panel cut-out P P
C : front panel centre line C 207 (3P)
207 292 (4P)
P 175 (3P) 195 (3P)
C
175 260 (4P) 195 280 (4P)
142.5 (3P) 187.5 (3P)
142.5 227.5 (4P) 187.5 272.5 (4P) control circuit terminals
auxiliary switch 28-M3.5 screws
arc barrier 2
terminal
2-ø 12 screw,M3.5
250
Fixing blocks
with ø12 holes.
Blocks are fitted
25
when the
breaker is sub-
ject to marine
*545 (min.)
N classification
society rules.
R116 1 Secure these
380
260
332.5
270
301
blocks to the
switchboard
frame.
145
20
50
55
30
90 (3P)
Fixed type P P
C 187.5 (3P) C : front panel centre line
187.5 272.5 (4P)
P 200 (3P)
C 162.5 285 (4P)
maintenance space
auxiliary switch
arc barrier 2
terminal screw, M3.5
*520 (min.)
N
1
260
270
30
25
100
230
260
4-ø14
255 (3P) 162.5 (3P)
255 340 (4P) 162.5 247.5 (4P) Mtg. holes
16
Outline Dimensions (mm)
• Type AT06,12,16 & 20 (with horizontal terminals) 5
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 600 x (D) 456.5 AT06 AT12 AT16 AT20
a 25 30 30 30
t 8 10 15 20
dust plate 2-ø11 45 conductor overlap max. w 45 55 55 55
5
10
w
a
CONNECTED position
225 90 20
TEST position P
142.5 (3P) C
ISOLATED position arc barrier 2 227.5 (4P) 142.5
rear panel
15 30 (not supplied) 2-M10 tapped
A
Mtg. holes
t
461
6 306.2
380
b
85 85 85
20
25 116 153 (3P)
126 200 127.2 238 (4P)
draw-out position
333 81.8 M8 screw earth terminal
453.2
w
a
P
N C
t
440
500
c
b
126 230 85 85 85
417
dust plate surface 4-ø14 Mtg. holes
2-ø 12 250
25
*545 (min.)
N
R116
332.5
380
1
301
270
260
145
50
55
30
20
90 (3P)
P 153 (3P)
C 238 (4P) 1-ø9 230
rear panel cut 260 4-ø14 mtg. holes
130 (3P)
3 front panel cut 130 215 (4P)
draw-out handle 184 (3P)
Note : 1 N is neutral pole of 4-pole breaker. 184 269 (4P)
2 Use arc barrier of a heat and flame resistant insulating material. (max.) (max.)
Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)
18
Outline Dimensions (mm)
• Type AT06,12,16 & 20 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 600 x (D) 456.5
5
AT06 AT12 AT16 AT20
a 25 30 30 50
dust plate b 12.5 12.5 17.5 15
5
10
t 8 10 15 15
w 50 55 65 80
front panel øD 2-ø11 2-ø11 2-ø11 3-ø12
c 120.5 115.5 105.5 100.5
225 90 d 82 82 82 62
CONNECTED position
TEST position 2-M10 tapped
rear panel mtg holes
ISOLATED position arc barrier 2 142.5 (3P) P
(not supplied) C
15 30 227.5 (4P) 142.5
conductor overlap max.
A
b
N
w
a
45
b
b
øD
w
a
6 306.2
b
461
380
Terminal
dimensions of
w
types AT06 to
AT16
t
20
c
85 85 85
25
116 øD 153 (3P)
20
126 200 127.2 238 (4P)
draw-out position
333 453.2 91.8 M8 screw earth
4-ø14 Mtg. holes terminal
dust plate surface
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules.
•Mounting angle steel not supplied.
19
5 Outline Dimensions (mm)
• Type AT25 (with vertical terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
FIXED TYPE P 252 (3P) Fixing blocks with
Draw-out type C
* The required distance is 625 mm. 252 367 (4P) ø12 holes. Blocks
Panel cut-out are fitted when the
P : front panel centre line 240 (3P)
P C breaker is subject
C 223 (3P) 240 355 (4P) to marine classifi-
223 338 (4P) cation society rules.
232.5 (3P)
232.5 347.5 (4P) Secure these blocks
187.5 (3P) to the switchboard
187.5 302.5 (4P) auxiliary switch control circuit terminals frame.
terminal screw, 28-M3.5 screws
2-ø 12 250 M3.5
arc barrier 2
25
*545 (min.)
R116
N
500
440
1
270
332.5
260
145
55
50
20
30
90 (3P)
198 (3P) 230
rear panel cut 313 (4P) draw-out 260 4-ø14 mtg. holes
handle 175 (3P)
3 front panel cut
1-ø9 175 290 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 229 (3P)
2 Use arc barrier of a heat and flame resistant insulating material. 229 344 (4P)
Cradle with arc barrier available on request. (max.) (max.)
3 If door flange is used, a large cut out is required. (260 x 280 mm)
P
C P
Fixed type 232.5 (3P) C : front panel centre line
232.5 347.5 (4P)
245 (3P)
207.5 360 (4P)
panel cut-out
250 (3P) (4P) control circuit
terminals
28-M3.5 screws
*520 (min)
600
N
260
1
270
25
30
100
230
260 4-ø14 Mtg. holes
300 300 (3P)
415 (4P) 207.5 (3P)
207.5 322.5 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 225 (3P)
2 Use arc barrier of a heat and flame resistant insulating material. 225 340 (4P)
20
Outline Dimensions (mm)
• Type AT25 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 600 x (D) 456.5
5
Note:* 3.2 mm spacer required (not supplied)
dust plate
5
10
front panel
225 93 3.2* rear panel P
C
CONNECTED position (not supplied) 187.5 (3P) 2-M10 tapped mtg. holes
TEST position 302.5 (4P) 187.5
conductor
2
ISOLATED position arc barrier overlap max.
A N
15 30
3-ø12
45
20 30 30 20 20 30 30 20
15 25 2515 15 25 25 15
100
80
461
525
80
80
500
80
6 306.2
100
130
110
15 15
20
25
M8 screw
116 20 earth terminal 115 115 115 3-ø14
draw-out position 126 200 127.2 198 (3P)
333 453.2 81.8 313 (4P)
dust plate surface 4-ø14 Mtg. holes
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.
137 225
front
panel 55
arc barrier 2
237 23
35 N
P
C
20 30 30 20 20 30 30 20
15 25 25 1515 25 25 15
140
100
80
500
440
80
10
80
80
80
100
105
185
85
15 15
3-ø12
126 230 21 115 115 115 3-ø14
417
dust plate surface
4-ø14 Mtg. holes
•Mounting angle steel not supplied.
1
5 Outline Dimensions (mm)
• Type AT25 (with horizontal terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
FIXED TYPE P 252 (3P) Fixing blocks with
Draw-out type C
* The required distance is 625 mm. 252 367 (4P) ø12 holes. Blocks
Panel cut-out are fitted when the
P : front panel centre line 240 (3P)
P C breaker is subject
C 223 (3P) 240 355 (4P) to marine classifi-
223 338 (4P) cation society rules.
232.5 (3P)
232.5 347.5 (4P) Secure these blocks
187.5 (3P) to the switchboard
187.5 302.5 (4P) auxiliary switch control circuit terminals frame.
terminal screw, 28-M3.5 screws
2-ø 12 250 M3.5
arc barrier 2
25
*545 (min.)
R116
N
500
440
1
270
332.5
260
145
55
50
20
30
90 (3P)
198 (3P) 230
rear panel cut 313 (4P) draw-out 260 4-ø14 mtg. holes
handle 175 (3P)
3 front panel cut
1-ø9 175 290 (4P)
Note : 1 N is neutral pole of 4-pole breaker.
2 Use arc barrier of a heat and flame resistant insulating material. 229 (3P)
Cradle with arc barrier available on request. 229 344 (4P)
3 If door flange is used, a large cut out is required. (260 x 280 mm) (max.) (max.)
2
Outline Dimensions (mm)
• Type AT25 (with horizontal terminals) 5
Note:* 3.2 mm spacer required (not supplied) N Neutral rated current 2000A
dust plate
5
10
front panel
225 93 3.2* rear panel P 2-M10 tapped
C
CONNECTED position (not supplied) 187.5 (3P) mtg. holes
TEST position 302.5 (4P) 187.5
2
ISOLATED position arc barrier A
N
15 30 45
80 80
50 50
15
60 50
60 50
525
500
80
80
461
15
50 60
50 60
6 306.2
20
100
100
20
25 10
3-ø14
M8 screw
116 earth terminal 115 115 115
draw-out position 126 200 127.2 198 (3P)
3-ø14
25 313 (4P)
333 453.2 32.8
dust plate surface 4-ø14 Mtg. holes
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.
3
5 Outline dimensions (mm)
• Type AT32 (with vertical terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 700 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type FIXED TYPE P 282 (3P) Fixing blocks
* The required distance is 675 mm. C
282 417 (4P) with ø12 holes,
P
Panel cut-out C : front panel centre line 270 (3P) blocks are fitted
when the
P 270 405 (4P)
C breaker is sub-
253 (3P)
262.5 (3P) ject to marine
253 388 (4P) classification
262.5 397.5 (4P)
society rules.
217.5 (3P)
auxiliary switch control circuit terminals Secure these
217.5 352.5 (4P) blocks to the
terminal screw, 28-M3.5 screws
250 switchboard
2-ø 12 M3.5
arc barrier 2 frame.
*545 (min.)
R116
25
N
500
440
260
270
332.5
145
55
50
20
90 (3P)
30
250
*520 (min)
600
N
1 control
260
270
circuit
terminals
28-M3.5
screws
25
30
100
230
330 (3P) 260 4-ø14
330 465 (4P)
237.5 (3P) Mtg. holes
237.5 372.5 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 255 (3P)
2 Use arc barrier of a heat and flame resistant insulating material. 255 390 (4P)
4
Outline dimensions (mm)
• Type AT32 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 700 x (D) 456.5
5
Note: *3.2mm spacer required (not supplied) N Neutral rated current 2000A
dust plate
5
10
15 30
45
15 30 30 30 15 15 30 30 30 15
15 25 25 15 15 25 25 15
120
80
461
80
80
500
306.2 525
80
6
120
130
90
15 18
20
25
M8 screw
116 earth terminal 4-ø14
135 135 135
126 200 127.2 20
draw-out position 228 (3P)
333 453.2 81.8 3-ø12 363 (4P)
dust plate surface 4-ø14 Mtg. holes
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.
137
front P
55 C
panel
arc barrier 2
N
237 23 35
15 30 30 30 15 15 30 30 30 15
15 25 2515 15 25 25 15
140
120
80
500
440
80
10
80
80
120
105
15 18
65
5
5
Outline dimensions (mm)
• Type AT32 (with horizontal terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 700 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type FIXED TYPE P 282 (3P)
* The required distance is 675 mm. C
282 417 (4P)
P
Panel cut-out C : front panel centre line 270 (3P) Fixing blocks with
ø12 holes, blocks
P 270 405 (4P) are fitted when
C 253 (3P) the breaker is
262.5 (3P)
253 388 (4P) subject to marine
262.5 397.5 (4P) classification
217.5 (3P) society rules.
auxiliary switch control circuit terminals Secure these
217.5 352.5 (4P) blocks to the
terminal screw, 28-M3.5 screws
switchboard
250 2-ø 12 M3.5 frame.
arc barrier 2
*545 (min.)
R116
25
N
500
440
260
270
332.5
145
55
50
20
90 (3P)
30
6
5
Outline dimensions (mm)
• Type AT32 (with horizontal terminals)
Note: *3.2mm spacer required (not supplied) N Neutral rated current 2000A
dust plate
5
10
15 30 55 80 100
45 50 70
15 (N)
60 50
60 60
20
461
80
525
80
500
20
306.2
100 50 60
6
60 60
20
90
25
20
M8 screw
116 earth terminal 3-ø14
135 135 135
draw-out position 126 200 127.2 10 228 (3P)
333 453.2 32.8 25 3-ø14 363 (4P)
dust plate surface 4-ø14 Mtg. holes
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.
7
5 Outline dimensions (mm)
• Type AT40 (with vertical terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 700 mm with respect to electrical devices,
grounded metal parts etc, located above.
FIXED TYPE
Draw-out type * The required distance is 675 mm. P 282 (3P)
C
282 417 (4P)
P
Panel cut-out C : front panel centre line 270 (3P)
P 270 405 (4P)
C 253 (3P) Fixing blocks with
253 388 (4P) 262.5 (3P) ø12 holes, blocks
are fitted when the
262.5 397.5 (4P) breaker is subject
217.5 (3P) to marine
217.5 352.5 (4P) auxiliary switch control circuit terminals classification society
rules. Secure these
terminal screw, 28-M3.5 screws blocks to the
250 M3.5 switchboard frame.
2-ø 12 arc barrier 2
*545 (min.)
25
R116
N
500
440
260
270
332.5
145
55
50
(3P)
30
20
90
228 (3P) 230
rear panel cut 363 (4P) 260 4-ø14 mtg.
205 (3P) holes
3 front panel cut 1-ø9 205 340 (4P)
Note : 1 N is neutral pole of 4-pole breaker. 259 (3P)
draw-out handle 259 394 (4P)
2 Use arc barrier of a heat and flame resistant
insulating material. Cradle with arc barrier available on request. (max.) (max.)
3 If door flange is used, a large cut out is required. (260 x 280 mm)
P
C
Fixed type 262.5 (3P)
262.5 397.5 (4P)
275 (3P)
237.5 410 (4P)
*520 (min)
N control cir-
1 cuit
270
260
terminals
28-M3.5
screws
30
100
25
230
260 4-ø14 Mtg
330 330 (3P) . holes
237.5 (3P)
465 (4P) 237.5 372.5 (4P)
255 (3P)
Note : 1 N is neutral pole of 4-pole breaker. 255 390 (4P)
2 Use arc barrier of a heat and flame resistant insulating material.
8
5
Outline dimensions (mm)
• Type AT40 (with vertical terminals)
Note: Dimensions of metal-clad construction (3 pole) (H) 575 x (W) 700 x (D) 456.5
Note: *3.2mm spacer required (not supplied) N Neutral pole rated current 2000A
dust plate
10
15 30
45
17.5
15 25 25 15 15 25 25 15
35 35 35
140
80
17.5
525
60
80
461
17.5
500
35 35 35
80
6 306.2
140
130
17.5
15 22
80
20
25
116 M8 screw
126 200 127.2 earth terminal 4-ø15
draw-out position 20 135 135 135
333 453.2 81.8
228 (3P)
4-ø14 mtg. holes 3-ø12 363 (4P)
dust plate surface
A To be used where the breaker is exposed to severe vibration, necessary when the breaker is
subject to marine classification society rules. •Mounting angle steel not supplied.
dust
406 conductor overlap max.
5 plate
10
137 225
front P
panel C
55
arc barrier 2
N
237 23
35
15 303030 1515 303030 15
15 2525 15 15 25 25 15
140
120
80
500
440
10
80
80
80
120
105
15 18
65
9
5 Outline dimensions (mm)
• Type AT06, 12, 16 & 20 (with front terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above. AT06 AT12 AT16 AT20
Draw-out type a 25 30 30 30
P
C : front panel centre line w 45 55 55 55
t 8 10 15 25
Panel cut-out d 11 11 11 12
207 207 (3P)
P 175 (3P) 292 (4P)
C
175 260 (4P) 195 195 (3P)
280 (4P)
142.5 (3P)
142.5 227.5 (4P) 187.5 187.5 (3P) control circuit terminals
auxiliary switch 272.5 (4P) 28-M3.5 screws
arc barrier 2
terminal
screw,M3.5
2-ø 12 250
Fixing blocks
with ø12 holes.
Blocks are fitted
when the
25
breaker is sub-
*545 (min.)
ject to marine
classification
N society rules.
Secure these
380
R116 1
260
301
blocks to the
270
332.5
switchboard
* frame.
145
50
55
20
90 (3P)
30
Connected
Front cover
Isolated
N
Test
arc barrier 2 P
15 30 C
20
*545
493
461
260
6 306.2
20
20
20
25
116
a 2-øD
126 200 127.2 w
t
Draw-out position
453.2 M8
333 32.8 85 85 85
Earth terminal
153 (3P)
Dustplate surface 238 (4P)
10
Outline dimensions (mm)
• Type AT25 (with front terminals)
Note: DRAW-OUT TYPE
5
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
Draw-out type P P Fixing blocks with
C : front panel centre line C 252 (3P)
367 (4P) ø12 holes. Blocks
252
Panel cut-out are fitted when the
240 (3P) breaker is subject to
P
C 223 (3P) 240 355 (4P) marine classification
223 338 (4P) society rules.
232.5 (3P)
232.5 347.5 (4P) Secure these blocks
187.5 (3P)
to the switchboard
187.5 302.5 (4P) auxiliary switch control circuit terminals frame.
terminal screw, 28-M3.5 screws
2-ø 12 250 M3.5
arc barrier 2
25
*545 (min.)
R116
N
500
440
1
332.5
260
270
145
55
50
20
30
90 (3P)
198 (3P) 230
rear panel cut
313 (4P) draw-out 260 4-ø14 mtg. holes
handle 175 (3P)
3 front panel cut 1-ø9 175 290 (4P)
229 (3P)
Note : 1 N is neutral pole of 4-pole breaker. 229 344 (4P)
2 Use arc barrier of a heat and flame resistant insulating material. (max.) (max.)
Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)
Connected P
5
Dust plate
225 93 C
10
Front
cover Test 302.5 187.5 2-M10
3.2 N tapped mtg.
20
holes
Isolated
arc barrier 2
15 30
30
600
*545
500
461
260
6 306.2
20
30
100
25
20
116 10 50
M8
80
Earth 4-ø12
126 200 127.2 terminal 115 115 115
t
Draw-out position
main pole N pole
333 453.2 32.8 198 (3P)
t 25 20
Dust plate surface 313 (4P)
11
5
Outline dimensions (mm)
• Type AT32 (with front terminals)
Note: DRAW-OUT TYPE
* When no arc barrier is used, the minimum required distance is 650 mm with respect to electrical
devices, grounded metal parts etc, located above.
Front connected type P
C : front panel centre line P 282 (3P) Fixing blocks
C
282 417 (4P) with ø12 holes,
blocks are
Panel cut-out 270 (3P)
fitted when the
P 270 405 (4P) breaker is sub-
C 253 (3P)
262.5 (3P) ject to marine
253 388 (4P) classification
262.5 397.5 (4P)
society rules.
217.5 (3P) Secure these
auxiliary switch control circuit terminals
217.5 352.5 (4P) blocks to the
terminal screw, 28-M3.5 screws
250 switchboard
M3.5
2-ø 12 arc barrier 2 frame.
*545 (min.)
R116
25
N
500
440
1
270
260
332.5
145
55
50
(3P)
30
20
90
rear panel cut 228 (3P) 230
363 (4P) 260 4-ø14
3 front panel cut mtg. holes
205 (3P)
1-ø9 205 340 (4P)
259 (3P)
Note : 1 N is neutral pole of 4-pole breaker. draw-out 259 394 (4P)
2 Use arc barrier of a heat and flame resistant handle (max.)
(max.)
insulating material. Cradle with arc barrier available on request.
3 If door flange is used, a large cut out is required. (260 x 280 mm)
Dust plate
5
10
Front cover
225 93 P 2-M10
352.5 C
217.5 tapped mtg
Connected 3.2 holes
N
20
Test
arc barrier 2
Isolated
30
15 30
*545
600
461
500
260
6 306.2
30
100
20
116
25 50 60
20
10
80 100
126 200 127.2 t
Draw-out position 135 135 135 4-ø14
32.8 M8 228 (3P)
333 453.2 Earth 363 (4P)
Dust plate surface terminal main pole N pole
Side View t 25 20
Back View
12
Outline dimensions (mm)
• OCR Options 5
PRQ-1 (Panel mounting type) PRQ-2 (Intregal with TemPower ACB)
C
L
Note: For further infor-
mation refer to TemTrip
catalogue I73Ea
164
220
395
C
L
132.5
145.5
4–ø6
250
140
Panel cut out
210
26
wiring diagrams.
Connection Description
1 A Gen N
( B Gen L ) 16.0
C Mains N
F BATTERY LED MAINS NEON
D Mains L E
190.0
F DC 24V output +VE C
A
1 Note: The main terminals used are C &
D for the AC Supply voltage and E & F
5.0
for the 24V DC output. If standby genera-
tion is available this may be connected to
terminals A & B. 26
19 + 19 2 - ø5.5
Refer to page 54 for wiring OCR SUPPLY MTG. HOLES
diagram.
50.0
20 – 2024V DC
9
4.7
1 - ø3.4
SIDE VIEW MTG. HOLE
TOP VIEW
13
6 TemPower
Connection diagrams
Main circuit Overcurrent trip (OCR) Undervoltage trip Motor charging/closing control Spring
(UVT) circuits charged
switch
+ 19
Customers Power suuply
supply SW1 option – 20 Source
– 20 19 + 9 11 1 3 15
k AUX Spring
L SW charged
CT4 k switch
CT5 L ON
L SW
CT6
n g kC kB kA S0 S1 SP Undervoltage
Overcurrent relay (OCR) trip controller
(for general feeder circuits)
k ->T0 kB (example AOR-1BL-GI)
CT2
L
UVT Motor
Operator
From
motor
circuit
->T0 kA AC AP AL AS AG AA a c TN TP
Interlock switch
L ->T0 kC TP
L
CT1 CT3
k ->T0 n MIT
k
TN
22 28 25 26 27 24 + 17 18 – 10 12 2 4
Note : Do not use these output contacts in circuits exceeding 250V Note : When control power is DC Note : Spring charged switch arrangement differs from the above
AC or 220V DC. refer to the circuit diagram on when control power is DC see circuit diagram on page 19.
page 21.
For the control power source
CT1-3 : CT for overcurrent trip for types AT06-AT20
AC rated voltage operating range is 85% to 110%
DC rated voltage operating range is 75% to 110%.
CT4-6 : CT for overcurrent trip for types AT25-AT40
17 18
Current measuring function terminals
19 20
Control power terminals Shunt trip (SHT) Auxiliary switch
22
Common line for ind. contact
23
Trip indication (single contact type) SHT 31
24
System alarm indication contact Shunt trip device Auxiliary switch
7 8 to
25
LTD ind. contact SHT Circuit 50
26 AUX.SW Auxiliary switch
STD / INST ind. contact
27
GFT ind. contact P B : Push-button switch
28
PRE-TRIP alarm contact
MHT
Magnetic hold trigger (tripping coil)
Source
switch For indication of tripping by elec-
Marine classification society's rules apply, they
Connected position
61-63 OFF
71-72 ON
operate in the SERVICE position only.
tromagnetic instantaneous trip 71-73 OFF
device only. Isolated position 81-82 ON
4 3
Source Source 81-83 OFF
Insert position 91-92 ON
Capacitor trip 91-93 OFF
Source
1 2
PB PB X1 X2
(open) (open)
Test Connected Isolated Insert
position position position position
7 7 13 17 31 33 35 37 39 41 43 45 47 49 61 71 81 91
AUX AUX
SW SW
*2
SHT SHT
8 8 14 18 32 34 36 38 40 42 44 46 48 50 62 63 72 73 82 83 92 93
93 92 91 22 23
15
7 TemPower Order Form
For general feeder use
Specifications
1 Type AT06 AT12 AT16 AT20 AT20L AT25 AT25L AT32 AT40
5 Type of mounting Fixed type - horizontal terminals vertical terminals front connection
Drawout type - horizontal terminals vertical terminals front connection
Main circuit safety shutters
Control circuit safety shutter Position switch- Connected Test Isolated Insert
Test jumper (lead wire 5m) __________ sets Mal-insertion prevention device
Door interlock Carrying roller
Arc gas barrier (draw-out type only) Breaker fixing blocks (draw-out type only)
9 Accessories for overcurrent CT for neutral line UPS Power supply module Supply voltage AC _______
trip
10 Other trips Shunt trip- AC______ DC______ Instantaneous operating Continuously rated
Capacitor trip
Undervoltage trip- AC______ DC______ Instantaneous Required (time-delay STD)
11 Other accessories Trip indication switch IP54 Cover IP54 Cover & depth frame Door flange
Key lock ( lock in open lock in close) Carrying handle Slow close jigs
Castell lock (facility only) Castell lock ______ symbol Close-open cycle counter
Mechanical interlock Vertical Horizontal Breakers pitch ______ mm
Dust plate Push-button lock Auxiliary switch 2A2B 5A5B 10A10B
12 Special environment Not required Tropicalization Anti-chemical treatment Cold climate treatment
specification
13 Spare parts Not required Required (please state individual spare parts required)
14 Documentation Test report ______ copies ACB Instruction manual ______ copies
16
TemPower Order Form
For generator protection use 7
Company Name Order No. __________
Specifications
1 Type AT06 AT12 AT16 AT20 AT20L AT25 AT25L AT32 AT40
5 Type of mounting Fixed type - horizontal terminals vertical terminals front connection
Drawout type - horizontal terminals vertical terminals front connection
Main circuit safety shutters
Control circuit safety shutter Position switch- Connected Test Isolated Insert
Test jumper (lead wire 5m) __________ sets Mal-insertion prevention device
Door interlock Carrying roller
Arc gas barrier (draw-out type only) Breaker fixing blocks (draw-out type only)
9 Accessories for overcurrent CT for neutral line UPS Power supply module Supply voltage AC _______
trip
10 Other trips Shunt trip- AC______ DC______ Instantaneous operating Continuously rated
Capacitor trip
Undervoltage trip- AC______ DC______ Instantaneous Required (time-delay STD)
11 Other accessories Trip indication switch IP54 Cover IP54 Cover & depth frame Door flange
Key lock ( lock in open lock in close) Carrying handle Slow close jigs
Castell lock (facility only) Castell lock ______ symbol Close-open cycle counter
Mechanical interlock Vertical Horizontal Breakers pitch ______ mm
Dust plate Push-button lock Auxiliary switch 2A2B 5A5B 10A10B
12 Special environment Not required Tropicalisation Anti-chemical treatment Cold climate treatment
specification
13 Spare parts Not required Required (please state individual spare parts required)
14 Documentation Test report ______ copies ACB Instruction manual ______ copies
17
7 TemPower Order Form
Spares listings
3 Serial No.
8 Other trips Shunt trip- AC______ DC______ Instantaneous operating Continuously rated
Capacitor trip
Undervoltage trip- AC______ DC______ Instantaneous required (time-delay STD)
9 Other accessories Trip indication switch IP54 Cover IP54 Cover & depth frame Door flange
Key lock ( lock in open lock in close) Carrying handle Slow close jigs
Castell lock (facility only) Castell lock ______ symbol Close-opening cycle counter
Mechanical interlock Vertical Horizontal Breakers pitch ______ mm
Dust plate Push-button lock Auxiliary switch 2A2B 5A5B 10A10B
10 RECOMMENDED SPARES: Although unlikely, should spare parts be stocked we would recommend to keep only the arc chutes and
arcing contacts.
18
Direct Response Prevents Costly Down Time.
their needs.
Terasaki (Europe) Ltd is the largest circuit breaker manufacturer in the United Kingdom and the
Channel 4 TV - Nissan Motor Plant - IBM (UK) Ltd - Shell - P & O Containers
and HV certifications.
For free advice and catalogue contact: Stuart Smith - Service Manager at