GE

Security

Kilsen Fire Systems Product Catalogue

g
In this catalogue you will find a wide range of

Fire Protection equipment from GE Security.

GE Security is a global technology leader dedicated

to supporting the needs of the rapidly growing

electronic security industry and to expanding

current technologies, products and services that

GE Security, create revenue growth opportunities for its

customers. As part of the GE family, GE Security


unrivalled expertise in shares the spirit of innovation that has
Fire Protection distinguished GE for well over 100 years. GE

Security's commitment to the ongoing success of

its partners and affiliates means that we maintain

a sharp focus on product and service innovation,

world-class manufacturing practices and

operational excellence.

GE Security is a worldwide organisation with sales

and technical support operations in 27 countries,

and manufacturing and logistics operations in

Europe, the U.S. and China.

GE Security has expertise in all areas of electronic

security, including:
z Intrusion and Fire Protection

z Electronic Access and Facility Management

z Key Management and Remote Access Systems

and Services

z Fibre Optic Transmission and Reception

Equipment

z CCTV, Digital Video and Surveillance Equipment

z Video Multiplexing and Digital Storage

When you're looking for the finest in Fire

Protection products with leading-edge

technology and the backing of a world leader, you

need look no further than this catalogue.


Conventional Fire Systems
Page : 3

Conventional fire alarm panel with 2 zones NKB602

The NKB600 Series microprocessor controlled, conventional fire panels


incorporate state of the art technology, reliability, ease of installation
and maintenance in a basic package. They are compatible with
conventional detectors such as the Kilsen 200, 300, 500 and 700 series
devices. The NKB602 has 2 conventional zones.

Specifications

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of 20
detectors
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm E Modern, elegant design
Manual call point resistance 100 Ohm, 2 W E Compact models for 2, 4 and 6 zones
Outputs
E Microprocessor controlled
Fire alarm 24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
E Multilingual keyboard
Environmental E 2 Access levels
Working temperature +5 to +40°C E Differentiation between alarms from manual call points
Storage temperature -10 to +70°C and automatic detectors in the same zone
Relative humidity 95 % (non-condencing)
E Acoustic indications for fire and fault
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm
E Optical indications for fire and fault by zone
Weight without batteries 3 kg E Low maintenance
E Compatible with all ranges of KILSEN conventional
Ordering Information detectors

NKB602 Conventional fire alarm panel with 2 zones


Conventional Fire Systems
Page : 4

Conventional fire alarm panel with 4 zones NKB604

The NKB600 Series microprocessor controlled, conventional fire panels


incorporate state of the art technology, reliability, ease of installation
and maintenance in a basic package. They are compatible with
conventional detectors such as the Kilsen 200, 300, 500 and 700 series
devices. The NKB604 has 4 conventional zones.

Specifications

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of 20
detectors
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm E Modern, elegant design
Manual call point resistance 100 Ohm, 2 W E Compact models for 2, 4 and 6 zones
Outputs
E Microprocessor controlled
Fire alarm 24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
E Multilingual keyboard
Environmental E 2 Access levels
Working temperature +5 to +40°C E Differentiation between alarms from manual call points
Storage temperature -10 to +70°C and automatic detectors in the same zone
Relative humidity 95 % (non-condencing)
E Acoustic indications for fire and fault
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm
E Optical indications for fire and fault by zone
Weight without batteries 3 kg E Low maintenance
E Compatible with all ranges of KILSEN conventional
Ordering Information detectors

NKB604 Conventional fire alarm panel with 4 zones


Conventional Fire Systems
Page : 5

Conventional fire alarm panel with 6 zones NKB606

The NKB600 Series microprocessor controlled, conventional fire panels


incorporate state of the art technology, reliability, ease of installation
and maintenance in a basic package. They are compatible with
conventional detectors such as the Kilsen 200, 300, 500 and 700 series
devices. The NKB606 has 6 conventional zones.

Specifications

Supply Voltage 125/230 VAC @ 50/60 Hz


Mains fuse (Type 5x20 mm) 0.5/0.25 A
Total consumption < 20 W
Nominal Output Voltage 24 VDC
Batteries
Recommended batteries 2 off 1.9 Ah, 12 V
Fuse Rating 1A
Maximum load current < 100 mA
Zone
Maximum Load 72 mA
Maximum number of 20
detectors
Ouput voltage 22 to 28 VDC
End-of-line resitance 4k7 Ohm E Modern, elegant design
Manual call point resistance 100 Ohm, 2 W E Compact models for 2, 4 and 6 zones
Outputs
E Microprocessor controlled
Fire alarm 24 VDC ± 15%, 300 mA
Fault alarm (Fail-to-safe) 24 VDC ± 15%, 100 mA
E Multilingual keyboard
Environmental E 2 Access levels
Working temperature +5 to +40°C E Differentiation between alarms from manual call points
Storage temperature -10 to +70°C and automatic detectors in the same zone
Relative humidity 95 % (non-condencing)
E Acoustic indications for fire and fault
Physical Characteristics
Size (w x h x d) 305 x 295 x 100 mm
E Optical indications for fire and fault by zone
Weight without batteries 3 kg E Low maintenance
E Compatible with all ranges of KILSEN conventional
Ordering Information detectors

NKB606 Conventional fire alarm panel with 6 zones


Conventional Fire Systems
Page : 6

Conventional fire panel with 2 fire alarm zones NK702

The NK700 series of conventional fire alarm and extinguishing control


panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The NK704 has 4
conventional zones.

Specifications

Supply voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 2.3 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per 20
zone
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay outputs (excluding 1 A @ 30 VDC
sounders) E Modern, attractive design
Extinguishing relay outputs
E Microprocessor-controlled
Maximum load NA
Fuse rating NA E From 2 up to 16-zones
Auxilliary output 250 mA E EN54 approved
24 VDC Resetable output E 2 User access levels
Maximum load 100 mA
Reset time 3s
E 2 Monitored sounder outputs
Environment E One-man test capability
Working temperature -5 °C to +40 °C E 24 Volt resetable output
Relative humidity 95 % (non condensing)
E External 'Class Change' facility
IP rating IP30
Physical characteristics E Alarm output with potential free relay
Size (mm) 297 (w) x 307 (h) x 105 (d) E Common fault output with potential free relay
Weight (without batteries) 3.6 kg E External watchdog

Ordering Information
E Active end-of-line support
E Addional optional modules with supervised or relay
NK702 Conventional fire panel with 2 fire alarm zones outputs
Conventional Fire Systems
Page : 7

Conventional fire panel with 4 fire alarm zones NK704

The NK700 series of conventional fire alarm and extinguishing control


panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The NK704 has 4
conventional zones.

Specifications

Supply voltage 230 VAC @ 50 Hz (±10%)


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 1A
Zone
Maximum load 72 mA
Max number of detectors 20
Sounders
Maximum load 300 mA
Relay outputs (excluding 2 A @ 250 V
Sounders)
Extinguishing relay outputs
Maximum load NA
Fuse rating NA E Modern, attractive design
Open collector outputs 15 mA E Microprocessor-controlled
Auxilliary output E From 2 up to 16-zones
Maximum load 300 mA
24 V resetable output
E EN54 approved
Maximum load 150 mA E 2 User access levels
Reset time 4 seconds E 2 Monitored sounder outputs
Delays
E One-man test capability
Sounder selectable 0.15 & 60 s
Relay module 3 to 180 s E 24 Volt resetable output
Enviroment E External 'Class Change' facility
Working temperature +5°C to +40 °C E Alarm output with potential free relay
Relative humidity 95 % (non-condensing)
E Common fault output with potential free relay
Ordering Information E External watchdog
E Active end-of-line support
NK704 Conventional fire panel with 4 fire alarm zones
E Addional optional modules with supervised or relay
outputs
Conventional Fire Systems
Page : 8

Conventional fire panel with 8 fire alarm zones NK708

The NK700 series of conventional fire alarm and extinguishing control


panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The NK708 has 8
conventional zones.

Specifications

Supply voltage (+10% - 15%) 230 / 110 VAC @ 50 / 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per 20
zone
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay outputs (excluding 1 A @ 30 VDC
sounders) E Modern, attractive design
Extinguishing relay outputs
E Microprocessor-controlled
Maximum load NA
Fuse rating NA E From 2 up to 16-zones
Auxilliary output 250 mA E EN54 approved
24 VDC Resetable output E 2 User access levels
Maximum load 100 mA
Reset time 3s
E 2 Monitored sounder outputs
Environment E One-man test capability
Working temperature -5 °C to +40 °C E 24 Volt resetable output
Relative humidity 95 % (non condensing)
E External 'Class Change' facility
IP rating IP30
Physical characteristics E Alarm output with potential free relay
Size (mm) 420 (w) x 335 (h) x 110 (d) E Common fault output with potential free relay
Weight (without batteries) 6.2 kg E External watchdog

Ordering Information
E Active end-of-line support
E Addional optional modules with supervised or relay
NK708 Conventional fire panel with 8 fire alarm zones outputs
Conventional Fire Systems
Page : 9

Conventional fire panel with 12 fire alarm zones NK712

The NK700 series of conventional fire alarm and extinguishing control


panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The NK712 has 12
conventional zones.

Specifications

Supply voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per 20
zone
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay outputs (excluding 1 A @ 30 VDC
sounders) E Modern, attractive design
Extinguishing relay outputs
E Microprocessor-controlled
Maximum load NA
Fuse rating NA E From 2 up to 16-zones
Auxilliary output 250 mA E EN54 approved
24 VDC Resetable output E 2 User access levels
Maximum load 100 mA
Reset time 3s
E 2 Monitored sounder outputs
Environment E One-man test capability
Working temperature -5 °C to +40 °C E 24 Volt resetable output
Relative humidity 95 % (non condensing)
E External 'Class Change' facility
IP rating IP30
Physical characteristics E Alarm output with potential free relay
Size (mm) 420 (w) x 335 (h) x 110 (d) E Common fault output with potential free relay
Weight (without batteries) 6.2 kg E External watchdog

Ordering Information
E Active end-of-line support
E Addional optional modules with supervised or relay
NK712 Conventional fire panel with 12 fire alarm zones outputs
Conventional Fire Systems
Page : 10

Conventional fire panel with 16 fire alarm zones NK716

The NK700 series of conventional fire alarm and extinguishing control


panels is the ideal solution for small to medium-sized installations. Very
powerful and cost-effective, they are extremely simple to install and
use due to their ergonomic, advanced design. The NK716 has 16
conventional zones.

Specifications

Supply voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7.5 Ah
Fuse rating 5A
Zone
Maximum load 94 mA
Max. number of detectors per 20
zone
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay outputs (excluding 1 A @ 30 VDC
sounders) E Modern, attractive design
Extinguishing relay outputs
E Microprocessor-controlled
Maximum load NA
Fuse rating NA E From 2 up to 16-zones
Auxilliary output 250 mA E EN54 approved
24 VDC Resetable output E 2 User access levels
Maximum load 100 mA
Reset time 3s
E 2 Monitored sounder outputs
Environment E One-man test capability
Working temperature -5 °C to +40 °C E 24 Volt resetable output
Relative humidity 95 % (non condensing)
E External 'Class Change' facility
IP rating IP30
Physical characteristics E Alarm output with potential free relay
Size (mm) 420 (w) x 335 (h) x 110 (d) E Common fault output with potential free relay
Weight (without batteries) 6.2 kg E External watchdog

Ordering Information
E Active end-of-line support
E Addional optional modules with supervised or relay
NK716 Conventional fire panel with 16 fire alarm zones outputs
Conventional Fire Systems
Page : 11

Conventional extinguishing control panel with 3 zones NK703

The NK703 conventional fire alarm and extinguishing control panels is


the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to
their ergonomic, advanced design. It has 1 double-knock extinguising
area consisting of two fire zones, and 1 free fire detection zone.

Specifications

Supply voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per 20
zone
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay outputs (excluding 1 A @ 30 VDC
sounders) E Modern, attractive design
Extinguishing relay outputs
E Microprocessor controlled
Maximum load 250 mA
Fuse rating 0.3 A E 3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Auxilliary output 250 mA E Automatic extinguishing agent release control
24 VDC resetable ouput E 2 Access levels
Maximum load 100 mA
Reset time 3s
E Supervised general sounder output
Environment E Supervised extinguishing inputs and outputs
Working temperature -5 °C to +40 °C E One-man test capability
Relative humidity 95 % (non condensing)
E 24 Volt resetable output
IP rating IP30
Physical characteristics E External 'class change' facility
Size (mm) 420 (w) x 335 (h) x 110 (d) E Alarm output with potential free relay
Weight (without batteries) 6.2 kg E General fault output with potential free relay

Ordering Information
E External watchdog

NK703 Conventional extinguishing control panel with 3 zones


Conventional Fire Systems
Page : 12

Conventional extinguishing control panel with 6 zones NK706

The NK706 conventional fire alarm and extinguishing control panels is


the ideal solution for small to medium-sized installations. Very powerful
and cost-effective, they are extremely simple to install and use due to
their ergonomic, advanced design. It has 2 double-knock extinguising
areas consisting of two fire zones each, and 2 free fire detection zones.

Specifications

Supply voltage (+10% - 15%) 230 VAC @ 50 Hz / 110 VAC @ 60 Hz


Batteries
Capacity 2 x 7 Ah
Fuse rating 2A
Zone
Maximum load 94 mA
Max. number of detectors per 20
zone
Maximum zone resistance 44 ohm
Sounders
Maximum load 250 mA
Delay Selectable 0 - 9 min
Relay outputs (excluding 1 A @ 30 VDC
sounders) E Modern, attractive design
Extinguishing relay outputs
E Microprocessor controlled
Maximum load 250 mA
Fuse rating 0.3 A E 3 zone (1 ext. area) and 6 zone (2 ext. areas) available
Auxilliary output 250 mA E Automatic extinguishing agent release control
24 VDC resetable ouput E 2 Access levels
Maximum load 100 mA
Reset time 3s
E Supervised general sounder output
Environment E Supervised extinguishing inputs and outputs
Working temperature -5 °C to +40 °C E One-man test capability
Relative humidity 95 % (non condensing)
E 24 Volt resetable output
IP rating IP30
Physical characteristics E External 'class change' facility
Size (mm) 420 (w) x 335 (h) x 110 (d) E Alarm output with potential free relay
Weight (without batteries) 6.2 kg E General fault output with potential free relay

Ordering Information
E External watchdog

NK706 Conventional extinguishing control panel with 6 zones


Conventional Fire Systems
Page : 13

Relay module, 4 potential free relays for NK700/Fx400 fire panels RB404

The RB404 relay expander module provides 4 additional voltage free


relays on the GE Security NK700/FP400/FEC400 conventional fire
panels ranges. It allows for these relays to be allocated to individual
detection zones, or for programming the activation of different relays
depending on the status of one or more zones. Up to 4 of these
modules may be used on every fire panel.

Specifications

Relay rating
Voltage 250 VAC / 30 VDC
Current 10 A
Delay setting 0 to 9 minutes

Ordering Information

RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels

E 4 Potential free relays


E Up to 4 modules may be housed inside the fire panel
cabinet
E Programmable with basic boolen functions
E Power supplied from fire panel bus
E Output delay setting per relay
Conventional Fire Systems
Page : 14

Relay module, 4 supervised relays for NK700/Fx400 fire panels SB404

The SB404 expander module provides 4 additional supervised relays


that provide 24 VDC outputs on the GE Security NK700/FP400/FEC400
conventional fire panels ranges. These relays may be configured to
power sounders or as standard 24 VDC supervised outputs for other
devices. Relays may be allocated to individual detection zones, or for
programming the activation of different relays depending on the status
of one or more zones. Up to 4 of these modules
may be used on every fire panel.

Specifications

Auxiliary supply 24 VDC


Relay Rating
Voltage 250 VAC / 30 VDC
Current 5A
Delay setting 0 to 9 minutes

Ordering Information

SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels

E 4 Supervised relays
E Up to 4 modules may be housed inside the fire panel
cabinet
E Programmable with basic boolen functions
E Output delay setting per relay
E Configurable for sounder control or as supervised
outputs
Conventional Fire Systems
Page : 15

Active end-of-line device for use with FP400/KL700 fire panels EOL-ACT

The EOL-ACT is designed for use with the NK700/FP400 fire panels from
GE-Interlogix. It is an active end-of-line device to allow the monitoring
of a conventional zone through a diode base (such as the KZ705D).

Ordering Information

EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels

E Small
E Easy to install
Accessories
Page : 16

Black front panel cover (small footprint) KLBlack-S

The KLBeige-S is a beige coloured, front panel housing lid for the
FP200/NKB600, FP402 and FP404/NK702 and NK704 series fire panels
from GE Security. It allows the user to change the facure colour of the
panel for colour matching or renewal in case of damage.

Ordering Information

KLBlack-S Black front panel cover (small footprint)

E Customisation of panel colour scheme


E Easy replacement

Black front panel cover (large footprint) KLBlack-B

The KLBlack-B is a black coloured, front panel housing lid for the FP408,
FP412 and FP416/NK708, NK712 and NK716, the FEC400/NK703 and
NK706, as well the FP1500/KSA701 series fire panels and repeaters
from GE Security. It allows the user to change the facure colour of the
panel for colour matching or renewal in case of damage.

Ordering Information

KLBlack-B Black front panel cover (large footprint)

E Customisation of panel colour scheme


E Easy replacement
Addressable Fire Systems
Page : 17

Analogue addressable fire detection panel - 1 loop KSA701-1

The KSA701 analogue addressable fire alarm control panel is the ideal
solution for small to medium-sized installations. Very powerful and
cost-effective, it is extremely simple to install and use due to its
ergonomic, advanced design. The panel is supplied in an elegant,
high-quality, conveniently sized, heavy-duty enclosure. The cabinet
allows for enough space for the batteries for the system to be housed
inside the cabinet. The KSA701 is fully compatible with the Kilsen 700A
series detectors and KAL400 series accessories.

Specifications

Supply voltage 110/230 VAC @ 50 Hz (+10% -15%)


Current consumption
(no devices connected) 175 mA Quiest. / 241 mA Alarm
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse rating 3A
Charger (Temp. comp. -3 V / 350 mA @ 27.6 VDC @ 20 °C
°C)
Loop characteristics per loop
Capacity 250 addresses
Maximum load 400 mA / 26 VDC to 32 VDC
E 4 x 40 characters LCD display
Maximum electrical 44 Ohm / 500 nF E 20 Display zones
characteristics
Sounders (reverse polarity
E EN54 compliant with approvals pending
supervision) E 2 User access levels
Maximum load (2 Outputs) 250 mA each / 18 to 24 VDC
Delays (adjustable in 10 s 10 to 600 seconds
E 2 Monitored sounder outputs
intervals) E 2 Programmable voltage free relays
Relay outputs (potential free) 1 A @ 30 VDC
24 V Auxiliary output
E 24 Volt auxiliary output
Maximum load 250 mA @ 18 VDC to 28 VDC E I/O programming capabilities with Boolean functions
Environment E Day/night sensitivity settings
Working temperature -5°C to +40 °C
E Coincidence within zones
Relative humidity 0-95%
(non-condensing) E Upload/download and graphic PC software
IP rating IP30
E Panel networking
Physical characteristics
Size 420 mm (w) x 335 (h) x 110 (d) E Installation test capability
Weight (without batteries) 6.2 kg

Ordering Information

KSA701-1 Analogue addressable fire detection panel - 1 loop


Addressable Fire Systems
Page : 18

Analogue addressable fire detection panel - 2 loops KSA701-2

The KSA701 analogue addressable fire alarm control panel is the ideal
solution for small to medium-sized installations. Very powerful and
cost-effective, it is extremely simple to install and use due to its
ergonomic, advanced design. The panel is supplied in an elegant,
high-quality, conveniently sized, heavy-duty enclosure. The cabinet
allows for enough space for the batteries for the system to be housed
inside the cabinet. The KSA701 is fully compatible with the Kilsen 700A
series detectors and KAL400 series accessories.

Specifications

Supply voltage 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)


Current consumption
(no devices connected) 175 mA Quiescent / 241 mA in alarm
Batteries
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse rating 3A
Charger rating (Temp. 350 mA @ 27.6 VDC @ 20 °C
compensated -3 V / °C)
Loop characteristics per loop
Capacity 250 addresses
Maximum load 400 mA / 26 VDC to 32 VDC
E 4 x 40 characters LCD display
Maximum electrical 44 Ohm / 500 nF approximately 2 km of 1.5 mm2 E 20 Display zones
characteristics diameter cable
Sounders (reverse polarity
E EN54 compliant with approvals pending
supervision) E 4 User access levels
Maximum load 250 mA each (2 Sounder outputs available) / 18 VDC
to 24 VDC E 2 Monitored sounder outputs
Delays (software adjustable in 10 to 600 seconds
10 second intervals) E 2 Programmable voltage free relays
Relay outputs (potential free) 1 A @ 30 VDC E 24 Volt auxiliary output
24 V Auxiliary output
E I/O programming capabilities with Boolean functions
Maximum load 250 mA @ 18 VDC to 28 VDC
Environment E Day/night sensitivity settings
Working temperature -5°C to +40 °C E Coincidence within zones
Relative humidity 0-95%
(non-condensing)
E Upload/download and graphic PC software
IP rating IP30 E Panel networking
Physical Characteristics E Installation test capability
Size 420 mm (w) x 335 (h) x 110 (d)
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah
batteries

Ordering Information

KSA701-2 Analogue addressable fire detection panel - 2 loops


Addressable Fire Systems
Page : 19

RS485 expansion kit for KSA701/FP1500 fire panels NC785

The NC785 RS485 expander allows for an easy upgrade to the


KSA701/FP1500 series addressable fire panels. Each module adds an
additional industry standard RS485 communication port to the panel.
This port could be used for communications with other network nodes
in the fire panel network.

Specifications

Number of ports 1
Communications medium RS485
Technical specifications
Maximum cable length 1200 m
Communication speed 9600 baud
Cable CAT5 - twisted with screen
Termination resistance 150 Ohm

Ordering Information

NC785 RS485 expansion kit for KSA701/FP1500 fire panels

E Industry standard RS485 communications


E No hardware configuration required
Addressable Fire Systems
Page : 20

KSA701 Series LCD Repeater (mains powered) KSA701R

The KSA701R repeater allows the user to monitor and control panels
connected to the KSA700 fire panel network via and RS485 link. It
displays 20 zones in alarm and fault on the face of the panel, whilst all
system messages are displayed on the easy to read, LCD display.

Specifications

Supply voltage
AC version 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
DC version 24 VDC
Current consumption 175 mA Quiescent / 200 mA in alarm
Battery charger (AC version only)
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse rating 3A
Charger rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Environment
Working temperature -5 °C to +40 °C
Relative humidity 95% (non condensing)
IP rating IP30
Physical characteristics
Size 420 mm (w) x 335 (h) x 110 (d) E Modern, attractive design
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah E 4 x 40 characters LCD display
batteries
Communication ports RS232 and RS485 standard E 20 Display zones
E 3 User access levels
Ordering Information
E 24 VDC or 230 VAC models available
KSA701R KSA701 Series LCD Repeater (mains powered) E Panel networking
E Full system control
Addressable Fire Systems
Page : 21

KSA701 Series LCD Repeater (24VDC powered) KSA701R-24

The KSA701R repeater allows the user to monitor and control panels
connected to the KSA700 fire panel network via an RS485 link. It
displays 20 zones in alarm and fault on the face of the panel, whilst all
system messages are displayed on the easy to read, LCD display.

Specifications

Supply voltage
AC version 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
DC version 24 VDC
Current consumption 175 mA Quiescent / 200 mA in alarm
Battery charger (AC version only)
Capacity 2 x 12 V - 7 AH (SLA type)
Fuse rating 3A
Charger rating 350 mA @ 27.6 VDC @ 20 °C (Temperature
compensated -3 V / °C)
Environment
Working temperature -5 °C to +40 °C
Relative humidity 95% (non condensing)
IP rating IP30
Physical characteristics
Size 420 mm (w) x 335 (h) x 110 (d) E Modern, attractive design
Weight 6.2 kg without batteries / 10.7 kg with 2 x 7 Ah E 4 x 40 characters LCD display
batteries
Communication ports RS232 and RS485 standard E 20 Display zones
E 3 User access levels
Ordering Information
E 24 VDC or 230 VAC models available
KSA701R-24 KSA701 Series LCD Repeater (24VDC powered) E Panel networking
E Full system control
Addressable Fire Systems
Page : 22

Analogue addressable fire panel (expandable to 5 loops) KSA705

The KSA700 Series analogue addressable fire panels offer leading-edge


technology for the control of analogue addressable fire detection
devices. Their unique user-friendly programming facilitate the ideal
control environment for either simple or complex fire systems.

Specifications

Supply voltage 230 VAC @ 50 Hz (+10% -15%)


Current consumption
(no devices connected) 175 mA Quiest. / 241 mA Alarm
Batteries
Capacity 2 x 12 V - 6 AH (SLA type)
Fuse rating 4A
Charger (Temp. comp. -3 V / 350 mA @ 27.6 VDC @ 20 °C
°C)
Loop characteristics per loop
Capacity 250 addresses
Maximum load 400 mA / 26 VDC to 32 VDC
Maximum electrical 44 Ohm / 500 nF
characteristics
Sounders (reverse polarity
supervision)
Maximum load (2 Outputs) 250 mA each / 18 to 24 VDC
E 4-line, 40-character LCD display
Delays (adjustable in 10 s 10 to 600 seconds E Panel networking capability
intervals)
Relay outputs (potential free) 1 A @ 30 VDC
E Graphic monitoring software
24 V Auxiliary output E Windows based up/download programming software
Maximum load 800 mA @ 18 to 28 VDC E Remote programming and maintenance via modem
Environment and TCP/IP
Working temperature -5 °C to +40 °C E Repeater facilities
Relative humidity 95% (non condensing)
IP rating IP41
E Powerful auto-configuration functions
Physical characteristics E Simple program options with on-screen menu selection
Size 480 mm (w) x 455 (h) x 140 (d) E EN54 compliant
Weight (without batteries) 13.6 kg

Ordering Information

KSA705 Analogue addressable fire panel (expandable to 5 loops)


Addressable Fire Systems
Page : 23

Analogue addressable fire panel with printer (expandable to 5 loops) KSA705P

The KSA700 Series analogue addressable fire panels offer leading-edge


technology for the control of analogue addressable fire detection
devices. Their unique user-friendly programming facilitate the ideal
control environment for either simple or complex fire systems. The
KSA705P offers an additional internal printer facility.

Specifications

Supply voltage 230 VAC @ 50 Hz (+10% -15%)


Current consumption (no devices 175 mA Quiescent / 241 mA in alarm
connect)
Batteries
Capacity 2 x 12 V - 6 AH (SLA type)
Fuse rating 4A
Charger (Temp. comp. -3 V / 350 mA @ 27.6 VDC @ 20 °C
°C)
Loop characteristics per loop
Capacity 250 addresses
Maximum load 400 mA / 26 VDC to 32 VDC
Maximum electrical 44 Ohm / 500 nF approximately 2 km of 1.5 mm2
characteristics diameter cable
Sounders (reverse polarity
supervision) E 4-line, 40-character LCD display
Maximum load 250 mA each (2 Sounder outputs available) / 18 VDC
to 24 VDC
E Panel networking capability
Delays (adjustable in 10 s 10 to 600 seconds E Graphic monitoring software
intervals)
Relay outputs (potential free) 1 A @ 30 VDC E Windows based up/download programming software
24 V Auxiliary output E Remote programming and maintenance via modem
Maximum load 800 mA @ 18 VDC to 28 VDC and TCP/IP
Environment E Repeater facilities
Working temperature -5 °C to +40 °C
E Powerful auto-configuration functions
Relative humidity 95% (non condensing)
IP rating IP41 E Simple program options with on-screen menu selection
Physical characteristics E EN54 compliant
Size 480 mm (w) x 455 (h) x 140 (d)
Weight 13.6 kg without batteries / 21.6 kg with 2 x 7 Ah
batteries

Ordering Information

KSA705P Analogue addressable fire panel with printer (expandable to 5 loops)


Addressable Fire Systems
Page : 24

Loop driver module for KSA702/705 control panels KAL701

The KAL701 1 loop expander allows for an easy upgrade to the KSA702
and KSA705 analalogue addressable fire panels. Each module consist
of a simple plug in card and requires no additional settings or
connections for full functionality. The KAL701 has loop isolators
supplied on both drivers and allows full class-A loop functionality with
up to 250 device addresses.

Specifications

Number of loops 1
Loop characteristics
Capacity 250 addresses
Maximum load 400 mA / 26 VDC to 32 VDC
Maximum electrical 44 Ohm / 500 nF
characteristics
Maximum loop length 2 km

Ordering Information

KAL701 Loop driver module for KSA702/705 control panels

E Expands the loop capabailities of the KSA702 and


KSA705
E Allows for the connection of an additional 250 devices
per unit
E Two isolated drivers support full class-A operation
E No hardware configuration required

RS232 communications module for KSA702/5 control panels KAL732

The KAL732 RS232 expander allows for an easy upgrade to the KSA702
and KSA705 analalogue addressable fire panels. Each module adds an
additional industry standard RS232 communication port to the panel.
This port could be used for communications with a PC or for
connections to a printer or modem.

Specifications

Number of ports 1
Communications medium RS232
Technical specifications
Maximum cable length 15 m
Communication speed 9600 baud
Cable 3 core with screen

Ordering Information
E Industry standard RS232 communications
KAL732 RS232 communications module for KSA702/5 control panels
E No hardware configuration required
Addressable Fire Systems
Page : 25

RS485 communications module for KSA702/5 control panels KAL785

The KAL785 RS485 expander allows for an easy upgrade to the KSA702
and KSA705 analalogue addressable fire panels. Each module adds an
additional industry standard RS485 communication port to the panel.
This port could be used for communications with other network nodes
in the fire panel network.

Specifications

Number of ports 1
Communications medium RS485
Technical specifications
Maximum cable length 1200 m
Communication speed 9600 baud
Cable CAT5 - twisted with screen
Termination resistance 150 Ohm

Ordering Information

KAL785 RS485 communications module for KSA702/5 control panels

E Industry standard RS485 communications


E No hardware configuration required

Protocol Converter RS232/485 - Kilsen / Johnsson Control KAL791

The KAL791 is a protocol converter for the integration of Kilsen KSA700


analogue fire alarm systems into Johnsson Controls building
management systems. It requires a 24 VDC supply from an auxiliary
power supply source.

Specifications

Supply Voltage 24 VDC


Current Consumption
260 mA
Environment
Working Temperature -5°C to +40 °C
Relative Humidity 0-95%
(non-condensing)
IP Rating IP41
Physical Characteristics
Size 390 mm (w) x 420 (h) x 135 (d)
E RS232 or RS485 port options
Weight 9.3 kg
E Seemless integration with no additional programming
Ordering Information on the fire system
E 24 VDC Supply
KAL791 Protocol Converter RS232/485 - Kilsen / Johnsson Control
KAL732 RS232 communications module for KSA702/5 control panels
KAL785 RS485 communications module for KSA702/5 control panels
Addressable Fire Systems
Page : 26

Analogue fire panel, 2 loops upgradable to 4, 64 display zones KSA1204

The KSA1204 allows for 2 addressble fire panel loops and 64 display
zones.

Specifications

Supply voltage 230 VAC (+10/-15%) 50 Hz


Supply current (max) 1.5 A
Min. supply current @ 24 VDC 0.2 A
Battery charger rating @ 27.6 1.6 A
VDC
Total supply rating @ 27.6 VDC 2.5 A
Relay rating @ 24 VDC 2A
Weight (no batteries) 8 kg
Dimensions (H x W x D) 440 x 444 x 125 mm

Ordering Information

KSA1204 Analogue fire panel, 2 loops upgradable to 4, 64 display zones


LC1502 2-loop extension board for 1200/2000 series fire panels
LON2000 LON700 driver for FP1200 / FP2000
NC2011 ARCNET RS485 network card with single RS485 interface
NC2051 ARCNET network card with single optical interface board E One man maintenance
NET1200 Dongle for 1200 series panel networking
RB2016 Relay extension board for 1200/2000 series fire panels E Maintenance warning
MOD2000 Modem kit E Soak test
PCC2000 Programming and configuration software
E On-line diagnostics and statistics
PCM2000 Maintenance and support software with copy protection key
E Power supply for 72 hour autonomy
E Floating background compensation
E Coincidence within and in between zones
E Start-up default mode
E Upload/download configuration facilities with PC
E I/O programming including Boolean functions
E EN54 p2 & 4 and VDS approved
E 2 or 4 class A loops
Addressable Fire Systems
Page : 27

Addressable fire panel, 2-8 loops, 64-255 display zones upgradable KSA1208

A versatile, powerful addressable fire panel, 2 to 8 loops, 16 to 64


displayed zones with extensive I/O features. The fire panel can operate
within a 31 panel network and can communicate with global repeaters
and PC graphics. It supports all the 700 series LON devices and
repeaters using a seperate two wire bus. It is truly user-friendly and
provides a generous 8 x 40 backlit graphic display. I/O control is done
via powerful boolean I/O programing. Extensive maintenance features
are provided standard. The KSA1200 series supports 1500 series
sensors and 400 series I/O units.

Specifications

Supply voltage 1 190 - 270 V ac


40 - 60 Hz
160 VA max.
Supply voltage 2 21 - 27 V dc
Current consumption
Quiescent @ 24 V dc (equipped 800 mA
loop)
Alarm current @ 24 V dc 1A
Available auxiliary current in 3A
alarm E One man maintenance
Battery charger rating @ 27.5 V 3A
dc E Graphic maintenance
Total supply rating @ 27.5 V dc 4A E Maintenance warning
Relay rating @ 24 V dc 2A
Weight (no batteries) 15 kg
E Service reminder signal
Dimensions (mm) (H x W x D) 804 x 441 x 109 E Soak test
E On-line diagnostics and statistics
Ordering Information
E Floating background compensation
KSA1208 Addressable fire panel, 2-8 loops, 64-255 display zones upgradable E Day/night sensitivity setting
E Coincidence within and in between zones
E Automatic timed and manual on/off zones
E Start-up default mode
E Service switch
E Upload/download, remote maintenance and graphic PC
software
E I/O programming including Boolean functions
E ARCNET panel networking
E EN54 approved; certified Bosec, VdS, NFA2P
E Networkable "black box" and "global zone" system
E Full range of repeater panels
E Full range of LON devices
Addressable Fire Systems
Page : 28

Repeater / emulator with 64 zone indications KSA1264R

A repeater / emulator with 64 displayed fire and fault zones, used in


KSA1200 networked systems. The repeater is connected on the arcnet
network and can operate in a local or global repeater mode. An 80 x 40
backlit graphic display and full indication and control keyboard is
provided standard.

Specifications

Supply voltage 230 Vdc


Current consumption 300 mA max
Weight 15 kg
Dimensions (mm) (H x W x D) 804 x 441 x 109

Ordering Information

KSA1264R Repeater / emulator with 64 zone indications

E 8 x 40 character graphic display


E Arcnet network connection to KSA1200 series fire
panels
E Global repeater function
E Comprehensive control and display functions
E Emulation function
E 64 zones fire and fault displayed
E 230 VAC operation
Addressable Fire Systems
Page : 29

Global zone repeater, 64 zones expandable up to 255 KSA12255R

A repeater/emulator with 64 fire and fault zones, expandable to 255,


used in 1200/2000 series networked systems. The repeater is
connected on the arcnet network and can operate in a local or global
repeater mode. An 80 x 40 character, backlit graphic display and full
indication and control keyboard is provided standard.

Specifications

Supply voltage 1 190 - 270 VAC


40- 60 Hz
160 VA max.
Current consumption
Quiescent 800 mA
Alarm current @ 24 V dc 1A
Available auxiliary current in 3 A
alarm
Battery charger rating @ 27.5 3 A
V dc
Total supply rating 4A
Weight (no batteries) 15 kg
Dimensions (mm H x W x D) 804 x 441 x 109

E On-line diagnostics and statistics


Ordering Information
E Upload/download, remote maintenance and graphic PC
software
KSA12255R Global zone repeater, 64 zones expandable up to 255
LON2000 LON700 driver for FP1200 / FP2000 E I/O programming including Boolean functions
NE2011 RS485 network extension board E ARCNET panel networking
NE2051 Fibre optic network extension board
ZE2064 64-zone LED extension fire and fault LED E Full range of 700 series LON devices
Addressable Fire Systems
Page : 30

2-loop extension board for 1200/2000 series fire panels LC1502

The LC1502 is a 2-loop extension board for 1200/2000 series fire


panels. It allows for 2 additional class-A loops to be inserted into the
fire panel, and supports up to 250 addressable loop devices per loop.

Specifications

Current consumption
Quiescent @ 24 VDC (Fully + 150 mA (252 detectors)
equipped loop)

Ordering Information

LC1502 2-loop extension board for 1200/2000 series fire panels

E 2 Class-A loops
E Up to 250 devices per loop (protocol dependent)
E Supports various detector protocols
E No hardware address required

LON700 driver for FP1200 / FP2000 LON2000

FP1200 / FP2000 series


A LON700 driver that connects FP1200 / FP2000 fire panels to LON700
devices

Ordering Information

LON2000 LON700 driver for FP1200 / FP2000


Addressable Fire Systems
Page : 31

LON driver for FP1200/2000 - closed loop systems LON2000R

The LON2000R is a LON700 driver that connects 1200/2000 series fire


panels to LON700 series devices on a closed loop, CLASS-A LON700
network.

Ordering Information

LON2000R LON driver for FP1200/2000 - closed loop systems

ARCNET RS485 network card with single RS485 interface NC2011

The NC2011 is an interface board to connect an RS485 copper network


directly into the 1200/2000 series fire panels. It is supplied with one
NE2011 pre installed.

Ordering Information

NC2011 ARCNET RS485 network card with single RS485 interface


NE2011 RS485 network extension board
Addressable Fire Systems
Page : 32

ARCNET network card with single optical interface board NC2051

The NC2051 is an interface board to connect a fiber optic network


directly into the 1200/2000 series fire panels. It is supplied with one
NE2051 pre installed.

Ordering Information

NC2051 ARCNET network card with single optical interface board


NE2051 Fibre optic network extension board

RS485 network extension board NE2011

The NE2011 is a RS485 network extension board for the NC2011 to


allow dual bus and closed ring networks.

Ordering Information

NE2011 RS485 network extension board


Addressable Fire Systems
Page : 33

Fibre optic network extension board NE2051

FP1200 / FP2000 series


An extension board for the NC2051 to allow a fibre optic ring bus

Ordering Information

NE2051 Fibre optic network extension board

Internal printer PR2000

The PR2000 is a panel mount, 40-column dot matrix printer to be used


with the 1200/2000 series fire panels. It is supplied with all necessary
accesories to allow easy installation into cabinets that allow for this
option.

Ordering Information

PR2000 Internal printer


Addressable Fire Systems
Page : 34

Relay extension board for 1200/2000 series fire panels RB2016

The RB2016 is an extension board for 1200/2000 series fire panels. It


allows for up to 18 additional potential free relays to be added into the
fire panel cabinet. Depending on the size and hardware configuration
of the panel, up to 4 RB2016s may be included in any panel.

Specifications

Relay Contact Rating 1 A @ 30 VDC / 0.3 A @ 110 VDC / 0.3 A @ 125 VAC

Ordering Information

RB2016 Relay extension board for 1200/2000 series fire panels

E Up to 18 potential free relay outputs


E No hardware address required

64-zone LED extension fire and fault LED ZE2064

The ZE2064 allows the extension of the zones of the Fx2x128 and
Fx2x255 fire panels and repeaters by 64 additional zones.

Ordering Information

ZE2064 64-zone LED extension fire and fault LED


LON700 Devices
Page : 35

LCD repeater FRL700

The LON700 LCD repeater is a smart and compact, cost-effective


solution for fire panel repeaters. It is also available as an FBP700 fire
brigade panel for Dutch and Scandinavian norms.

Specifications

Dimensions (l x w x d) 240 x 320 x 60 mm


Weight 1.5 kg
Operating temp °C -5°C to +40°C
Operating voltage 15 - 30 VDC
Current consumption
Max. quiesent 100 mA
Bus Connection two wire LON700
Bus Cable CAT 5
Total number of repeaters
700/1200/2000 Series 15

Ordering Information

FRL700 LCD repeater

E 2 wire connection between fire panel and repeaters


E Up to 1500 metre bus length
E 24 Volt power supply
E Cost effective repeater solutions
E Easily installed, simple operation
E 4 x 20 charater LCD display, common LED's, push
button control
E LON700 module
LON700 Devices
Page : 36

LON700 network amplifier (4 way) NA704

The NA704 is an interface board to allow an extension of the LON700


network above its normal limitations. It acts as a network amplifier
allowing for reconstruction and re-transmission of the LON700 signal,
as well as allowing for T-offs of the network as required.

Ordering Information

NA704 LON700 network amplifier (4 way)


NE771 LON700 driver for the NC771 and NA704
NE2051 Fibre optic network extension board

LON700 interface board NC700

The NC700 is an interface board to connect a LON700 bus from a fire


panel to a FB7xx 'black box'.

Ordering Information

NC700 LON700 interface board


LON700 Devices
Page : 37

LON700 closed loop communication board (no driver) NC771

The NC771 is an interface board to connect a LON bus from a fire


panel to a FB7xx 'black box' panel. It allows for full Class-A type
LON700 networks.

Ordering Information

NC771 LON700 closed loop communication board (no driver)


NE771 LON700 driver for the NC771 and NA704
NE2051 Fibre optic network extension board

LON700 driver for the NC771 and NA704 NE771

The NE771 is a LON700 network extension board to allow dual bus and
closed ring networks on the NC771 and the NA771.

Ordering Information

NE771 LON700 driver for the NC771 and NA704


LON700 Devices
Page : 38

LON700 output board with 24 open collector outputs OCB724

The OCB724 is a 24 way open collector board used in a LON700


system.

Ordering Information

OCB724 LON700 output board with 24 open collector outputs

Plug-in power supply 3.5 A PS700

The PS700 power supply can be used to extend the power output in
LON700 systems.

Ordering Information

PS700 Plug-in power supply 3.5 A


LON700 Devices
Page : 39

LON700 output board with 8 relays RB708

The RB708 is an eight way relay board used in LON700 systems.

Specifications

Number of outputs 8
Relay contact rating
Switching current 2A
Switching volage 42V ac/dc
Switching power 60W

Ordering Information

RB708 LON700 output board with 8 relays

Supervised input board 16 way LON700 SIB716

The SIB716 is a sixteen way input board used in LON700 systems.

Ordering Information

SIB716 Supervised input board 16 way LON700


LON700 Devices
Page : 40

LON700 output board with 8 supervised outputs SOB708

The SOB708 provides eight supervised outputs that can be used in


LON700 systems.

Specifications

Number of outputs 8
Output type polarity reversal
End of line resistor 5.6 Kohm
Output current per output 500mA
Total current for all outputs 2A
Open circuit >27 Kohm
Normal 1.2 - 18 Kohm
Short circuit < 470 ohm

Ordering Information

SOB708 LON700 output board with 8 supervised outputs

8 zone input extension board ZI708

The ZI708 is an eight zone input expansion board for LON700


compatible systems. It allows for the connection of up to 8
conventional fire detector zones and is compatible with most industry
standard conventional detectors.

Ordering Information

ZI708 8 zone input extension board


Gas Detection
Page : 41

CO detection control panel - 1 Zone (English Version) KM260/1R3-03

The KM-Series CO detection system is designed for applications such


as vehicle parking areas where concentrations of CO may accumulate.
The range is compliant with the UNE23.300/84 standard. The KM260/1
is a 1 (upgradable to 2) zone control unit, using KM170 detectors.

Specifications

Power supply
Mains supply 230 VAC ±10% 50 Hz
Power consumption 95 W (max)
Zone configuration
Zone input voltage 10-20 VDC/VAC
Sensitiviy 0-300 ppm
Cable requirement 3 core 1.5 mm²
Cable length (max) 350 m
No. of detectors (max) 15
No. of zones (max) 2
Mechanical
Housing (w x h x d) 275 x 335 x 130 mm
Weight 6 kg

E Designed according to norm 23300/84


Ordering Information
E Miner CDM8001 and CDM8002 standard password
KM260/1R3-03 CO detection control panel - 1 Zone (English Version) E LGAI 154.909 and 96013132 standard certification
E Easy to use
E Low current consumption
E Direct reading of measured levels
E Easy installation
E Extraction relays and alarm outputs per area
E From 1 to 5 areas
E 3-wire system
E Modular design
E Up to 15 detectors per zone
E 10 seconds response time
E Elegant design
E Supervision of all zone lines
E Available in various languages
Gas Detection
Page : 42

CO detection control panel - 3 Zones (English Version) KM260/3R3-03

The KM-Series CO detection system is designed for applications such


as vehicle parking areas where concentrations of CO may accumulate.
The range is compliant with the UNE23.300/84 standard. The KM260/3
is a 3 (upgradable to 5) zone control unit, using KM170 detectors.

Specifications

Power supply
Mains supply 230 VAC ±10% 50 Hz
Power consumption 95 W (max)
Zone configuration
Zone input voltage 10-20 VDC/VAC
Sensitiviy 0-300 ppm
Cable requirement 3 core 1.5 mm²
Cable length (max) 350 m
No. of detectors (max) 15
No. of zones (max) 5
Mechanical
Housing (w x h x d) 470 x 335 x 130 mm
Weight 10.2 kg

E Designed according to norm 23300/84


Ordering Information
E Miner CDM8001 and CDM8002 standard password
KM260/3R3-03 CO detection control panel - 3 Zones (English Version) E LGAI 154.909 and 96013132 standard certification
E Easy to use
E Low current consumption
E Direct reading of measured levels
E Easy installation
E Extraction relays and alarm outputs per area
E From 1 to 5 areas
E 3-wire system
E Modular design
E Up to 15 detectors per zone
E 10 seconds response time
E Elegant design
E Supervision of all zone lines
E Available in various languages
Gas Detection
Page : 43

CO detection expansion module (English Version) KM260EXT3-03

The KM260 is an expansion module for the KM260-Series CO panels


from GE-Interlogix. It allows for an additional monitoring zone to be
added to the control panel, each module allowing for an additional 15
sensors to be connected.

Specifications

Power supply
Mains supply 230 VAC ±10% 50 Hz
Power consumption 95 W (max)
Zone configuration
Zone input voltage 10-20 VDC/VAC
Sensitiviy 0-300 ppm
Cable requirement 3 core 1.5 mm²
Cable length (max) 350 m
No. of detectors (max) 15
No. of zones (max) 1

Ordering Information

KM260EXT3-03 CO detection expansion module (English Version)


E Designed according to norm 23300/84
E Miner CDM8001 and CDM8002 standard password
E LGAI 154.909 and 96013132 standard certification
E Easy to use
E Low current consumption
E Direct reading of measured levels
E Easy installation
E Extraction relays and alarm outputs per area
E 3-wire system
E Up to 15 detectors per zone
E 10 seconds response time
E Supervision of zone line
E Available in various languages
Gas Detection
Page : 44

Blanking plate for KM260 panels KM260C

The blanking plate is used on KM260 panels during upgrading of


modules to cover up any unused positions that may exist on the panel.

Ordering Information

KM260C Blanking plate for KM260 panels


Gas Detection
Page : 45

CO detector with base and mounting supplement KM170

The KM170 detector is specifically designed to react to the presence of


carbon monoxide. The design complies with the requirements of the
UNE 23-300 standard.

Specifications

Sensor type TGS semicondictor


Useful life 4 years
Electrical characteristics
Supply voltage 10 to 20 VDC
Quiescent current 35 mA
Reaction time 10 s
Environmental
Operating temperature 0 °C to +40 °C
Protection index IP205
Mechanical
Size (h x Ø) 81 x 109 mm
Weight 115 g
Material and colour ABS white
Installation
Number of detectors per zone 15
E Complies with the requirements of the UNE23-300
Covarage 300 m² standard

Ordering Information
E Microprocessor based
E Resolution of up to 5 ppm
KM170 CO detector with base and mounting supplement E Response time of 10 s
E Low current consumption
E Local status indication of:
-Normal operation
-50ppm detected
-Fault
E Useful life of up to 4 years
Gas Detection
Page : 46

Detector base for KL400/KM170 series devices KZ400

The KZ400 base is designed to be used with the KL400 series detectors,
but may also be used as a substitution base for KM170 CO detectors.

Specifications

Dimensions
Diameter 107 mm
Height 22 mm

Ordering Information

KZ400 Detector base for KL400/KM170 series devices

E Polarity sensitive
E Remote indicator contact available

Surface mount supplement for KL300/KM170 detectors S300

The S300 is a base accessory designed for use with the KZ300 and
KZ400 detector base. It allows for a surface mount conduit and cable
to enter the base from the side. The KZ300 and KZ400 base fits on top
of this accessory. The S300 can also be used with KM170 CO detectors.

Specifications

Dimensions
Diameter 107 mm
Height 25 mm

Ordering Information

S300 Surface mount supplement for KL300/KM170 detectors

E Surface mount accessory for KZ300


E May be used with KM170 CO Detectors
Aspiration Systems
Page : 47

Aspiration Smoke Detector ASD20C

The ASD20 Aspiration Smoke Detector consists of an analysis chamber


with one or two smoke detectors, connected to standard 25 mm Ø
PVC piping. The detectors can be of conventional or analogue
technology, ionisation or optical.

Specifications

Power supply voltage 24 VDC


Current Consumption
Standby 250 mA
1st alarm 280 mA
2nd alarm 320 mA
Fault 220 mA
Environmental Characteristics
Working temperature -10 to +60°C
Storage temperature -10 to +70°C
Relative humidity <95%
Physical Characteristics
Size 314 x 254 x 115
Weight 4 kg
Colour RAL9999
E Used with conventional or analogue detectors
Material Polycarbonate
Cable input 3 x PG11 E Direct connection to an analogue loop or stand-alone
operation
Wire cross-section Max. 1.5 mm²
Coverage area per intake 30 m² E Alarm 1, alarm 2 and fault relay outputs
Maximum num. of intakes 12 E 24 VDC power supply
DIN 8062-type PVC pipes Ø25 mm
E Simple and robust architecture
Useful lifetime of motor 65 000 hours at 40°C
E 30 m² coverage per sample intake
Ordering Information E Standard 25 mm PVC piping system
E Installation of piping in I-shape and U-shape
ASD20C Aspiration Smoke Detector (symmetrical or assymmetrical)
ASD20F Filter housing for ASD20
E Continuous supervision of pipe flow volume
ASD20FIL Filter only for ASD20
Aspiration Systems
Page : 48

Filter housing for ASD20 ASD20F

The ASD20F is an aluminium filter housing for the ASD20 aspiration


detection system. It houses and protects the the air filter, the ASD20FIL,
that has to be ordered seperately.

Ordering Information

ASD20F Filter housing for ASD20


ASD20FIL Filter only for ASD20

E Robust, light weight, aluminium construction


E Easy to install
E Easy filter replacement

Filter only for ASD20 ASD20FIL

Filter only for ASD20 Aspiration Detector.

Ordering Information

ASD20FIL Filter only for ASD20


Conventional Fire Systems
Page : 49

Rate-of-Rise Heat Detector KV210

The KV210 heat detectors are designed to activate when the


temperature exceeds a preset level or when the speed at which the
temperature changes is above a set threshold, even if the fixed
activation temperature point has not been reached. These detectors
comply to the UNE 23-007 part 5 standard.

Specifications

Operating voltage 16 to 28 VDC


Current consumption
Quiescent at 24 VDC < 100 A
Alarm at 24 VDC < 100 mA
Remote alarm output NA
Heat specification UNE 23.007/5 compliant
Working Area 20-30 m²
Installation Height (max.) 6m
Operating temperature -10 to +60 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP205
Dimensions (h x Ø) 60 mm x 108 mm
E Very low standby current
Ordering Information E Two-wire connection
E No mechanical parts subject to wear and tear
KV210 Rate-of-Rise Heat Detector E Rate-of-rise and thermostatic
E Remote indicator output on KV210P
E Latching alarm
E Compact and water resistant electronics
E Highly resistant to humidity and corrosion
E Modern and elegant design
E No base required
E Excellent price/quality ratio
Conventional Fire Systems
Page : 50

Rate-of-Rise Heat Detectors with remote indicator output KV210P

The KV210 heat detectors are designed to activate when the


temperature exceeds a preset level or when the speed at which the
temperature changes is above a set threshold, even if the fixed
activation temperature point has not been reached. These detectors
comply to the UNE 23-007 part 5 standard. The KV210P has an output
for a remote indicator.

Specifications

Operating voltage 16 to 28 VDC


Current consumption
Quiescent at 24 VDC < 100 A
Alarm at 24 VDC < 100 mA
Remote alarm output < 100 mA
Heat specification UNE 23.007/5 compliant
Working Area 20-30 m²
Installation Height (max.) 6m
Operating temperature -10 to +60 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP205
E Very low standby current
Dimensions (h x Ø) 60 mm x 108 mm
E Two-wire connection
Ordering Information E No mechanical parts subject to wear and tear
E Rate-of-rise and thermostatic
KV210P Rate-of-Rise Heat Detectors with remote indicator output
E Remote indicator output on KV210P
E Latching alarm
E Compact and water resistant electronics
E Highly resistant to humidity and corrosion
E Modern and elegant design
E No base required
E Excellent price/quality ratio
Conventional Fire Systems
Page : 51

Low Profile Ionisation Smoke Detector KL500

The KL500 ionisation smoke detector reacts to the presence of both


visible and invisible combustion smoke, which makes it ideal for early
fire detection, even before flames appear.

Specifications

Operating voltage 18 to 28 VDC


Current consumption
Quiescent at 24 VDC 30 mA
Alarm at 24 VDC < 70 mA
Radio-active source Americium 241
Average activity < 1mCi
Remote alarm output < 100 mA
Operating temperature -10 to +60 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP205
Dimensions (h x Ø)
Head 60 mm x 108 mm
Base 24 mm x 103 mm
Coverage 60 - 80 m²
E Response to the full range of combustion smoke
Maximum installation height 12 m
E Low standby current
Ordering Information E No mechanical parts subject to wear and tear
E High luminosity alarm indicator
KL500 Low Profile Ionisation Smoke Detector
E Remote indicator output available
KZ500 Fire detector base for KL500 detectors
S300 Surface mount supplement for KL300/KM170 detectors E Latching alarm
PA25/3L Low current remote LED indicator E Two wire connection
E Highly resistant to humidity and corrosion
E Modern and elegant design
E Easy installation
E More than 90% of materials recyclable (including the
radio-active source)
Conventional Fire Systems
Page : 52

Fire detector base for KL500 detectors KZ500

The KZ500 is a detecor base for use with the KL500 detectors from
Kilsen. It allows for a remote indicator to be connected.

Specifications

Dimensions
Diameter 108 mm
Height 18 mm

Ordering Information

KZ500 Fire detector base for KL500 detectors

E Polarity sensitive
E Remote indicator contact available
Conventional Fire Systems
Page : 53

Ionisation detector, conventional KL700

Of outstanding performance, efficiency and durability, the 700 series


fire detectors are the ideal solution for conventional installations. They
are designed specifically for use with the Kilsen NKB600, NK600 and
NK700 series conventional fire panels, but are also compatible with
most 3rd party industry standard conventional control panels.

Specifications

Operating voltage 18 to 28 VDC


Current consumption
Quiescent at 24 VDC 30 A
Alarm at 24 VDC < 100 mA
Radio-active source Americium 241
Average activity 0.33 +/-0.04 Ci (12.1 +/- 1.5 kBq)
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 to +60 °C
Storage temperature -10 to +70 °C
Humidity (non-condensing) 0 - 95%
IP rating IP43
Number of detectors per zone 20
E Full line consisting of Optical, Ionisation and Heat
Recommended protection 300 ohm detectors
resistor
Dimensions (h x Ø) E An ultra-fine grid prevents the ingress of dust and
Head 45 mm x 99 mm insects in smoke detectors
Base 24 mm x 103 mm E Attractive, low-profile design
Approvals* EN54 (BOSEC)
E EN54 approved *
* Check current status with local
office E Innovative base compensates for uneven surfaces
E Field exchangeable optical chamber for ease of
Ordering Information maintenance

KL700 Ionisation detector, conventional


KZ700 Universal fire detector base
KZ705 Universal fire detector base with earth connection
KZ705D Conventional fire detector base with diode
PA25/3L Low current remote LED indicator
Conventional Fire Systems
Page : 54

Temperature detector (fixed and rate-of-rise), conventional KL710

Of outstanding performance, efficiency and durability, the 700 series


fire detectors are the ideal solution for conventional installations. They
are designed specifically for use with the Kilsen NKB600, NK600 and
NK700 series conventional fire panels, but are also compatible with
most 3rd party industry standard conventional control panels.

Specifications

Operating voltage 18 to 28 VDC


Current consumption
Quiescent at 24 VDC 70 A
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification Max. & ROR to EN54p5
Operating temperature -10 °C to +70 °C
Storage temperature -10 °C to +80 °C
Humidity (non-condensing) 95%
IP rating IP43
Number of detectors per zone 20
E Full line consisting of Optical, Ionisation and Heat
Recommended protection 300 ohm detectors
resistor
Dimensions (h x Ø) E An ultra-fine grid prevents the ingress of dust and
Head 45 mm x 99 mm insects in smoke detectors
Base 24 mm x 103 mm E Attractive, low-profile design
Approvals* EN54 (BOSEC)
E EN54 approved *
* Check current status with local
office E Innovative base compensates for uneven surfaces
E Field exchangeable optical chamber for ease of
Ordering Information maintenance

KL710 Temperature detector (fixed and rate-of-rise), conventional


KZ700 Universal fire detector base
KZ705 Universal fire detector base with earth connection
KZ705D Conventional fire detector base with diode
PA25/3L Low current remote LED indicator
Conventional Fire Systems
Page : 55

Optical detector, conventional (with field exchangeable optical block) KL731

Of outstanding performance, efficiency and durability, the 700 series


fire detectors are the ideal solution for conventional installations. They
are designed specifically for use with the Kilsen NKB600, NK600 and
NK700 series conventional fire panels, but are also compatible with
most 3rd party industry standard conventional control panels.

Specifications

Operating voltage 9 to 28 VDC


Current consumption
Quiescent at 24 VDC 85 A
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 °C to +70 °C
Storage temperature -10 °C to +70 °C
Humidity (non-condensing) 95%
IP rating IP43
Number of detectors per zone 20
E An ultra-fine grid prevents the ingress of dust and
Recommended protection 300 ohm insects in smoke detectors
resistor
Dimensions (h x Ø) E Attractive, low-profile design
Head 45 mm x 99 mm E EN54 approved
Base 24 mm x 103 mm
E Innovative base compensates for uneven surfaces
Approvals* EN54 (BOSEC)
* Check current status with local E Field exchangeable optical chamber for ease of
office maintenance

Ordering Information

KL731 Optical detector, conventional (with field exchangeable optical block)


KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors
KZ700 Universal fire detector base
KZ705 Universal fire detector base with earth connection
KZ705D Conventional fire detector base with diode
KZ705R Conventional 12 VDC fire detector base with relay
PA25/3L Low current remote LED indicator
Conventional Fire Systems
Page : 56

Optical detector, conventional - Black KL731B

Of outstanding performance, efficiency and durability, the 700 series


fire detectors are the ideal solution for conventional installations. They
are designed specifically for use with the Kilsen NKB600, NK600 and
NK700 series conventional fire panels, but are also compatible with
most 3rd party industry standard conventional control panels. The
KL731B is a black detector specifically designed for use in false
ceilings.

Specifications

Operating voltage 9 to 28 VDC


Current consumption
Quiescent at 24 VDC 85 A
Alarm at 24 VDC < 100 mA
Radio-active source
Average activity
Remote alarm output < 100 mA
Heat specification
Operating temperature -10 °C to +70 °C
Storage temperature -10 °C to +70 °C
Humidity (non-condensing) 95% E An ultra-fine grid prevents the ingress of dust and
IP rating IP43 insects in smoke detectors
Number of detectors per zone 20
E Attractive, low-profile design
Recommended protection 300 ohm
resistor E EN54 certification marks (*)
Dimensions (h x Ø)
E Field exchangable optical chamber for ease of
Head 45 mm x 99 mm maintenance
Base 24 mm x 103 mm
E Black colour
Approvals* EN54 (BOSEC)
* Check current status with local
office

Ordering Information

KL731B Optical detector, conventional - Black


KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors
Conventional Fire Systems
Page : 57

Calibration Tool for KL731/DP331I Fire Detectors KCT731

The KCT731 is a calibration tool to recalibrate the conventional


detectors after replacement of the field exchangeable optical block.

Specifications

Supply 2 x 9 V batteries
Dimensions (w x h x d) 104 x 195 x 63 mm

Ordering Information

KCT731 Calibration Tool for KL731/DP331I Fire Detectors

E Easy to use
E Simple "go/no-go" function
E Battery operated
Addressable Fire Systems
Page : 58

Analogue addressable ionisation sensor KL700A

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity
and error free operation of the fire system, without compromising
speed. All sensors are compatible with a standard base that makes
them easily interchangeable and that supports the connection of a
remote indicator.

Specifications

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 200 A
In alarm less than 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote alarm output Available
Environment
Storage temperature -10 °C to +70 °C
Operating temperature -10 °C to +60 °C
Humidity (non condencing) 95%
IP rating IP205
Radioactive source 0.33 ± 0.04 Ci Am 241
E Remote signalling capabilities
Dimensions (h x Ø) 45 mm x 99 mm
E Easy soft addressing (1-125)
Ordering Information E SMD technology
E Reliable communication protocol
KL700A Analogue addressable ionisation sensor
E Full diagnostic self testing
E Full range: Ionisation, Optical and Heat and Duel
sensors (optical/heat)
E Full range of supporting I/O units and accessories
E EN54 Approved
Addressable Fire Systems
Page : 59

Analogue addressable temperature sensor KL710A

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity
and error free operation of the fire system, without compromising
speed. All sensors are compatible with a standard base that makes
them easily interchangeable and that supports the connection of a
remote indicator.

Specifications

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 250 A
In alarm less than 11 mA
Alarm indication (Dual LED) White OFF - Red ON
Remote alarm output Available
Environment
Storage temperature -10 °C to +80 °C
Operating temperature -10 °C to +70 °C
Humidity (non condencing) 95%
IP rating IP205
Radioactive source NA
E Remote signalling capabilities
Dimensions (H x Ø) 45 mm x 99 mm
E Fixed and Rate-of-Rise heat detectors
Ordering Information E Easy soft addressing (1-125)
E SMD technology
KL710A Analogue addressable temperature sensor
E Reliable communication protocol
E Full diagnostic self testing
E Full range: Ionisation, Optical and Heat and Duel
sensors (optical/heat)
E Full range of supporting I/O units and accessories
E EN54 Approved
Addressable Fire Systems
Page : 60

Analogue addressable optical sensor (with field exchangeable chamber) KL731A

The KL700A series detectors use a microprocessor for measurement


and communication. An enhanced protocol ensures the overall
integrity and error free operation of the system, without compromising
detection speed.

All sensors are compatible with a standard base that makes them
easily interchangeable and support the connection of the PA25/3L
remote indicator.

Specifications

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 350 A
In alarm Less than 11 mA
Alarm indication (Dual LED) Red
Remote alarm output Available
Environment
Storage temperature -10 °C to +70 °C
Operating temperature -10 °C to +60 °C
Humidity (non condencing) 95% E Remote signalling capabilities
IP rating IP205
Radioactive source NA
E Field exchangeable optical chamber
Dimensions (h x Ø) 45 mm x 99 mm E Easy soft addressing (1-125)
E SMD technology
Ordering Information
E Reliable communication protocol
KL731A Analogue addressable optical sensor (with field exchangeable chamber)
E Full diagnostic self testing
KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors E Full range: Ionisation, Optical and Heat and Duel
KZ700
sensors (optical/heat)
Universal fire detector base
KZ705 Universal fire detector base with earth connection E Full range of supporting I/O units and accessories
KZ705AS Analogue fire detector base with sounder
KZ705IAS Analogue fire detector base with isolator and sounder E EN54 Approved
KZ705I Analogue fire detector base with isolator E Black Colour
PA25/3L Low current remote LED indicator
Addressable Fire Systems
Page : 61

Analogue addressable optical detector - Black KL731AB

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity
and error free operation of the fire system, without compromising
speed. All sensors are compatible with a standard base that makes
them easily interchangeable and that supports the connection of a
remote indicator. The KL731B is a black detector specificlly designed
for false ceilings.

Specifications

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 350 A
In alarm Less than 11 mA
Alarm indication (Dual LED) Red
Remote alarm output Available
Environment
Storage temperature -10 °C to +70 °C
Operating temperature -10 °C to +60 °C
Humidity (non condencing) 95%
IP rating IP205 E Remote signalling capabilities
Radioactive source NA
Dimensions (h x Ø) 45 mm x 99 mm
E Field exchangeable optical chamber
E Easy soft addressing (1-125)
Ordering Information E SMD technology
E Reliable communication protocol
KL731AB Analogue addressable optical detector - Black
KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors
E Full diagnostic self testing
E Full range: Ionisation, Optical and Heat and Duel
sensors (optical/heat)
E Full range of supporting I/O units and accessories
E EN54 Approved
E Black Colour
Addressable Fire Systems
Page : 62

Analogue addressable dual (optical and thermal) sensor KL735A

The KL700A Series uses a microprocessor for measurement and


communication. An enhanced protocol ensures the overall integrity
and error free operation of the fire system, without compromising
speed. All sensors are compatible with a standard base that makes
them easily interchangeable and that supports the connection of a
remote indicator.

Specifications

Operating voltage 22 - 38 VDC


Current consumption
Quiescent @ 38 VDC 350 A
In alarm Less than 5 mA
Alarm indication (Dual LED) Red
Remote alarm output Available
Environment
Storage temperature -10 °C to +70 °C
Operating temperature -10 °C to +70 °C
Humidity (non condencing) 95%
IP rating IP42
Radioactive source NA
E Remote signalling capabilities
Dimensions (h x Ø) 51 mm x 99 mm
E Fixed and Rate-of-Rise heat detectors
Ordering Information E Easy soft addressing (1-125)
E SMD technology
KL735A Analogue addressable dual (optical and thermal) sensor
E Reliable communication protocol
E Full diagnostic self testing
E Full range: Ionisation, Optical and Heat and Duel
sensors (optical/heat)
E Full range of supporting I/O units and accessories
E EN54 Approved
Addressable Fire Systems
Page : 63

Fire sensor programmer PG700

The PG700 is a handheld device programmer and tester for the


KL700A/Dx1500 series detectors. It is battery operated and allows the
installer to perform installation tasks (such as device addressing) and
maintenance tasks (such as device calibration) in the field without
external assistance.

Specifications

Supply 2 x 9 V batteries
Dimensions (w x h x d) 104 x 195 x 63 mm

Ordering Information

PG700 Fire sensor programmer

E Easy to use
E Battery operated
E 4 User selectable programs
-Device analogue value
-Change Device Address
-Sequential device addressing
-KL731A Calibration
Detector Bases & Accessories
Page : 64

Replacement Optical Chamber for KL731/A & DP331I/1561 detectors KOB700

The KOB700 is an optical replacement chamber for KL731/KL731A and


DP331I/DP1561 detectors. It is an inexpensive part that allows easy
maintenance of these detectors on site without the need for cleaning
solvents or complicated cleaning procedures. Once replaced, the
detector performs as if it was a new device.

Specifications

Dimensions (Ø x h) 65 x 19 mm

Ordering Information

KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors

E Inexpensive
E Easy replacement
E Reduces maintenance time
E No additional tools required

Dust Protector Cover for KL700/A and Dx300/1500 detectors KL7A

The KL7A is a dust protector cover for the KL700/DI322I and


KL731/DP331I conventional, as well as the KL700A/DP1552 and
KL731A/DP1561A addressable detectors. It allows for the protection of
the detector chamber against the ingress of dust from building
materials during construction or renovation of the building.

Ordering Information

KL7A Dust Protector Cover for KL700/A and Dx300/1500 detectors

E Negligible cost
E Easy to install and remove
E Avoids unnecessary contamination of the detector
during building works
Detector Bases & Accessories
Page : 65

Universal fire detector base KZ700

The KZ700 is a 4 contact universal detector base. It has the ability to


compensate for uneven mounting surfaces. It is also available in black
for special applications in false ceilings.

Specifications

Dimensions
Diameter 104 mm
Height 24 mm

Ordering Information

KZ700 Universal fire detector base


KZ700B Universal fire detector base (for KL700/A and Dx300/1500) - Black

E Polarity sensitive
E Universal base fits conventional and analogue
detectors
E Compensates for uneven surfaces
E Remote indicator contact available
E EN54 approved
E Variant in black also available
Detector Bases & Accessories
Page : 66

Universal fire detector base (for KL700/A and Dx300/1500) - Black KZ700B

The KZ700B is a black 4 contact universal detecor base for use with the
KL700/Dx300 and KL700A/Dx1500 series detectors from GE-Interlogix.
It has the ability to compensate for uneven mounting surfaces.

Specifications

Dimensions
Diameter 104 mm
Height 24 mm

Ordering Information

KZ700B Universal fire detector base (for KL700/A and Dx300/1500) - Black

E Polarity sensitive
E Universal base fits conventional and analogue
detectors
E Compensates for uneven surfaces
E Remote indicator contact available
E EN54 approved
E Variant in black also available
Detector Bases & Accessories
Page : 67

Universal fire detector base with earth connection KZ705

The KZ705 is a 5 contact universal detector base for use with the
KL700/Dx300 and KL700A/Dx1500 series detectors from GE-Interlogix.
In addition to the normal base and remote indication connectors, the
KZ705 also has an additional earth terminal connector to allow for
easy terminations of a possible cable screen.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage -
Current Consumption -
Isolation Current -
Isolation Resistance -
Sounder Frequency -
Sound Output
@ 3 mA -
@ 5 mA -
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
Relative Humidity (max) 95 % (non-cond.)
E Polarity sensitive
Ordering Information E Universal base fits conventional and analogue
detectors
KZ705 Universal fire detector base with earth connection E Additional earth terminal available
E Remote indicator contact available

Surface mount accessory for KZ700 and KZ705 series bases S700

The S700 is a base accessory designed for use with the KZ700 series
detector bases. It allows for a surface mount conduit and cable to
enter the base from the side. The KZ700 series base fits on top of this
accessory.

Specifications

Dimensions
Diameter 95 mm
Height 30 mm

Ordering Information

S700 Surface mount accessory for KZ700 and KZ705 series bases

E Surface mount accessory for KZ700 series bases


Addressable Fire Systems
Page : 68

Analogue fire detector base with isolator KZ705I

The KZ705I is a detector base with built in isolator for use with the
KL700A/Dx1500 series detectors from GE-Interlogix. The isolator
protects the loop from short circuit conditions. A LED on the side of the
base indicates the status of the isolator.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 17 - 34 V
Current Consumption 50 A
Isolation Current 6 mA
Isolation Resistance 140 Mohm
Sounder Frequency -
Sound Output
@ 3 mA -
@ 5 mA -
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
Storage Temperature -10 °C to +70 °C
Relative Humidity (max) 95 % (non cond.)

E Polarity sensitive
Ordering Information
E Universal base for analogue detectors
KZ705I Analogue fire detector base with isolator E Additional earth terminal available
E Remote indicator contact available
E Built in isolator
Addressable Fire Systems
Page : 69

Analogue fire detector base with sounder KZ705AS

The KZ705AS is a detector base with built in analogue addressable


sounder for use with the KL700A/Dx1500 series detectors from
GE-Interlogix. The sounder has its own address on the fire panel loop
and works independent of the detector. It is fully controlled from the
fire panel.

Specifications

Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 300 A Quiescent
Isolation Current -
Isolation Resistance -
Sounder Frequency 1 kHz (Continuous)
Sound Output
@ 3 mA 85 dBA
@ 5 mA 90 dBA
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
Storage Temperature -10 °C to +70 °C
Relative Humidity (max) 95 % (non cond.)
E Polarity sensitive
IP Rating IP21c
E Universal base for analogue detectors
Ordering Information E Additional earth terminal available
E Remote indicator contact available
KZ705AS Analogue fire detector base with sounder
E Built in sounder
E Up to 90 dBA sound output
E Low current consumption
Addressable Fire Systems
Page : 70

Analogue fire detector base with isolator and sounder KZ705IAS

The KZ705IAS is a detector base with built in analogue addressable


sounder and isolator for use with the KL700A/Dx1500 series detectors
from GE-Interlogix. The sounder has its own address on the fire panel
loop and works independent of the detector. It is fully controlled from
the fire panel. The isolator protects the loop from short circuit
conditions.

Specifications

Dimensions (Ø x h) 120 x 58 mm
Operating Voltage 22 - 38 V
Current Consumption 350 A Quiescent
Isolation Current 6 mA
Isolation Resistance 140 Mohm
Sounder Frequency 1 kHz (Continuous)
Sound Output
@ 3 mA 85 dBA
@ 5 mA 90 dBA
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
Storage Temperature -10 °C to +70 °C
E Polarity sensitive
Relative Humidity (max) 95 % (non cond.)
IP Rating IP21c
E Universal base for analogue detectors
E Additional earth terminal available
Ordering Information E Remote indicator contact available
E Built in sounder
KZ705IAS Analogue fire detector base with isolator and sounder
E Up to 90 dBA sound output
E Low current consumption
E Built in isolator
Conventional Fire Systems
Page : 71

Conventional fire detector base with diode KZ705D

The KZ705D is a 5 contact universal detector base for use with the
KL700/Dx300 series detectors from GE-Interlogix. In addition to the
normal base and remote indication connectors, the KZ705D also has
an additional earth terminal connector to allow for easy terminations
of a possible cable screen. The built in diode is specifically targeted at
systems using active end-of-line devices.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage -
Current Consumption -
Isolation Current -
Isolation Resistance -
Sounder Frequency -
Sound Output
@ 3 mA -
@ 5 mA -
Environmental Characteristics
Operating Temperature -10 to 70 °C
Storage Temperature -10 to 70 °C
E Polarity sensitive
Relative Humidity (max) 95 % (non-cond.)
E Universal base for conventional detectors
Ordering Information E Additional earth terminal available
E Remote indicator contact available
KZ705D Conventional fire detector base with diode
E Built in diode for active end-of-line systems

Conventional 12 VDC fire detector base with relay KZ705R

The KZ705R is a 5 contact detector base for use with the KL731/DP331I
detectors from GE-Interlogix. In addition to the normal base and
remote indication connectors, the KZ705R also has an additional earth
terminal connector to allow for easy terminations of a possible cable
screen. A built in 12 V relay makes it ideal for use on low voltage
intrusion systems.

Specifications

Dimensions (Ø x h) 100 x 29 mm
Operating Voltage 12 V ± 10%
Current Consumption 12 A
Isolation Current -
Isolation Resistance -
Sounder Frequency -
Sound Output
@ 3 mA - E Polarity sensitive
@ 5 mA -
E 12 V relay for 4 wire systems
Environmental Characteristics
Operating Temperature -10 °C to +70 °C
E Additional earth terminal available
Storage Temperature -10 °C to +70 °C E Remote indicator contact available
Relative Humdity 95 % (non cond.)

Ordering Information

KZ705R Conventional 12 VDC fire detector base with relay


Annunciators
Page : 72

Low current remote LED indicator PA25/3L

The PA25 remote indicators have been designed for direct connection
to fire detectors (conventional and analogue), enabling luminous
indication outside the area where the detector is installed.

Specifications

Electrical Specifications
Supply Voltage (Analogue) 5 to 10 VDC
Current Consumption 2 to 79 mA
Supply Voltage (Conventional) 2 to 5 VDC
Current Consumption 6.5 to 61.5 mA
Mechanical Specifications
Size (w x h x d) 80 x 80 x 42 mm
Weight 10 g
Box material A.B.S.
Colour White
Environmental Specifications
Protection level IP20
Working temperature -10 to +60 °C
Storage temperature -10 to +70 °C

E Direct two-wire connection to detector


Ordering Information
E Large angle of visibility - lit up on four sides
PA25/3L Low current remote LED indicator E Low current consumption
E Flashing option
E 2 to 10 VDC power supply
E High luminosity
E Compatible with third party products
E IP20 protection level
E Modern and elegant design
E ABS plastic casing with ruby red polycarbonate
spy-hole
E Shock resistant
Addressable Fire Systems
Page : 73

Conventional Zone Monitor Unit - 1 Zone KAL410

Allows the connection of one conventional zone to the analogue fire


system loop. This zone is constantly monitored. Up to 20 conventional
devices may be connected to this zone.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 90 A
Quiescent @ 35 V 105 A
Alarm < 3 mA
Aux. supply (24 VDC) 200 A + equip
quiescent
Aux. supply (24 VDC) alarm < 85 mA
End-of-line resistor 4.7 kohm
Relay contact rating NA
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 117 x 80 x 44 mm
E Easy numeric addressing
Ordering Information E Continuous supervision of the conventional zones
E Surface mount
KAL410 Conventional Zone Monitor Unit - 1 Zone
E Local alarm indication
E Externally or loop powered
E Aesthetically pleasing
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 74

Conventional Zone Monitor Unit - 4 Zones KAL414C

Allows the connection of four conventional zones to the analogue fire


system loop. These zones are constantly monitored. Up to 20
conventional devices may be connected to any zone.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm < 5 mA
Aux. Supply (24V DC) 200 A + equip
Quiescent
Aux. Supply (24V DC) Alarm < 360 mA
End-of-line resistor 4.7 kOhm
Relay contact rating NA
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity 0-95 %
(non-condensing)
Dimensions (l x w x h) 163 x 107 x 36 mm E Easy numeric addressing

Ordering Information
E Continuous supervision of the conventional zones
E Surface mount
KAL414C Conventional Zone Monitor Unit - 4 Zones E Local alarm indication
E Externally powered
E Aesthetically pleasing
E Part of a family of I/O modules consisting of:
E - Conventional Zone Monitors
E - Digital Input Modules
E - Extinguishing Control Modules
E - Isolator Modules
E - Manual Call Points
E - Output Units
E - Retention Units
E - Supervised Output Units for sounder control
Addressable Fire Systems
Page : 75

Extinguishing Control Module KAL426C

The 400 Series modules consists of a complete range of interfaces


developed for input/output control in the KSA700/FP1500 analogue fire
systems from GE Interlogix. The KAL426 allows for the connection and
control of one extinguishing area to the addressable fire panel loop.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 210 A
Alarm < 10 mA
Aux. supply (24 VDC) 120 mA
quiescent
Aux. supply (24 VDC) alarm <1A
End-of-line resistor 4.7 kOhm
Relay contact rating 2½ A
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
Dimensions (L x W x H) 163 x 107 x 36 mm E Aesthetically pleasing
E Easy numeric addressing
Ordering Information
E Externally powered
KAL426C Extinguishing Control Module E Supervised I/O
E Surface mount
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 76

Relay Module - 1 Relay KAL430

Provides for one potential free relay output for the fire system loop.
Each relay allows for COMMON, NORMALLY OPEN and NORMALLY
CLOSED contacts. The output may be used to activate ventilation
controls, warning signs, activation of other alarm devices etc. during
fire situations.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 70 A
Quiescent @ 35 V 100 A
Alarm < 3.5 mA
Aux. 24 VDC quiescent 22 mA
Aux. 24 VDC alarm < 50 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
E Easy numeric addressing
Dimensions (L x W x H) 117 x 80 x 44 mm
E Externally or loop powered
Ordering Information E Normally open / normally closed operation for I/O
E Surface mount
KAL430 Relay Module - 1 Relay
E Aesthetically pleasing
E Local status indication
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 77

Addressable Relay Module - 4 Relays KAL434C

Provides for four potential free relay outputs for the fire system loop.
Each relay allows for COMMON, NORMALLY OPEN and NORMALLY
CLOSED contacts. The outputs may be used to activate ventilation
controls, warning signs, activation of other alarm devices etc. during
fire situations.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm 10 mA
Aux. 24VDC Quiescent 100 A
Aux. 24VDC Alarm 10 mA
End-of-line resistor NA
Relay contact rating 2½A @ 250 VAC
Environmental
Storage temperature -10 to +50°C
Operating temperature -10 to +70°C
Relative humidity (non-cond.) 0-95 %
E Easy numeric addressing
Dimensions (l x w x h) 163 x 107 x 36 mm
E Externally powered
Ordering Information E Normally open / normally closed operation for I/O
E Surface mount
KAL434C Addressable Relay Module - 4 Relays
E Aesthetically pleasing
E Local status indication
E Part of a family of I/O modules consiting of:
E - Conventional Zone Monitors
E - Digital Input Modules
E - Extinguishing Control Modules
E - Isolator Modules
E - Manual Call Points
E - Output Units
E - Retention Units
E - Supervised Output Units for sounder control
Addressable Fire Systems
Page : 78

Supervised Relay Module KAL440

Allows for the supervision of a single, 24 Volt powered output contact


on the fire system loop. This unit may be used to control for e.g.
sounders in case of fire conditions, but may also be used to switch any
output considered crucial enough to have the cable integrity between
the unit and the switch point monitored.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm < 3.6 mA
Aux. 24 VDC quiescent 23 mA
Aux. 24 VDC alarm 23 mA + equip
End-of-line resistor 4.7 kohm
Relay contact rating 1¼ A @ 250 VAC
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
Relative humidity 95 % (non condensing)
E Easy numeric addressing
Dimensions (L x W x H) 117 x 80 x 44 mm
E Externally powered
Ordering Information E Supervised 24 VDC Output
E Surface mount
KAL440 Supervised Relay Module
E Aesthetically pleasing
E Local status indication
E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 79

Addressable Manual Call Point KAL450

The 400 Series modules consists of a complete range of interfaces


developed for input/output control in the KSA700/FP1500 analogue fire
systems from GE Interlogix. The KAL450 is an addressable manual call
point for manual fire activation.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 90 A
Quiescent @ 35 V 120 A
Alarm < 3.5 mA
Aux. supply (24 VDC) NA
quiescent
Aux. supply (24 VDC) alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 °C to +70°C
Operating temperature -10 °C to +50°C
Relative humidity 95 % (non condensing)
Ingress Protection IP20 E Easy numeric addressing
Dimensions (L x W x H) 87 x 87 x 20 mm E Loop powered
Weight 98 g
E Local test facility
Ordering Information E Surface or flush mount
E Aesthetically pleasing
KAL450 Addressable Manual Call Point E Local status indication
DM715 EN54 universal glass for manual call point
DM780 Terminal tray for MCP E Part of family of I/O modules consisting of:
DM781 GS card -Conventional Zone Monitors
DM782 Hinged transparent MCP protection cover -Digital Input Modules
DM783 BZB black bezel -Extinguishing Control Modules
DM784 Test key -Isolator Modules
DM785 Spacer box, red -Manual Call Points
DM787 Surface mounting box with connectors, red -Output Units
DM788 Surface mount box without connectors, red
-Retention Units
DM790 -Supervised Output Units for sounder control
Flush mount cradle with connectors
DM795 Flush mount cradle, connectors & forkgrips
DM798 Breakable seal for MCP E Wide range of accessories
DM799 Terminal tray ETT/3 with bezel 3
DM800 Resettable element for MCP DM700/KAL450
Manual Call Points
Page : 80

EN54 universal glass for manual call point DM715

The DM715 is a universal EN54 approved break glass for the DM700
series and KAL450 manual call points.

Ordering Information

DM715 EN54 universal glass for manual call point


DM800 Resettable element for MCP DM700/KAL450

E Plastic coated to prevent operator injury


E No glass fragments on breaking
E No hammer required
E Approved EN54 part 11

Hinged transparent MCP protection cover DM782

The DM782 anti-tamper plastic cover is a protection cover for the


DM700 and KAL450 manual call points. It prevents accidental
activation of the alarm by enforcing a two step action i.e. lifting the
cover, then activating the alarm.

Ordering Information

DM782 Hinged transparent MCP protection cover


DM798 Breakable seal for MCP

E Unobtrusive
E Transparent
E Protects from accidental alarm activation
Manual Call Points
Page : 81

Surface mounting box with connectors, red DM787

The DM787 is surface mounting back-box for DM700 series and


KAL450 series manual call points. The DM787 is red and has 3 wiring
terminals

Specifications

Material Self-extinguishing Noryl SE100


Colour Red - RAL N°3020
Operating temperature -40° to +85°C
Relative humidity max. 90% RV

Ordering Information

DM787 Surface mounting box with connectors, red


DM787Y Surface mounting box with connectors, yellow
DM787B Surface mounting box with connectors, blue
DM787G Surface mounting box with connectors, green
DM788 Surface mount box without connectors, red

E Easy to install
E For flush mounting of manual call points
E Three terminals
Addressable Fire Systems
Page : 82

Digital Input Module KAL460

Provides a remote input to the fire system loop. The input is constantly
monitored and its status communicated to the fire control panel. The
input may be activated by closing or opening a potential free contact,
depending on the module configuration.

This module may be used to monitor any contact by showing its status
through the fire control panel e.g. the monitoring of pressure
equipment and closure fire break doors.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm < 10 mA
Aux. 24 VDC quiescent 200 A
Aux. 24 VDC alarm < 50 mA
End-of-line resistor NA
Relay contact rating NA
Environmental E Easy numeric addressing
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
E Externally or loop powered
Relative humidity 95 % (non condensing) E Normally open / normally closed operation for I/O
Dimensions (L x W x H) 117 x 80 x 44 mm E Surface mount
E Aesthetically pleasing
Ordering Information
E Local status indication
KAL460 Digital Input Module E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 83

Isolator Module KAL470

The 400 series modules consist of a complete range of interfaces


developed for input/output control in the KSA700/FP1500 analogue fire
systems from GE Interlogix. The KAL470 is an isolator module in this
series that isolates the faulty zone on a fire panel loop during short
circuit conditions. The KAL470 does not use an address on the loop.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm 10 mA
Aux. supply (24 VDC) NA
quiescent
Aux. supply (24 VDC) alarm NA
End-of-line resistor NA
Relay contact rating NA
Environmental
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +50°C
Relative humidity 95 % (non condensing) E Requires no device address
Dimensions (L x W x H) 75 x 45 x 28 mm E Automatic reset
E Local status indication
Ordering Information
E Surface mount
KAL470 Isolator Module E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 84

Retention Module - 1 Input / 1 Output KAL490

Provides a remote input and a potential free voltage relay output to


the fire system loop. The input signal is constantly monitored and its
status displayed on the control panel, whilst the output is fail-to-safe.
Auxiliary supply monitoring is also included.

The module is used to for e.g. control and monitor doors such as fire
break doors. The relay provides the door activation and the input
monitors the door status.

Specifications

Supply voltage 22-38 VDC


Current consumption
Quiescent @ 24 V 110 A
Quiescent @ 35 V 135 A
Alarm 10 mA
Aux. 24 VDC quiescent 200 A
Aux. 24 VDC alarm < 50 mA
End-of-line resistor NA
Relay contact rating 1A @ 30 VAC/VDC
Environmental E Easy numeric addressing
Storage temperature -10 °C to +50°C
Operating temperature -10 °C to +70°C
E Externally or loop powered
Relative humidity 95 % (non condensing) E Normally open / normally closed operation for I/O
Dimensions (L x W x H) 117 x 80 x 44 mm E Surface mount
E Aesthetically pleasing
Ordering Information
E Local status indication
KAL490 Retention Module - 1 Input / 1 Output E Part of family of I/O modules consisting of:
-Conventional Zone Monitors
-Digital Input Modules
-Extinguishing Control Modules
-Isolator Modules
-Manual Call Points
-Output Units
-Retention Units
-Supervised Output Units for sounder control
Addressable Fire Systems
Page : 85

Addressable loop powered siren SK07A

The SK07A loop powered siren is designed for connection to and


control by the KSA700/FP1500 analogue fire detection systems from
GE-Interlogix. Communication is done digitally between the fire panel
and the sounder.

Specifications

Electrical
Supply Voltage 22 - 38 VDC
Quiescent current 300 A
Alarm current 6 mA
Maximum sound level 87 dBA
Mechanical
Dimensions 63 mm (h) x 93 mm Ø
Maximum cable size 2.5 mm²
Fastening Screws 2 x 30 mm
Environmental
Working temperature -20 °C to +50 °C
Storage temperature -20 °C to +70 °C
Relative humidity (maximum) 95 %
Protection Index IP445
E EN54 part 3 compliant
Ordering Information E Up to 87 dBA sound output
E Low current consumption
SK07A Addressable loop powered siren E Low profile
E IP445 protection level
E Easy installation
E Polarity sensitive
E Rear and side cable entry possible
E Low and easy maintenance
Annunciators
Page : 86

Illuminated warning sign (No text) 24VDC KR24B

The KR24 is specifically designed as an evacuation warning sign for


gas extinguising areas. The KR24B has no text on the backlit display,
and text may therefor be added as required for the application. Units
supplied with text in various languages are also available.

Specifications

Electrical Specifications
Supply Voltage 18 to 27 VDC
Activation Voltage 18 to 27 VDC
Current Consumption 600 mA
Switching Polarity NA
Indicators 24 V 3 W
Environmental Specifications
Working Temperature -10 to 75 °C
Physical Specifications
Number of zones NA
Buzzer output 80 dB
Housing Colour Grey
Display Colour Red
Weight 700 g
E Low current consumption
Size (w x h x d) 255 x 110 x 50 mm
IP Rating IP50 E Large angle of view
E Optical and acoustic indications selectable
Ordering Information E Modern and elegant design

KR24B Illuminated warning sign (No text) 24VDC


Annunciators
Page : 87

Illuminated extinguishing waring sign (English version) 24VDC KR24-ING

The KR24 is a backlit "No Entry / Extinguishing Release" warning sign to


be used with gas extinguishing areas. Warning text is available in
various languages.

Specifications

Electrical Specifications
Supply Voltage 18 to 27 VDC
Activation Voltage 18 to 27 VDC
Current Consumption 600 mA
Switching Polarity NA
Indicators 24 V 3 W
Environmental Specifications
Working Temperature -10 to 75 °C
Physical Specifications
Number of zones NA
Buzzer output 80 dB
Housing Colour Grey
Display Colour Red
Weight 700 g
Size (w x h x d) 255 x 110 x 50 mm
E Low Consumption
IP Rating IP50
E Large angle of vision
Ordering Information E Optical and acoustic indication selectable
E Modern and elegant design
KR24-ING Illuminated extinguishing waring sign (English version) 24VDC
Annunciators
Page : 88

Low consumption multi-tone alarm siren SK07

The SK07 multi-tone siren is designed to sound an acoustic alarm


inside buildings. This small, low profile siren combines a high sound
output with low power consumption. It complies with the requirements
of EN 54 part 3.

Specifications

Electrical
Supply Voltage 22 - 26 VDC
Alarm current 3 mA at 85 dBA or less than 20 mA at 95 dBA
Maximum sound level 95 dBA
Working temperature -20 °C to 50 °C
Storage temperature -20 °C to 70 °C
Maximum relative humidity 95 % (non condencing)
Mechanical
Dimensions 63 mm (h) x 93 mm Ø
Protection Index IP445
Fastening screws 2 x 30 mm
Maximum cable section 2.5 mm²
Recommended cable size Single core 1.5 mm²

E Low profile
Ordering Information
E Easy installation
SK07 Low consumption multi-tone alarm siren E Back and side cable entry
E Polarity sensitive
E Connection base included
E Input and output terminals included
E Acoustic power output selection
E Up to 95 dBA sound output
E Eight different alarm tones
E Automatic tone change
E Low current consumption
E Low maintenance
E IP445 protection level
E EN54 part 3 compliant
Addressable Fire Systems
Page : 89

KSA701/FP1500 Configuration software kit PCC-Config

PCC-Config allows easy, menu driven, programming of all the features


and settings of the panel. Common texts can be easily copied to
sensors and zones. Programming becomes simple as all settings are
displayed for the programmers convenience.

Specifications

Hardware requirements
Communication RS232, modem and/or TCP/IP
Display VGA or higher resolution
Hard disk 2 Gb with 650 Mb free space
Keyboard Required
Pointing device Required
Printer System printer required for printing
Processor 133 MHz or higher Pentium-compatible CPU
RAM 64 Mb or more
Removable media 1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system Win '98, Win 2000, Win XP

Ordering Information
E Windows based
PCC-Config KSA701/FP1500 Configuration software kit E Complete external configuration of the installation
KSP700 KSA702/5 Configuration software kit E Configuration possibilities for single and networked fire
systems
E Local or remote operation via modem or TCP/IP
E Standard RS232 communication
Addressable Fire Systems
Page : 90

Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) PCG-Graphic102

The PCG-Config series consists of 3 software applications. The


individual software formats allows the graphic package to grow with
the installation. PCG-Config102 operates with a single panel and allows
for the configuration of all devices up to a maximum of two loops.

Specifications

Hardware requirements
Communication RS232, modem and/or TCP/IP
Display SVGA or higher resolution
Hard disk 2 Gb with 650 Mb free space
Keyboard Required
Pointing device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable media 1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system Windows '98 or Windows 2000

Ordering Information
E Bi-directional communication with single panels and
networked fire systems
PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops)
E Local or remote connection via modem or TCP/IP
E Large selection of user configurable icons
E Visualises device alarms and status of in- and outputs
E Event texts retrieval from the panel
E Configurator and operator contol levels
E Navigation buttons allowed
E Event logs with reporting facilities
E Basic drawing package included
E Imports bmp & drw format graphics
Addressable Fire Systems
Page : 91

Graphic Software for KSA700/FP1500 Fire Systems (1 panel-5 loops) PCG-Graphic105

The PCG-Config series consists of 3 software applications. The


individual software formats allows the graphic package to grow with
the installation. PCG-Config105 supports a single panel up to 5 loops.

Specifications

Hardware requirements
Communication RS232, modem and/or TCP/IP
Display SVGA or higher resolution
Hard disk 2 Gb with 650 Mb free space
Keyboard Required
Pointing device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable media 1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system Windows '98 or Windows 2000

Ordering Information

E Bi-directional communication with single panels and


PCG-Graphic105 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-5 loops) networked fire systems
E Local or remote connection via modem or TCP/IP
E Large selection of user configurable icons
E Visualises device alarms and status of in- and outputs
E Event texts retrieval from the panel
E Configurator and operator contol levels
E Navigation buttons allowed
E Event logs with reporting facilities
E Basic drawing package included
E Imports bmp & drw format graphics
Addressable Fire Systems
Page : 92

Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) PCG-GraphicNW

The PCG-Config series consists of 3 software applications. The


individual software formats allows the graphic package to grow with
the installation. PCG-ConfigNW allows for monitoring on networked
systems with multiple panels.

Specifications

Hardware requirements
Communication RS232, modem and/or TCP/IP
Display SVGA or higher resolution
Hard disk 2 Gb with 650 Mb free space
Keyboard Required
Pointing device Required
Printer System printer required for printing
Processor 1 GHz or higher Pentium III-compatible CPU
RAM 256 Mb or more
Removable media 1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system Windows '98 or Windows 2000

Ordering Information
E Bi-directional communication with single panels and
networked fire systems
PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel)
E Local or remote connection via modem or TCP/IP
E Large selection of user configurable icons
E Visualises device alarms and status of in- and outputs
E Event texts retrieval from the panel
E Configurator and operator contol levels
E Navigation buttons allowed
E Event logs with reporting facilities
E Basic drawing package included
E Imports bmp & drw format graphics
Addressable Fire Systems
Page : 93

KSA702/5 Configuration software kit KSP700

The KSP700 provides for a interface for the Kilsen KSA702 and KSA705
analogue addressable fire panels for the up/downloading of the fire
panel configuration software from a PC. It is supplied as a kit, including
the configuration cable together with PCC-Config, the software
configuration program for these panels.

Specifications

Hardware requirements
Communication RS232, modem and/or TCP/IP
Display VGA or higher resolution
Hard disk 2 Gb with 650 Mb free space
Keyboard Required
Pointing device Required
Printer System printer required for printing
Processor 133 MHz or higher Pentium-compatible CPU
RAM 64 Mb or more
Removable media 1.44 Mb stiffy and CD-ROM or DVD drive
Software requirements
Operating system Win '98, Win 2000, Win XP

E Windows based
Ordering Information
E Complete external configuration of the installation
KSP700 KSA702/5 Configuration software kit E Configuration possibilities for single and networked fire
systems
E Local or remote operation via modem or TCP/IP
E Communications interface included
Addressable Fire Systems
Page : 94

PC Configuration RS232 Cable for KSA701/FP1500 fire panels KSP701

The KSP701 is a RS232 cable for connecting the KSA701 Series or


FP1500 Series fire panels to an industry standard RS232 port on any
PC. It is normaly included with all software applications for these
panels, but may also be ordered seperately when required.

Ordering Information

KSP701 PC Configuration RS232 Cable for KSA701/FP1500 fire panels

E Complete RS232 cable with connectors


Addressable Fire Systems
Page : 95

Programming and configuration software PCC2000

PCC2000 allows easy, menu driven, programming of all the panel's


features and settings. Common texts can be easily copied while
sensors, zones and areas increment or follow automatically. Boolean
logic programming becomes simple as inputs and outputs are
continuously displayed for the programmer's convenience.

Specifications

Processor 486 66 MHz


RAM 12 Mb
Display adapter VGA
Hard disk space 20 MB
Pointing device MS Mouse
Graphical environment Windows 98, 2000, XP
Communications ports 1 x RS232
1 x Parallel

Ordering Information

PCC2000 Programming and configuration software

E Provide communication with single fire panels and


networked fire systems, both locally or remote via
modem
E Windows 98, 2000 and XP compatible
E For use with 2000/1200 series panels
E Menu driven
E Full or partial up- and download
Addressable Fire Systems
Page : 96

Graphics package network application with copy protection key PCG-N

2 Packages allow the graphic package to grow with the installation.


The basic version PCG-S operates with a single panel, while the PCG-N
supports a network. Upgrades do not require rework on the existing
database, drawings, etc.

Specifications

Processor Pentium II 266 MHz (or better)


RAM 64 Mb (or more)
Display adapter SVGA or better
Hard disk space 200 MB
Pointing device MS Mouse, Bus or P/S2
Graphical environment Windows NT
Communication ports 1 x RS-232 - Depending on drivers
1 x Parallel - Printer port (for key)

Ordering Information

PCG-N Graphics package network application with copy protection key

E Provide bi-directional communication with single fire


panels and networked fire systems, both locally and
remote via modem
E Windows 2000 and NT compatible
E For use with FP2000, FP1200, FP1100 and FP700
E Constructed around Sybase SQL Anywhere
E Large selection of icons
E Visualises inputs & outputs
E Information page per point
E Get texts from panel
E Several operator levels and passwords
E Operator configurable
E Multiple navigation buttons
E Event logs
E Basic drawing package included
E Imports .bmp & .wmf drawings from virtually any
package
E Hardware key protected
Addressable Fire Systems
Page : 97

Graphics package with copy protection key PCG-S

2 Packages allow the graphic package to grow with the installation.


The basic version PCG-S operates with a single panel, while the PCG-N
supports a network. Upgrades do not require rework on the existing
database, drawings, etc.

Specifications

Item Recommended
Processor Pentium II 266 MHz (or better)
RAM 64 Mb (or more)
Display adapter SVGA or better
Hard disk space 200 MB
Pointing device MS Mouse, Bus or P/S2
Graphical environment Windows NT
Communication ports 1 x RS-232 - Depending on drivers
1 x Parallel - Printer port (for key)

Ordering Information

PCG-S Graphics package with copy protection key

E Provide bi-directional communication with single fire


panels and networked fire systems, both locally and
remote via modem
E Windows 2000 and NT compatible
E For use with FP2000, FP1200, FP1100 and FP700
E Constructed around Sybase SQL Anywhere
E Large selection of icons
E Visualises inputs & outputs
E Information page per point
E Get texts from panel
E Several operator levels and passwords
E Operator configurable
E Multiple navigation buttons
E Event logs
E Basic drawing package included
E Imports .bmp & .wmf drawings from virtually any
package
E Hardware key protected
Addressable Fire Systems
Page : 98

Maintenance and support software with copy protection key PCM2000

PCM2000 allows local and remote maintenance facilities for 1200/2000


series fire panels. Amongst others, it allows for full panel emulation,
data retrieval and central alarm monitoring.

Specifications

Processor Pentium 133Mhz (or better)


RAM 32 Mb (or more)
Display Adapter VGA
Hard Disk Space 20 MB
Pointing Device Bus or P/S2 Mouse
Graphical Environment Windows 98, NT or 2000
Communications ports Depending on Drivers Printer port (for key)
1 Parallel

Ordering Information

PCM2000 Maintenance and support software with copy protection key

E Provide communication with single fire panels and


networked fire systems, both locally or remote via
modem
E Windows 95, 98 and NT compatible
E For use with FP2000, FP1200
E Full panel emulation
E Data retrieval
E Central station
E History log
E Address book
E Dynamic Link Library (DLL) for third party integration
Special Temperature Detectors
Page : 99

High Temperature Thermal Probe with 2 wire connection ST801

The ST801 thermal probe high temperature heat detector is designed


to protect from hazards where high temperatures are produced at a
specific point. The sensitive element (bulb) can be set at a distance of
up to 1 meter from the connection box. The ST801 may be connected
via 2 wires directly to a conventional fire panel zone.

Specifications

Suppy Voltage 24 VDC


Current Consumption
Quiescent Ø
Alarm 100 mA
Alarm Monitoring Two wires to conventional zone
Capilliary pipe length 1m
Probe Dimentions (l x Ø) 150 x 3 mm
Dimensions 140 x 100 x 70 mm
Colour Grey RAL7032
Working Temperature 50 °C to 300 °C
Weight 0.8 kg

Ordering Information
E Completely metal
ST801 High Temperature Thermal Probe with 2 wire connection E Adjustable from 50 to 300 °C
E Back and side cable input
E Sensitive probe with 1 m of stainless steel capillary
piping
E Resistant to heat, grease and humidity
E Easy installation
E Easy connection
E Easy maintenance
E Ideal for commercial areas
Special Temperature Detectors
Page : 100

High Temperature Thermal Probe with relay output ST802

The ST802 thermal probe high temperature heat detector is designed


to protect from hazards where high temperatures are produced at a
specific point. The sensitive element (bulb) can be set at a distance of
up to 1 meter from the connection box. The ST802 provides a protential
free relay output for alarm indication with COM, NC and NO contacts.

Specifications

Suppy Voltage 24 VDC


Current Consumption
Quiescent Ø
Alarm 100 mA
Alarm Monitoring 5A potential free relay
Capilliary pipe length 1m
Probe Dimentions (l x Ø) 150 x 3 mm
Dimensions 140 x 100 x 70 mm
Colour Grey RAL7032
Working Temperature 50 °C to 300 °C
Weight 0.6 kg

Ordering Information
E Completely metal
ST802 High Temperature Thermal Probe with relay output E Adjustable from 50 to 300 °C
E Back and side cable input
E Sensitive probe with 1 m of stainless steel capillary
piping
E Resistant to heat, grease and humidity
E Easy installation
E Easy connection
E Easy maintenance
E Potenial free alarm relay output
Door Magnets
Page : 101

Electronic delay control for double-leaf fire doors CR255

The CR255 is an electronic delay control unit for use with double-leaf
fire doors. It allows for the release of the one leaf of the fire door to be
slightly delayed to allow for the two leafs to close properly and in the
correct sequence.

Ordering Information

CR255 Electronic delay control for double-leaf fire doors

E Easy to install
E May be installed inside the door release magnet
housing
E 24 VDC operation
Content

NKB602 Conventional fire alarm panel with 2 zones Page : 3


NKB604 Conventional fire alarm panel with 4 zones Page : 4
NKB606 Conventional fire alarm panel with 6 zones Page : 5
NK702 Conventional fire panel with 2 fire alarm zones Page : 6
NK704 Conventional fire panel with 4 fire alarm zones Page : 7
NK708 Conventional fire panel with 8 fire alarm zones Page : 8
NK712 Conventional fire panel with 12 fire alarm zones Page : 9
NK716 Conventional fire panel with 16 fire alarm zones Page : 10
NK703 Conventional extinguishing control panel with 3 zones Page : 11
NK706 Conventional extinguishing control panel with 6 zones Page : 12
RB404 Relay module, 4 potential free relays for NK700/Fx400 fire panels Page : 13
SB404 Relay module, 4 supervised relays for NK700/Fx400 fire panels Page : 14
EOL-ACT Active end-of-line device for use with FP400/KL700 fire panels Page : 15
KLBlack-S Black front panel cover (small footprint) Page : 16
KLBlack-B Black front panel cover (large footprint) Page : 16
KSA701-1 Analogue addressable fire detection panel - 1 loop Page : 17
KSA701-2 Analogue addressable fire detection panel - 2 loops Page : 18
NC785 RS485 expansion kit for KSA701/FP1500 fire panels Page : 19
KSA701R KSA701 Series LCD Repeater (mains powered) Page : 20
KSA701R-24 KSA701 Series LCD Repeater (24VDC powered) Page : 21
KSA705 Analogue addressable fire panel (expandable to 5 loops) Page : 22
KSA705P Analogue addressable fire panel with printer (expandable to 5 loops) Page : 23
KAL701 Loop driver module for KSA702/705 control panels Page : 24
KAL732 RS232 communications module for KSA702/5 control panels Page : 24
KAL785 RS485 communications module for KSA702/5 control panels Page : 25
KAL791 Protocol Converter RS232/485 - Kilsen / Johnsson Control Page : 25
KSA1204 Analogue fire panel, 2 loops upgradable to 4, 64 display zones Page : 26
KSA1208 Addressable fire panel, 2-8 loops, 64-255 display zones upgradable Page : 27
KSA1264R Repeater / emulator with 64 zone indications Page : 28
KSA12255R Global zone repeater, 64 zones expandable up to 255 Page : 29
LC1502 2-loop extension board for 1200/2000 series fire panels Page : 30
LON2000 LON700 driver for FP1200 / FP2000 Page : 30
LON2000R LON driver for FP1200/2000 - closed loop systems Page : 31
NC2011 ARCNET RS485 network card with single RS485 interface Page : 31
NC2051 ARCNET network card with single optical interface board Page : 32
NE2011 RS485 network extension board Page : 32
NE2051 Fibre optic network extension board Page : 33
PR2000 Internal printer Page : 33
RB2016 Relay extension board for 1200/2000 series fire panels Page : 34
ZE2064 64-zone LED extension fire and fault LED Page : 34
FRL700 LCD repeater Page : 35
NA704 LON700 network amplifier (4 way) Page : 36
NC700 LON700 interface board Page : 36
NC771 LON700 closed loop communication board (no driver) Page : 37
NE771 LON700 driver for the NC771 and NA704 Page : 37
OCB724 LON700 output board with 24 open collector outputs Page : 38
PS700 Plug-in power supply 3.5 A Page : 38
RB708 LON700 output board with 8 relays Page : 39
SIB716 Supervised input board 16 way LON700 Page : 39
SOB708 LON700 output board with 8 supervised outputs Page : 40
ZI708 8 zone input extension board Page : 40
KM260/1R3-03 CO detection control panel - 1 Zone (English Version) Page : 41
KM260/3R3-03 CO detection control panel - 3 Zones (English Version) Page : 42
KM260EXT3-03 CO detection expansion module (English Version) Page : 43
KM260C Blanking plate for KM260 panels Page : 44
KM170 CO detector with base and mounting supplement Page : 45
KZ400 Detector base for KL400/KM170 series devices Page : 46
S300 Surface mount supplement for KL300/KM170 detectors Page : 46
ASD20C Aspiration Smoke Detector Page : 47
ASD20F Filter housing for ASD20 Page : 48
ASD20FIL Filter only for ASD20 Page : 48
KV210 Rate-of-Rise Heat Detector Page : 49
KV210P Rate-of-Rise Heat Detectors with remote indicator output Page : 50
KL500 Low Profile Ionisation Smoke Detector Page : 51
KZ500 Fire detector base for KL500 detectors Page : 52
KL700 Ionisation detector, conventional Page : 53
KL710 Temperature detector (fixed and rate-of-rise), conventional Page : 54
KL731 Optical detector, conventional (with field exchangeable optical block) Page : 55
KL731B Optical detector, conventional - Black Page : 56
KCT731 Calibration Tool for KL731/DP331I Fire Detectors Page : 57
KL700A Analogue addressable ionisation sensor Page : 58
KL710A Analogue addressable temperature sensor Page : 59
KL731A Analogue addressable optical sensor (with field exchangeable chamber) Page : 60
KL731AB Analogue addressable optical detector - Black Page : 61
KL735A Analogue addressable dual (optical and thermal) sensor Page : 62
PG700 Fire sensor programmer Page : 63
KOB700 Replacement Optical Chamber for KL731/A & DP331I/1561 detectors Page : 64
KL7A Dust Protector Cover for KL700/A and Dx300/1500 detectors Page : 64
KZ700 Universal fire detector base Page : 65
KZ700B Universal fire detector base (for KL700/A and Dx300/1500) - Black Page : 66
KZ705 Universal fire detector base with earth connection Page : 67
S700 Surface mount accessory for KZ700 and KZ705 series bases Page : 67
KZ705I Analogue fire detector base with isolator Page : 68
KZ705AS Analogue fire detector base with sounder Page : 69
KZ705IAS Analogue fire detector base with isolator and sounder Page : 70
KZ705D Conventional fire detector base with diode Page : 71
KZ705R Conventional 12 VDC fire detector base with relay Page : 71
PA25/3L Low current remote LED indicator Page : 72
KAL410 Conventional Zone Monitor Unit - 1 Zone Page : 73
KAL414C Conventional Zone Monitor Unit - 4 Zones Page : 74
KAL426C Extinguishing Control Module Page : 75
KAL430 Relay Module - 1 Relay Page : 76
KAL434C Addressable Relay Module - 4 Relays Page : 77
KAL440 Supervised Relay Module Page : 78
KAL450 Addressable Manual Call Point Page : 79
DM715 EN54 universal glass for manual call point Page : 80
DM782 Hinged transparent MCP protection cover Page : 80
DM787 Surface mounting box with connectors, red Page : 81
KAL460 Digital Input Module Page : 82
KAL470 Isolator Module Page : 83
KAL490 Retention Module - 1 Input / 1 Output Page : 84
SK07A Addressable loop powered siren Page : 85
KR24B Illuminated warning sign (No text) 24VDC Page : 86
KR24-ING Illuminated extinguishing waring sign (English version) 24VDC Page : 87
SK07 Low consumption multi-tone alarm siren Page : 88
PCC-Config KSA701/FP1500 Configuration software kit Page : 89
PCG-Graphic102 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-2 loops) Page : 90
PCG-Graphic105 Graphic Software for KSA700/FP1500 Fire Systems (1 panel-5 loops) Page : 91
PCG-GraphicNW Graphic Software for KSA700/FP1500 Fire Systems (multi-panel) Page : 92
KSP700 KSA702/5 Configuration software kit Page : 93
KSP701 PC Configuration RS232 Cable for KSA701/FP1500 fire panels Page : 94
PCC2000 Programming and configuration software Page : 95
PCG-N Graphics package network application with copy protection key Page : 96
PCG-S Graphics package with copy protection key Page : 97
PCM2000 Maintenance and support software with copy protection key Page : 98
ST801 High Temperature Thermal Probe with 2 wire connection Page : 99
ST802 High Temperature Thermal Probe with relay output Page : 100
CR255 Electronic delay control for double-leaf fire doors Page : 101
www.gesecurity.net IPSCAT-2005-12-6 16:09:40