DSE4310/20 ENVIRONMENTAL TESTING STANDARDS

AUTO START AND AUTO MAINS FAILURE ELECTRO-MAGNETIC COMPATIBILITY

CONTROL MODULES BS EN 61000-6-2


EMC Generic Immunity Standard for
the Industrial Environment
FEATURES BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment

The DSE4310 Auto Start Control Electronic J1939 (CAN) and non- ELECTRICAL SAFETY

Module and the DSE4320 Auto electronic (alternator sensing) *AVAILABLE VARIANTS BS EN 60950
Safety of Information Technology Equipment,
Mains (Utility) Failure Control engine support for diesel, gas and 4310-01 Auto Start including Electrical Business Equipment
Module are suitable for a wide petrol engines all in one variant. TEMPERATURE
4310-02 Auto Start with current measurement
variety of single gen-set With a number of flexible inputs, BS EN 60068-2-1
o
applications. outputs and protections, the 4320-01 Auto Mains Failure Ab/Ae Cold Test -30 C
BS EN 60068-2-2
modules can be easily adapted to Bb/Be Dry Heat +70 oC
4320-02 Auto Mains Failure with current
Whilst maintaining functions suit a wide range of applications measurement
VIBRATION
included within higher end including lighting towers with the BS EN 60068-2-6
controllers, such as generator or added option for staged loading Ten sweeps in each of three
load power monitoring, the outputs. major axes
5 Hz to 8 Hz @ +/-7.5 mm,
DSE43xx range of especially 8 Hz to 500 Hz @ 2 gn
compact controllers provide the Through USB Communication both
HUMIDITY
user with the ultimate size to modules can be easily configured BS EN 60068-2-30
feature ratio. using the DSE Configuration Suite Db Damp Heat Cyclic 20/55 oC
PC Software or can be fully @ 95% RH 48 Hours
BS EN 60068-2-78
Monitoring engine speed, oil configured through the module's Cab Damp Heat Static 40 oC
pressure, coolant temperature, front panel editor. @ 93% RH 48 Hours
frequency, voltage, current, power SHOCK
and fuel level, the modules will give All DSE products are supported by BS EN 60068-2-27
comprehensive engine and the DSE global technical support Three shocks in each of three major axes
15 gn in 11 mS
alternator protection. This will be team which gives our customers
indicated on the largest back-lit and end users access to 24 hour DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
LCD icon display in its class via an system help and advice. BS EN 60529
array of warning, electrical trip and IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
shutdown alarms.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
PC

4 4 3

USB CONFIGURABLE DC OUTPUT ANALOGUE SENDERS DC POWER


PORT INPUTS (2 for DSE4310) SUPPLY

DEUTZ
DSE4310/20 ISUZU
PERKINS
CATERPILLAR
MTU
7

OTHER
*SEE AVAILABLE VARIANTS ABOVE VOLVO
CUMMINS
SCANIA

MAINS (UTILITY) DC OUTPUT GENERATOR / DC OUTPUT GENERATOR CHARGE FUEL AND START ELECTRONIC
SENSING 4320 1 OF 4 LOAD CURRENT 4310 1 OF 2 SENSING ALTERNATOR OUTPUTS ENGINE CAN
(DSE4320) 4320 1 OF 4 (Flexible with CAN)

VOLTS
VOLTS D+ +
+ + W/L

1ph 1 1ph 1 1ph


N N

ISSUE 1
®

DSEGenset

DSE4310/20 SPECIFICATION

AUTO START AND AUTO MAINS FAILURE DC SUPPLY


CONTINUOUS VOLTAGE RATING

CONTROL MODULES 8 V to 35 V Continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
FEATURES supply recovers to 5 V. This is achieved
without the need for internal batteries.
DSE4320 LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


85 mA at 12 V, 96 mA at 24 V

MAXIMUM STANDBY CURRENT


DSE4310 51 mA at 12 V, 47 mA at 24 V

MAXIMUM SLEEP CURRENT


35 mA at 12 V, 32 mA at 24 V

MAXIMUM DEEP SLEEP CURRENT


<10 uA at 12 V, <10 uA at 24 V

MAINS (UTILITY) DSE4320 ONLY


VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage

OUTPUT B (START)
KEY BENEFITS • IP65 rating (with optional • 4 configurable DC outputs (2 for 10 A short term, 5 A continuous,
• Ultimate size to feature ratio gasket) offers increased DSE4310) at supply voltage
• Automatically transfers between resistance to water ingress • 3 configurable analogue/digital AUXILIARY OUTPUTS C & D
mains (utility) and generator inputs 2 A DC at supply voltage
(DSE4320 only) KEY FEATURES • 4 configurable digital inputs
AUXILIARY OUTPUTS E & F DSE4320
• Hours counter provides accurate • Largest back-lit icon display in • Configurable staged loading 2 A DC at supply voltage
information for monitoring and its class outputs
maintenance periods • Current sensing options • CAN and alternator speed GENERATOR
VOLTAGE RANGE
• User-friendly set-up and button available sensing in one variant 15 V to 415 V AC (Ph to N)
layout for ease of use • Fully configurable via the fascia • 3 engine maintainance alarms 26 V to 719 V AC (Ph to Ph)
• Multiple parameters are or PC using USB • Engine speed protection
FREQUENCY RANGE
monitored simultaneously which communication • Engine hours counter 3.5 Hz to 75 Hz
are clearly displayed on the • Extremely efficient power save • Engine pre-heat
largest back-lit icon display in mode • Engine run-time scheduler DIMENSIONS
OVERALL
its class • Single phase generator sensing • Engine idle control for starting & 140 mm x 113 mm x 43 mm
• The module can be configured • Single phase mains (utility) stopping 5.5’’ x 4.4” x 1.7”
to suit a wide range of sensing (DSE4320 only) • Battery voltage monitoring
PANEL CUT-OUT
applications • Compatible with 600 V ph - ph • Start on low battery voltage 118 mm x 92 mm
• Compatible with a wide range nominal systems • Configurable remote start input 4.6’’ x 3.6”
of CAN engines, including tier 4 • Generator/load power • 1 alternative configuration
MAXIMUM PANEL THICKNESS
engine support monitoring (kW, kV A, kV Ar, pf) • Comprehensive warning, 8 mm
• Uses DSE Configuration Suite • Generator overload protection electrical trip or shutdown 0.3”
PC Software for simplified (kW) protection upon fault condition
STORAGE TEMPERATURE RANGE
configuration • Generator/load current • LCD alarm indication -40°C to +85°C
• Licence-free PC software monitoring and protection • Event log (15)
• Fuel and start outputs OPERATING TEMPERATURE RANGE
-30°C to +70°C
(configurable when using CAN) -40°C to +70°C (for heated display variant)

RELATED MATERIALS
TITLE PART NO’S OPTIONAL PARTS
DSE4310/20 Installation Instructions 053-158 PART PART NUMBER
DSE4310/20 Operator Manual 057-177 IP65 Gasket 020-282
DSE4310/20 Configuration Suite PC Manual 057-178

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-154/01/16 (4) US
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457

You might also like