Brief Overview
t 6X
IL1
I >> t o >>
t >> I S >>
I << t Start d
t << t Stall
IB e
t CT
I o >> SW
f
g
IL2
Figure 1: Front panel overview
Symbols
a – Run LED
a) Run LED
2 I>> Short circuit
Run LED shows the motor status. Refer to 3.2.1 Motor
Starting.
3 t>> Short circuit delay time
Off Motor stopping
Blink Motor starting 4 I<< Undercurrent
On Motor running
5 t<< Undercurrent delay time
b) Trip LED
6 Unbalance
Trip LED is normally off. During tripping pickup, where
tripping delay is counting down, Trip LED blinks. Trip
LED on during tripping. 7 t Unbalance delay time
Off Normal
Blink Pickup 8 I0 >> Earth fault
On Tripping
9 t0 >> Earth fault delay time
c) Thermal LED
A IS >> Prolonged starting / stalled rotor
Thermal LED blinks when motor current is more than
105% of IB. Thermal LED on during thermal overload
b t Start >> Prolonged starting delay time
tripping, and when thermal capacity is more than 40%
after overload tripping (in which R1 is off, motor not
allowed to start) c t Stall >> Stalled rotor delay time
Off Normal
Blink Thermal overload warning d IB Base/full load current
On Thermal overload tripping
Thermal capacity high, R1 off
E External CT ratio
2
3.2 Programming Setting
Step 1: Press "RESET/MODE" until the Function LED shows the required setting.
Step 4: To save the new value, press "UP" and "DOWN" simultaneously again. Programming mode exits,
function LED stop blinking.
Run LED shows the motor status. Upon power on the Imax is the maximum phase current among the 3 phases.
relay, if there is no tripping, Relay 1 turns on. Imin is the minimum phase current among the 3 phases.
If motor current is more than 1.1 x IB, motor is Tripping takes place when unbalance value is more than
considered starting, Run LED blinks. If motor current is unbalance setting % for longer than unbalance delay. It
less than 1.05 x IB, motor is running, Run LED on. Motor can be disabled by setting unbalance delay to 'off'.
is stopping when motor current drops below 0.1 x IB.
Figure 4: Thermal tripping curve
If motor starts abnormally for longer than 60s, Run LED
stops blinking and turns off, Relay 1 also turns off. This
condition reset when motor current drops below 0.1 x IB. time
2hour
3.2.2 Thermal Overload
1hour
The protection is based on mathematical model of motor
thermal image. The thermal capacity is calculated 30min
continuously when motor is starting, overloading or even 20min
after tripping. Tripping takes place when the thermal 10min
capacity of the motor reaches 100%. This could happen
when the motor current is higher than 1.05 x IB. After 5min
tripping a new start is not allowed until the motor cools 3min
down to less than 40% of thermal capacity. Thermal 2min
capacity can be cleared to 0% by pressing "UP" and t6x
"DOWN" simultaneously for longer than 1.5 seconds 1min
during thermal capacity display. 40s 40s
30s 30s
Warning: Clearing thermal capacity effectively reset 20s 20s
to cold start condition, user is not encouraged to 10s 10s
clear thermal capacity until motor is cool enough to
start/run within its thermal limit. 5s 5s
3s
2s 2s
3.2.3 t6X Thermal overload Time Constant 1.05
1s 1s
t6X sets the themal overload time constant (heating 1 2 5 6
3 4
constant), which is the maximum period of time when I/IB
motor current is allowed to reach a 6 x IB. Cooling (a) With 0% thermal capacity (cold start)
constant time is defined as 4 times of heating constant
time and is applicable when motor current is less than time
0.2 x IB. Refer to the thermal tripping curve on Figure 4.
2hour
3.2.4 Short Circuit
1hour
4
3.2.7 Phase Loss 3.2.12 External CT Ratio
Phase loss fault is detected when average motor current The CT ratio shall be set accordingly for the display to
is larger than 0.28 x IB but any phase current is less than show primary current. For example when using 150/5
0.1 x IB. Tripping takes place in less than 120ms when CT, set the value to:
phase loss is detected.
150
External CT ratio = = 30
3.2.8 Phase Sequence 5
Phase sequence fault is detected when the phase 3.2.13 Manual or Auto Reset
sequence in any 2 or all the phases are reversed.
Tripping takes place in less than 120ms when phase The relay can be set to manual or auto reset when the
sequence fault is detected. relay trips. Resetting of relay is allowed when the tripping
condition cleared. Manual reset is performed by pressing
Phase loss and phase sequence protection can be the "RESET/MODE" (or using binary input if it is
enabled and disabled separately. Refer to 3.2.16 Phase configured as 1 - Reset trip). Thermal overload is always
sequence / phase loss option auto reset.
For prolonged starting and stalled rotor there is one IS>> The binary input is a dry contact input that can be
setting and separate delay time setting for each configured to perform various functions.
protection. IS>> shall be set below the motor starting/ 0 - Block relay 1
stalled current. These protections are useful when The input, when triggered, will force relay 1 off.
thermal overload protection is not fast enough to protect
1 - Reset tripping
the motor during stalling.
The input is used to manually reset a tripping.
Delay time for prolonged starting, tStart>> shall be set 2 - Instant tripping
longer than specified motor starting time. Tripping takes The input will generate a tripping condition. Refer to
place when any phase current is larger than IS> for 4.4 Binary Input Tripping.
longer than tStart during motor starting.
3.2.15 Relay 2
Delay time for stalled rotor, tStall>> is activated upon
completing the motor starting. Tripping occurs when any The relay 2 output can be configured to turn on in these
phase current is larger than IS>> for longer than tStall>> conditions:
during motor running. 0 - On any tripping
Relay 2 on during any tripping.
Both protections can be disabled by setting IS>> to 'off'. 1 - On thermal tripping
To disable only one of the protection, set the respective Relay 2 on during thermal tripping only.
delay time for the protection to be disabled to much
2 - On thermal warning
longer than specified.
Relay 2 on when motor current is more than 1.05 x IB.
3.2.10 Earth Fault
3.2.16 Phase sequence / phase loss option
Earth fault protection is based on zero sequence current
Phase sequence and phase loss detection can be on
calculation. Tripping takes place when the current is
(enabled) and off (disabled) separately.
larger than earth fault setting in % of IB for longer than
t0>. It can be disabled by setting t0>> to 'off'.
0 - Phase sequence and phase loss off
1 - Phase sequence on
3.2.11 Base Current
2 - Phase loss on
3 - Phase sequence and phase loss on
Base current is the motor full load current. The range of
setting is model dependent.
3.2.17 Frequency
The formula is:
Nominal value of the network frequency. Select either 50
1 or 60 Hz.
IB = Motor full load current X
CT ratio
For example to use the relay with motor that has full load
current of 138A, using external CT of 150/5,
5
IB = 138 X = 4.6A
150
5
4. Tripping
4.1 Tripping Display 4.2 Tripping Reset
During tripping, Trip LED on, Thermal LED also on During tripping condition, press "RESET/MODE" to
during thermal overload tripping. Function LED and Data reset, the relay will reset if condition permits. If relay is
LED blinks showing tripping current or source as shown set to auto reset, the relay will reset automatically if the
below: tripping condition is cleared with a 5% hysteresis.
Trip LED Thermal Function Data LED Description 4.3 Tripping Test
LED LED
On On t oL Thermal Overload Press and hold "TEST" for 3.5 seconds to simulate a
tripping tripping condition, Trip LED blinks when "TEST" is
On Off 2 tripping current Short circuit tripping pressed. During Test Tripping, "tESt" blinks, R1 off and
On Off 4 tripping current Undercurrent tripping R2 on if set to "On any tripping". Press "RESET/MODE"
to reset. Tripping Test is disabled when motor is
On Off 6 Ub Unbalance tripping
starting/running.
On Off 6 PS Phase sequence error
tripping
4.4 Binary Input Tripping
On Off 6 PL Phase loss tripping
On Off 8 tripping current Earth fault tripping When Binary input is set to 2 - Instant tripping, binary
On Off A tripping current Prolonged input will generate a tripping condition. "triP" will blink,
starting/Stalled rotor R1 off and R2 on if set to "On any tripping". Press
tripping "RESET/MODE" to reset. If relay is set to auto reset, the
On On t ESt Trip Test relay will reset after the input is normal for 1s.
On Off t riP Binary input tripping
4.5 Tripping History Display
Table 2: Tripping display
During Current/Thermal display, press "RESET/MODE"
to jump to Tripping History Display. Display shows the
previous tripping status with a 'dot' blinking at Function
LED. To clear tripping history, press "UP" and "DOWN"
simultaneously.
5. Typical Application Diagram
L3 L2 L1 L F2
F4
F1 F2 F3 F1
NO 11 3 NO
11 3
NC 12 4 NC S2
12 4 S2
R1 Stop R1 Stop
COM 13 COM
13 5 5
COM COM
14 6 S1 14 6 S1
R2
Start K1 R2
Start K1
15 7 NC 15 7 NC
Binary Binary
input NO input NO
16 8 16 8
M H1 K1 M H1 K1
Block R1/
Block R1/
Reset/
Reset/
Trip
Trip N N
6
6. Techinical Data
SETTING RANGES
Thermal Overload time constant, t6X : 1 – 40s. In steps of 0.1s for 1-10s, in steps of 1s for 10-40s
Short circuit, I>> : off, 2 – 12 x IB. In steps of 1 x IB
Short circuit delay time, t>> : 0 – 25s. In steps of 0.1s for 1-10s, in steps of 1s for 10-25s
Undercurrent, I<< : off, 20 – 90% of IB. In steps of 1%
Undercurrent delay time, t<< : 0 – 60s. In steps of 0.1s for 1-10s, in steps of 1s for 10-60s
Unbalance, : off, 10 – 50%. In steps of 1%
Unbalance delay time, t : 0 – 25s. In steps of 0.1s for 1-10s, in steps of 1s for 10-25s
Earth fault, I0>> : off, 10 – 60% of IB. In steps of 1%
Earth fault delay time, t0>> : 0 – 25s. In steps of 0.1s for 1-10s, in steps of 1s for 10-25s
Phass loss : <120ms
Phase sequence : <120ms
Prolonged starting/stalled rotor, IS : off, 2 – 12 x IB. In steps of 0.1 x IB
Prolonged starting delay time, tStart : 0 – 60s. In steps of 0.1s for 1-10s, in steps of 1s for 10-60s
Stalled rotor delay time, tStall : 0 – 60s. In steps of 0.1s for 1-10s, in steps of 1s for 10-60s
CT RATINGS
AUXILIARY SUPPLY
110 ~ 370 V DC Fr o n t
Supply frequency : 50 or 60 Hz
Maximum power consumption : 3 VA typical
CONTACTS
INDICATORS
MECHANICAL