Checklist-Quality Form-.Q.R 7.3.1of2
Checklist-Quality Form-.Q.R 7.3.1of2
1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 1 of 27
Sections
Table of Contents................................................................................................................................. 1
Introduction.........................................................................................................................................2
Quality and Technical Checklist...........................................................................................................2
General Items....................................................................................................................................2
Administration..................................................................................................................................4
Civil...................................................................................................................................................4
Landscape.........................................................................................................................................5
Structural..........................................................................................................................................6
Architectural......................................................................................................................................7
Mechanical.....................................................................................................................................10
Electrical..........................................................................................................................................10
Telecommunication........................................................................................................................11
Inter Disciplines...............................................................................................................................11
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 2 of 27
INTRODUCTION
This document outlines the technical and quality checklists to be used during design control and
engineering review for DAAR projects. In addition to the contract requirements, these checklists
addresses the need to verify the information contained related to the design of DAAR
residential/commercial projects, facilities and structures.
By having design controls in place in the procedures, the chances of errors and design failures
are minimized, which would prevent damage to property or loss of life, help maintain credibility
and reputation, potentially save money, and minimize liability.
The development of design and selection of construction methods and materials shall proceed
to meet the design objectives, to include: feasibility, constructability, reliability, operability, and
maintainability, sustainability, occupant and building safety, flexibility for future changes,
durability, less redundancy, resource availability, timely delivery of customer/market
requirements of performance, convenience, quality, and aesthetics at the lowest overall cost.
Good design is achieved by appropriately balancing the fundamental design objectives.
Compliance with the standards and guidelines alone does not guarantee good design.
Administration
1. Verify Coversheet information and spelling corresponds to
project brief/manual.
2. Verify stamping and signing of consultant’s document
3. Verify index sheet corresponds to drawings and titles.
4. Verify Abbreviations and symbols correspond with
abbreviations and symbols in the documents.
5. Verify conformance of building codes, life safety, fire
protection, zoning, Civil Defense or other governmental
authority. Obtain written approval for any variance
Civil
1. Verify existing conditions with owner furnished information, i.e.,
surveys, topographies, zoning, utilities, easements, etc.
2. Verify that existing to remain power/telephone poles, pole
guys, drainage inlets, manholes, valve boxes, street signs, etc.;
do not interfere with new site improvements or landscaping.
3. Verify that the new power/telephone utilities, grease traps, fuel
tanks, etc., do not interfere with new site improvements,
existing conditions or landscaping.
4. Verify site limits of construction, i.e., clearing, grading,
landscaping, utilities, building, etc.
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 5 of 27
Landscape
1. Verify that the sprinklers, lighting, hardscape, etc., correspond
with the site limits, including the building and civil plans.
2. Verify that the maintenance and landscape is coordinated in
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 6 of 27
Structural
1. Verify that all structural components, correspond with the site
limits, including the building and civil plans.
2. Verify that the column orientation and gridlines on the
structural and architectural drawings match.
3. Verify that the load bearing walls and the column locations
match with architectural drawings.
4. Verify that the slab elevations match the architectural
drawings.
5. Verify that the depressed or raised slabs are indicated and
match the architectural drawings.
6. Verify that the limits of slabs on the structural drawing match
the architectural drawings.
7. Verify that the expansion joints through the structural
drawings match the architectural drawings.
8. Verify the footings depths and coverage with the existing and
final grades.
9. Verify that foundations piers, footings, grade beams are
coordinated with schedule.
10. Verify that footing and pier locations with the new and existing
utilities, trenches and tanks.
11. Verify the foundations wall elevations match the architectural
drawings.
12. Verify that the locations of floor & roof framing column lines
and column orientation match the foundation plan column
lines and column orientation.
13. Verify that the structural perimeter floor and roof lines match
the architectural drawings.
14. Verify that the section and details callouts are proper and
cross-referenced.
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 7 of 27
Architectural
1. Verify site property lines and existing conditions match with
survey or civil.
2. Verify building location meets all set back requirements,
zoning codes, and deed restrictions.
3. Verify building limits match with civil, plumbing and electrical
on site plans.
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 8 of 27
Mechanical
1. Mechanical plans match architectural and reflected ceiling
plans.
2. HVAC ducts are commensurate with architectural space and
not in conflict with conduit, piping, etc.
3. Mechanical equipment fits architectural space with room for
access, safety and maintenance.
4. Verify mechanical openings match architectural and structural
and do not clash with electrical and other equipment
5. Verify spacing and clearances meet National & International
Standards (or NFPA) standards for Fire Protection
6. Verify piping isometric, schematic drawings, ducting plans,
duct supports, air flow diagrams, plumbing systems, vent
risers, equipment schedule and material take-off are correct,
adequate and conform to specifications and standards.
7. Verify mechanical engineering calculations is in accordance
with the latest applicable codes and correct supported by
calculations and design analysis reports
Electrical
1. Electrical plans match architectural and reflected ceiling
plans.
2. Verify circuit breakers, one-line diagram, cable and conduits
schedules, equipment ratings, control devices, spare capacity
and spare breakers are adequate and correct
3. Verify relays, switches, wire identifications and equipments
are shown, identified and matches with other drawings
4. Verify phase loads are balanced, total-load demand are
correct and conduit routing is optimum and without
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 11 of 27
Telecommunication
1. Telecommunication, low voltage electronic systems and fire
alarm plans match architectural and reflected ceiling plans.
2. Verify cable trays, cable conduit runs and outlet locations are
optimum and coordinated
3. Verify grounding systems, ground wire, and bus bar are sized
correctly
4. Verify conduits, pull boxes are sized correctly and conduit
type is suitable for the specified location
Inter Disciplines
A. Code research.
a) Code research report
b) Travel distances
c) Exit widths
d) Stair widths.
e) Guard rail compliance
f) Handrail compliance
g) Handicapped requirements
i. Toilets stalls
ii. Toilet turn around
iii. Toilet entrance doors and circulation
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 12 of 27
G. Ceilings
a) Type of ceilings used.
i. Wet areas
ii. Circulation and assembly areas (type)
iii. Office and similar areas (type)
iv. Toilets – accessibility to valves
v. Rated assemblies – do they meet code
b) Ceiling mounted mechanical, electrical and
plumbing devices – show and dimension
locations
i. Diffusers
ii. Return air grilles
iii. Slot diffusers – coordinate length shown
with length provided by mechanical
c) Ceiling shapes, sizes, proportions at plaster
and dry wall.
d) Soffit perimeter drip joints
e) Ceiling height changes shown
f) Condition at soffit and wall perimeters
(thermal movements)
g) Exterior ceiling material types are noted and
extent is clear
h) Ceiling access panels shown and sized
i) Details are referenced for all conditions
Form: QR 7.3.1/2
Rev. : A
Quality and Technical Checklist for Design Control Issued by: QMR
Page 16 of 27
Checked by:
Name, Sign & Date Name, Sign & Date Name, Sign & Date Name, Sign & Date Name, Sign & Date Name, Sign & Date