DESIGN CALCULATION
FOR
160 KLD STP (MBBR TECH.)
FOR
GE (U) WATER SUPPLY
NARAINA
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10-2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
1 INTRODUCTION 3
2 GEOMETRY DESCRIPTION 3
3 DESIGN BASIS 3
4 DESIGN INPUTS 4
6 APPENDICES 5
APPENDIX IV: Design Calcutaion for Rectangular MS Tank (Final Filter Feed Tank)
1.0 INTRODUCTION
The proposed SewageTreatment Plant includes 3 underground circular concrete tanks,and others
are steel tanks those are rest on ground.
It includes 1 raw sewage sump tank of size of diameter 6.0m x 4.0m deep which collects the sewage
sump. Then the filtered through screen chamber and oil & grease chamber. After this the fluid is
transferred to a equilization tank of size of diameter 5.0m x 2.9m deep. At final stage after all
treatment process finished the water is collected at Treated water tank of size of diameter 4.0m x
2.5m deep, 1
Clear Max Water Depth in tank = 2.6m with free board of 300mm.
Raw sewage sump Tank Dimension = 6.0m Dia with 4.0m height
Clear Max Water Depth in tank = 1.8m with free board of 2200mm.
Clear Max Water Depth in tank = 2.0m with free board of 500mm.
Steel Tank sizes are L W H
Anoxix Tank 2.12 2.20 3.50
MBBR-1 2.00 2.20 3.50
MBBR-2 2.00 2.20 3.50
Tube Settler 2.28 2.20 3.50
Chlorine Contact Tank 5.50 2.20 3.50
Load Combinations
Load combinations considering for design of Tanks are taken as per IS 3370 Part 2 - 2021.
6.0 APPENDICES
APPENDIX I: Design Calcutaion for Raw Sewage Sump Tank (67 Pages)
APPENDIX IV: Design Calcutaion for Rectangular MS Tank (Final Filter Feed Tank)
APPENDIX - I
APPENDIX - II
APPENDIX - III
Design Calcutaion for
Treated Water Tank
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10-2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
APPENDIX - IV
Design Calcutaion for
Rectangular MS Tank (Final
Filter Feed Tank)
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10-2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
APPENDIX - V
Design Calcutaion for
Rectangular MS Tank
(Sludge Holding Tank)
QUANTITY ESTIMATION
RCC M30
#REF!
TOTAL #REF!
PCC 1:4:8 with 40mm coarse aggregate 0.1
#REF!
EXCAVATION 0.3 3
#REF!
#REF!
CURVED SHUTTERING
#REF!
PLAIN SHUTTERING
#REF!
#REF!
#REF!
wall 3 #REF! #REF!
vertical joint 3 5.45 16.35
sump wall 2 15.05 30.10
vertical joint 2 3 6.00
#REF!
#REF!
39 39
19 19
58
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
ɸ6
4.2 1.8
Plan Elevation
Dimension Inputs
Total depth H = 4m
Grade of concrete M = 25
Case 1: Empty Tank (No water inside only earth pressure from outside)
0.2 F
GL
Surchar
h 4. ge
Earth
= 35 Pressur
e h/ h/
2
3
t
Bending Moment due to triangular load in cylindrical wall per unit height, MEarth▲
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 4 - Moment Coefficient for case 1
(Case 1 - Cylindrical wall, Fixed base, Free top and subject to Triangular load.)
Cover to thickness ratio, d'/t = 0.87
H /Dt
2
= 8.89
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
0.2 FGL
Interpolation
H2/Dt Coefficient
h = 4.35 8.00 -0.0146
Earth
Pressure 10.00 -0.0122
h/3 8.89 -0.014
ws
0.2 FGL
Interpolation
H /Dt Coefficient
2
h = 4.35 Surchar
ge 8.00 -0.0184
10.00 -0.0147
h/ 8.89 -0.017
2
Minimum required effective thickness will be, teff = sqrt[Mu / (0.36 fck b)]
teff = 50.97 mm
b
Applied Maximum Moment, Mcr = 15.59 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
acr c =cr 81.983 mm
2 2 2
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
1000h x =
2
2 0.0007
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
Case 2: Full Tank with water (No earth pressure from outside)
D
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
D
R Interpolation
H /Dt Coefficient
2
8.00 -0.0146
H 10.00 -0.0122
8.89 -0.014
t = 300 mm
water side
Minimum Steel Area as per IS 3370 part 2 (2021) = AMIN = 0.12% Ac = 360 mm2
As thickness is equal or more than 300mm as per Cl 8.1.1 & 8.1.2 (Ref. Table 5)
Required Steel Area, A required = Max(AMIN , AT ) = 586 mm2
b
Applied Maximum Moment, Mcr = 0.79 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
=cr 81.983 mm
acr c
2 2 2
Percentage of Reinforcement provided, pt = 0.31 %
Depth of Neutral Axis, from the method of transformed section,
bx2/2 = m*As*(d-x)
Quadratic Equation bx2/2 + m*As*x - m*As*d = 0
x =[-m*Ast+sqrt((m*Ast)^2-4*b/2*(m*Ast))/(2*b/2 = 80.6 mm
Lever Arm, z = d - x / 3 = 215 mm
Reinforcement Stress, fs = Mcr / As.z = 4.86 N/mm2
1000h x =
2
2 0.0007
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
3.acr . m
Calculated Crack Width, wcr = 0.111 mm
acr c
1 2.
(referhEq. 7x ofAnnex B of IS 3370 Part 2 - 2021)
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 3 - Ring Tension Coefficients for Case 1 Arrangement
(Case 1 - Cylindrical wall, Fixed base, Free top and subject to Triangular load.)
Interpolation
H /Dt Coefficient
2
8.00 0.575
10.00 0.608
8.89 0.590
Positive sign indicates tension in the outside.
Coefficient at point 0.6H = 2.4m from top Ftc = 0.590
(for triangular loading)
Hoop Tension in wall, Ft =Ftc x w x H x (D + t)/2 = 33.43 kN/m
Refer Cl 3.1.1 of IS 3370 (Part 4/Sec 3) : 2021 (for triangular loading)
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
acr c =cr 105 mm
2 2 2
Strain at level considered, ε1 = 0.5 * fy / Es = 0.0013
(refer B-4 of Annex B of IS 3370 Part 2 - 2021)
Refer of Annex B of IS 3370 Part 2
Stress due to stiffening effect of concrete between cracks,
= 0.0008
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 18 - Shear at base of cylindrical wall
Interpolation
H2/Dt Coefficient
8.00 0.174
10.00 0.158
8.89 0.167
Positive sign indicates tension in the outside.
Coefficient for Shear at base due to triangular loading, Vc = 0.167
(for triangular loading)
Shear at base V = Vc x w x H 2 = 26.70 kN/m
(for triangular loading)
where,
Design direct tension, Pu = 33434 N
Gross cross-sectional area of concrete, Ag = 300000 mm2
Case 1: Empty Tank (No water inside only earth pressure from outside)
Case 2: Full Tank with water (No earth pressure from outside)
Bending Moment in circular slab per unit height
Refer IS 3370 (Part 4/Sec 3) : 2021 Table 2 Loading Config. and End-Restraint Conditions for Circular Slabs
Case 8: Fixed base, without centre support, subjected to uniformly distributed loading
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
Max. of Design Bending Moment at Edge from case 1 & 2 Medge = 55.96 kNm
Maximum Design Bending Moment at Edge Mu = 1.5M = 83.93 kNm
Mu/bd^2 = 0.984 N/mm2
Required, Ast = 100/2*fy/fck * sqrt (1 - sqrt (4.6*Mu/(bd^2*fck)))*d = 553.3 mm2
water side
t = 350 mm
bottom
Minimum Steel Area as per IS 3370 part 2 (2021) = AMIN = 0.12% Ac = 420 mm2
As thickness is equal or more than 300mm as per Cl 8.1.1 & 8.1.2 (Refer Table 5)
Required Steel Area, A required = Max(AMIN , Ast ) = 553 mm2
Max. of Design Bending Moment at Centre from case 1 & 2 Mmid = 27.98 kNm
Maximum Design Bending Moment at Edge Mu = 1.5M = 41.97 kNm
Mu/bd^2 = 0.492 N/mm2
Ast required = 100/2*fy/fck * sqrt (1 - sqrt (4.6*Mu/(bd^2*fck)))*d = 610.4 mm2
b
Applied Maximum Moment, Mcr = 55.96 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
=cr 81.983 mm
acr c
2 2 2
f s h x = 0.0018
Strain at level considered, 1 .
Es d x
Refer of Annex B of IS 3370 Part 2
Considering the crack-width at the surface remote from the compression face
Stress due to stiffening effect of concrete between cracks,
1000h x =
2
2 0.0008
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
3.acr . m =
Calculated Crack Width, wcr 0.187 mm
acr c
1 2.
(referhEq. 7x ofAnnex B of IS 3370 Part 2 - 2021)
ɸ5
2.9 2.6
Plan Elevation
Dimension Inputs
Grade of concrete M = 25
Case 1: Empty Tank (No water inside only earth pressure from outside)
0.3 FGL
Surcharge
h 2.85
= Earth
Pressure
h/2
h/3
Bending Moment due to triangular load in cylindrical wall per unit height, MEarth▲
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 4 - Moment Coefficient for case 1
(Case 1 - Cylindrical wall, Fixed base, Free top and subject to Triangular load.)
Cover to thickness ratio, d'/t = 0.84
H /Dt
2
= 6.73
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
0.3 FGL
Interpolation
H /Dt Coefficient
2
w
s
0 FGL
.
3
Interpolation
H /Dt Coefficient
2
h = 2.85 Sur
cha 6.00 -0.0242
rge 8.00 -0.0184
h 6.73 -0.022
/
2
Positive sign indicates tension in the outside.
Minimum required effective thickness will be, teff = sqrt[Mu / (0.36 fck b)]
teff = 35.48 mm
b
Applied Maximum Moment, Mcr = 7.55 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
acr c = cr 82.464 mm
2 2 2
1000h x =
2
2 0.0008
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
Case 2: Full Tank with water (No earth pressure from outside)
D
R
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
D
R Interpolation
H /Dt Coefficient
2
6.00 -0.0187
H 8.00 -0.0146
6.73 -0.017
t = 250 mm
water side
b
Applied Maximum Moment, Mcr = 3.02 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
= cr 82.464 mm
acr c
2 2 2
1000h x =
2
2 0.0008
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
3.acr . m
Calculated Crack Width, wcr = 0.101 mm
acr c
1 2.
h x(refer
Eq. 7 of Annex B of IS 3370 Part 2 - 2021)
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 3 - Ring Tension Coefficients for Case 1 Arrangement
(Case 1 - Cylindrical wall, Fixed base, Free top and subject to Triangular load.)
Interpolation
H /Dt Coefficient
2
6.00 0.514
8.00 0.575
6.73 0.536
Positive sign indicates tension in the outside.
Coefficient at point 0.6H = 1.74m from top Ftc = 0.536
(for triangular loading)
Hoop Tension in wall, Ft =Ftc x w x H x (D + t)/2 = 36.60 kN/m
Refer Cl 3.1.1 of IS 3370 (Part 4/Sec 3) : 2021 (for triangular loading)
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
acr c = cr 83 mm
2 2 2
Strain at level considered, ε1 = 0.5 * fy / Es = 0.0013
(refer B-4 of Annex B of IS 3370 Part 2 - 2021)
Refer of Annex B of IS 3370 Part 2
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 18 - Shear at base of cylindrical wall
Interpolation
H2/Dt Coefficient
6.00 0.197
8.00 0.174
6.73 0.189
Positive sign indicates tension in the outside.
Coefficient for Shear at base due to triangular loadin Vc = 0.189
(for triangular loading)
Shear at base V = Vc x w x H 2 = 15.86 kN/m
(for triangular loading)
where,
Design direct tension, Pu = 36596 N
Gross cross-sectional area of concrete, Ag = 250000 mm2
Case 1: Empty Tank (No water inside only earth pressure from outside)
Bending Moment in circular slab per unit height
Refer IS 3370 (Part 4/Sec 3) : 2021 Table 2 Loading Config. and End-Restraint Conditions for Circular Slabs
Case 8: Fixed base, without centre support, subjected to uniformly distributed loading
Case 2: Full Tank with water (No earth pressure from outside)
Bending Moment in circular slab per unit height
Refer IS 3370 (Part 4/Sec 3) : 2021 Table 2 Loading Config. and End-Restraint Conditions for Circular Slabs
Case 8: Fixed base, without centre support, subjected to uniformly distributed loading
Max. of Design Bending Moment at Edge from case 1 Medge = 22.96 kNm
Maximum Design Bending Moment at Edge Mu = 1.5M = 34.45 kNm
Mu/bd^2 = 0.906 N/mm2
Required, Ast = 100/2*fy/fck * sqrt (1 - sqrt (4.6*Mu/(bd^2*fck)))*d = 375.0 mm2
water side
t = 250 mm
bottom
b
Applied Maximum Moment, Mcr = 22.96 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
acr c = cr 82.464 mm
2 2 2
1000h x =
2
2 0.0008
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
ɸ4
2.5 2
Plan Elevation
Dimension Inputs
Grade of concrete M = 25
Case 1: Empty Tank (No water inside only earth pressure from outside)
0.5 FGL
Surcharge
h = 2.25
Earth Pressure
h/2
h/3
Bending Moment due to triangular load in cylindrical wall per unit height, MEarth▲
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 4 - Moment Coefficient for case 1
(Case 1 - Cylindrical wall, Fixed base, Free top and subject to Triangular load.)
Cover to thickness ratio, d'/t = 0.84
H /Dt
2
= 6.25
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
0.5 FGL
Interpolation
H /Dt Coefficient
2
w
s
0 FGL
.
5
Interpolation
H /Dt Coefficient
2
h = 2.25 Surc
harg 6.00 -0.0242
e 8.00 -0.0184
h 6.25 -0.023
/
2
Positive sign indicates tension in the outside.
Minimum required effective thickness will be, teff = sqrt[Mu / (0.36 fck b)]
teff = 29.20 mm
b
Applied Maximum Moment, Mcr = 5.12 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
cr =
acr c 82.464 mm
2 2 2
bx2/2 = m*As*(d-x)
Quadratic Equation bx2/2 + m*As*x - m*As*d = 0
x =[-m*Ast+sqrt((m*Ast)^2-4*b/2*(m*Ast))/(2 = 65.8 mm
Lever Arm, z = d - x / 3 = 173 mm
Reinforcement Stress, fs = Mcr / As.z = 56.45 N/mm2
f s h x
Strain at level considered, 1 . = 0.0004
Es d x
Refer of Annex B of IS 3370 Part 2
Considering the crack-width at the surface remote from the compression face
Stress due to stiffening effect of concrete between cracks,
1000h x
2
2 = 0.0008
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
Case 2: Full Tank with water (No earth pressure from outside)
D
R Interpolation
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
R
H2/Dt Coefficient
6.00 -0.0187
H 8.00 -0.0146
6.25 -0.018
t = 250 mm
water side
Minimum Steel Area as per IS 3370 part 2 (2021) = AMIN =0.12% Ac = 300 mm2
As thickness is equal or more than 300mm as per Cl 8.1.1 & 8.1.2 (Ref. Table 5)
Required Steel Area, A required = Max(AMIN , AT ) = 462 mm2
b
Applied Maximum Moment, Mcr = 1.46 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
cr =
acr c 82.464 mm
2 2 2
f s h x = 0.0001
Strain at level considered,
1 .
Es d x
Refer of Annex B of IS 3370 Part 2
Considering the crack-width at the surface remote from the compression face
Stress due to stiffening effect of concrete between cracks,
1000h x
2
2 = 0.0008
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
3.acr . m
Calculated Crack Width, wcr = 0.122 mm
acr c
1 2.
h (refer
x Eq. 7 of Annex B of IS 3370 Part 2 - 2021)
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 3 - Ring Tension Coefficients for Case 1 Arrangement
(Case 1 - Cylindrical wall, Fixed base, Free top and subject to Triangular load.)
Interpolation
H /Dt Coefficient
2
6.00 0.514
8.00 0.575
6.25 0.522
Positive sign indicates tension in the outside.
Coefficient at point 0.6H = 1.5m from top Ftc = 0.522
(for triangular loading)
Hoop Tension in wall, Ft =Ftc x w x H x (D + t)/2 = 22.17 kN/m
Refer Cl 3.1.1 of IS 3370 (Part 4/Sec 3) : 2021 (for triangular loading)
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
cr =
acr c 83 mm
2 2 2
Refer IS 3370 (Part 4/Sec 3) : 2021 - Table 18 - Shear at base of cylindrical wall
Interpolation
H2/Dt Coefficient
6.00 0.197
8.00 0.174
6.25 0.194
Positive sign indicates tension in the outside.
Coefficient for Shear at base due to triangular loading, Vc = 0.194
(for triangular loading)
Shear at base V = Vc x w x H 2 = 12.13 kN/m
(for triangular loading)
where,
Design direct tension, Pu = 22169 N
Gross cross-sectional area of concrete, Ag = 250000 mm2
Case 1: Empty Tank (No water inside only earth pressure from outside)
Bending Moment in circular slab per unit height
Refer IS 3370 (Part 4/Sec 3) : 2021 Table 2 Loading Config. and End-Restraint Conditions for Circular Slabs
Case 8: Fixed base, without centre support, subjected to uniformly distributed loading
Case 2: Full Tank with water (No earth pressure from outside)
Bending Moment in circular slab per unit height
Refer IS 3370 (Part 4/Sec 3) : 2021 Table 2 Loading Config. and End-Restraint Conditions for Circular Slabs
Case 8: Fixed base, without centre support, subjected to uniformly distributed loading
Max. of Design Bending Moment at Edge from case 1 & Medge = 23.32 kNm
Maximum Design Bending Moment at Edge Mu = 1.5M = 34.98 kNm
Mu/bd^2 = 0.920 N/mm2
Required, Ast = 100/2*fy/fck * sqrt (1 - sqrt (4.6*Mu/(bd^2*fck)))*d = 374.0 mm2
water side
t = 250 mm
bottom
Minimum Steel Area as per IS 3370 part 2 (2021) = AMIN =0.12% Ac = 300 mm2
As thickness is equal or more than 300mm as per Cl 8.1.1 & 8.1.2 (Refer Table 5)
Required Steel Area, A required = Max(AMIN , Ast ) = 374 mm2
Edge
10 DIA AT 150 C/C both direction Safe
Ast PROVIDED 0.21 % = 523.60 mm2 per side
Diameter of Bar, fcr = 10 mm
Spacing of Reinforcement, s = 150 mm
Area of Reinforcement, As = 524 mm2
b
Applied Maximum Moment, Mcr = 23.32 kN-m /m
Distance from the point considered at surface from the nearest longitudinal bar,
0.5
s 2 cr
2
cr =
acr c 82.464 mm
2 2 2
1000h x
2
2 = 0.0008
3.E s . As .d x
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
1000h x
Title : DESIGN CALCULATION FOR STP TANKS 2 CALC NO. : MES-W2P-000-01
2
3.E s . As .d x
(refer Eq. 8 of Annex B of IS 3370 Part 2 - 2021)
APPENDIX IV: Design Calcutaion for Rectangular MS Tank (Final Filter Feed Tank)
The most critical tank will be "Chlorine Contact Tank" of Size 5.5x2.2x3.5 m.
Hence, we consider design for most critical tank.
Dimension Inputs
Design Inputs
By principle of superposition, each panel can be considered subject to a uniform and a triangular load
R Reactions kN
5 R5 = 0.5*P4*H4 0.59
h1.100
4 =
Pannel 4
= P4 R4 = 0.5*(P4+P3)*(H4+H3)/217.81
R P4
4
h31.100 Pannel 3
=
R P4 P3 - P4 P3 R3 = 0.5*(P3+P2)*(H3+H2)/221.67
3
h20.650 Pannel 2
= P3 P2 - P3 R2 = 0.5*(P2+P1)*(H2+H1)/220.25
R P2
h1 0.6502 Pannel 1
= R P1 R1 = 0.5*P1*H1 11.16
1
P2 P1 - P2
Calculating Hydrostatic Pressure
Design Pressure for tank fill with full water, per unit width
Pd = 1*H*g*ρ Pd = 34.34 kPa
a/b = 1.18
Interpolation Interpolation
a/b ß1 a/b ß2
1.40 0.453 Uniform 1.00 0.1600
over
1.60 0.5172 entire 1.50 0.2600
1.18 0.3830 plate 1.18 0.1964
β1 is taken from Roark's Formula 7Th Ed, Table 11.4 Case ß1a:
1 All edges=simply supported.
0.3830 Uniform over
entire plate
ß2 = 0.1964
β2 is taken from Roark's Formula 7Th Ed, Table 11.4 Case 1d: All edges simply supported. Uniformly
increasing along length
t2 = 4.68 mm
t2 + C.A = 4.68 mm
= 11.159 kN/m
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = R1 x b4 / 192 x E x ta
= 5318.26 mm4
= 0.532 cm4
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R2 = R2 x b4 / 192 x E x ta
= 9648.85 mm4
= 0.965 cm4
Provided horizontal stiffener Angle 50 x 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 12.9 cm4
Hence, Bottom Horizontal Stiffener is sufficient
Design of Vertical Stiffener
Reaction for vertical stiffener RV = (P1 + P2)*b*0.5
= 17.13 kN/m
Interpolation
a/b α
1.00 0.0138
1.20 0.0188
1.18 0.018
α = 0.018
α is taken from Roark's Formula 7Th Ed, Table 11.4 Case 8a: All edges fixed. Uniformly over entire plate
Maximum deflection of plate Ymax = α x Pavg x h14 / (E x ta3)
Modulus of Elasticity E = 2.0E+05 N/mm2
2.0E+08 kPa
Ymax = 4.080 mm
Ymax < 0.5 ta
4.080 > 2.5
Thickness alone fail, provide stiffeners
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = 12 xα x Pavg x b3 / x E x ta/2
= 2.28 mm4
= 0.00023 cm4
Provided horizontal stiffener Flat 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 0.0025 cm4
Hence, adopted Vertical stiffener is sufficient
Intermediate Pannel 2
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
ß1 = 0.383
ß2 = 0.196
t2 = 4.68 mm
t2 + C.A = 4.68 mm
Thickness using average load
t = 3.35 mm
t + C.A = 3.35 mm
Imin_R1 = R3 x b4 / 192 x E x ta
= 10329.71 mm4
= 1.033 cm4
Provided horizontal stiffener Angle 50 x 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 12.9 cm4
Interpolation
a/b α
1.00 0.0138
1.20 0.0188
1.18 0.018
α = 0.018
α is taken from Roark's Formula 7Th Ed, Table 11.4 Case 8a: All edges fixed. Uniformly over entire plate
Maximum deflection of plate Ymax = α x Pavg x h24 / (E x ta3)
Modulus of Elasticity E = 2.0E+05 N/mm2
2.0E+08 kPa
Ymax = 3 mm
Ymax < 0.5 ta
3.245 > 2.34
Thickness alone fail, provide stiffeners
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = 12 xα x Pavg x b3 / x E x ta/2
= 2 mm4
= 0.00018 cm4
Provided horizontal stiffener Flat 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 0.0025 cm4
Hence, adopted Vertical stiffener is sufficient
Intermediate Pannel 3
height of hor.stiffner from bottom a = 1100 mm
ß1 = 0.6456
ß2 = 0.3600
t3 = 4.46 mm
t3 + C.A = 4.46 mm
α is taken from Roark's Formula 7Th Ed, Table 11.4 Case 8a: All edges fixed. Uniformly over entire plate
Modulus of Elasticity E = 2.0E+05 N/mm2
2.0E+08 kPa
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = 12 xα x Pavg x b3 / x E x ta/2
= 1.79 mm4
= 0.00018 cm4
Provided horizontal stiffener Flat 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 0.0025 cm4
Hence, adopted Vertical stiffener is sufficient
Top Pannel 4
height of hor.stiffner from bottom a = 1100 mm
ß = 0.3600
β is taken from Roark's Formula 7Th Ed, Table 11.4 Case 1d: All edges simply supported. Uniformly
increasing along length
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
β is taken from Roark's Formula 7Th Ed, Table 11.4 Case 1d: All edges simply supported. Uniformly
increasing along length
t4 = 2.67 mm
t4 + C.A = 2.67 mm
t = 3.86 mm
t + C.A = 3.86 mm
Interpolation
a/b α
1.00 0.0138
1.20 0.0188
2.00 0.039
α = 0.039
α is taken from Roark's Formula 7Th Ed, Table 11.4 Case 8a: All edges fixed. Uniformly over entire plate
Modulus of Elasticity E = 2.0E+05 N/mm2
2.0E+08 kPa
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = 12 xα x Pavg x b3 / x E x ta/2
= 1 mm4
= 0.00008 cm4
Provided horizontal stiffener Flat 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 0.0025 cm4
Hence, adopted Vertical stiffener is sufficient
Interpolation
a/b ß1
1.00 0.2874 Uniform
over
1.20 0.3762 entire
1.00 0.2874 plate
β1 is taken from Roark's Formula 7Th Ed, Table 11.4 Case ß1a:
1 All edges=simply supported.
0.2874 Uniform over
entire plate
Thickness using average load
Minimum coroded required thickness, t = √{(ß*Pd*b2)/Sa}
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
t = 4.25 mm
t + C.A = 4.25 mm
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin = Rbeam x b4 / 192 x E x ta
= 4500.07 mm4
= 0.450 cm4
Provided horizontal stiffener Angle 50 x 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 12.9 cm4
Interpolation
a/b α
1.00 0.0138
1.20 0.0188
1.00 0.014
α = 0.014
α is taken from Roark's Formula 7Th Ed, Table 11.4 Case 8a: All edges fixed. Uniformly over entire plate
Maximum deflection of plate Ymax = α x Pd x a4 / (E x ta3)
Modulus of Elasticity E = 2.00E+05 N/mm2
2.00E+08 kPa
Ymax = 1.734 mm
Ymax < 0.5 ta
1.734 > 0
Thickness alone fail, provide stiffeners
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = 12 xα x Pd x a3 / x E x ta/2
= 1.89 mm4
= 0.00019 cm4
Provided horizontal stiffener Flat 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 0.0025 cm4
Hence, adopted Vertical stiffener is sufficient
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
Dimension Inputs
Design Inputs
By principle of superposition, each panel can be considered subject to a uniform load and a triangular load
Reactions kN
R
R4 = 0.5*P3*H3 0.52
h31.025
4
Pannel 3
= P3 R3 = 0.5*(P3+P2)*(H3+H2)/2
#REF!
R P3
h2 1.025
3
Pannel 2
= P3 P2 - P3 R3 = 0.5*(P2+P1)*(H2+H1)/2
16.13
R P2
2
h1 0.550 Pannel 1
= P2 P1 - P2 P1 R1 = 0.5*P1*H1 7.01
R
1
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
Design Pressure for tank fill with full water, per unit width
Pd = 1*H*g*ρ Pd = 25.51 kPa
Lower Pannel 1
Wall Thickness Calculation
In order to produce minimum bending in the plate plate place a stiffener at a distance 0.5774*H from top,
where H is the height of tank.
= 1501 mm
height of hor.stiffner from bottom a = 550 mm
No. of vertical stiffeners along the length, in lower panel
n1_LP = 9
No. of vertical stiffeners along the width, in lower panel
n2_LP = 3
Spacing, along the length, between two stiffeners
L/(n1_LP+1) = 230 mm
Spacing, along the width, between two stiffeners
W/(n2_LP+1) = 550 mm
Interpolation Interpolation
a/b ß1 a/b ß2
1.40 0.453 Uniform 1.00 0.1600
over
1.60 0.5172 entire 1.50 0.2600
1.00 0.3246 plate 1.00 0.1600
ß1 All edges simply
β1 is taken from Roark's Formula 7Th Ed, Table 11.4 Case 1a: = 0.3246 Uniform over
supported.
entire plate
ß2 = 0.1600
β2 is taken from Roark's Formula 7Th Ed, Table 11.4 Case 1d: All edges simply supported. Uniformly
increasing along length
t2 = 3.48 mm
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
t2 + C.A = 3.48 mm
t = 2.74 mm
t + C.A = 2.74 mm
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = R1 x b4 / 192 x E x ta
= 3342.91 mm4
= 0.334 cm4
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
MAWERICK ENGINEERING SOLUTIONS LLP
CLIENT : GE (U) WATER SUPPLY BY : MR
PROJECT : 160 KLD STP (MBBR TECH.) AT NARAINA DATE : 10-10.2021
Title : DESIGN CALCULATION FOR STP TANKS CALC NO. : MES-W2P-000-01
Imin_R2 = R2 x b4 / 192 x E x ta
= 7685.92 mm4
= 0.769 cm4
Provided horizontal stiffener Angle 50 x 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 12.9 cm4
Interpolation
a/b α
1.00 0.0138
1.20 0.0188
1.00 0.014
α = 0.014
α is taken from Roark's Formula 7Th Ed, Table 11.4 Case 8a: All edges fixed. Uniformly over entire plate
Maximum deflection of plate Ymax = α x Pavg x h14 / (E x ta3)
Modulus of Elasticity E = 2.0E+05 N/mm2
2.0E+08 kPa
Ymax = 1.034 mm
Ymax < 0.5 ta
1.034 < 2.5
Hence, adopted thickness is satisfactory - no stiffener is required
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = 12 xα x Pavg x b3 / x E x ta/2
= 1.13 mm4
= 0.00011 cm4
Provided horizontal stiffener Flat 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 0.0025 cm4
Hence, adopted Vertical stiffener is sufficient
Intermediate Pannel 2
height of hor.stiffner from bottom a = 1025 mm
a/b ß1 a/b ß2
1.80 0.5688 Uniform 1.00 0.1600
over
2.00 0.6102 entire 1.50 0.2600
1.86 0.5820 plate 1.86 0.3327
ß1 = 0.582
ß2 = 0.333
t2 = 4.45 mm
t2 + C.A = 4.45 mm
Thickness using average load
t = 3.53 mm
t + C.A = 3.53 mm
Interpolation
a/b α
1.00 0.0138
1.20 0.0188
1.86 0.035
α = 0.035
α is taken from Roark's Formula 7Th Ed, Table 11.4 Case 8a: All edges fixed. Uniformly over entire plate
Maximum deflection of plate Ymax = α x Pavg x h24 / (E x ta3)
Modulus of Elasticity E = ### N/mm2
### kPa
Ymax = 20 mm
Ymax < 0.5 ta
19.928 > 2.22
Thickness alone fail, provide stiffeners
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin_R1 = 12 xα x Pavg x b3 / x E x ta/2
= 2 mm4
= 0.00018 cm4
Provided horizontal stiffener Flat 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 0.0025 cm4
Hence, adopted Vertical stiffener is sufficient
Top Pannel
height of hor.stiffner from bottom a = 1025 mm
Interpolation
a/b ß2
1.50 0.2600
2.00 0.3400
1.86 0.3182
ß = 0.3182
β is taken from Roark's Formula 7Th Ed, Table 11.4 Case 1d: All edges simply supported. Uniformly
increasing along length
t3 = 2.42 mm
t3 + C.A = 2.42 mm
Thickness using average load
t = 3.22 mm
t + C.A = 3.22 mm
Interpolation
a/b α
1.50 0.0430
2.00 0.0600
1.86 0.055
α = 0.055
Interpolation
a/b ß1
1.00 0.2874 Uniform
over
1.20 0.3762 entire
0.96 0.2681 plate
ß
β1 is taken from Roark's Formula 7Th Ed, Table 11.4 Case 1a: = 0.2681 Uniform over
1 All edges simply supported.
entire plate
Thickness using average load
Minimum coroded required thickness, t = √{(ß*Pd*b2)/Sa}
t = 3.70 mm
t + C.A = 3.70 mm
Minimum required moment of inertia, for bottom stiffener (Beam fixed a both ends)
Imin = Rbeam x b4 / 192 x E x ta
= 3993.42 mm4
= 0.399 cm4
Provided horizontal stiffener Angle 50 x 50 x 6
Moment inertia of used stiffener Ixx = Iyy = 12.9 cm4