Professional Documents
Culture Documents
Installation Instructions: Warning LGH/LCH242H LGH/LCH300H LGH/LCH360H
Installation Instructions: Warning LGH/LCH242H LGH/LCH300H LGH/LCH360H
Installation Instructions: Warning LGH/LCH242H LGH/LCH300H LGH/LCH360H
INSTALLATION
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE INSTRUCTIONS
LGH/LCH242H (20 TON)
WARNING LGH/LCH300H (25 TON)
Improper installation, adjustment, alteration, ser
vice or maintenance can cause property damage, per
sonal injury or loss of life. Installation and service
LGH/LCH360H (30 TON)
GAS AND COOLING PACKAGED UNITS
must be performed by a licensed professional HVAC
506765-05
installer or equivalent, service agency, or the gas sup 4/2022
plier Supersedes 3/2020
Table Of Contents
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . Page 8
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . Page 2 Blower Operation and Adjustments . . . . . . . . . . . . Page 12
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 Cooling Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 17
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3 Gas Heat Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 33
Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4 Heating Operation and Adjustments . . . . . . . . . . . . Page 35
Duct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 Electric Heat Start-Up . . . . . . . . . . . . . . . . . . . . . . . . Page 35
Rigging Unit For Lifting . . . . . . . . . . . . . . . . . . . . . . . Page 5 Variable Air Volume Start-Up . . . . . . . . . . . . . . . . . . Page 35
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 Multi-Staged Air Volume Start-Up . . . . . . . . . . . . . . Page 37
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 Optional Economizer Settings . . . . . . . . . . . . . . . . . Page 42
Pressure Test Gas Piping . . . . . . . . . . . . . . . . . . . . . Page 6 Optional Outdoor Air CFM Control . . . . . . . . . . . . . Page 47
High Altitude Derate . . . . . . . . . . . . . . . . . . . . . . . . . Page 7 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 48
Factory-Installed Options . . . . . . . . . . . . . . . . . . . . . Page 7
LGH/LCH242, 300 & 360 Parts Arrangement
Note: LGH shown; LCH will have electric heat in the same
location as gas heat.
FILTERS REHEAT EVAPORATOR CONDENSER
ECONOMIZER COIL COIL FANS (6)
(TWELVE
DAMPERS
20 X 20 X 2”)
(OPTIONAL)
BLOWER
MOTOR
UNIT
CONTROLLER FILTER
DRIERS
CONDENSATE
DRAIN CONDENSER
COILS
BURNERS
GAS VALVES (2)
COMBUSTION AIR
INDUCERS (2)
LGH/LCH242, 300 & 360 Dimensions - LGH Heat Section Shown
4-1/4
(108)
18 (457)
17-1/2 28 28
(711) (711)
(445) 20 (508) 4-1/2 20 (508)
(114)
BOTTOM SUPPLY
AIR OPENINGS
4 (102)
OPTIONAL
115 VOLT OUTLET
(Factory-Installed Inside Unit)
OPTIONAL
GAS SUPPLY OUTDOOR
65 INLET GRILLE KIT
(1651) (For Bottom (Field Installed)
Gas Supply Only) FLUE (Both Sides)
61-3/4 OUTLET
SIDE (1568)
ELECTRICAL
INLETS
5-3/4
(137)
Page 2
LGH/LCH242 units are available with variable air volume A pre-filter must be installed at the entry to the return
only. LGH/LCH300 and 360 are available in constant air air duct.
volume, variable air volume, or multi-staged air volume. The return air duct must be provided and sealed to
Refer to the 9th character of the model number to the unit.
determine type of blower: Return air temperature range between 55°F (13°C)
B - Constant Air Volume and 80°F (27°C) must be maintained.
V - Variable Air Volume
Air filters must be replaced and pre-filters must be
M - Multi-Stage Air Volume
removed upon construction completion.
Units are available using R410A, an ozone-friendly HFC The input rate and temperature rise must be set per
refrigerant. Refer to the Cooling Start-Up section for the unit rating plate.
precautions when installing unit. The heat exchanger, components, duct system, air
filters and evaporator coil must be thoroughly
IMPORTANT cleaned following final construction clean-up.
The unit operating conditions (including airflow,
Supply air VFD motor rotation is controlled indepen
dently from scroll compressor rotation. See Blower cooling operation, ignition, input rate, temperature
Operation and Adjustments section for correct com rise and venting) must be verified according to these
pressor rotation. Compressor damage due to im installation instructions.
proper rotation is the responsibility of the installer. See figure 1 and table 1 for unit clearances.
UNIT CLEARANCES
Requirements
Optional
Use of this unit as a construction heater or air conditioner Outdoor
Air Hood C
is not recommended during any phase of construction.
Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced filters will
damage the unit.
D B
If this unit has been used for heating or cooling of
buildings or structures under construction, the following
conditions must be met or the warranty will be void:
Page 3
A-Downflow Discharge Application
WARNING Roof Mounting with S6CURB
Electric shock hazard and danger of 1- The roof mounting frame must be installed, flashed
explosion. Can cause injury, death or and sealed in accordance with the instructions
product or property damage. Turn off provided with the frame.
gas and electrical power to unit before 2- The roof mounting frame should be square and level
performing any maintenance or
servicing operations on the unit. Follow to 1/16” per linear foot (5mm per linear meter) in any
lighting instructions attached to unit direction.
when putting unit back into operation 3- Duct must be attached to the roof mounting frame
and after service or maintenance.
and not to the unit; supply and return plenums must
be installed before setting the unit.
IMPORTANT Installer's Roof Mounting Frame
The Clean Air Act of 1990 bans the intentional venting Many types of roof frames can be used to install the unit
of refrigerant (CFC's and HCFC's) as of July 1, 1992. depending upon different roof structures. Items to keep
Approved methods of recovery, recycling or reclaim in mind when using the building frame or supports are:
ing must be followed. Fines and/or incarceration may
be levied for non-compliance. 1- The base is fully enclosed and insulated, so an
enclosed frame is not required.
2- The frames or supports must be constructed with
CAUTION non-combustible materials and should be square and
As with any mechanical equipment, contact with level to 1/16” per linear foot (5mm per linear meter)
sharp sheet metal edges can result in personal injury. in any direction.
Take care while handling this equipment and wear
3- Frame or supports must be high enough to prevent any
gloves and protective clothing.
form of moisture from entering unit. Recommended
minimum frame height is 14” (356mm).
NOTICE 4- Duct must be attached to the roof mounting frame
Roof Damage! and not to the unit. Supply and return plenums must
This system contains both refrigerant and oil. Some be installed before setting the unit.
rubber roofing material may absorb oil, causing the 5- Units require support along all four sides of unit base.
rubber to swell. Bubbles in the rubber roofing
material can cause leaks. Protect the roof surface to Supports must be constructed of steel or suitably
avoid exposure to refrigerant and oil during service treated wood materials.
and installation. Failure to follow this notice could Note-When installing a unit on a combustible surface for
result in damage to roof surface. downflow discharge applications, an S6CURB roof
mounting frame is required.
B-Horizontal Discharge Applications
Unit Support 1- Units installed in horizontal airflow applications must
use an LARMFH30/36 horizontal roof mounting
In downflow discharge installations, install the unit on a frame. The supply air duct connects to the horizontal
non-combustible surface only. Unit may be installed on supply air opening on the LARMFH30/36. The return
combustible surfaces when used in horizontal discharge air duct connects to the unit horizontal return air
applications or in downflow discharge applications when opening. Refer to unit dimensions.
installed on an S6CURB roof mounting frame. 2- Specified installation clearances must be maintained
when installing units. Refer to figure 1.
Note - Securely fasten roof frame to roof per local codes.
3- Top of support slab should be approximately 4”
(102mm) above the finished grade and located so no
CAUTION run-off water from higher ground can collect around
the unit.
To reduce the likelihood of supply / return air bypass
and promote a proper seal with the RTU, duct work / 4- Units require support along all four sides of unit base.
duct drops / diffuser assemblies must be supported Supports must be constructed of steel or suitably
independently to the building structure. treated wood materials.
Page 4
Duct Connection Condensate Drains
All exterior ducts, joints and openings in roof or building Remove cap and make drain connection to the 1” N.P.T.
walls must be insulated and weather-proofed with drain coupling provided on unit. A trap must be installed
flashing and sealing compounds in accordance with between drain connection and an open vent for proper
applicable codes. Any duct passing through an condensate removal. See figure 3. It is sometimes
unconditioned space must be insulated. acceptable to drain condensate onto the roof or grade;
however, a tee should be fitted to the trap to direct
condensate downward. The condensate line must be
CAUTION vented. Check local codes concerning condensate disposal.
In downflow applications, do not drill or punch holes Refer to pages 1 and 2 for condensate drain location.
in base of unit. Leaking in roof may occur if unit base is Note - The drain pan is made with a glass reinforced
punctured.
engineered plastic capable of withstanding typical joint
torque but can be damaged with excessive force. Tighten
Rigging Unit For Lifting pipe nipple hand tight and turn an additional quarter turn.
Rig unit for lifting by attaching four cables to holes in unit CONDENSATE DRAIN CONNECTION
base rail. See figure 2.
CAULK AROUND
1- Detach wooden base protection before rigging. Note - Allow clearance to open CONDENSATE
doors when installing conden COUPLING
2- Connect rigging to the unit base using both holes in sate piping.
each corner. UNIT
Minimum Pitch
3- All panels must be in place for rigging. 1” (25 mm) per
OPEN VENT
10' (3 m) of line
4- Place field‐provided H‐style pick in place just above
top edge of unit. Frame must be of adequate
ÁÁ MOUNTING
ÁÁ
strength and length. (H-style pick prevents damage FRAME
ÁÁ
to unit.)
Unit
Lbs.
RIGGING
*Weight
Kg.
ÁÁ FIGURE 3
LGH 3585 1626
LCH 3509 1592
Connect Gas Piping (Gas Units)
*Maximum weight with all available Before connecting piping, check with gas company or
factory-installed accessories.
authorities having jurisdiction for local code
LIFTING POINT SHOULD BE DIRECTLY requirements. When installing gas supply piping, length
ABOVE CENTER OF GRAVITY of run from gas meter must be considered in determining
pipe size for 0.5” w.c. (.12kPa) maximum pressure drop.
IMPORTANT - ALL PANELS MUST Do not use supply pipe smaller than unit gas connection.
BE IN PLACE FOR RIGGING. For natural gas units, operating pressure at the unit gas
connection must be a minimum of 4.7” w.c. (1.17kPa) and
a maximum of 10.5” (2.60kPa) w.c. For LP/propane gas
units, operating pressure at the unit gas connection must
be a minimum of 11” w.c. (2.74kPa) and a maximum of
13.5” w.c. (3.36kPa).
When making piping connections a drip leg should be
installed on vertical pipe runs to serve as a trap for
sediment or condensate. A 1/8” N.P.T. plugged tap is
located on gas valve for test gauge connection. Refer to
Heating Start-Up section for tap location. Install a ground
joint union between the gas control manifold and the main
CAUTION - Do not
walk on unit. manual shut-off valve. See figure 4 for gas supply piping
entering outside the unit. Figure 5 shows complete
FIGURE 2 bottom gas entry piping.
Page 5
Compounds used on threaded joints of gas piping shall be Pressure Test Gas Piping (Gas Units)
resistant to the action of liquified petroleum gases.
When pressure testing gas lines, the gas valve must
OUTSIDE OF UNIT GAS PIPING be disconnected and isolated. Gas valves can be
TO damaged if subjected to more than 0.5 psig (3.5kPa).
GAS See figure 6.
VALVE
Note-Codes may require that manual main shut-off valve
and union (furnished by installer) be installed in gas line
GROUND
external to unit. Union must be of the ground joint type.
JOINT UNION After all connections have been made, check all piping
MANUAL MAIN
connections for gas leaks. Also check existing unit gas
SHUT-OFF VALVE
connections up to the gas valve; loosening may occur
during installation. Use a leak detection solution or other
TO
GAS preferred means. Do not use matches candles or other
SUPPLY sources of ignition to check for gas leaks.
CAUTION
(REFER TO
Some soaps used for leak detection are corrosive to
LOCAL CODES) DRIP LEG certain metals. Carefully rinse piping thoroughly
GAS PIPING
SUPPORT
after leak test has been completed. Do not use
matches, candles, flame or othe sources of ignition to
check for gas leaks.
FIGURE 4
PRESSURE TEST GAS LINE
GROUND
JOINT UNION
MANUAL MAIN
SHUT-OFF VALVE FIGURE 6
WARNING
EXISTING Danger of explosion. Can cause injury
SUPPLY DRIP LEG or product or property damage. Do not
use matches, candles, flame or other
sources of ignition to check for leaks.
CAP
Note-In case emergency shut down is required, turn off
the main manual shut-off valve and disconnect main
FIGURE 5 power to unit. These devices should be properly labeled
by the installer.
Page 6
High Altitude Derate 6- Install back filter bracket on unit division panel as
shown in figure 9.
Locate the high altitude conversion sticker in the unit
literature bag. Fill out the conversion sticker and affix next OUTDOOR AIR HOOD
to the unit nameplate.
Refer to table 2 for high altitude adjustments. See Detail A
TABLE 2
HIGH ALTITUDE DERATE LEFT HOOD TOP
SIDE PANEL
Altitude Ft.* Gas Manifold Pressure
2000-4500 See Unit Nameplate Detail A
4500 And Above Derate 2% / 1000 Ft. Above Sea Level
Factory-Installed Options
CAULK
A-Economizer BOTH ENDS
Page 7
RIGHT
FILTERS FILTER
SEAL
LEFT
FILTER
SEAL
FIGURE 10
Electrical Connections Refer to unit nameplate for minimum circuit ampacity
and maximum fuse size.
POWER SUPPLY 1- Units are factory-wired for 230/460/575 volt supply.
A-Wiring For 208V supply, remove the insulated terminal
cover from the 208V terminal on the control
Route field wiring in conduit between bottom power entry transformer. Move the wire from the transformer
disconnect. See figure 11. This does not supersede local 230V terminal to the 208V terminal. Place the
codes or authorities having jurisdiction. insulated terminal cover on the unused 230V
FIELD WIRE ROUTING terminal.
2- Route power through the bottom power entry area
and connect to line side of unit disconnect, circuit
breaker or terminal block. See unit wiring diagram.
OPTIONAL 3- Units With Optional 120v GFCI Outlet -
SIDE ENTRY
120V GFI Route and connect separate 120v wiring to GFCI
KNOCKOUTS
outlets which do not have factory-installed wiring.
Route field wiring in conduit between bottom power
MAKE- entry and GFCI. See figure 11.
UP BOX
B-Unbalanced Three-Phase Voltage - VFD Units Only
Units equipped with an optional inverter (VFD) are
designed to operate on balanced, three-phase power.
Operating units on unbalanced three-phase power will
RUN FIELD
WIRING IN
reduce the reliability of all electrical components in the
FIELD PRO unit. Unbalanced power is a result of the power delivery
SEAL VIDED CONDUIT
WATERTIGHT system supplied by the local utility company.
BOTTOM
POWER ENTRY Factory-installed inverters are sized to drive blower
FIGURE 11 motors with an equivalent current rating using balanced
three-phase power. When unbalanced three-phase
WARNING power is supplied; the installer must replace the existing
Do not apply power or close disconnect switch until factory-installed inverter with an inverter that has a higher
installation is complete. Refer to start-up directions. current rating to allow for the imbalance. Use table 3 to
Refer closely to unit wiring diagram. determine the appropriate replacement inverter.
Page 8
TABLE 3 IMPORTANT - Unless field thermostat wires are rated for
INVERTER UP-SIZING maximum unit voltage, they must be routed away from
Factory-Installed Inverter HP Replacement Inverter HP line voltage wiring.
2 5
C-Wiring Connections
3 7-1/2
5 10 The Unit Controller will operate the unit from a thermostat
or zone sensor based on the System Mode. The default
7-1/2 15*
System Mode is the thermostat mode. Refer to the Unit
10 20*
Controller Setup Guide to change the System Mode.
*Replace the existing mounting plate. 1- Default Thermostat Mode -
CONTROL WIRING The Unit Controller will operate two stages of heating
A-Thermostat Location and cooling based on thermostat demands. Install
thermostat assembly in accordance with instructions
Room thermostat mounts vertically on a standard 2” X 4”
provided with thermostat. See figure 12 for field
handy box or on any non-conductive flat surface.
wiring and wiring diagrams on unit.
Locate thermostat approximately 5 feet (1524mm)
IMPORTANT-Terminal connections at the wall plate or
above the floor in an area with good air circulation at
subbase must be made securely. Loose control wire
average temperature. Avoid locating the room
connections may result in intermittent operation.
thermostat where it might be affected by:
-drafts or dead spots behind doors and in corners 2- Zone Sensor Mode
-hot or cold air from ducts The Unit Controller will operate heating and cooling
based on the Unit Controller internal setpoints and
-radiant heat from sun or appliances
the temperature from the A2 zone sensor. An optional
-concealed pipes and chimneys Network Control Panel (NCP) can also be used to
B-Wire Routing provide setpoints. A thermostat or return air sensor
Route thermostat cable or wires from subbase through can be used as a back-up mode. Make zone sensor
wiring connections as shown in figure 13.
knockout provided in unit. For thermostat wire runs up to
60 feet, use 18 gauge wire. For 60 to 90 feet runs, use 16 Note - Install sensor and make communication wiring
gauge wire. connections as shown in literature provided with sensor.
FIELD WIRING WITH ELECTRONIC AND ELECTRO-MECHANICAL THERMOSTATS
(Thermostat Mode)
24 V POWER
J262C
P262
J297A P297
R 1 A55
TO UNIT CONTROLLER 10
THERMOSTAT INPUTS
R C 2
TO R B 11
C G 3
2
G 2 7 W1 4 W1
TO G
K55−1
W1 S86 W2 5 W2
B 5 12
K55
W2 2 Y1 6
TO Y1
A Y1 Y2 7
ALL OTHER THERMOSTAT
Y2 SIGNALS REMAIN CONNECTED OCP 8
AS SHOWN ON THE RIGHT. C
OCP 9
FIGURE 12
Page 9
CONTROL WIRING (continued) 24 VOLT FIELD WIRING
FOR UNITS WITH SUPPLY AIR VFD
24VAC
J298
COMMON
A2 SENSOR VENTILATION
DEMAND
FIGURE 13
HEATING DEMAND
Page 10
FIELD WIRING REHEAT UNITS (Using A Humidity FIELD WIRING REHEAT UNITS
Sensor With Less Than 150 Ft. Wire Runs) (Using A Dehumidification Switch)
J298A P298
J299
1 R 10
7 R
A91 2 C 11
B DEHUMIDIFICATION 8 DI−4
VIN 3 AI−1 SWITCH
9 C
4
C 12 10
5 HUM
GND 6
Use 24 VAC (R) from any terminal
7 TMP available on J299−2, −5, or −7.
D
J262B
P262
8 DO−1
VO 9 C FIGURE 17
5
FIGURE 15
Wire runs over 150 feet (mm):
Use a local, isolated 24VAC transformer such as
Lennox cat #18M13 (20VA minimum) to supply power
to RH sensor as shown in figure 16. Use two shielded
cables containing 20AWG minimum, twisted pair
conductors with overall shield. Belden type 8762 or
88760 (plenum) or equivalent.
FIELD WIRING REHEAT UNITS
(Using A Humidity Sensor With
More than 150 Ft. Wire Runs)
NOT
CONNECTED ISOLATED 24V
TRANSFORMER A55 UNIT
CONTROLLER
J298A P298
1 R
A91 DRAIN C
2
B
VIN NOT 3 AI-1
CONNECTED
4
C
5 HUM
GND 6
7 TMP
D
8 DO-1
VO 9 C
10 DO-2
DI-1
FIGURE 16
Page 11
Blower Operation and Adjustments B-Blower Access
1- Disconnect blower harness at K3 contactor or A96
Units Equipped With A VFD - The blower rotation will inverter. Failure to do so could damage harness or
always be correct. Checking blower rotation is not a valid components.
method of determining voltage phasing for incoming power.
2- Remove screws on either side of blower assembly
sliding base. See figure 18.
IMPORTANT 3- Pull base toward outside of unit.
Three Phase Scroll Compressor Voltage Phas C-Determining Unit CFM
ing
Variable Air Volume Units - Refer to the Variable Air
Three phase scroll compressors must be phased sequen
tially to ensure correct compressor and blower* rotation Volume Start-Up section.
and operation. Compressor and blower are wired in phase Multi-Staged Air Volume Units - Refer to Multi-Stage
at the factory. Power wires are color-coded as follows: line Air Volume Start-Up section to set additional blower
1-red, line 2-yellow, line 3-blue.
speeds.
1-Observe suction and discharge pressures and blower*
rotation on unit start-up. 1- The following measurements must be made with a
dry indoor coil. Run blower at full speed without a
2-Suction pressure must drop, discharge pressure must rise
and blower* rotation must match rotation marking. cooling demand. Measure the indoor blower shaft
RPM. Air filters must be in place when measurements
If pressure differential is not observed or blower* rotation is
not correct: are taken.
3-Disconnect all remote electrical power supplies. 2- With all access panels in place, measure static
4-Reverse any two field-installed wires connected to the pressure external to unit (from supply to return).
line side of S48 disconnect or TB13 terminal strip. Do not Blower performance data is based on static pressure
reverse wires at blower contactor. readings taken in locations shown in figure 19.
5-Make sure the connections are tight. Note - Static pressure readings can vary if not taken where
Discharge and suction pressures should operate at shown.
their normal start‐up ranges.
3- Referring to Page 15, use static pressure and RPM
*Supply air VFD motors should rotate in the correct di readings to determine unit CFM. Use Page 16 when
rection; verify scroll compressor rotation separately.
installing units with any of the optional accessories listed.
Contact technical support if the VFD blower is rotating
incorrectly. 4- The blower RPM can be adjusted at the motor pulley.
Loosen Allen screw and turn adjustable pulley
Units Equipped With Optional VFD or Voltage or clockwise to increase CFM. Turn counterclockwise to
Phase Detection - The Unit Controller checks the decrease CFM. See figure 18. Do not exceed
incoming power during start-up. If the voltage or phase is minimum and maximum number of pulley turns as
incorrect, the Unit Controller will display an alarm and the shown in table 4.
unit will not start. TABLE 4
MINIMUM AND MAXIMUM PULLEY ADJUSTMENT
A-Blower Operation
Belt Minimum Turns Open Maximum Turns Open
Initiate blower only (G) demand at thermostat according A Section No minimum 5
to instructions provided with thermostat. Unit will cycle on B Section 1* 6
thermostat demand. The following steps apply to *No minimum number of turns open when B belt is used on
applications using a typical electro-mechanical pulleys 6” O.D. or larger.
thermostat. D-Blower Belt Adjustment
1- Blower operation is manually set at the thermostat Maximum life and wear can be obtained from belts only if
subbase fan switch. With fan switch in ON position, proper pulley alignment and belt tension are maintained.
blowers will operate continuously. Tension new belts after a 24-48 hour period of operation.
This will allow belt to stretch and seat grooves. Make sure
2- With fan switch in AUTO position, the blowers will blower and motor pulley are aligned. See figure 20 for
cycle with demand. Blowers and entire unit will be off blowers not equipped with a tensioner and figure 21 for
when system switch is in OFF position. blowers equipped with an optional tensioner.
Page 12
BLOWER ASSEMBLY
CAV UNITS:
BELT TENSION
TO INCREASE CFM LOOSEN SCREWS TO ADJUSTING SCREWS
LOOSEN ALLEN SCREW & ADJUST BELT TENSION ALLEN
TURN PULLEY CLOCKWISE SCREW
TO DECREASE CFM
TURN PULLEY
LOOSEN FOUR
COUNTERCLOCKWISE
SCREWS TO AD
JUST BELT TENSION
SIDE VIEW BLOWER
MOTOR
MOTOR ALLEN
SCREW
PULLEY PULLEY
FIGURE 18
LOCATION OF STATIC PRESSURE READINGS
INSTALLATIONS WITH DUCTWORK INSTALLATIONS WITH CEILING DIFFUSERS
RETURN AIR
READING LOCATION
RETURN AIR
READING
RE RE
SUPPLY TURN SUPPLY LOCATION
TURN
FIRST BRANCH
OFF OF MAIN RUN
MAIN
DUCT RUN
SUPPLY AIR SUPPLY AIR
READING READING DIFFUSER
LOCATION LOCATION
FIGURE 19
PULLEY ALIGNMENT - NO TENSIONER PULLEY ALIGNMENT - WITH TENSIONER
ALIGNED
ALIGNED
TENSIONER
MOTOR BLOWER
PULLEY BELT
PULLEY BELT
MOTOR BLOWER
PULLEY PULLEY
NOT ALIGNED
NOT ALIGNED
FIGURE 20 FIGURE 21
Page 13
Blowers Without Belt Tensioner Blowers Equipped With Belt Tensioner
1- Loosen four screws securing blower motor to sliding 1- Loosen the bolt in the center of the tensioner. See
base. See figure 18. figure 22.
2- To increase belt tension - 2- Place belt over all three pulleys. Tensioner pulley
Turn belt tension adjusting screw to the right, or must be oriented toward blower, not motor.
clockwise, to tighten the belt. This increases the 3- Using a 15/16” wrench on the tensioner body nut, turn
distance between the blower motor and the blower the tensioner nut until marks align (3rd mark).
housing. 4- Hold the tensioner with marks aligned and tighten the
To loosen belt tension - bolt to 22 ft.lbs. using the 9/16” wrench.
Turn the adjusting screw to the left, or 5- If tensioner pulley is past 7 o'clock when secured,
counterclockwise to loosen belt tension. The distance between the motor and blower pulleys
3- Tighten four screws securing blower motor to sliding need to be increased. Refer to the steps in figure 18
base once adjustments have been made. to increase belt tension.
BLOWER ASSEMBLY - WITH TENSIONER
TENSIONER
BODY NUT
MOUNTING
BOLT
TENSIONER
ALIGN
MARKS
FIGURE 22
E-Check Belt Tension (Models Without Tensioner)
MEASURE BELT TENSION
Overtensioning belts shortens belt and bearing life.
Check belt tension as follows:
1- Measure span length X. See figure 23.
Page 14
BLOWER DATA
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL & AIR FILTERS IN PLACE
FOR ALL UNITS ADD:
1 - Wet indoor coil air resistance of selected unit.
2 - Any factory installed options air resistance (electric heat, economizer, etc.)
3 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.)
Then determine from blower table blower motor output and drive required.
See page 15 for wet coil and option/accessory air resistance data.
See page 15 for factory installed drive kit specifications.
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT
All units require 10,500 cfm minimum air with electric heat.
TOTAL STATIC PRESSURE - In. w.g.
Air
Volume 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00 2.20 2.40 2.60
cfm
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 372 0.26 433 0.65 497 0.99 565 1.27 630 1.54 687 1.79 738 2.04 784 2.30 824 2.56 861 2.82 897 3.10 932 3.40 --- ---
4500 382 0.41 441 0.79 506 1.12 574 1.41 638 1.69 694 1.95 744 2.22 790 2.50 831 2.77 868 3.05 903 3.35 938 3.66 974 4.01
5000 392 0.56 451 0.93 516 1.25 584 1.55 646 1.85 702 2.12 751 2.41 796 2.70 837 3.00 874 3.30 909 3.61 944 3.93 980 4.30
5500 402 0.73 462 1.08 527 1.40 594 1.72 655 2.02 710 2.31 758 2.61 802 2.92 843 3.24 880 3.56 916 3.88 951 4.22 987 4.60
6000 414 0.89 473 1.24 539 1.56 605 1.90 665 2.21 718 2.51 766 2.83 809 3.16 850 3.51 887 3.84 922 4.18 957 4.52 994 4.91
Page 15
6500 426 1.07 486 1.41 551 1.74 616 2.10 675 2.42 727 2.73 774 3.07 817 3.43 857 3.80 894 4.15 929 4.49 964 4.85 1001 5.24
7000 439 1.26 499 1.60 565 1.93 628 2.31 685 2.64 737 2.97 782 3.34 825 3.72 864 4.11 901 4.48 937 4.83 971 5.19 1008 5.59
7500 453 1.46 513 1.79 579 2.14 641 2.55 696 2.88 747 3.24 792 3.63 833 4.04 872 4.45 909 4.83 945 5.20 979 5.56 1016 5.97
8000 467 1.66 528 2.00 593 2.38 653 2.81 708 3.15 757 3.53 801 3.95 843 4.39 881 4.82 918 5.22 953 5.59 988 5.96 1025 6.37
8500 483 1.88 544 2.22 608 2.65 667 3.10 720 3.44 768 3.85 812 4.30 852 4.78 890 5.22 927 5.63 962 6.01 997 6.39 1034 6.81
9000 499 2.11 561 2.47 624 2.95 681 3.41 733 3.76 780 4.20 823 4.69 862 5.19 900 5.65 936 6.07 972 6.46 1007 6.85 1044 7.28
9500 516 2.36 578 2.75 640 3.26 696 3.73 746 4.10 792 4.58 834 5.11 873 5.64 910 6.12 946 6.54 982 6.93 1018 7.34 1055 7.78
10,000 534 2.64 596 3.06 657 3.60 711 4.07 760 4.48 805 5.00 845 5.57 884 6.12 921 6.61 957 7.03 992 7.43 1028 7.86 1066 8.32
10,500 553 2.93 615 3.39 674 3.95 727 4.44 775 4.90 817 5.46 857 6.06 895 6.62 932 7.12 967 7.55 1003 7.96 1039 8.40 1077 8.89
11,000 572 3.24 634 3.74 692 4.31 744 4.83 789 5.35 830 5.95 869 6.58 907 7.16 943 7.65 978 8.09 1013 8.51 1050 8.98 1089 9.49
11,500 592 3.58 653 4.12 711 4.70 760 5.27 803 5.85 843 6.49 881 7.13 918 7.71 954 8.21 989 8.65 1025 9.10 1062 9.59 1101 10.12
12,000 613 3.95 674 4.53 729 5.14 776 5.75 818 6.39 857 7.06 894 7.71 930 8.30 965 8.80 1000 9.25 1036 9.71 1073 10.22 1112 10.77
12,500 635 4.37 695 4.98 748 5.62 792 6.29 832 6.98 870 7.67 906 8.33 941 8.91 976 9.42 1011 9.87 1048 10.35 1085 10.86 1124 11.42
13,000 657 4.83 715 5.50 766 6.18 808 6.89 847 7.61 883 8.32 918 8.98 953 9.56 988 10.06 1023 10.52 1059 11.00 - - - --- --- ---
13,500 680 5.35 736 6.06 784 6.78 824 7.53 861 8.29 896 9.00 930 9.66 965 10.24 1000 10.74 1035 11.20 - - - --- --- --- --- ---
14,000 704 5.92 757 6.67 801 7.44 839 8.23 875 9.00 909 9.72 943 10.38 977 10.94 1012 11.43 - - - --- --- --- --- --- --- ---
14,500 727 6.55 777 7.34 818 8.16 854 8.97 889 9.75 922 10.48 955 11.12 - - - --- --- --- --- --- --- --- --- --- --- ---
15,000 750 7.23 797 8.07 834 8.92 868 9.75 902 10.54 935 11.26 - - - --- --- --- --- --- --- --- --- --- --- --- --- ---
BLOWER DATA
FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS
Motor Efficiency Nominal Maximum Drive Kit Number RPM Range
hp hp
Standard 5 5.75 5 660 - 810
Standard 5 5.75 6 770 - 965
Standard 5 5.75 7 570 - 720
Standard 5 5.75 8 480 - 630
Standard 5 5.75 9 410 - 535
Standard 7.5 8.63 3 715 - 880
Standard 7.5 8.63 4 770 - 965
Standard 10 11.50 1 740 - 895
Standard 10 11.50 2 870 - 1045
NOTES
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within
the service factor limitations outlined on the motor nameplate.
For VFD applications, nominal motor output is also maximum usable motor output.
Page 16
TABLE 5
MANUFACTURER'S NUMBERS (60 HZ)
DRIVE COMPONENTS
Drive ADJUSTABLE SHEAVE FIXED SHEAVE BELTS BELTS W/ TENSIONER SPLIT BUSHING
No. OEM Part Supplier OEM Part Supplier OEM Part Supplier OEM Part OEM Part
Supplier No. No. No. No. No. No. No. No. Supplier No. No.
1 1VP71x1-3/8 100239-06 BK140H 100788-13 BX78 100245-44 BX77 100245-43 H - 1-3/16 105616-02
2 1VP71x1-1/8 100239-06 BK120H 100788-07 BX75 31K9801 BX73 100245-41 H - 1-3/16 105616-02
3 1VP65x1-3/8 78M7101 BK130H 100788-08 BX75 31K9801 BX74 100245-42 H - 1-3/16 105616-02
4 1VP60x1-3/8 78L5501 BK110H 100788-06 BX71 31K9701 BX71 31K9701 H - 1-3/16 105616-02
5 1VP56x1-1/8 P-8-1492 BK120H 100788-07 BX71 31K9701 BX71 31K9701 H - 1-3/16 105616-02
6 1VP60x1-1/8 41C1301 BK110H 100788-06 BX70 31K9601 BX70 31K9601 H - 1-3/16 105616-02
7 1VP50x1-1/8 P-8-1977 BK120H 100788-07 BX70 31K9601 BX70 31K9601 H - 1-3/16 105616-02
8 1VP44x1-1/8 36C0701 BK120H 100788-07 BX70 31K9601 BX70 31K9601 H - 1-3/16 105616-02
9 1VP44x1-1/8 36C0701 BK140H 100788-13 BX73 100245-41 BX72 100245-14 H - 1-3/16 105616-02
Cooling Start-Up VFD Units and Units Equipped With Optional Voltage or
Phase Detection - The Unit Controller checks the incoming
power during start-up. If the voltage or phase is incorrect, the
IMPORTANT-The crankcase heater must be energized
Unit Controller will display an alarm and the unit will not start.
for 24 hours before attempting to start compressor. Set
thermostat so there is no demand to prevent
A-Preliminary Checks
compressors from cycling.
1- Make sure that unit is installed in accordance with the
VFD Units - The blower rotation will always be correct on installation instructions and applicable codes.
VFD units. Checking blower rotation is not a valid method of 2- Inspect all electrical wiring, both field‐ and
determining voltage phasing for incoming power. factory‐installed, for loose connections. Tighten as
required.
IMPORTANT 3- Check to ensure that refrigerant lines do not rub against
Three Phase Scroll Compressor Voltage Phas the cabinet or against other refrigerant lines.
ing 4- Check voltage at disconnect switch. Voltage must be
Three phase scroll compressors must be phased sequen within range listed on nameplate. If not, consult
tially to ensure correct compressor and blower* rotation power company and have voltage condition
and operation. Compressor and blower are wired in phase corrected before starting unit.
at the factory. Power wires are color-coded as follows: line
1-red, line 2-yellow, line 3-blue. 5- Make sure filters are in place before start‐up.
1-Observe suction and discharge pressures and blower*
rotation on unit start-up. B-Start-Up
2-Suction pressure must drop, discharge pressure must rise VFD Units - Refer to the Optional VFD Start-Up section.
and blower* rotation must match rotation marking. 1- Initiate first and second stage cooling demands
If pressure differential is not observed or blower* rotation is according to instructions provided with thermostat.
not correct:
3-Disconnect all remote electrical power supplies. 2- First-stage thermostat demand will energize
compressors 1 and 2. Second-stage thermostat
4-Reverse any two field-installed wires connected to the
line side of S48 disconnect or TB13 terminal strip. Do not demand will energize compressors 3 and 4. On
reverse wires at blower contactor. units with an economizer, when outdoor air is
5-Make sure the connections are tight. acceptable, a first-stage demand will energize the
economizer; a second-stage demand will energize
Discharge and suction pressures should operate at
their normal start‐up ranges. compressors 1 and 2.
*Supply air VFD motors should rotate in the correct di 3- Units contain four refrigerant circuits or systems.
rection; verify scroll compressor rotation separately. Evaporator and condenser coil refrigerant circuits 1
Contact technical support if the VFD blower is rotating and 2 make up stage 1 cooling. Evaporator and
incorrectly. condenser refrigerant circuits 3 and 4 make up stage
2 cooling. See figure 24 or 25.
Page 17
4- Each refrigerant circuit is separately charged with 5- Refer to Cooling Operation and Adjustment section for
R410A refrigerant. See unit rating plate for correct proper method to check refrigerant charge.
amount of charge.
CONSTANT AIR VOLUME SUPPLY AIR REFRIGERANT CIRCUITS
EVAPORATOR
COIL
STAGE 2
EVAPORATOR
COIL
STAGE 1
EVAPORATOR
COIL
STAGE 1
CONDENSER COIL
STAGE 2
CONDENSER COIL
FIGURE 24
VARIABLE AND STAGED SUPPLY AIR UNIT REFRIGERANT CIRCUITS
CIRCUIT 4
CIRCUIT 3
EVAPORATOR
COIL
EVAPORATOR
COIL CONDENSER
COIL
CONDENSER
COIL
FIGURE 25
Page 18
C-R410A Refrigerant 2- Check each system separately with all stages
Units charged with R410A refrigerant operate at much operating. Compare the normal operating pressures
higher pressures than R22. The expansion valve and (see tables 6 - 10) to the pressures obtained from the
liquid line drier provided with the unit are approved for use gauges. Check unit components if there are
significant differences.
with R410A. Do not replace them with components
designed for use with R22.
3- Measure the outdoor ambient temperature and the
R410A refrigerant is stored in a pink cylinder. suction pressure. Refer to the appropriate circuit
charging curve to determine a target liquid
IMPORTANT temperature.
Page 19
TABLE 6
LGH/LCH242 VAV Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc
(psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig)
97 232 99 268 102 309 104 358 104 407 109 465
106 234 109 269 111 310 113 358 116 409 118 467
Circuit 1
129 241 126 275 129 318 132 363 134 416 139 469
148 247 152 283 148 325 152 372 154 422 158 475
103 225 104 263 107 303 108 353 108 407 113 471
110 227 113 262 116 305 117 354 119 407 122 473
Circuit 2
133 236 130 267 133 313 135 358 138 414 141 475
151 243 155 275 152 319 155 366 158 420 160 478
117 237 118 273 120 321 122 370 123 422 125 478
126 239 128 272 130 322 131 371 133 422 135 479
Circuit 3
149 245 148 280 149 328 151 376 153 430 157 483
169 254 173 288 170 335 173 383 176 435 179 485
118 234 120 271 122 313 124 361 124 409 129 471
127 236 129 270 131 317 133 364 136 411 139 475
Circuit 3
150 244 149 277 150 325 153 370 156 421 159 476
169 254 172 289 172 331 174 379 178 428 180 482
TABLE 7
LGH/LCH300H CAV Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc
(psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig)
103 243 105 282 108 327 110 377 112 429 114 489
112 244 114 283 116 327 119 378 121 432 124 489
Circuit 1
131 251 133 289 136 334 138 383 140 434 143 496
147 259 154 299 157 342 160 390 163 444 167 499
105 251 108 291 109 337 112 391 113 456 115 552
114 254 116 293 118 339 120 392 122 453 125 537
Circuit 2
135 258 137 297 138 343 140 394 142 449 144 520
150 268 158 306 161 351 165 399 167 455 168 513
107 237 109 277 111 323 112 379 114 434 117 494
116 239 118 280 120 324 122 377 124 432 126 495
Circuit 3
136 245 138 285 140 330 142 381 144 431 146 499
151 250 159 295 161 339 164 387 166 443 169 502
102 252 105 293 108 328 110 393 112 449 114 523
109 256 114 297 116 345 118 399 121 455 123 529
Circuit 4
130 261 133 303 135 348 137 402 139 456 141 525
148 266 156 312 158 358 161 407 163 464 166 526
Page 20
TABLE 8
LGH/LCH300H Variable and Staged Supply Air Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc
(psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig)
91 273 96 304 99 354 102 400 106 451 114 505
102 278 107 315 110 356 112 404 114 455 119 509
Circuit 1
120 287 124 323 127 368 130 409 132 460 138 522
140 297 142 332 146 372 151 422 154 467 158 525
100 264 105 306 104 345 107 393 109 450 112 514
107 269 111 306 113 348 116 395 118 452 121 515
Circuit 2
125 276 128 312 131 357 134 399 137 451 140 517
146 284 148 318 151 359 155 410 158 456 161 520
114 279 117 317 120 366 122 417 125 475 129 539
124 282 128 323 130 370 132 420 134 478 137 539
Circuit 3
144 294 146 332 149 378 151 423 153 478 158 542
151 298 167 339 170 383 174 436 177 484 181 546
116 268 122 311 121 349 123 397 125 452 128 508
125 270 128 309 130 353 132 400 135 454 136 512
Circuit 4
143 283 145 319 148 364 151 405 154 455 156 519
151 288 165 327 169 369 173 419 176 466 179 525
TABLE 9
LGH/LCH360 CAV Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc
(psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig)
96 254 102 295 105 338 107 393 107 446 111 511
106 260 111 298 112 345 115 395 117 448 120 508
Circuit 1
126 267 131 307 133 356 135 399 137 456 140 511
144 275 151 318 154 360 157 412 159 462 162 525
98 255 104 301 106 349 108 405 109 477 113 563
108 262 112 305 114 353 116 408 118 468 121 547
Circuit 2
129 272 133 313 135 363 136 407 138 468 141 532
146 279 154 326 156 369 159 423 160 474 162 540
99 253 108 299 110 345 112 400 113 452 116 525
110 256 116 302 118 348 120 398 122 452 125 518
Circuit 3
132 266 137 314 139 362 140 405 142 460 145 522
148 281 156 326 159 372 162 425 164 478 166 537
102 258 104 313 106 359 110 414 110 471 114 544
112 267 112 320 115 366 116 418 118 471 121 539
Circuit 4
130 287 133 330 136 378 137 422 138 479 142 541
148 298 153 345 157 392 159 444 162 497 163 558
Page 21
TABLE 10
LGH/LCH360 Variable and Staged Supply Air Normal Operating Pressures
Outdoor Coil Entering Air Temperature
65 °F 75 °F 85 °F 95 °F 105 °F 115 °F
Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc Suct Disc
(psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig) (psig)
88 252 90 301 97 351 98 388 102 450 104 516
100 255 102 305 105 355 107 403 111 456 113 523
Circuit 1
115 268 119 314 123 361 125 403 129 463 129 527
133 282 137 327 140 371 144 425 147 473 152 544
97 257 100 303 102 349 104 385 106 447 107 524
104 256 107 305 110 353 112 399 115 451 117 523
Circuit 2
121 270 125 313 128 355 130 397 134 454 134 521
135 280 140 322 145 364 148 416 151 464 154 535
106 272 110 319 115 366 116 404 118 469 120 537
118 266 120 320 123 375 124 422 127 472 130 545
Circuit 3
137 285 139 332 142 379 144 418 147 477 148 544
155 294 158 344 161 393 164 443 167 492 172 563
113 258 115 304 117 349 119 384 121 445 123 511
119 253 122 305 125 356 128 399 130 450 132 520
Circuit 4
138 280 142 320 145 359 147 400 149 456 151 521
156 293 159 333 163 374 166 424 169 471 173 539
Page 22
LGH/LCH242 Variable Supply Air Circuit 1 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
100
85°
90
75°
80
65°
70
60
120 115°
110 105°
Liquid Temperature (° F)
100 95°
90
85°
80
75°
70
65°
60
Page 23
LGH/LCH242 Variable Supply Air Circuit 3 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
100
85°
90
75°
80
65°
70
60
110
Liquid Temperature (° F)
95°
100
85°
90
80 75°
70 65°
60
Page 24
LGH/LCH300H CAV Circuit 1 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
100
85°
90
75°
80
65°
70
60
100 110 120 130 140 150 160 170
110
Liquid Temperature (° F)
95°
100
85°
90
75°
80
65°
70
60
100 110 120 130 140 150 160 170
Page 25
LGH/LCH300H CAV Circuit 3 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
100 85°
90
75°
80
65°
70
60
100 110 120 130 140 150 160 170
120
105°
110 95°
Liquid Temperature (° F)
85°
100
90 75°
65°
80
70
60
100 110 120 130 140 150 160 170
Page 26
LGH/LCH300H Variable and Staged Supply Air Circuit 1 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
100 95°
90 85°
80 75°
70
65°
60
90 100 110 120 130 140 150 160
120 115°
110 105°
Liquid Temperature (° F)
100 95°
90
85°
80
75°
70 65°
60
100 110 120 130 140 150 160 170
Suction Pressure (psig)
Page 27
LGH/LCH300H Variable and Staged Supply Air Circuit 3 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
100
90 85°
80 75°
65°
70
60
110 120 130 140 150 160 170 180 190
120
105°
110
Liquid Temperature (° F)
95°
100
85°
90
80 75°
65°
70
60
110 120 130 140 150 160 170 180
Page 28
LGH/LCH360 CAV Circuit 1 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
100 85°
90 75°
80 65°
70
60
90 100 110 120 130 140 150 160 170
Suction Pressure (psig)
115°
120
105°
110
Liquid Temperature (° F)
95°
100 85°
90 75°
80 65°
70
60
90 100 110 120 130 140 150 160 170
Page 29
LGH/LCH360 CAV Circuit 3 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
85°
100
90 75°
80 65°
70
60
90 100 110 120 130 140 150 160 170
Suction Pressure (psig)
85°
100
75°
90
65°
80
70
60
90 100 110 120 130 140 150 160 170
Page 30
LGH/LCH360 Variable and Staged Supply Air Circuit 1 Charging Curve
Outdoor Temperature (°F)
130
115°
120
105°
110
Liquid Temperature (° F)
95°
100
85°
90
75°
80
65°
70
60
80 90 100 110 120 130 140 150 160
Suction Pressure (psig)
120 115°
110 105°
Liquid Temperature (° F)
100 95°
90 85°
80 75°
70 65°
60
90 100 110 120 130 140 150 160
Page 31
LGH/LCH360 Variable and Staged Supply Air Circuit 3 Charging Curve
130 Outdoor Temperature (°F)
115°
120
105°
110
Liquid Temperature (° F)
95°
100
85°
90 75°
80 65°
70
60
100 110 120 130 140 150 160 170 180
Suction Pressure (psig)
120
105°
110
Liquid Temperature (° F)
95°
100
85°
90
75°
80
65°
70
60
110 120 130 140 150 160 170 180
Page 32
F-Compressor Controls Condenser fan 3 is de-energized when both S11 and
See unit wiring diagram to determine which controls are S84 pressure switches (via K149) open due to low
used on each unit. pressure. S11 and S84 are located in refrigerant
1- High Pressure Switch (S4, S7, S28, S96) circuits 1 and 2 respectively.
The compressor circuit is protected by a high Condenser fan 4 is de-energized when both S85 and
pressure switch which opens at 610 psig + 15 psig S94 pressure switches (via K150) open due to low
(4206 kPa + 103 kPa) and automatically resets at 475 pressure. S85 and S94 are located in refrigerant
psig + 15 psig (3275kPa + 103 kPa). circuits 3 and 4.
2- Low Pressure Switch (S87, S88, S97, S98)
The compressor circuit is protected by a loss of
charge switch. Switch opens at 40 psig + 5 psig (276 CONDENSER FAN CYCLING
+ 34 kPa) and automatically resets at 90 psig + 5 S85 & S94 40F, 4C
psig (621 kPa + 34 kPa). EVAP COIL COND. COND.
FAN 4 FAN 1
3- Crankcase Heater (HR1, HR2, HR5, HR11) K150 K10
Units have compressors which contain a belly band
compressor oil heater which must be on 24 hours COND. COND.
FAN 5 FAN 2
before running compressors. Energize by setting 55F, 13C K68
K152
thermostat so that there is no cooling demand, to 55F, 13C
prevent compressor from cycling, and apply power
to unit. K1 K2 K14 K146 COND. COND.
FAN 6 FAN 3
4- Freezestats (S49, S50, S53, S95) 1 2 3 4 K153 K149
Switches de-energize compressors when 40F, 4C S11 & S84
Y1 Y2
evaporator coil temperature falls below 29F (-2C)
to prevent evaporator freeze-up. Switches reset FIGURE 26
when evaporator coil temperature reaches 58F
(15C).
5- Low Ambient Pr. Sw. (S11, S84, S85, S94) Gas Heat Start-Up (Gas Units)
Switch maintains adequate discharge pressure by
de-energizing condenser fan when liquid pressure
falls below 240 psig +10 (1655 kPa+69). Switch FOR YOUR SAFETY READ BEFORE LIGHTING
closes to energize condenser fan when pressure BEFORE LIGHTING smell all around the appliance area
rises to 450 psig +10 (3103kPa + 69). for gas. Be sure to smell next to the floor because some
6- Thermal Protector (S5, S8, S31, S180) gas is heavier than air and will settle on the floor.
The compressors used on 242H units are protected
Use only your hand to push in or turn the gas control knob.
by an external temperature switch. The n.c. switch
Never use tools. If the knob will not push in or turn by
opens at 248F + 9 (120C + 5) and automatically
hand, do not try to repair it, call a qualified service
resets at 169F + 18 (76C + 10). The compressors
technician. Force or attempted repair may result in a fire
used on 300H and 360H units are protected by an or explosion.
internal thermal protector switch.
This unit is equipped with an automatic spark ignition
Condenser Fan Operation system. There is no pilot. In case of a safety shutdown,
Condenser fans 1, 2, and 3 are energized on a Y1 move thermostat switch to OFF and return the thermostat
cooling demand; condenser fans 4, 5, and 6 are switch to HEAT to reset ignition control.
energized on a Y2 cooling demand. Condenser fans
1, 2, 5, and 6 are energized after a 2 second delay.
See figure 26. WARNING
Condenser fans 2 and 5 are de-energized when Danger of explosion. Can cause injury
outdoor temperature drops below 55F (13C). or death. Do not attempt to light
Condenser fans 1 and 6 are de-energized when manually. Unit has a direct spark
outdoor air temperature is below 40F (4C). ignition system.
Page 33
HONEYWELL VR8305Q SERIES GAS VALVE
WARNING
Electric shock hazard. Can cause injury HIGH FIRE LOW FIRE
or death. Do not use this unit if any part ADJUSTMENT ADJUSTMENT
has been under water. Immediately call
a qualified service technician to inspect
the unit and to replace any part of the
control system and any gas control
which has been under water.
WARNING INLET
PRESSURE
TAP
Danger of explosion. Can cause injury
or product or property damage. If
Gas valve knob is shown in OFF position.
overheating occurs or if gas supply
fails to shut off, shut off the manual gas FIGURE 27
valve to the appliance before shutting
off electrical supply.
5- Turn the knob on the gas valve clockwise to OFF.
Do not force.
WARNING 6- Wait five minutes to clear out any gas. If you then
SMOKE POTENTIAL smell gas, STOP! Immediately call your
gas supplier from a neighbor's phone. Follow the gas
The heat exchanger in this unit could be a source of
smoke on initial firing. Take precautions with respect supplier's instructions. If you do not smell gas, go to
to building occupants and property. Vent initial sup the next step.
ply air outside when possible.
7- Turn the knob on the gas valve counterclockwise
to ON. Do not force.
WARNING 8- Close or replace the heat section access panel.
Electric shock hazard. Can cause injury 9- Turn on all electrical power to unit.
or death. Before attempting to perform
any service or maintenance, turn the 10- Set thermostat to desired setting.
electrical power to unit OFF at
11- The ignition sequence will start.
disconnect switch(es). Unit may have
multiple power supplies. 12- If the appliance does not light the first time (gas line
A-Placing Unit In Operation not fully purged), it will attempt up to two more
ignitions before locking out.
13- If lockout occurs, repeat steps 1 through 10.
WARNING
14- If the appliance will not operate, follow the
Danger of explosion and fire. Can cause instructions “Turning Off Gas to Appliance” and call
injury or product or property damage.
You must follow these instructions your service technician or gas supplier.
exactly.
Turning Off Gas to Unit
Gas Valve Operation for Honeywell VR8305Q (Figure 1- If using an electromechanical thermostat, set to the
27) Series Gas Valve lowest setting.
1- Set thermostat to lowest setting. 2- Before performing any service, turn off all electrical
2- Turn off all electrical power to appliance. power to the unit.
3- This appliance is equipped with an ignition device 3- Open or remove the heat section access panel.
which automatically lights the burner. Do not try to 4- Turn the knob on the gas valve clockwise to
light the burner by hand. OFF. Do not force.
4- Open or remove the heat section access panel. 5- Close or replace the heat section access panel.
Page 34
Heating Operation and Adjustments Electric Heat Start-Up (LCH Units)
(Gas Units) Factory- or Field-Installed Option
A-Heating Sequence of Operation Electric heat will stage on and cycle with thermostat
1- On a heating demand the combustion air inducer demand. Number of stages of electric heat will vary
starts immediately. depending on electric heat assembly. See electric heat
2- Combustion air pressure switch proves inducer wiring diagram on unit for sequence of operation.
operation. After a 30-second pre-purge, power is
allowed to ignition control. Switch is factory set and Variable Air Volume Start-Up
requires no adjustment.
Units may contain an optional supply air blower
3- Spark ignitor energizes and gas valve solenoid opens.
equipped with a variable frequency drive A96 (VFD)
4- Spark ignites gas, ignition sensor proves the flame which varies supply air CFM.
and combustion continues.
The supply air VFD (A96) is located near the
5- If flame is not detected after first ignition trial, ignition
compressors. See figure 29.
control will repeat steps 3 and 4 two more times
before locking out the gas valve. A-Start-Up
6- For troubleshooting purposes, an ignition attempt 1- A pressure transducer (A30) is shipped in a box in the
after lock out may be re-established manually. Move blower compartment. Install the transducer
thermostat to “OFF” and return thermostat switch to according to manufacturer's instructions.
“HEAT” position. Note - Make sure the transducer is installed in the main
B-Limit Controls duct at least 2/3 of the distance away from the unit.
Limit controls are factory-set and are not adjustable. Two
limits are located on the drip shield in the blower SUPPLY AIR VARIABLE FREQUENCY DRIVE
compartment. See figure 28. A55 UNIT
CONTROLLER
LIMIT LOCATION
DRIP
SHIELD TB24
TB18
LIMITS
FIGURE 28
C-Heating Adjustment
Main burners are factory-set and do not require adjustment.
Gas manifold pressures should match pressures shown
in table 11.
TABLE 11
A96 SUPPLY
Natural Gas Propane (LP) Gas AIR VFD
1st Stage 2nd Stage 1st Stage 2nd Stage
+ 0.2 + 0.3 + 0.2 + 0.3
FIGURE 29
1.6 3.7 5.5 10.5
Page 35
TABLE 12
PRESSURE TRANSDUCER WIRING RECORD ADJUSTED SETPOINTS
A30 TWISTED UNIT
TB18 Setpoint Setpoint Display
0 PAIR Parameter
Description “w.c. Setting
6
386 Smoke
387 Ventilation
9 388 Heating
DRAIN
NOT
_ CONNECTED 389 Cooling
B-Unit Operation
Use the Unit Controller to check unit mechanical
operation. See the Service - Test section of the Unit FIGURE 31
Controller manual.
Page 36
SUPPLY AIR VFD BYPASS CONNECTOR Multi-Staged Air Volume Start-Up
Disconnect Connect
LGH/LCH300 & 360 Units Only
P247 P247 Units may contain an optional supply air blower
equipped with a variable frequency drive A96 (VFD)
J249 which stages supply air CFM.
The supply air VFD (A96) is located near the
J247 compressors. See figure 29.
A-Design Specifications
FIGURE 32
Use table 13 to fill in field-provided, design specified
blower CFM for appropriate unit.
4- Disconnect J248 from P248 and connect connect
P248 jumper plug to J248. P248 jumper plug is If only high and low cooling design specifications are
attached to the J248 wire harness near the J248 provided, set the medium cooling CFM at the high or low
jack connector. See figure 33. cooling design spec or any CFM between.
B-Set Maximum CFM
SUPPLY AIR VFD BYPASS CONNECTOR
Use table 13 to determine highest blower CFM for
Disconnect
appropriate unit. Adjust the blower pulley to deliver that
P248 amount of CFM with only the blower operating. See the
Connect
Blower Operation and Adjustment section.
P248 TABLE 13
Jumper CFM DESIGN SPECIFICATIONS -
Plug 300 & 360 UNITS WITH STAGED BLOWER
J248 J248 No. Of Stages / Con Design
Blower Speed1
trol Type Specified CFM
FIGURE 33 Htg.
Clg. High
5- Locate VFD control relay K203 on the lower control 2 Stages / T'Stat
Clg. Low
panel next to terminal strip TB24. See figure 31.
Ventilation
6- Locate wires labeled K203-A and K203-B in area
Htg.
shown in figure 31. Disconnect insulated terminals.
Clg. High
7- Locate wires labeled K3-A and K3-B coming from K3
3 Stages / T'Stat2 Clg. Med.
blower relay. Connect to K203-A to K3-A and K203-B
to K3-B. Clg. Low
Ventilation
8- Restore power to unit. Blower will operate in constant
air volume (CAV) mode. Htg.
Clg. High
9- Check the indoor blower motor nameplate for full load 4 Stages /
amperage (FLA) value. Measure the amp readings Room Sensor OR Clg. Med. High
from the indoor blower motor operating in bypass Discharge Air Clg. Med. Low
mode. If measured amps are higher than nameplate Control
Clg. Low
FLA value, decrease the CFM by opening (turning
counterclockwise) the motor pulley. See figure 18. Do Ventilation
not exceed minimum and maximum number of pulley 1Available blower speeds vary by unit and thermostat stages.
turns as shown in table 4. 2Requires a transfer relay (K27) and three-stage thermostat.
Page 37
C-Set Blower Speeds TABLE 14
MINIMUM AND MAXIMUM CFM -
1- Use the following menu to enter the blower design 300 & 360 UNITS WITH STAGED BLOWERS
specified CFM into the Unit Controller. Make sure
Gas Heat Minimum CFM
blower CFM is within limitations shown in table 14.
Refer to the Unit Controller manual provided with unit. Unit Gas Heat Size Airflow CFM
SETUP > TEST & BALANCE > BLOWER > LGH300 Std., Med. 5950
To configure the unit to bypass the inverter automatically, Unit Not Applicable Airflow CFM
Page 38
Hot Gas Reheat Start-Up And Operation Reheat will terminate when the indoor relative humidity
falls 3% (57% default) or the digital output de-energizes.
General The reheat deadband can be adjusted at Settings -
Hot gas reheat units provide a dehumidifying mode of Control menu.
operation. These units contain a reheat coil adjacent to A91 Humidity Sensor
and downstream of the evaporator coil. Reheat coil
solenoid valves, L14 and L30, route hot discharge gas Relative humidity should correspond to the sensor (A91)
from the compressor to the reheat coil. Return air pulled output voltage listed in table 15. For example: if indoor air
across the evaporator coil is cooled and dehumidified; the relative humidity is 80% + 3%, the humidity sensor output
reheat coil adds heat to supply air. should read 8.00VDC.
See figure 34 for reheat refrigerant routing. See figure Check the sensor output annually for accuracy. Keep the
35 for cooling only refrigerant routing. air intake openings on the sensor clean and free of
obstructions and debris.
L14/L30 Reheat Coil Solenoid Valve TABLE 15
When Unit Controller input (Unit Controller J298-5 or Relative Humidity (%RH + 3%) Sensor Output (VDC)
J299-8) indicates room conditions require
20 2.00
dehumidification, L14/L30 reheat valve is energized
(Unit Controller P269-3 or P269-4) and refrigerant is 30 3.00
routed to the reheat coil. 40 4.00
Reheat Setpoint 50 5.00
Reheat is factory-set to energize when indoor relative 60 6.00
humidity rises above 60% (default). The reheat setpoint 70 7.00
can be adjusted by changing Unit Controller Settings -
80 8.00
Control menu. A setting of 100% will operate reheat from
an energy management system digital output. 90 9.00
REHEAT MODE REFRIGERANT ROUTING 300, 360H4M
EVAPORATOR
COIL NOTE:Refrigerant circuits one and two operate
during reheat.
MIXED
INDOOR/OUTDOOR
AIR
“NEUTRAL”
DEHUMIDIFIED
AIR REHEAT COIL
CONDENSER
COIL
REHEAT COIL
OUTDOOR
AIR
REFRIGERANT
CIRCUIT 1
REFRIGERANT
CIRCUIT 2
REFRIGERANT
CIRCUIT 3
REFRIGERANT
CIRCUIT 4
REHEAT VALVE
CHECK VALVE
THERMAL
EXPANSION
VALVES
FIGURE 34
Page 39
COOLING MODE REFRIGERANT ROUTING 300, 360H4M
EVAPORATOR
COIL
MIXED
INDOOR/OUTDOOR
AIR
“NEUTRAL”
DEHUMIDIFIED
AIR REHEAT COIL CONDENSER
COIL
REHEAT COIL
OUTDOOR
AIR
REFRIGERANT
CIRCUIT 1
REFRIGERANT
CIRCUIT 2
REFRIGERANT
CIRCUIT 3
REFRIGERANT
CIRCUIT 4
REHEAT VALVE
CHECK VALVE
THERMAL
EXPANSION
VALVES
FIGURE 35
Check-Out For other reheat control options, refer to the Unit
Test reheat operation using the following procedure. Controller manual.
1- Make sure reheat is wired as shown in wiring section. Additional Cooling Stages
2- Make sure unit is in local thermostat mode.
Units are shipped from the factory to provide two stages of
3- Use Unit Controller key pad to elect SERVICE > cooling.
TEST > DEHUMIDIFIER.
Three stages of cooling is available in zone sensor mode.
300, 360 - Three stages of cooling is also available by installing a
The blower, compressor 1, and compressor 2 (reheat) transfer relay and a three-stage thermostat. Refer to the Main
should be operating. L14 and L30 LEDs on the Unit Control Operation section in the Unit Controller manual when
Controller should also be ON, indicating the reheat valves using the transfer relay.
are energized. REHEAT MODE will be appear on the Unit
Controller display. Additional Cooling Stages
4- Press BACK on the Unit Controller display to stop the Four stages of cooling is available in zone sensor mode on
testing mode. units with four compressors.
Default Reheat Operation Compressors are not de-energized when unit operation
Reheat will operate as shown in table 16 once three changes from cooling to reheat or from reheat to cooling.
conditions are met: Instead, L14 and L30 reheat valves are energized
(reheat) or de-energized (cooling).
1- Blower must be operating.
NOTE - Another thermostat staging option is available
2- System must be in occupied mode.
which allows both compressors to be energized during
3- System must NOT be operating in heating mode. free cooling. See Unit Controller manual for details.
IMPORTANT - Free cooling does not operate during
reheat.
Page 40
TABLE 16
REHEAT OPERATION
Two-Stage Thermostat - Default
Operation
T'stat and Humidity Demands
300, 360 (4-Compressors)
Reheat Only Compressor 1 & 2 Reheat
Compressor 1 & 2 Reheat and
Reheat & Y1
Compressor 3 & 4 Cooling1
Reheat &Y1 & Y2 Compressor 1, 2, 3 & 4 Cooling3
Page 41
SETUP > TEST & BALANCE > DAMPER > MIN
Optional Economizer Settings DAMPER POSITION BLOWER ON LOW = .%
A-Control Settings C-Economizer Operation
The economizer, when configured, controls:
Note - Use indicating lights on Unit Controller to
Damper position, which determines how much determine thermostat demand.
outdoor air is used to meet free cooling or indoor air
quality requirements, and See table 21 for economizer operation with a standard
two-stage thermostat
Can be used to control optional power exhaust fans.
On a cooling demand, outdoor air is used for free cooling Table 22 shows economizer operation with an energy
instead of first-stage compressor(s) when outdoor air is management system which uses a global sensor.
suitable. Both tables show the occupied and unoccupied time
To enable the economizer, if installed, go to SETUP > period. The occupied time period is determined by the
INSTALL and go through the wizard. When reaching thermostat or energy management system.
Configuration ID 1, position 2 will need to be set to the
Table 23 shows economizer operation in zone sensor
applicable type of economizer. Valid types are as
mode.
indicated below:
M = Motorized Outdoor Air Damper Only D-IAQ Damper Operation
T = Economizer - Temperature (Note: Used for both The Unit Controller has a 0-10VDC IAQ input for a
set point and offset temperature control.) standard 0-2000ppm CO2 sensor. The economizer
G = Economizer - Global starts opening at a CO2 level of 500 ppm (default) and
reaches full open at a CO2 level of 1000ppm.
S = Economizer - Single Enthalpy
Adjustments may be made to the indoor air quality
D = Economizer - Dual Enthalpy
parameters to alter operation or meet required
The following options are available depending on specifications. Use the user interface to change
economizer set above. These settings are available Parameter 117 through 119. Go to SETTINGS > RTU
through the main menu at SETUP > TEST & BALANCE > OPTIONS > EDIT PARAMETER.
DAMPER.
If the economizer is operating in the free cooling mode
B-Damper Minimum Position Setting and the IAQ sensor demands more fresh air, the IAQ
Use the following menu path to modified the minimum demand will override the free cooling demand to open the
damper positions for both high and low operations. dampers further or to keep them open.
SETUP > TEST & BALANCE > DAMPER > MIN The IAQ function is not energized during the unoccupied
DAMPER POSITION BLOWER ON HIGH = .% or night time period.
TABLE 17
MENU INTERFACE (LEVEL 1 - SETTINGS) - M (MOTORIZED OUTDOOR AIR DAMPER ONLY)
USE THE ADJUST AND SET VALUES AR
Level 2 Level 3 Level 4 Level 5 ROWS TO SCROLL UP OR DOWN FOR SE
LECTION OPTIONS.
MIN DAMPER POSITION
BLOWER ON HIGH = X.X %
MIN DAMPER POSITION
BLOWER ON LOW = X.X %
DEMAND CONTROL VENT
DAMPER START OPEN = XXXX.X PPM
DEMAND CONTROL VENT
RTU OPTION DAMPER DAMPER FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT
DAMPER MAX OPENING = XXX.X%
FRESH AIR HEATING
ENABLE FAH = YES OR FRESH AIR HEATING FAH SETPOINT = XX F
NO
FRESH AIR COOLING
ENABLE AFC = YES OR FRESH AIR COOLING AFC SETPOINT = XX F
NO
Page 42
TABLE 18
MENU INTERFACE (LEVEL 1 - SETTINGS) - T (TEMPERATURE ECONOMIZER)
USE THE ADJUST AND SET VALUES AR
Level 2 Level 3 Level 4 Level 5 ROWS TO SCROLL UP OR DOWN FOR SE
LECTION OPTIONS.
ECONOMIZER TEMP ECON TYPE = TEMPERATURE OFFSET OR TEMPERATURE SETPT
ECONOMIZER
OAT SETPOINT = XX.X F
FREE COOLING
SUPPLY AIR SETPOINT = XX F
MIN DAMPER POSITION
BLOWER ON HIGH = X.X %
MIN DAMPER POSITION
BLOWER ON LOW = X.X %
DEMAND CONTROL VENT
RTU OPTION DAMPER DAMPER START OPEN = XXXX.X PPM
DEMAND CONTROL VENT
DAMPER FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT
DAMPER MAX OPENING = XXX.X%
FRESH AIR HEATING
ENABLE FAH = YES OR FRESH AIR HEATING FAH SETPOINT = XX F
NO
FRESH AIR COOLING
ENABLE AFC = YES OR FRESH AIR COOLING AFC SETPOINT = XX F
NO
TABLE 19
MENU INTERFACE (LEVEL 1 - SETTINGS) - G (GLOBAL ECONOMIZER)
USE THE ADJUST AND SET VALUES AR
Level 2 Level 3 Level 4 Level 5 ROWS TO SCROLL UP OR DOWN FOR SE
LECTION OPTIONS.
FREE COOLING
SUPPLY AIR SETPOINT = XX F
MIN DAMPER POSITION
BLOWER ON HIGH = X.X %
MIN DAMPER POSITION
BLOWER ON LOW = X.X %
DEMAND CONTROL VENT
DAMPER START OPEN = XXXX.X PPM
RTU OPTION DAMPER DEMAND CONTROL VENT
DAMPER FULL OPEN = XXXX.X PPM
DEMAND CONTROL VENT
DAMPER MAX OPENING = XXX.X%
FRESH AIR HEATING
ENABLE FAH = YES OR FRESH AIR HEATING FAH SETPOINT = XX F
NO
FRESH AIR COOLING
ENABLE AFC = YES OR FRESH AIR COOLING AFC SETPOINT = XX F
NO
Page 43
TABLE 20
DEMAND CONTROL VENTILATION PARAMETERS
Control Parameter Control Value
Parameter Short
No Screen Name Description Min. Default Max. Units Description
Demand Control
Maximum allowed demand control
117 DCV MAX DAMPER OPEN Ventilation Maximum 0 100 100 %
ventilation damper open position.
Damper Open
Page 44
Page 45
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
TABLE 21
ECONOMIZER OPERATION - Standard Two-Stage Thermostat (Default Option)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
THERMOSTAT DEMAND DAMPER POSITION UNOCC. DAMPER POSITION OCCUPIED MECHANICAL COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ OUTDOOR AIR IS NOT SUITABLE FOR FREE COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OFF CLOSED CLOSED NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
G CLOSED MINIMUM NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Y1 CLOSED MINIMUM STAGE 1
Y2 CLOSED MINIMUM STAGES 1 AND 2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ OUTDOOR AIR IS SUITABLE FOR FREE COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OFF CLOSED CLOSED NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
G CLOSED MINIMUM NO
Y1 MODULATING MODULATING NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Y2 MODULATING MODULATING (1) STAGE 1
Note - Modulating dampers adjust to control supply air (RT6) to 55F (13C). (1) The Unit Controller goes into a “cool down” or “warm-up” mode when
the occupied time period starts. (2) Units with two-stage compressor operation will operate only stage 1 with a Y2 demand.
TABLE 22
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ECONOMIZER OPERATION WITH GLOBAL SENSING - Energy Management System (Default Option)
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
THERMOSTAT DEMAND DAMPER POSITION UNOCC. DAMPER POSITION OCCUPIED MECHANICAL COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
GLOBAL INPUT OFF
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OFF CLOSED CLOSED NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
G CLOSED MINIMUM NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Y1 CLOSED MINIMUM STAGE 1
Y2 CLOSED MINIMUM STAGES 1 AND 2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ GLOBAL INPUT ON
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OFF MODULATING MODULATING NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
G MODULATING MODULATING NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Y1 MODULATING MODULATING STAGE 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Y2 MODULATING MODULATING (1) STAGES 1 AND 2 (2)
Note - Modulating dampers adjust to control supply air (RT6) to 55F (13C). (1) The Unit Controller goes into a “cool down” or “warm-up” mode when
the occupied time period starts. (2) Units with two-stage compressor operation will operate only stage 1 with a Y2 demand (default).
TABLE 23
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
DEMAND DAMPER POSITION UNOCC. DAMPER POSITION OCCUPIED MECHANICAL COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OUTDOOR AIR IS NOT SUITABLE FOR FREE COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OFF CLOSED CLOSED NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
G CLOSED MINIMUM NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 1 CLOSED MINIMUM COMPRESSOR 1
Cooling Stage 2 CLOSED MINIMUM COMPRESSOR 1 & 2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 3 CLOSED MINIMUM COMPRESSOR 1, 2, & 3
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 4 CLOSED MINIMUM COMPRESSOR 1, 2, 3, & 4
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ OUTDOOR AIR IS SUITABLE FOR FREE COOLING
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OFF CLOSED CLOSED NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
G CLOSED MINIMUM NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 1 MODULATING MODULATING NO
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 2 FULL OPEN* FULL OPEN* COMPRESSOR 1
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 3 FULL OPEN* FULL OPEN* COMPRESSORS 1 & 2
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Cooling Stage 4 FULL OPEN* FULL OPEN* COMPRESSORS 1, 2, 3, & 4
*Damper will modulate to maintain 55F supply air when parameter 164 is changed to setting “0”. Note - Modulating dampers adjust to control supply
air (RT6) to 55F (13C).
Page 46
Optional Outdoor Air CFM Control VELOCITY SENSOR LOCATION
Outdoor Air CFM Control is a factory-installed option
available on units equipped with a supply air variable
frequency drive (VFD) and economizer. A24
SENSOR
The Unit Controller modulates outdoor air dampers to
maintain a constant amount of outdoor air regardless of
blower speed. This ensures minimum ventilation
requirements are met at lower supply air speeds.
The Unit Controller uses a velocity sensor (A24) to
modulate dampers. The sensor is located in the outdoor A24
air stream. See figure 36. CONTROL
Page 47
Service Blower shaft bearings are prelubricated. For extended
bearing life, relubricate at least once every two years with
The unit should be inspected once a year by a qualified
a lithium base grease, such as Alvania 3 (Shell Oil),
service technician.
Chevron BRB2 (Standard Oil) or Regal AFB2 (Texas Oil).
Use a hand grease gun for relubrication. Add only enough
CAUTION grease to purge through the bearings so that a bead of
Label all wires prior to disconnection when servicing grease appears at the seal lip contacts.
controls. Wiring errors can cause improper and dan
gerous operation. Verify proper operation after ser C-Burners (Gas Units)
vicing. Periodically examine burner flames for proper
A-Filters appearance during the heating season. Before each
Units are equipped with twelve 20 X 20 X 2” (508 X 508 heating season examine the burners for any deposits or
X 51mm) filters. Filters should be checked monthly and blockage which may have occurred.
replaced when necessary with filters of like kind and
Clean burners as follows:
size. Take note of air flow direction marking on filter
frame when reinstalling filters. See figure 38. 1- Turn off both electrical power and gas supply to unit.
Note - Filters must be U.L.C. certified or equivalent for use 2- Open burner compartment access panel.
in Canada. 3- Remove screws securing burner assembly to burner
B-Lubrication support and remove assembly. See figure 39. Clean
as necessary.
All motors are lubricated at the factory. No further
lubrication is required. BURNER BOX AS
SEMBLY
REMOVE FILTERS GAS 480KBTUH SHOWN
VALV BURNER ASSEMBLY
E SECURED WITH
MULTIPLE SCREWS
PULL TO
REMOVE
FILTERS
GAS
MANIFOLD
FIGURE 39
Page 48
7- Replace access panel.
WARNING 8- Restore electrical power and gas supply. Follow
Danger of explosion. Can cause injury lighting instructions attached to unit and use
or death. Do not overtighten main inspection port in access panel to check flame.
burner mounting screws. Snug tighten
only. D-Combustion Air Inducer (Gas Units)
A combustion air blower proving switch checks
IGNITOR combustion air inducer operation before allowing power
to the gas controller. Gas controller will not operate if
SPARK GAP inducer is obstructed.
SHOULD BE
1/8” (3mm) Under normal operating conditions, the combustion air
inducer wheel should be checked and cleaned prior to the
heating season. However, it should be examined
periodically during the heating season to establish an
ideal cleaning schedule. With power supply
disconnected, the condition of the inducer wheel can be
determined by looking through the vent opening.
Clean combustion air inducer as follows:
Page 49
IGNITOR AND SENSOR POSITION
IGNITOR SENSOR
A A
B B
TOP VIEW
C C
1-3/4”
1-3/8” (45mm)
(35mm)
13/16” 3/8”
(21mm) (10mm)
BURNER BOX
FIGURE 41
5- Return combustion air inducer motor and vent HEAT EXCHANGER ASSEMBLY
connector to original location and secure with
retained screws. It is recommended that the
HEAT
combustion air inducer gasket be replaced during EXCHANGER
reassembly. TUBE
Page 50
F-Evaporator Coil H-Condenser Coil
Inspect and clean coil at beginning of each cooling season. Clean condenser coil annually with water and inspect
Clean using mild detergent or commercial coil cleaner. monthly during the cooling season. Access panels are
Flush coil and condensate drain with water taking care not provided on front and back of condenser section.
to get insulation, filters and return air ducts wet. Clean the all-aluminum coil by spraying the coil steadily
G-Supply Air Blower Wheel and uniformly from top to bottom. Do not exceed 900 psi or a
45 angle; nozzle must be at least 12 inches from the coil
Annually inspect supply air blower wheel for accumulated dirt face. Take care not to fracture the braze between the fins
or dust. Turn off power before attempting to remove access and refrigerant tubes. Reduce pressure and work
panel or to clean blower wheel. cautiously to prevent damage.
Page 51
START-UP REPORT
Job Name:___________________________________ Inspections and Checks
Store No.___________Start-Up Date:______________ Damage? Yes No R22 R410A
Address:_____________________________________ If yes, reported to:____________________________
City:______________________________State:______
Verify factory and field-installed accessories.
Start-Up Contractor:____________________________
Check electrical connections. Tighten if necessary.
Technician:___________________________________
Supply voltage: L1-L2______L1-L3_____L2-L3_____
Model No.:___________________________________
If unit contains a 208-230/240 volt transformer:
Serial No.:____________________________________ Check primary transformer tap
RTU No.:________ Catalog No.:__________________ Transformer secondary voltage: __________
Cooling Checks
Page 52