Grouped Protection Settings (ST) 4 Settings

Menu Text Col Row Default Setting Available Setting


Description
CB Fail Settings 45 01

Fdr CBF Reset by 45 02 I< and 52a 52a / I< / I< and 52a
only for Feeder CB; for coupler CB, it's fixed to I<
Setting which determines the conditions to reset the feeder circuit breaker fail. “I< and 52a” means that disappearance of the
current (I<) AND circuit breaker auxiliary contacts open will reset the feeder circuit breaker fail.
Note: Coupler CB fails are always reset with current reset (I<) criterion, whatever the choice of ‘Fdr CBF Reset by’ setting.
From Setting that determines the circuit
I< Current Set 45 05 5%
breaker fail reset criteria. to step
Setting that determines the circuit breaker fail reset criteria.
From Setting for the circuit breaker fail timer
CB Fail 1 Timer 45 07 50ms
stage 1 (retrip) for internal initiation. to step
Setting for the circuit breaker fail timer stage 1 (retrip) for internal initiation.
From Setting for the circuit breaker fail timer
stage 2 (backtrip) for internal initiation. Must be
CB Fail 2 Timer 45 09 200ms
at least 40ms greater than CB Fail 1 Timer to
step
Setting for the circuit breaker fail timer stage 2 (backtrip) for internal initiation. Must be at least 40ms greater than CB Fail 1
Timer
From Setting for the circuit breaker fail timer
CB Fail 3 Timer 45 0A 50ms
stage 1 (retrip) for external initiation. to step
Setting for the circuit breaker fail timer stage 1 (retrip) for external initiation.
From Setting for the circuit breaker fail timer
stage 2 (backtrip) for external initiation. Must
CB Fail 4 Timer 45 0B 200ms
be at least 40ms greater than CB Fail 3 Timer
to step
Setting for the circuit breaker fail timer stage 2 (backtrip) for external initiation. Must be at least 40ms greater than CB Fail 3
Timer
I> Status 45 0E Disabled Disabled or Enabled
To enable (activate) or disable (turn off) the overcurrent confirmation for the start of the circuit breaker fail function
From If “I> Status” is enabled, pick-up setting
I> Current Set 45 0F 120%
for overcurrent confirmation to step
If “I> Status” is enabled, pick-up setting for overcurrent confirmation
T1 45 10

Fdr CBF Reset by 45 11 I< and 52a 52a / I< / I< and 52a
only for Feeder CB; for coupler CB, it's fixed to I<
Setting which determines the conditions to reset the feeder circuit breaker fail. “I< and 52a” means that disappearance of the
current (I<) AND circuit breaker auxiliary contacts open will reset the feeder circuit breaker fail.
Note: Coupler CB fails are always reset with current reset (I<) criterion, whatever the choice of ‘Fdr CBF Reset by’ setting.
From Setting that determines the circuit
I< Current Set 45 12 5%
breaker fail reset criteria. to step
Setting that determines the circuit breaker fail reset criteria.
From Setting for the circuit breaker fail timer
CB Fail 1 Timer 45 13 50ms
stage 1 (retrip) for internal initiation. to step
Setting for the circuit breaker fail timer stage 1 (retrip) for internal initiation.
From Setting for the circuit breaker fail timer
stage 2 (backtrip) for internal initiation. Must be
CB Fail 2 Timer 45 14 200ms
at least 40ms greater than CB Fail 1 Timer to
step

P746/EN ST/Pb2 Page (ST) 4-45