Ad 30560

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Application Data

30-560
Page 1

January 2001
Supersedes Application Data 30-560,
Dimensions not to be used for construc-
tion purposes. Contact Busway Marketing
Cutler-Hammer
pages 1-28, dated March 1996 to confirm dimensions.

Busway Systems

In This Section
Item Page
Pow-R-Way II Design (225-400
Amps Only) 2, 3, 7
Pow-R-Way Design (600-5000
Amps 4-6, 8, 9
Fittings 10-21
Hangers 22
Plug-in Devices 23-25
Line-to-Line Voltage Drop 26
Engineering, Test Data 27
Dimensions and Weights 27
Typical Specifications 28

Warning: There is a hazard of electri-


cal shock or burn whenever working
in or around electrical equipment.
Application Data
30-560
Page 2 Cutler-Hammer

Pow-R-Way® Busway Systems


Pow-R-Way II Busway An optional 50% internal ground bar is and are identical to the plug-in openings
(225-400 Amperes Only) available in either copper or aluminum. of 600A through 4000A Pow-R-Way. Thus,
Eaton’s Cutler-Hammer Pow-R-Way II The ground bar is bolted to the housing at plug-in units are interchangeable with all
single bolt per bar busway (225 and 400 each joint, thus ensuring a good ground ratings or Pow-R-Way. (See photo below.)
amperes only) was designed to provide an path through the entire housing.
Joint
economical system, yet meet the speci- Plug-in Openings
fication which are the most important. The joint of Pow-R-Way II utilizes one cap-
Totally enclosed and non-ventilated, it is Plug-in openings are on 24-inch centers
available in indoor plug-in and indoor
feeder which can be used interchangeably
without adaptors or special splice plates. Typical Plug-in Straight Length
(Not available for outdoor applications.)
Pow-R-Way II is available with aluminum
or copper bus bars in ratings of 225 and
400 amperes only. The following systems
are available:
3-phase, 3-wire
3-phase, 3-wire with 50% internal
ground
Plug-in Straight Length With Side Channel Removed
3-phase, 4-wire, full neutral
3-phase, 4-wire, full neutral with 50%
internal ground
All 3-wire systems have a maximum volt-
age rating of 600 volts and all 4-wire sys-
tems have a maximum of 347/600 volts.
Pow-R-Way II can be mounted in flatwise,
or edgewise, without derating. When the
busway is mounted with the bus bars in Typical Construction Details
the flatwise position, hangers may be on
10 ft.-0 in. max. centers. When the bus-
way is mounted with the bus bars in
the edgewise position, hangers must
be on 5 ft.-0 in. max. centers. Fire-
stops are required when passing through
walls or floors. When applying Pow-R-Way
II in vertical risers, the Busway Division
must be advised.
Pow-R-Way II busway is listed by Under-
writers Laboratories, Inc. and is manufac-
tured in accordance with NEMA standards
for busway.
Construction
Housing
Pow-R-Way II busway uses an all bolted
housing. It is pretreated and then painted
ANSI #61 gray baked-on enamel applied
by an electro-coat process. (See typical
construction details.)
Bus Bars
The bus bars run straight through the
housing and remain on 13/16 inch centers.
They are insulated their entire length by a
uniform layer of epoxy which is a Class B
(130oC) material. This insulation is applied
utilizing the fluidized bed process. The
bus bars are silver plated at all contact
surfaces. The bus bars are held firmly in
place by high strength molded polyester Typical Plug-in Opening
glass insulators.

March 2001
Application Data
30-560
Cutler-Hammer Page 3

Pow-R-Way® Busway Systems


tive bolt per bar making for as labor-free Exploded View of Joint Details
a joint connection as possible. The left
end of every section of Pow-R-Way II has
offset bus bars with 5/16 inch diameter
hex head bolts which are held captive
by threaded steel inserts. Hex head bolts
have flanged head which evenly distrib-
utes pressure over the entire width of the
bus bar. The right end has straight bus
bars with open slots.
The ends of the bus bars are staggered
to assure adequate electrical clearances
between phases. The joint is made up by
simply tightening the joint bolts to 20-25
ft.-lbs. and then installing the two joint
covers.
Tightening the four captive bolts on each
joint cover completes the assembly and
provides a good mechanical connec-
tion between sections. The joint covers
are identical with the ones used on 600
through 5000 ampere Pow-R-Way.
Assembled Joint Without Covers

Assembled Joint

March 2001
Application Data
30-560
Page 4 Cutler-Hammer

Pow-R-Way® Busway Systems


Pow-R-Way Busway Full rounded edge bus bars (6) are avail-
(600-5000 Amperes) able in either high strength 55% minimum
The Cutler-Hammer Pow-R-Way (600-5000 conductivity aluminum or 98% conductiv-
amperes) busway is totally enclosed and ity pure copper. The bus bars are silver
non-ventilated, it is available in three plated at all contact surfaces.
forms: outdoor feeder, indoor feeder,
Each bus bar is covered with a uniform
and indoor plug-in which can be used
interchangeably without adaptors or
special splice plates. This eliminates the
need for a variety of busway types in the
construction of a complete low-voltage
power distribution system. One set of fit-
tings-elbows, tees, flanges, etc. has been
designed for use with both the plug-in
and feeder types of POW-R-WAY busway,
complementing even more the flexibility
of the POW-R-WAY system.
Construction
General
POW-R-WAY busway is one basic design
which can be supplied as indoor plug-in,
indoor feeder, or outdoor feeder. POW-R-
WAY busway is available with aluminum
bus bars in ratings from 600-4000 amps.
and with copper bus ratings from
600-5000 amps.
The following systems are available:
3-phase, 3-wire
3-phase, 3-wire with 50% internal
ground
3-phase, 4-wire, FN
3-phase, 4-wire, FN, with 50% internal
ground
All 3-wire systems have a maximum
voltage rating of 600 volts and all 4-wire
systems have a maximum of 347/600
volts. One hanger is supplied for every 10
feet of horizontally mounted duct. POW-R-
WAY busway can be mounted in flatwise,
edgewise, or vertical positions without
derating. POW-R-WAY busway is listed
by Underwriters Laboratories, Inc. and is
manufactured in accordance with NEMA
standards for busway.
Housing (See right)
The duct housing is made of 14 and 16
gauge steel. It is bonderized inside and
outside and given one coat of ASA #61
light gray baked-on enamel applied by an
electro-coat process. The bottom channel
is spot welded to the “C” covers (1) and
the top channel is bolted to the “C” covers
using 1/4-20 high tensile strength (100,000
psi) bolts, located on 4-inch max. centers.
Bus Bar and Insulation (See below)

March 2001
Application Data
30-560
Cutler-Hammer Page 5

Pow-R-Way® Busway Systems


layer of epoxy insulation (5), which is Exploded View of Joint Details
a Class B (130oC) material. This epoxy
insulation is applied by the fluidized bed
process, which ensures a smooth, even,
continuous insulation and eliminates hand
taping.
An optional 50% internal ground bus bar
(2) is available in either copper or alumi-
num.
Joint
Bus bars on the left-end (bolt end) of a
busway section are flared out and have a
closed slot. The left end also has an insu-
lated captive joint bolt. This joint bolt must
be tightened to 30 ft.-lbs. torque for 2-inch
and 21/2-inch wide bus bars, and 60 ft.-lbs.
torque for 3-inch and wider bus bars. For
6-inch, 61/2-inch and 71/2-inch wide bus bars,
two joint bolts are used to assure good
electrical contact between bus bars. Bolt
retainers, which keep bolt head from turn-
ing, can easily be moved to the opposite
side of the duct by removing two #10-32
retainer screws. Also captive to the left-end
are two belleville washers which evenly
distribute pressure over the entire contact
area.
High strength molded polyester glass joint
insulators are inserted between opposite
phases of bus bars and between bus bars
and the housing. This provides adequate
over the surface electrical clearances and
mechanical strength for the joint.
Bus bars on the right-end (slot end) of a
busway section are flared and have an
open slot to accept the captive joint bolt.
Joint insulators on this end also have an
open slot.
Joint covers with captive hardware
complete the housing joint giving a good
mechanical connection between sections.
The same universal joint cover is used for
all ratings of Pow-R-Way, 225-5000
Amperes, both plug-in and feeder.
Note: Pow-R-Way plug-in design with bus
bars under 3-inch wide (225-600 Alumi-
num or 225-800A Copper) requires 101/4
inches to joint centerline when passing
through walls or floors. This is necessary
to keep joint covers clear of walls and
floors.

March 2001
Application Data
30-560
Page 6 Cutler-Hammer

Pow-R-Way® Busway Systems


Plug-in Openings Outdoor Pow-R-Way Design
Splice Cover

Drain Holes
Sealing Compound

Removable Drain Plug


Plug-in openings are on 24-inch centers.
Plug-in opening doors have a formed
hinge and remain on duct at all times.
At each plug-in opening, the bus bars are Joint Gaskets
flared out to 13/16-inch centers to allow
plug-in stabs to engage bus bars. High
strength molded polyester glass plug-in
insulators provide protection of the duct Drain Holes
in the event of stresses due to a fault and
provide full isolation of the stabs of any
plug-in device installed on the duct.
Joint Cover

Pow-R-Way outdoor duct is the same • Housing is of galvanized steel and has
design as indoor duct except for the fol- drain holes.
lowing features as shown above: • All seams are sealed with sealing
• Gasket splice plates with removable compound.
drain plugs are supplied to cover joint
bolt. CAUTION
• Special outdoor joint covers with After Busway Joint has been assembled,
removable drain plugs. remove and discard all rubber drain plugs
located on the underside of the duct.
• All four sides of duct have neoprene
gasketing to seal out all water. Pow-R-Way II Straight Lengths

Assembled Joint, Outdoor Pow-R-Way

March 2001
Application Data
30-560
Cutler-Hammer Page 7

Pow-R-Way® Busway Systems


(225-400 Amperes Only) Indoor Only
Plug-in Straight Lengths
Straight lengths of Pow-R-Way II plug-in
busway are supplied only in 2, 4, 6, 8 and
10 foot lengths to maintain 24-inch spac- Typical Plug-in Straight Length
ing for plug-in openings.
Risers
Refer to Cutler-Hammer.

Feeder Straight Lengths


Straight lengths of feeder busway can be
supplied in any length from 24-inch to
10-feet.

Typical Feeder Straight Length

Dimensions in Inches

March 2001
Application Data
30-560
Page 8 Cutler-Hammer

Pow-R-Way® Busway Systems


Pow-R-Way Straight Lengths
(600-5000 Amperes)
Plug-in Straight Lengths
Straight lengths of plug-in busway are
supplied only in 2, 4, 6, 8, and 10 foot
lengths, with the exception that 2-feet
lengths are not available in aluminum for
600 amps, and in copper for 600 and
800 amps.
In all two and three bar per phase ar-
rangements, tie bars between like phases
are added in order to electrically balance
the busway.
Figures A through D illustrate configura-
tion of duct for available ampere ratings.
See Table A for reference to proper figure.
Table B shows number of plug-in open-
ings available for standard lengths.

Dimensions in Inches
March 2001
Application Data
30-560
Cutler-Hammer Page 9

Pow-R-Way® Busway Systems


Pow-R-Way Straight Lengths Straight lengths of feeder busway can be
(600-5000 Amperes) supplied in any length from 24 in. to
10 ft.-0 in.
Feeder Straight Lengths
Figures A through D illustrate configura-
tion of duct for available ampere ratings.
See table below for reference to proper
figure.

Dimensions in Inches
March 2001
Application Data
30-560
Page 10 Cutler-Hammer

Pow-R-Way® Busway Systems


Fittings for Pow-R-Way II and Upward
Pow-R-Way Busway
There is a basic fitting to meet every ap- Rearward
plication need: flanges, elbows, offsets,
tees, cable tap boxes, weatherheads,
transformer connections, power take off
sections, reducers, adapter cubicles, expan-
sion joints and end closers. These fittings, Forward
along with standard and minimum dimen-
sions are described on the following pages.
When making field measurements and
layouts, it should be remembered that
dimensions of fittings are given from Downward
the centerline of the busway. Rela-
tionship of fitttings to straight lengths is
illustrated at right.
Assembled sections of busway are marked
“T” for top and “F” for front. When assem-
bling the system, “T” and “F” markings of
adjacent sections must match.

Flanges➀ coordination between busway and any section, as required. Minimum dimen-
Flanges join busway housing to the equipment, detailed drawings must ac- sions are shown in the tables below.
switchgear or other apparatus and include company the order.
standardized bus extensions for electrical
connection. Flange can be supplied on left or right of

When busway extends into switchgear,


switchboards or motor control centers,
the opening and flange drillings must be
provided by the switchgear builder. In
which case, the cutout dimensions and
drilling plan must be followed. For proper

Flush Flanges
Flush Flange is used when duct must lay
flat on top of a switchboard. Flange can be
supplied on left or right end of section, as
required. Extensions can extend out of top
or bottom as required.

➀ Flange hardware to be supplied by others.


➁ Dimensional purposes only. Pow-R-Way II is
standard design in this rating.

March 2001
Application Data
30-560
Cutler-Hammer Page 11

Pow-R-Way® Busway Systems


Fittings, Continued

Elbows
Elbows are used to make 90o changes in
the direction of busway runs. There are
four types available.
See minimum leg lengths in tables.

➀ Pow-R-Way II is standard design in this rating.

March 2001
Application Data
30-560
Page 12 Cutler-Hammer

Pow-R-Way® Busway Systems


Fittings, Continued

Elbow Flanges➀
Flanges can be supplied on end of right or
left leg as required. Minimum leg lengths
are shown below.

➀ Flange hardware to be supplied by others.


➁ Pow-R-Way II is standard design in this rating.

March 2001
Application Data
30-560
Cutler-Hammer Page 13

Pow-R-Way® Busway Systems


Fittings, Continued

Offsets
An offset is used to avoid obstacles and
to conform with building structure. It is
simply two elbows fabricated into one
unit for use where it is impossible to use a
standard elbow because of space restric-
tions.
Minimum leg lengths are shown below.

➀ Pow-R-Way II is standard design in this rating.


➁ For outdoor duct, add 13/4 inches.

March 2001
Application Data
30-560
Page 14 Cutler-Hammer

Pow-R-Way® Busway Systems


Fittings, Continued

Tees
A tee is a busway fitting suitable for connection in three directions. Minimum lengths
are shown below.

➀ Pow-R-Way II is standard design in three rating.


➁ For outdoor duct, add 13/4 inches.
➂ For outdoor duct, add 1 inch.

March 2001
Application Data
30-560
Cutler-Hammer Page 15

Pow-R-Way® Busway Systems


Fittings, Continued

Crosses
A cross is a busway fitting suitable for
connection in four directions. It is used
where a run of duct branches off in three
directions in the same plane.

Dimensions in Inches

Expansion Joint
Expansion joints accommodate the ex-
pansion and contraction of bus bars with
respect to the enclosure. They are neces-
sary to compensate for the difference in the
coefficient of expansion of steel housing and
copper or aluminum bus bars.
An expansion joint should be installed in the
center of extremely long runs of the busway.
If such runs have an end closer at one end,
so that the bus bars are free to move, or if
the run contains elbows, expansion joint
may be omitted.
Expansion joints must also be used wher-
ever a run of busway crosses an expansion
joint in a building. The use of expansion
joints should be engineered for individual
installations.

➀ Dimensional purposes only. Pow-R-Way II is standard


design in this rating.
➁ 225A and 400A (Pow-R-Way II) is 51¦32 inches total width.
➂ B dimension is centered on “F” side of duct.

March 2001
Application Data
30-560
Page 16 Cutler-Hammer

Pow-R-Way® Busway Systems


Fittings, Continued

End Cable Tap Box


End cable tap boxes are used where a run the duct is connected without overcurrent
of duct is fed at the end by cable and protection.
conduit, or where equipment served by

➀ Pow-R-Way II is standard design in this rating. Note: Add 1/4 inch to A, B dimensions for
➁ For outdoor end cable tap box add 1/4 in. to A and B dimensions, 1/8 in. to E dimension outdoor cable tap box and “T” must be on
and 2 in. to G dimension and “T” must be on top for horizontal runs. top for horizontal runs.
➂ #6-250 MCM lugs.

Center Cable Tap Box


Center cable tap boxes are used where the duct is connected without overcurrent
a run of duct is center fed by cable and protection.
conduit, or where equipment served by

➀ Pow-R-Way II is standard design in these rating.


➁ Add 2 inches for outdoor cable tap box.
➂ #6-250 MCM lugs.

Plug-in Cable Tap Box Removable


Plug-in cable tap boxes are used to feed
the busway run, or where equipment

served by the busway is connected with-


out overcurrent protection. Plug-in cable
tap boxes plug into any Pow-R-Way bus-
way (225-4000 amps) plug-in openings.

March 2001
Application Data
30-560
Cutler-Hammer Page 17

Pow-R-Way® Busway Systems


Fittings, Continued

A weatherhead is used where power is fed End closers terminate run of duct and can
into a building by cable from a utility ser- be used to close either the right or left
vice drop, or from a transformer. Cables end.
enter bottom of weatherhead per N. E. C.
drip loop requirements.
➀ T and F marking must be shown.

March 2001
Application Data
30-560
Page 18 Cutler-Hammer

Pow-R-Way® Busway Systems


Fittings, Continued Transformer Taps

Single-Phase Transformer Tap


This type of transformer tap arrangement
is used when making connections to three
single-phase transformers. The bus exten-
sions do not include drilling or lugs unless
specified on the order.

Three-Phase Transformer Tap


This type of transformer tap arrangement
is used when making connections to a
3-phase transformer. The bus extensions
do not include drilling or lugs unless
specified on the order.

➀ Pow-R-Way II is standard design in these


ratings.
➁ For outdoor duct, add 31/2 inches.
➂ For outdoor duct, add 3/4 inch.

Transformer Throat Connections


All transformer throat connections include
flexible connectors between transformer
low-voltage studs and bus bars. For trans-
former with drilled flanges, busway will bolt
to throat instead of using a
sealing ring.

March 2001
Application Data
30-560
Cutler-Hammer Page 19

Pow-R-Way® Busway Systems


Power Take-off Sections➁➂
Power take-off sections are used in the following situations:
1. To take large amounts of power off a run (beyond the current
carrying capabilities of plug-in stabs).
2. Where space restrictions dictate that the wide dimensions
of the busway be flat against a wall or ceiling or other obstruc-
tions, bolt-on units are used instead of plug-in units.
3. Where panelboards are mounted on busway.
The plug-in power take-off is a design that permits the take-off
of power (1600A max.) at a standard plug-in opening. The mold-
ed insulator in the opening is removed completely. The power
take-off conductor is inserted into the opening until contact is
made with the bus bars in the bus duct. A single bolt design in
the power take-off is then torqued to 60 ft.-lb., permitting 1600A
maximum capacity.
The bolt-on circuit breaker, fusible switch or tap box is then
bolted to the power take-off by solid buswork. The plug-in power
take-off cannot, in itself, be used as a cable tap box. An overcur-
rent protective device must be priced with the power take-off.
This device for load applications as shown.

➀ Right leg must be 24 inches.


➁ When laying out the bus run, “T” and “F” must be shown.
➂ Built-in power take-off device, 1250-amp max.

Dimensions in Inches

Built-in Power Take-off (1250 Amp Max)

Dimensions in Inches

March 2001
Application Data
30-560
Page 20 Cutler-Hammer

Pow-R-Way® Busway Systems


Fittings, Continued service entrance.) Meter Center Fusible Switch
The main meter center fusible switch can
Non-Fused Reducers Flatwise-to-flatwise, reduces to left or also be used in conjunction with a Pow-R-
Non-fused reducers are used to reduce right. Way plug-in unit. With this device, busway
the capacity of busway without overcur- ➀ Pow-R-Way II is standard design in this rating. can be applied to feed meter stacks. These
rent protective devices. No overcurrent ➁ N. E. C. Class H fuses. main service cubicles can be utilized with
protection is required where busway is ➂ Class L fuses. either left-or right-hand bus tap connec-
reduced in size, provided the length of the ➃ For height and width dimensions, refer to Cutler- tions as required by building layout. The
Hammer.
smaller duct does not extend more than Busway Plug-In Unit for Connection to
meter stacks are then added to the fusible
50 feet and has a current rating of at least switch cubicle on the side opposite the
1/3 of the overcurrent device next back on bus tap flange. (Not approved for service
the line. (See NEC Section 364-11.) entrance.)
Circuit Breaker or Fused Reducer For 400- and 600-amp only.
Reducer cubicles are available with either
a circuit breaker or fused non-automatic
circuit breaker to furnish overcurrent
protection and serve as a disconnecting
means. Reduction in bus capacity is made
within the cubicle. The line side of the
cubicle is connected to the large rating
of duct and the load side to the reducing
rating of duct. (Not approved for use as

Dimensions in Inches

Dimensions in Inches

March 2001
Application Data
30-560
Cutler-Hammer Page 21

Pow-R-Way® Busway Systems


Miscellaneous Fittings

Wall Flanges Roof Flange


A roof flange should be used with outdoor duct where the duct penetrates the roof.

Wall/floor flanges are used to fit around


busway and close off hole in wall or floor
where duct penetrates.

Dimensions in Inches

Joint Puller
A joint puller is available to assist in joining two sections of duct.

March 2001
Application Data
30-560
Page 22 Cutler-Hammer

Pow-R-Way® Busway Systems


Hangers for Horizontal Mounting
One hanger is supplied for every 10 feet of horizontally mounted busway. Type of hanger
supplied is determined by the specific mounting requirements of the duct. Types of hang-
ers are shown below. Drop rods (1/2 in. dia.) must be furnished by customer.

Dimensions in Inches

Hangers for Vertical Mounting


When busway is to be installed vertically,
a spring suspension type hanger is fur-
nished. This unique hanger equalizes the
weight of vertically mounted duct among
all supports. A vertical hanger must be
used on each floor and at the end of the
busway on the last floor. The maximum
span permitted by UL on vertical hang-
ers is 16 feet. Intermediate hangers are
required if floor heights exceed 16 feet.
Note: Vertical hangers must be priced as
part of busway.


▲ ▲
Edgewise
Flatwise
Dimensions in Inches

March 2001
Application Data
30-560
Cutler-Hammer Page 23

Pow-R-Way® Busway Systems


Plug-in Protective Devices Interlock Defeater
All Pow-R-Way and Pow-R-Way II plug-
in units (both circuit breaker and fusible Load End
types) have the following features: Dual Purpose
Interlock
Personnel Safety (See Fig. 1)
Plug-in units have a dual purpose interlock
Neutral
to prevent cover from being opened while Stab
the device is in the “ON” position and to
prevent accidental closing of the device
while cover is open. This dual purpose
interlock may be defeated if necessary for
maintenance.
The plug-in unit and the busway are
interlocked to ensure that the device is in
the “OFF” position prior to installation or Ground
removal from the unit (Fig. 2). Stab

The plug-in enclosure is grounded to the


busway housing before the phase and
neutral stabs make contact with the bus-
way bus bars.
The operating handle remains in control Fig. 1. Open View Plug-in Units
of the disconnect device at all times.
All plug-in units are polarized to make it
impossible to put plugs on backwards and
have neutral stab touch a phase bar.
The clamp and guide are designed to
allow plug-in units to be hung in place on
horizontal runs prior to insertion of stabs.
Flexibility (See Fig. 3)
Two-position handle location allows
handle to be mounted on the end of the
unit for horizontal runs or on the side of Interlock
the unit for vertical runs. (Accessible) Interlock
(Not Accessible)
Neutral stab and ground stab are field
mountable.
Backfeeding is an industry-acknowledged Fig. 2. Plug-in Unit Mounted on Busway
practice whereby incoming power is fed
into the load side of a plug-in unit to feed
a busway run. UL permits “backfeeding”
a circuit breaker, providing it has a non-
interchangeable trip or is a Seltronic-type
breaker.
UL will not permit “backfeeding” a
TRI-PAC® type circuit breaker or a fusible
plug-in device.
Using Cutler-Hammer Series C circuit
breaker bus plugs, system interrupting
ratings can be increased up to 100K AIC
(480V) or 200K AIC (240V) when F-(150A),
J-(250A), or K-(400A) frames are used. By
changing out the breaker only and leav-
ing the enclosure intact, this allows for
flexibility to deal with system short circuit Handle Mounted for Handle Mounted
availability changes (up to the rating of Horizontal Run for Vertical Run
the busway), as well as downstream pro-
tection through series ratings.
Fig. 3. Universal Handle Mounting

March 2001
Application Data
30-560
Page 24 Cutler-Hammer

Pow-R-Way® Busway Systems


Ground Detector and Neutralizer PC SELTRONIC™ Plug-in Device Mounting
Plug-in Breaker Cubicle The load end of a plug-in unit varies with
24”
the orientation of the busway as deter-
mined by the “F” and “T” markings. See
drawings below.

273¦8”

3000 Ampere Seltronic Circuit Breaker

In rare cases, bus bars in a busway sys- In today‘s complex distribution systems
tem pick up static electricity. In order to sophisticated solid-state tripping charac-
discharge this potential, a neutralizer plug teristics are sometimes required on circuit
is available which also serves as a ground protective devices. The PC Seltronic circuit
detector. The unit has three 18,000 ohm breaker can be used as a main breaker in
resistors connected between the bus bars a run of duct or as branch feeder protec-
and the ground. Static electricity is dis- tion. They are available 600 through 3000
charged through these resistors. A neon amperes with interrupting ratings up to
lamp is placed in series with the bus bar 100,000 AIC symmetrical at 600 volts.
and part of the resistor and burns continu-
ously. If there is a ground anywhere on (Not approved for use as service entrance
the system which is of lower resistance equipment.)
than the path through the lamp, the lamp
will go out, indicating that there is a short
in the system. For 3-phase, 3-wire systems
only.
Plug-in Combination Starters and Con-
tactors
Starter Transformer

Control
Circuit
Fuse

MCP or
Breaker

Plug-in combination starters or contactors A 120-volt control transformer fused on the


are mounted in enclosures identical to the secondary, selector switches and indicating
standard circuit breaker or fusible switch lights are available as optional items.
enclosure including safety interlocks and
two-position handle location. They are Provisions for neutral stab and/or ground
available from size 0 through size 4 with a stab are provided. For outline dimensions
circuit breaker, MCP or fusible disconnect. of enclosure refer to Cutler-Hammer.

March 2001
Application Data
30-560
Cutler-Hammer Page 25

Pow-R-Way® Busway Systems


Dimensions and Weights, Plug-in Units

Dimensions in Inches

March 2001
Application Data
30-560
Page 26 Cutler-Hammer

Pow-R-Way® Busway Systems


Dimensions and Weights, Bolt-on Units and Bus Bars

Dimensions in Inches

Dimensions in Inches
March 2001
Application Data
30-560
Cutler-Hammer Page 27

Pow-R-Way® Busway Systems


Line-to-Line Voltage Drop Derating Chart for Higher Ambient
The tables below give average 3-phase voltage drop per 100 feet Temperatures
at rated current and varying power factor. Line-to-neutral volt- POW-R-WAY busway may be operated
age drop is obtained by multiplying the line value by .577. continuously at its assigned ratings
without exceeding the maximum hot-
spot temperature rise of 55oC, provided
the ambient temperature does not
exceed 40oC. For higher ambient tem-
peratures, the ratings should be reduced
by applying the appropriate multiplier
shown in chart.

March 2001
Application Data
30-560
Page 28

Pow-R-Way® Busway Systems


o
Typical Specifications For for tightening or inspection of the joint. Any a 40 C ambient temperature. The busway shall
POW-R-WAY Busway one section of the duct should be remov- withstand for one minute, without breakdown, the
able without disturbing adjacent pieces. All application of 2200 volts of
General hardware required to make up an indoor 60-Hertz alternating potential between conductors,
The feeder and/or plug-in busway shall joint shall be captive. and between conductors and the enclosure. Each
consist of either aluminum or copper piece of Pow-R-Way busway is given a 5000-volt
Bus Bars Ac high pot. Test after assembly to ensure that the
conductors in a totally enclosed housing
and shall be capable of being mounted in All bus bars shall be fabricated from either insulation system is properly applied.
any position without derating. Plug-in and high-strength, 55% conductivity aluminum
or all shall be of 98% conductivity cop- Plug-In Units
feeder sections shall be interchangeable Where required, plug-in units of the types
without the use of special adapter joint cov- per. Bus bars shall be silver plated at all
electrical contact surfaces. Bus bars shall and ratings indicated on the plans and
ers. The complete installation shall be co- specifications shall be supplied. Plug-in
ordinated throughout and, where possible, be insulated over their entire length, except
at joints and contact surfaces, with epoxy units shall be Underwriters Laboratories,
shall consist of standard 10-foot sections Inc. listed. Plug-in units shall be mechani-
with special sections and fittings provided insulation applied by the fluidized bed
process. This insulation shall be Class B cally interlocked with the busway housing
to suit the installation. Horizontal runs of to prevent their installation or removal
busway shall be suitable for hanging on 10 (130oC).
while the switch is in the “ON” position. The
ft.-0 in. maximum support centers. Verti- Plug-in Openings enclosure of any plug-in unit shall make
cally mounted busway shall be approved On plug-in type busway a suitable support positive ground connection to the duct
for that purpose and one adjustable vertical shall be provided at each plug-in opening to housing before the stabs make contact with
hanger shall be provided for 16 ft.-0 in. provide protection of the duct in the event the bus bars. A ground stab shall be provid-
maximum support centers. Where required, of stresses due to a fault and to provide ed, where required, to engage the busway
busway suitable for outdoor service shall full isolation and polarization of the stabs internal ground bar. All plug-in units shall
be supplied. An internal ground bar of 50- of any plug-in device installed in the duct. be equipped with a defeatable interlock to
percent capacity shall be supplied where When an internal ground bar is included in prevent the cover from being opened while
called for on the plans or drawings. All the busway, the plug-in support shall also the switch is in the “ON” position and to
material and installation shall comply with provide for its positive engagement by the prevent the accidental closing of the switch
the applicable standards, practices, and grounding stab of the plug-in device. while the cover is open. The plugs must be
codes of ASA, IEEE, NEMA and Underwrit- provided with a means of padlocking the
ers Laboratories, Inc. The busway shall be Voltage Drop
The three-phase, line-to-line voltage drop cover closed and the disconnect device in
listed by Underwriters Laboratories, Inc. the “OFF” position. The operating handle
for the feeder busway shall not exceed 3.32
Housing volts per one-hundred feet (concentrated and mechanism must remain in control of
The housing shall be of the non-venti- load) at 80-percent power factor. The volt- the disconnect device at all times. It shall
lated type meeting NEC requirements and age drop for the plug-in busway shall not be possible to mount the handle on either
constructed of code gauge steel which is exceed 1.87 volts per one-hundred feet (dis- the end or the side of the plug-in unit,
pretreated and painted ANSI #61, on both tributed load) at 80-percent power factor. permitting its easy operation from the floor
inside and outside using an electro-coat by means of a hookstick or chain. For safety
process. Plug-in type busway, except for Short-Circuit Bracing reasons, no projections shall extend into
fittings, shall have provisions for plug-in The busway, feeder and/or plug-in, shall be the busway housing, other than plug-in
openings with a hinged outlet cover braced to withstand the maximum avail- stabs, which shall be silver plated. The plug-
provided for each. able short-circuit currents as indicated on in units shall be interchangeable without
the plans and drawings and shall in all alteration or modification on all ratings of
Joint cases be braced for no less than the NEMA Pow-R-Way plug-in bus duct.
The joint design of 600 through 5000 standard for that rating.
ampere busway shall permit safe, practical Fusible type plugs shall have a quick-make,
testing of its tightness without de-energiz- Operating Characteristics quick-break disconnect switch and positive
ing the run. The joint shall be of the single- The busway shall be so designed and pressure fuse clips.
bolt pressure design providing optimum tested that, at rating, the bus bars shall not
exceed a 55oC temperature rise based on The busway shall be Pow-R-Way as manu-
electrical contact and mechanical strength.
factured by Cutler-Hammer or approved
The joint shall be of the overlap type with a
equal.
joint bolt which passes through the overlap
to maintain positive pressure. Access to
only one side of the duct need be required

Cutler-Hammer
Pittsburgh, Pennsylvania U.S.A.
March 2001
Printed in U.S.A.

You might also like