Approval - Material - ACR - Calculation

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GAMUDA LOOK 18

Estimated Gas consumption = 350,000 btu/hr

Total unit = 1

Total gas consumption = Total unit X Effective gas consumption per hour
= 350000 btu/hr

Total effective gas demand = Total gas consumption X (( 0.95/ ( Total unit)^0.3))
= 332500 btu/hr

50 kg cylinder vaporization rate = 100,000 btu/hr

Total gas cylinder require = Total effective gas demand


50 kg cylinder vaporization rate

= 3.325
≈ 4

Conclusion
* Note : Provide 12 nos of cylinders (4 operates and 8 for stanby)
Based on Automatic Changeover Regulators (ACR) catalog, maximum capacity ACR is 1210 000 BTU/Hr

Hence, the ACR proposed is suitable as the energy consumption needed is 35 000btu/hr which is less than
the maximum capacity of the ACR as proposed

You might also like