Professional Documents
Culture Documents
Metering
Metering
CT selection
Tr primary current 500*1000/(1.73*11*1000)
26.27A
25/5A class 0.2s 3nos 15va CT
PT selection
(11/√3KV)/(110/√3V) class 0.2 100VA 3phase
Meter selection
110/√3V /5A 0.2S 3phase 4wire
trivector TOD meter