Tag Description LOGIC valve MOV_1 Description Tag

Manual Open MOV valve


AND
AUTO/MANU selector:
02-YS-001M
Manual position
selected from HMI

02-HS-001M OPEN command HMI

Auto Open MOV valve


AUTO/MANU selector:
02-YS-001
AUTO position selected AND
from HMI

02-BL-MOV-001
02-FQIT-01 NOT
Interlock

02-BL-MOV-001 S OPEN Command 02-HS-001A


02-HS-001
02-WIT-01 NOT
Interlock
Permission for normal Operation R CLOSE Command 02-HS-001B
02-HS-001

02-YS-001 Local/Remote Selector AND

In Remote position

02-XA-001 General fault


NOT

Manuel Close MOV valve

AUTO/MANU selector:
02-YS-001M
Manual position
selected from HMI AND

02-HS-001M CLOSE command HMI

Auto Close MOV valve

AUTO/MANU selector:
02-YS-001
AUTO position selected
from HMI
AND

02-BL-MOV-001
02-FQIT-01
Interlock

02-BL-MOV-001
02-WIT-01
Interlock

Discrepancy Open
fault
MOV-001 OPEN
02-HS-001A
02-HS-001 OPEN command AND Timer FAIL

NOT
02-ZSO-001 OPEN FEEDBACK

Discrepancy close
fault

02-HS-001B MOV-001
02-HS-001 CLOSE command AND Timer
CLOSE FAIL

02-ZSC-001 CLOSE FEEDBACK NOT