AIR-TO-WATER HEAT PUMP

(50Hz/R410A)
5BPU0-03C(Replace:5BPU0-03B)
CONTENTS

Part 1. Indoor Unit(Hydro kit)


Part 2. Outdoor Unit
Part 3. Accessories
Part 1. Indoor Unit (Hydro kit)

1. Features
2. Nomenclature
3. Specification
4. Drawing
5. Wiring Diagram
6. Piping Diagram
7. Operation Range
8. Pump Hydraulic Performance
1. Features
• Providing eco-friendly heating
• High energy efficiency
• Easy installation
• Space heating, cooling, and sanitary water heating

Indoor Unit

Air-to-Water Heat Pump _ 1


2. Nomenclature
2.1 Global Model Name
AH N W 16 A 06 A 1
Serial Number
Chassis Name
Heater Capacity (kW)
Ex) 06 : 6kW Class
Heater Electrical Ratings
6 : 1 phase 220-240V 50Hz
8 : 3 phase 380-415V 50Hz
A : 3 phase 220V 50Hz
Heating Capacity (kW)
Ex) 16 : 16kW Class
Model Type
W : DC Inverter Heat Pump
H : Heat Pump
Classification
Indoor Unit

N : Indoor Unit U : Outdoor Unit - : Set


Air-to-Water Heat Pump for R410A

2.2 Europe Model Name

H N 09 1 4
Heater Capacity (kW)
Ex) 04 : 4kW Class 06 : 6kW Class 09 : 9kW Class
Electrical Ratings
1 : 1 Phase 220-240V 50Hz
2 : 3 Phase 220V 50Hz
3 : 3 Phase 380-415V 50Hz
Classification
09 (Combined with 09kW of Outdoor Unit)
16 (Combined with 12/14/16kW of Outdoor Unit)
N : Hydro kit (Indoor Unit)

H : Air to Water Heat Pump

2 _ Air-to-Water Heat Pump


3. Specification
AHNW166**A1 AHNW168**A1 AHNW16A**A1
Technical Specification
(HN161* NK1) (HN163* NK1) (HN162* NK1)
Nominal Power Input W 205 205 205
Nominal Running Current without Electric Heater A 0.89 0.89 0.89
Operation Range Cooling(Fan coil unit) °C 6 ~ 30 6 ~ 30 6 ~ 30
(Min.~Max.) Cooling(Under floor) °C 16 ~ 30 16 ~ 30 16 ~ 30
Leaving Water Heating(Fan coil unit or Radiator) °C 15 ~ 55 15 ~ 55 15 ~ 55
Temperature Heating(Under floor) °C 15 ~ 55 15 ~ 55 15 ~ 55
Pump Type - Canned type for hot water circulation
Steps of Speed EA 2 (In Max. / Med. / Min., Min. step is not used)
Power Input W 205 205 205
Water Flowrate Limit LPM At least 15.0 At least 15.0 At least 15.0
Heat Exchanger Type - Brazed Plate HEX Brazed Plate HEX Brazed Plate HEX
Number of Plate EA 67 67 67
Quantity EA 1 1 1
Expansion Vessel Volume liter 8 8 8
Water Pressure(Max.) bar 3 3 3
Water Pressure(Pre) bar 1 1 1
Strainer Mesh Size mm 1x1 1x1 1x1

Indoor Unit
Material - Stainless Steel Stainless Steel Stainless Steel
Water Circuit Safety Valve bar 3 3 3
Entering Side Diameter inch Male PT 1 Male PT 1 Male PT 1
Leaving Side Diameter inch Male PT 1 Male PT 1 Male PT 1
Manometer - O O O
Drain Valve / Fill Valve - O O O
Shut Off Valve - O O O
Air Vent - O O O
Refrigerant Circuit Gas Side Diameter mm(inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Liquid Side Diameter mm(inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Dimensions Unit(H x W x D) mm 850 x 490 x 315 850 x 490 x 315 850 x 490 x 315
Packed Unit(H x W x D) mm 1080 x 563 x 375 1080 x 563 x 375 1080 x 563 x 375
Weight Unit kg 54.5 54.5 54.5
(Without water) Packed Unit kg 61.5 61.5 61.5
Sanitary Water Tank Type - Indirect heating(+ Electric heater)
Heater Capacity kW Max. 3
Power Supply Ø / V / Hz 1 / 230 / 50
Power Supply Type - Separated power source
Thermal Protector Range °C Max. 90
Magnet switch - Needed
MCCB A 40
Sensor Adaptor Diameter mm(inch) 12.7 (1/2)
Accessory Kit - LG Supply (model : PHLTA) LG Supply (model : PHLTC) LG Supply (model : PHLTC)

AHNW166**A1 AHNW168**A1 AHNW16A**A1


Electrical Specification
(HN161* NK1) (HN163* NK1) (HN162* NK1)
Electric Heater Type - Sheath Sheath Sheath
Number of Heating Coil EA 2 3 3
Capacity Combination kW 3+3 6 or 9 6 or 9
Operation - Automatic Automatic Automatic
Heating Steps Step 2 2 2
Power Supply Ø / V / Hz 1 / 220-240 / 50 3 / 380-415 / 50 3 / 220 / 50
Rated Current A 25 - -
Maximum Current(MCA) A 32 - -
Note :
1. The specification may be subject to change without prior notice for purpose of improvement.

Air-to-Water Heat Pump _ 3


3. Specification
Technical Specification AHNW09604A1 AHNW09606A1 AHNW09A06A1 AHNW09806A1
(HN0914 NK1) (HN0916 NK1) (HN0926 NK1) (HN0936 NK1)
Nominal Power Input W 135
Nominal Running Current without Electric Heater A 0.59
Operation Range Cooling(Fan coil unit) °C 6~30
(Min.~Max.) Cooling(Under floor) °C 16~30
Leaving Water Heating(Fan coil unit or Radiator) °C 15~55
Temperature Heating(Under floor) °C 15~55
Pump Type - Canned type for hot water circulation
Steps of Speed EA 2 (In Max. / Med. / Min. , Min. step is not used)
Power Input W 135
Water Flowrate Limit LPM At least 15 LPM
Heat Exchanger Type - Blazed Plate HEX
Number of Plate EA 54
Quantity EA 1
Expansion Vessel Volume liter 8
Water Pressure(Max.) bar 3
Water Pressure(Pre) bar 1
Strainer Mesh Size mm 1x1
Indoor Unit

Material - Stainless Steel


Water Circuit Safety Valve bar 3
Entering Side Diameter inch Male PT 1
Leaving Side Diameter inch Male PT 1
Manometer - O
Drain Valve / Fill Valve - O
Shut Off Valve - O
Air Vent - O
Refrigerant Circuit Gas Side Diameter mm(inch) 15.88 (5/8)
Liquid Side Diameter mm(inch) 9.52 (3/8)
Dimensions Unit(H x W x D) mm 850 x 490 x 315
Packed Unit(H x W x D) mm 1,032 x 563 x 375
Weight Unit kg 48
(Without water) Packed Unit kg 55
Sanitary Water Tank Type - Indirect heating (+ Electric heater)
Heater Capacity kW Max. 3
Power Supply Ø / V / Hz 1/ 230 / 50
Power Supply Type - Separated power source
Thermal Protector Range °C Max. 90
Magnet switch - Needed
MCCB A 40
Sensor Adaptor Diameter mm(inch) 12.7 (1/2)
Accessory Kit - LG Supply (model : PHLTA) LG Supply (model : PHLTA) LG Supply (model : PHLTC) LG Supply (model : PHLTC)

Electrical Specification AHNW09604A1 AHNW09606A1 AHNW09A06A1 AHNW09806A1


(HN0914 NK1) (HN0916 NK1) (HN0926 NK1) (HN0936 NK1)
Electric Heater Type - Sheath Sheath Sheath Sheath
Number of Heating Coil EA 2 2 3 3
Capacity Combination kW 2+2 3+3 6 6
Heating Steps Step 2 2 2 2
Power Supply Ø / V / Hz 1 / 220-240 / 50 1 / 220-240 / 50 3 / 220 / 50 3 / 380-415 / 50
Maximum Current(MCA) A 30 32 - -

Note :
1. The specification may be subject to change without prior notice for purpose of improvement.

4 _ Air-to-Water Heat Pump


AWHP
AHNW09***A1 (HN09** NK1)
474 305 AHNW16***A1 (HN16** NK1)
4.1 Internal
4. Drawing

No Name Remarks
1 Refrigerant Pipe Ø15.88mm
2 Refrigerant Pipe Ø9.52mm
3 Entering Water Pipe Male PT 1 inch
4 Leaving Water Pipe Male PT 1 inch
5 Control Panel Built-in Remote Controller
6 Water Pump Max Head 7.5 / 6.5 meter
7 Safety Valve Open at water pressure 3 bar
8 Thermal switch Cut-off power input to electric heater at 90 centigrade (manual return at 55 centigrade)
Cut-off power input to electric heater at 90(primary) and 200(secondary) centigrade (auto
8' Thermal switch
return at 70 centigrade for first thermal switch)

848
9 Control Box PCB and terminal blocks
10 Flow Switch Minimum operation range at 12 LPM
11 Plate Heat Exchanger Heat exchange between refrigerant and water
12 Pressure Gage Indicates circulating water pressure
13 Expansion Tank Absorbing Volume change of heated water
14 Air Vent Air purging when Charging water
15 Electric Heater Additional heating source
16 Strainer Filtering and stacking particles inside circulating water
17 Shut-off valve When connecting water pipes,drain water or block the flow from indoor unit
18 Carrying handle To carry the product
Notice : Item 8 and Item 8’ will be applied exclusively

Note
1. Unit should be installed in compliance with the installation manual in
the product box.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.

[Unit:mm]

Hydro kit

Air-to-Water Heat Pump _ 5


Indoor Unit
Indoor Unit

AWHP
AHNW09***A1 (HN09** NK1)
AHNW16***A1 (HN16** NK1)
4.2 External
4. Drawing

No Name Remarks
1 Door Control panel is shown after this door is opened.

6 _ Air-to-Water Heat Pump


2 Handle Used to cover or uncover the front case

Note
1. Unit should be installed in compliance with the installation manual in
the product box.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.

[Unit:mm]

Hydro kit
AWHP
AHNW09***A1 (HN09** NK1)
Mounting to Wall AHNW16***A1 (HN16** NK1)
Step 1. After releasing eight screws, detach front cover from the indoor unit. While detaching the Step 3. Detach the Installation sheet. Screw bolts with supporting plate at the hole
4. Drawing

front cover, grab the carrying handles at left and right sides of the front cover. Then pull marks on the wall. When screwing bolts, use M8 ~ M11 anchor bolts to
into upward direction. When assemble the front cover, remove detached side brackets of secure hanging the indoor unit.
the front cover and ONLY tighten two screws of bottom.
4.3 For Installation

(Ha
ll m
ark
s)

Bottom
screws
Remove

Step 2. Attach "Installation Sheet" to the wall and mark the location of bolts. This sheet helps to Step 4. Hang the indoor unit at the supporting plate. Also, catch the carrying han-
find correct location to the bolts. dles at left and right sides of the indoor unit.

Hydro kit

Air-to-Water Heat Pump _ 7


Indoor Unit
Indoor Unit

AWHP
AHNW09***A1 (HN09** NK1)
AHNW16***A1 (HN16** NK1)
4. Drawing

Fixation Service Space


4.3 For Installation

8 _ Air-to-Water Heat Pump


250
241

248
200
384

500
1300

350

[Unit:mm]

Hydro kit
5. Wiring Diagram
AHNW**6**A1 (HN**1* NK1)

Indoor Unit

Air-to-Water Heat Pump _ 9


5. Wiring Diagram
AHNW**A**A1 (HN**2* NK1), AHNW**8**A1 (HN**3* NK1)
Indoor Unit

10 _ Air-to-Water Heat Pump


5. Wiring Diagram (External Connection)
AHNW**6**A1 (HN**1* NK1)

Indoor Unit

Air-to-Water Heat Pump _ 11


5. Wiring Diagram (External Connection)
AHNW**A**A1 (HN**2* NK1), AHNW**8**A1 (HN**3* NK1)
Indoor Unit

MCCB

M/C
220V
50Hz
3~

MCCB
3

M/C

M/C
230V
50Hz
1~

12 _ Air-to-Water Heat Pump


AHNW*****A1 (HN**** NK1)

Solar
6. Piping Diagram

Thermal
Componets

Fan
Coil
Unit

Underfloor
Heating

Radiator
Sanitary water tan Solar thermal syst
k is installed em is connected
(Sanitary water tan (Solar thermal kit i
Basic installation k kit is necessary) s necessary)
(IDU + ODU)

Air-to-Water Heat Pump _ 13


Indoor Unit
6. Piping Diagram
Category Symbol Meaning PCB Connector Remarks
Refrigerant temperature sensor
TH1 CN_PIPE/OUT
(Gas side) - Meaning is expressed based on Cooling
Refrigerant temperature sensor mode.
TH2 CN_PIPE/IN
(Liquid side)
TH3 Entering Water temperature sensor
- TH3, TH4, and TH5 are connected at 6 pin
TH4 Interim Water temperature sensor CN_TH3
type connector CN_TH3.
TH5 Leaving Water temperature sensor
F/S Flow Switch CN_FLOW1
Indoor Unit
- Heating capacity is divided into two level :
partial capacity by E/HEAT(A) and full
capacity by E/HEAT(A) + E/HEAT(B).
CN_E/HEAT(A)
E/HT Electric Heater - Operating power(230V AC 50Hz) of
CN_E/HEAT(B) E/HEAT(A) and E/HEAT(B) are supplied by
external power source via magnet switch
and MCCB
- Operating power(230V AC 50Hz) of internal
W_PUMP1 Internal Water Pump CN_W/PUMP(A)
water pump is supplied by the connector.
EXP/TANK Expansion Tank (no connector) - Absorb volume change of heated water,
- Optional accessory (sold separately)
TH8 Remote Air temperature sensor CN_ROOM
Indoor Unit

- Model : PQRSTA0
CTR/PNL Control Panel (or ‘Remote Controller’) CN_REMO - Pre built-in at indoor unit
- 3rd party accessory and Field installation
(sold separately)
2WAY V/V_1 To control water flow for Fan Coil Unit CN_2WAY(A) - 2wire NO or NC type 2way valve is
supported.
- 3rd party accessory and Field installation
W/TANK (sold separately)
Sanitary Water Tank (no connector)
- Generating and storing sanitary hot water by
AWHP or built-in electric heater-
- 3rd party accessory and Field installation
B/HT Electric Heater CN_B/HEAT(A) (usually built-in at W/TANK)
- Supplying additional water heating capacity.
Water
- Flow control for water which is leaving from
Heating - 3rd party accessory and Field installation
indoor unit. CN_3WAY(A)
3WAY V/V_1 (sold separately)
- Flow direction switching between under-
floor and water tank - SPDT type 3way valve is supported.
Water to be heated by Indoor unit and B/HT (no connector)
CITY WATER - Field installation
of W/TANK
SHOWER Water supplied to end-user (no connector) - Field installation
- TH6 and TH7 are connected at 4 pin type
TH6 W/TANK water temperature sensor connector CN_TH4.
- TH6 is a part of sanitary water tank kit.
CN_TH4 (model: PHLTA)
TH7 Solar-heated water temperature sensor - TH7 is a part of solar thermal kit
(model: PHLLA)
- Flow control for water which is heated and
- 3rd party accessory and Field installation
3WAY V/V_2 circulated by SOLAR THERMAL SYSTEM. CN_3WAY(B) (sold separately)
- Flow direction switching between SOLAR
THERMAL SYSTEM and W/TANK - SPDT type 3way valve is supported.

- 3rd party accessory and Field installation


Solar (sold separately)
W_PUMP/2 External Water Pump CN_W/PUMP(B) - If water pump of SOLAR THERMAL SYSTEM
Heating
is incapable of circulation,external water pump
can be used.
- This system can include following compo-
nents : Solar panel, Sensors, Thermostats,
SOLAR THER- Interim heat exchanger, Water pump, etc. - 3rd party accessory and Field installation
(no connector) (sold separately)
MAL SYSTEM - To utilized hot water heated by SOLAR
THERMAL SYSTEM, end-user must by LG
AWHP Solar-Kit.

14 _ Air-to-Water Heat Pump


7. Operation Range
7.1 Cooling Operation
AHUW096A1 (HU091 U41), AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31), AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)

(Fan coil unit) (Under floor)

48 48
43 43
)

)
Outdoor Temperature(

Outdoor Temperature(

Indoor Unit
10 10
5 5

6 16 25 30 16 25 30
Leaving Water Temperature( ) Leaving Water Temperature( )

Continuous Operation

Operative

Air-to-Water Heat Pump _ 15


7. Operation Range
7.2 Heating Operation
AHUW096A1 (HU091 U41), AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31), AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)

(Fan coil unit or Radiator) (Under floor)

30 30
)

)
24 24
Outdoor Temperature(

Outdoor Temperature(
Indoor Unit

-15 -15
-20 -20

15 20 50 55 15 20 50 55
Leaving Water Temperature( ) Leaving Water Temperature( )

Continuous Operation

Operative

16 _ Air-to-Water Heat Pump


8. Pump Hydraulic Performance
8.1 Static Pressure Drop
Model : AHNW09***A1 (HN09** NK1)
8.0
7.5
7.0
6.5
6.0
Hydraulic Head Loss(mH2O)

5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
Med.
1.5

Indoor Unit
Max.
1.0
12.0
0.5
0.0
0 10 20 30 40 50 60 70 80 90 100 110
Water Flowrate(l/min)

Model : AHNW16***A1 (HN16** NK1)


8.0
7.5
7.0
6.5
6.0
5.5
Hydraulic Head Loss(mH2O)

5.0
4.5
Max.
4.0
3.5
Med.
3.0
2.5
2.0
1.5
15.0
1.0
0.5
0.0
0 10 20 30 40 50 60 70 80 90 100 110
Water Flowrate(l/min)

H Max. : high speed setting


Med. : low speed setting

Warning : Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.
: Operation cutoff range

Air-to-Water Heat Pump _ 17


Part 2. Outdoor Unit

1. Features
2. Nomenclature
3. Specification
4. Drawing
5. Wiring Diagram
6. Piping Diagram
7. Performance Data
8. Noise Criteria
1. Features
• Providing eco-friendly heating
• High energy efficiency
• Easy installation
• Space heating, cooling, and sanitary water heating

Outdoor Unit

Air-to-Water Heat Pump _ 1


2. Nomenclature
2.1 Global Model Name
AH U W 16 8 A 1
Serial Number
Chassis Name
Electrical Ratings
6 : 1 phase 220-240V 50Hz
8 : 3 phase 380-415V 50Hz
Nominal Heating Capacity Indication
Conversion to kW
Ex) "09" : 9 kW Class
"12" : 12 kW Class
"14" : 14 kW Class
"16" : 16 kW Class
Combination of Inverter Type
and Cooling Only or Heat Pump
W : DC Inverter Heat Pump
Classification
U : Outdoor Unit
Air-to-Water Heat Pump for R410A

2.2 Europe Model Name


H U 09 1 M
Leaving Water Combination
None : Low Temperature Leaving Water
H : High Temperature Leaving Water
M : Middle Temperature Leaving Water

1 : 1 Phase 220-240V 50Hz


3 : 3 Phase 380-415V 50Hz
Outdoor Unit

Nominal Heating Capacity Indication


Conversion to kW Class
Ex) "09" : 9 kW Class
"12" : 12 kW Class
"14" : 14 kW Class
"16" : 16 kW Class

U : Outdoor Unit

H : Air to Water Heat Pump

2 _ Air-to-Water Heat Pump


3. Specification
Nominal Capacity and Nominal Input AHUW096A1 AHUW126A1
(HU091 U41) (HU121 U31)
* Capacity Cooling kW 9.00 14.5
Heating kW 9.00 12.0
* Power Input Cooling kW 2.65 4.00
Heating kW 2.20 2.67
* EER Cooling W/W 3.40 3.63
COP Heating W/W 4.09 4.49

Technical Specification AHUW096A1 AHUW126A1


(HU091 U41) (HU121 U31)
Operation Range(Min.~Max.) Cooling °C DB 5~48 5 ~ 48
Outdoor Temperature Heating °C DB -20~30 -20 ~ 30
Compressor Type - Hermetic Motor Hermetic Motor
Model - GJT240DAA GPT425DBA
Quantity EA 1 1
Displacement cm /Rev.
3 24 42.5
Capacity kW 7.28 12.05
Compressor Motor Type - Brushless Brushless
Quantity EA 1 1
Rated Output W 1,700 4,000
Refrigerant Type - R410A R410A
Charge g(oz) 1,900(67.0) 2,850(100.5)
Control - Electronic Expansion Valve Electronic Expension Valve
Refrigerant Oil Type - FVC68D FVC68D
Charged Volume cc 900 1,300
Heat Exchanger Quantity EA 1 2
Rows EA 2 2
Columns EA 38 32
FPI Fins/inch 17 17
Fan Type - Propeller Propeller
Quantity EA 1 2
Air Flow Rate CMM(l/s) 60(1,000) 60(1,000)
Fan Motor Model - SIC-72FW-F1124-3 SIC-72FW-F1124-3
Quantity EA 1 2
Output W 124 124
Sound Pressure Cooling dB(A)±3 52 54
Level Heating dB(A)±3 52 53
Liquid Piping Type - Flare Flare
Connection Outer Diameter mm(inch) 9.52(3/8) 9.52(3/8)
Gas Piping Type - Flare Flare

Outdoor Unit
Connection Outer Diameter mm(inch) 15.88(5/8) 15.88(5/8)
Piping Length Minimum m 3 3
(Outdoor Unit ~ Standard m 7.5 7.5
Indoor Unit) Maximum m 50 50
Height Difference
Maximum m 30 30
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge g/m 30 60
Dimensions Unit(W x H x D) mm 950 x 834 x 330 950 Χ 1,380 Χ 330
Packed Unit(W x H x D) mm 1,140 x 900 x 461 1,140 Χ 1,462 Χ 461
Weight Unit kg 64 105
Packed Unit kg 69 116

Electrical Specification AHUW096A1 AHUW126A1


(HU091 U41) (HU121 U31)
Power Supply Ø / V / Hz 1 / 220-240 / 50 1 / 220-240 / 50
Maximum Running Cooling A 15 28
Current Heating A 15 28
Wiring Connections For Power Supply
Number of wires 3 3
(Included Earth)
For Connection with
Number of wires 4 4
Indoor Unit (Included Earth)

Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Air-to-Water Heat Pump _ 3


3. Specification
Nominal Capacity and Nominal Input AHUW146A1 AHUW166A1 AHUW128A1
(HU141 U31) (HU161 U31) (HU123 U31)
* Capacity Cooling kW 15.5 16.1 14.6
Heating kW 14.0 16.0 12.0
* Power Input Cooling kW 4.69 5.07 4.02
Heating kW 3.15 3.81 2.72
* EER Cooling W/W 3.30 3.18 3.60
COP Heating W/W 4.44 4.2 4.41

Technical Specification AHUW146A1 AHUW166A1 AHUW128A1


(HU141 U31) (HU161 U31) (HU123 U31)
Operation Range(Min.~Max.) Cooling °C DB 5 ~ 48 5 ~ 48 5~48
Outdoor Temperature Heating °C DB -20 ~ 30 -20 ~ 30 -20~30
Compressor Type - Hermetic Motor Hermetic Motor Hermetic Motor
Model - GPT425DBA GPT425DBA GPT425DAA
Quantity EA 1 1 1
Displacement cm /Rev.
3 42.5 42.5 42.4
Capacity kW 12.05 12.05 12.05 (at 60Hz)
Compressor Motor Type - Brushless Brushless Brushless
Quantity EA 1 1 1
Rated Output W 4,000 4,000 4,000
Refrigerant Type - R410A R410A R410A
Charge g(oz) 2,850(100.5) 2,850(100.5) 2,980(105.1)
Control - Electronic Expension Valve Electronic Expension Valve Electronic Expansion Valve
Refrigerant Oil Type - FVC68D FVC68D FV50S
Charged Volume cc 1,300 1,300 1,300
Heat Exchanger Quantity EA 2 2 2
Rows EA 2 2 2
Columns EA 32 32 32
FPI Fins/inch 17 17 17
Fan Type - Propeller Propeller Propeller
Quantity EA 2 2 2
Air Flow Rate CMM(l/s) 60(1,000) 60(1,000) 60(1,000)
Fan Motor Model - SIC-72FW-F1124-3 SIC-72FW-F1124-3 SIC-72FW-F1124-3
Quantity EA 2 2 2
Output W 124 124 124
Sound Pressure Cooling dB(A)±3 54 54 54
Level Heating dB(A)±3 53 53 53
Liquid Piping Type - Flare Flare Flare
Connection Outer Diameter mm(inch) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas Piping Type - Flare Flare Flare
Outdoor Unit

Connection Outer Diameter mm(inch) 15.88(5/8) 15.88(5/8) 15.88(5/8)


Piping Length Minimum m 3 3 3
(Outdoor Unit ~ Standard m 7.5 7.5 7.5
Indoor Unit) Maximum m 50 50 50
Height Difference
Maximum m 30 30 30
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge g/m 60 60 50
Dimensions Unit(W x H x D) mm 950 Χ 1,380 Χ 330 950 Χ 1,380 Χ 330 950 x 1,380 x 330
Packed Unit(W x H x D) mm 1,140 Χ 1,462 Χ 461 1,140 Χ 1,462 Χ 461 1,140 x 1,462 x 461
Weight Unit kg 105 105 105
Packed Unit kg 116 116 116

Electrical Specification AHUW146A1 AHUW166A1 AHUW128A1


(HU141 U31) (HU161 U31) (HU123 U31)
Power Supply Ø / V / Hz 1 / 220-240 / 50 1 / 220-240 / 50 3/380-415/50
Maximum Running Cooling A 28 28 11
Current Heating A 28 28 11
Wiring Connections For Power Supply
Number of wires 3 3 5
(Included Earth)
For Connection with
Number of wires 4 4 4
Indoor Unit (Included Earth)

Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

4 _ Air-to-Water Heat Pump


3. Specification
Nominal Capacity and Nominal Input AHUW148A1 AHUW168A1
(HU143 U31) (HU163 U31)
* Capacity Cooling kW 15.5 16.8
Heating kW 14.0 16.0
* Power Input Cooling kW 4.65 5.09
Heating kW 3.24 3.81
* EER Cooling W/W 3.33 3.30
COP Heating W/W 4.32 4.20

Technical Specification AHUW148A1 AHUW168A1


(HU143 U31) (HU163 U31)
Operation Range(Min.~Max.) Cooling °C DB 5~48 5~48
Outdoor Temperature Heating °C DB -20~30 -20~30
Compressor Type - Hermetic Motor Hermetic Motor
Model - GPT425DAA GPT425DAA
Quantity EA 1 1
Displacement cm /Rev.
3 42.4 42.4
Capacity kW 12.05 (at 60Hz) 12.05 (at 60Hz)
Compressor Motor Type - Brushless Brushless
Quantity EA 1 1
Rated Output W 4,000 4,000
Refrigerant Type - R410A R410A
Charge g(oz) 2,980(105.1) 2,980(105.1)
Control - Electronic Expansion Valve Electronic Expansion Valve
Refrigerant Oil Type - FV50S FV50S
Charged Volume cc 1,300 1,300
Heat Exchanger Quantity EA 2 2
Rows EA 2 2
Columns EA 32 32
FPI Fins/inch 17 17
Fan Type - Propeller Propeller
Quantity EA 2 2
Air Flow Rate CMM(l/s) 60(1,000) 60(1,000)
Fan Motor Model - SIC-72FW-F1124-3 SIC-72FW-F1124-3
Quantity EA 2 2
Output W 124 124
Sound Pressure Cooling dB(A)±3 54 54
Level Heating dB(A)±3 53 53
Liquid Piping Type - Flare Flare
Connection Outer Diameter mm(inch) 9.52(3/8) 9.52(3/8)
Gas Piping Type - Flare Flare

Outdoor Unit
Connection Outer Diameter mm(inch) 15.88(5/8) 15.88(5/8)
Piping Length Minimum m 3 3
(Outdoor Unit ~ Standard m 7.5 7.5
Indoor Unit) Maximum m 50 50
Height Difference
Maximum m 30 30
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge g/m 50 50
Dimensions Unit(W x H x D) mm 950 x 1,380 x 330 950 x 1,380 x 330
Packed Unit(W x H x D) mm 1,140 x 1,462 x 461 1,140 x 1,462 x 461
Weight Unit kg 105 105
Packed Unit kg 116 116

Electrical Specification AHUW148A1 AHUW168A1


(HU143 U31) (HU163 U31)
Power Supply Ø / V / Hz 3/380-415/50 3/380-415/50
Maximum Running Cooling A 11 11
Current Heating A 11 11
Wiring Connections For Power Supply
Number of wires 5 5
(Included Earth)
For Connection with
Number of wires 4 4
Indoor Unit (Included Earth)

Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Air-to-Water Heat Pump _ 5


Outdoor Unit

AHUW096A1 (HU091 U41)


4. Drawing

6 _ Air-to-Water Heat Pump


Liquid side service valve(mm)
Gas side service valve(mm)
Air discharge grill
Control Cover
3

Note
1. Unit should be installed in compliance with the installation manual in
the product box.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.

[Unit:mm]

U4
AHUW126A1 (HU121 U31)
AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31)
4. Drawing

AHUW128A1 (HU123 U31)


AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)

Liquid side service valve(mm)


Gas side service valve(mm)
Supporter
Air discharge grill
Control Cover

Note
1. Unit should be installed in compliance with the installation manual in
the product box.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.

[Unit:mm]

Air-to-Water Heat Pump _ 7


Outdoor Unit
5. Wiring Diagram
AHUW096A1(HU091 U41)
Outdoor Unit

8 _ Air-to-Water Heat Pump


5. Wiring Diagram
AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31), AHUW166A1 (HU161 U31)

Outdoor Unit

Air-to-Water Heat Pump _ 9


5. Wiring Diagram
AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31), AHUW168A1 (HU163 U31)
Outdoor Unit

10 _ Air-to-Water Heat Pump


6. Piping Diagram
AHUW096A1 (HU091 U41), AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31), AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)

INDOOR UNIT OUTDOOR UNIT

EEV
LIQUID SIDE

3-Way
Service Valve Th6
Th2
Th7

Th8
Indoor Unit Outdoor Unit
Plate Heat Heat Exchanger
Exchanger
Low Pressure
Switch
Th3

GAS SIDE Th4

3-Way Reversing Valve


Accumulator
Service Valve
Th5
High Pressure
COMPRESSOR COOLING
Switch
HEATING

Description
PCB Connector

Outdoor Unit
Category Symbol Meaning AHUW126A1 AHUW128A1 Remarks
AHUW096A1 AHUW146A1 AHUW148A1
AHUW166A1 AHUW168A1
- Optional accessory (being sold sepa-
Th1 Remote air temperature sensor CN_ROOM CN_ROOM CN_ROOM rately)
- Not shown in diagram
Indoor Unit
Th2 Inlet evaporator temperature sensor CN_PIPE/IN CN_PIPE/IN CN_PIPE/IN - Meaning is expressed based on Cool-
Th3 Outlet evaporator temperature sensor CN_PIPE/OUT CN_PIPE/OUT CN_PIPE/OUT ing mode.

Compressor-suction pipe temperature


Th4
sensor - Th4 and Th5 are connected at 4 pin
CN_TH3 CN_TH2 CN_TH2
Compressor-discharge pipe tempera- type.
Th5
ture sensor
Th6 Condenser temperature sensor - Description is expressed based on
Outdoor Cooling mode.
CN_TH2 CN_TH1 CN_TH1
Unit Th7 Outdoor air temperature sensor - Th6 and Th7 are connected at 4 pin
type.

- Th8 is connected at 4 pin type.


Th8*1 Condenser middle temperature sensor CN_TH4 CN_TH3 CN_TH3 - Only AHUW096A1 model is connected
at 3 pin type.
- Adjusting mass flow rate of circulating
EEV Electronic Expansion Valve CN_EEV1 CN_EEV1 CN_EEV
refrigerant

*1:Applied Model : AHUW128A1, AHUW148A1, AHUW168A1, AHUW096A1, AHUW126A1, AHUW146A1, AHUW166A1

Air-to-Water Heat Pump _ 11


7. Performance Data
7.1 Cooling Operation

Outdoor LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20°C 6.58 1.54 7.39 1.57 8.21 1.60 8.55 1.61 9.05 1.63 9.29 1.64
30°C 6.47 2.17 7.10 2.20 7.73 2.23 8.15 2.25 8.78 2.28 9.20 2.30
AHUW096A1 35°C 6.21 2.41 6.91 2.44 7.51 2.47 8.04 2.52 9.00 2.65 9.02 2.71 9.33 2.74
(HU091 U41) 40°C 5.79 2.86 6.38 2.89 6.97 2.93 7.37 2.96 7.96 3.00 8.32 3.03 8.68 3.06
45°C 5.15 3.03 5.75 3.09 6.35 3.15 6.75 3.20 7.35 3.26 7.27 3.06 7.18 2.87

Outdoor LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20°C 9.54 2.00 11.04 2.34 12.55 2.68 14.06 3.03 15.56 3.37 17.07 3.72
30°C 12.82 4.19 13.15 4.25 14.07 4.40 15.45 4.44 15.38 4.21 16.02 3.98
AHUW126A1 35°C 11.65 4.48 12.53 4.65 13.40 4.75 14.44 4.77 14.50 4.00 14.97 4.28 15.57 4.53
(HU121 U31) 40°C 11.17 4.89 11.61 5.02 12.68 5.18 13.43 5.25 13.31 4.39 13.77 4.49 14.29 4.59
45°C 9.37 5.24 10.39 5.37 11.41 5.51 12.43 5.64 13.46 5.77 14.16 5.83 14.87 5.89

Outdoor LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20°C 10.63 2.51 12.16 2.83 13.69 3.15 15.22 3.47 16.75 3.79 18.28 4.11
30°C 13.36 4.58 13.83 4.65 14.91 4.81 16.42 4.85 16.50 4.76 17.19 4.67
AHUW146A1 35°C 12.15 4.90 13.17 5.08 14.20 5.20 15.35 5.22 15.50 4.69 16.06 5.02 16.71 5.32
(HU141 U31) 40°C 11.65 5.34 12.21 5.49 13.43 5.66 14.28 5.74 14.28 5.15 14.78 5.26 15.34 5.38
45°C 9.35 5.73 10.56 5.87 11.78 6.01 13.00 6.14 14.22 6.28 14.72 6.21 15.23 6.15

Outdoor LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
Outdoor Unit

Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20°C 13.64 4.17 14.84 4.26 16.03 4.36 17.23 4.45 18.43 4.55 19.62 4.64
30°C 13.72 4.84 14.36 4.91 15.63 5.08 17.30 5.12 17.58 5.18 18.31 5.23
AHUW166A1 35°C 12.48 5.18 13.68 5.37 14.88 5.49 16.17 5.51 16.10 5.07 17.11 5.63 17.80 5.73
(HU161 U31) 40°C 11.96 5.64 12.68 5.80 14.08 5.98 15.03 6.06 15.21 5.54 15.74 5.67 16.34 5.80
45°C 10.17 6.11 11.06 6.10 11.96 6.10 12.86 6.09 13.75 6.09 14.43 6.13 15.10 6.17

LWT : Leaving Water Temperature


TC : Total Capacity (Averaged value, kW)
PI : Power Input(kW)

Notice : Measuring procedure follows EN-14511


Notice : Above table values may not be matched according to installation condition

12 _ Air-to-Water Heat Pump


7. Performance Data

Outdoor LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20°C 12.80 3.49 13.98 3.55 15.16 3.62 15.95 3.66 17.13 3.73 17.92 3.77
30°C 12.33 4.00 13.39 4.06 14.45 4.15 15.16 4.20 16.18 4.28 16.86 4.33
AHUW128A1 35°C 11.94 4.46 13.02 4.56 14.10 4.66 14.33 4.56 14.60 4.02 15.83 4.66 16.43 4.69
(HU123 U31) 40°C 11.45 4.72 12.07 4.91 13.34 5.06 13.70 5.04 14.00 5.10 14.47 5.16 14.93 5.23
45°C 8.59 4.55 9.92 4.65 10.24 4.18 10.46 3.87 11.20 3.90 12.15 3.93 12.82 3.95

Outdoor LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20°C 13.40 3.97 14.64 4.04 15.88 4.12 16.70 4.17 17.94 4.24 18.76 4.29
30°C 12.70 4.44 13.80 4.51 14.89 4.60 15.62 4.67 16.67 4.75 17.37 4.81
AHUW148A1 35°C 12.30 4.95 13.23 5.00 14.15 5.05 14.77 5.06 15.50 4.65 16.31 5.17 16.93 5.21
(HU143 U31) 40°C 11.79 5.24 12.26 5.39 13.39 5.49 13.71 5.54 14.42 5.66 14.90 5.73 15.38 5.81
45°C 8.59 4.55 9.92 4.65 10.24 4.18 10.46 3.87 11.20 3.90 12.15 3.93 12.82 3.95

Outdoor LWT 7°C LWT 10°C LWT 13°C LWT 15°C LWT 18°C LWT 20°C LWT 22°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI TC PI
20°C 11.23 2.92 13.43 3.57 15.56 4.22 16.98 4.65 18.66 4.85 19.78 4.98
30°C 13.75 4.83 14.94 4.91 16.12 5.01 16.92 5.08 18.05 5.17 18.81 5.23
AHUW168A1 35°C 12.50 5.17 14.26 5.36 15.35 5.48 16.20 5.50 16.80 5.09 17.72 5.62 18.33 5.67
(HU163 U31) 40°C 11.99 5.64 13.22 5.77 14.52 5.95 15.04 6.02 15.53 5.57 16.18 5.64 16.83 5.71
45°C 8.59 4.55 9.92 4.65 10.24 4.18 10.46 3.87 11.20 3.90 12.15 3.93 12.82 3.95

LWT : Leaving Water Temperature


TC : Total Capacity (Averaged value, kW)
PI : Power Input(kW)

Outdoor Unit
Notice : Measuring procedure follows EN-14511
Notice : Above table values may not be matched according to installation condition

Air-to-Water Heat Pump _ 13


7. Performance Data
7.2 Heating Operation
Outdoor LWT 30°C LWT 35°C LWT 40°C LWT 45°C LWT 50°C LWT 55°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI
-15 7.55 3.20 6.98 3.15 6.13 3.27 5.85 3.19 5.66 3.44
-7 8.76 3.11 8.61 3.19 7.41 3.34 7.3 3.32 6.88 3.37 5.71 3.13
-2 6.83 1.94 6.55 2.12 6.13 2.32 5.99 2.33 5.88 2.54 5.41 2.65

AHUW096A1 2 7.13 1.95 6.87 2.07 6.48 2.30 6.35 2.31 6.29 2.57 6.08 2.60
(HU091 U41) 7 9.29 1.98 9.00 2.20 8.43 2.42 8.25 2.44 7.69 2.62 7.37 2.70
10 9.81 2.06 9.71 2.20 9.27 2.35 9.12 2.49 8.11 2.58 7.47 2.61
15 10.34 1.82 10.17 1.82 9.71 2.09 9.44 2.31 8.67 2.59 7.00 2.33
18 10.64 1.85 10.49 1.92 10.03 2.16 9.63 2.35 9.00 2.66 6.71 2.16

Outdoor LWT 30°C LWT 35°C LWT 40°C LWT 45°C LWT 50°C LWT 55°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI
-15 10.13 4.22 9.40 4.10 8.31 4.36 7.95 4.24 7.60 4.75
-7 12.26 4.19 11.48 4.16 10.61 4.53 10.4 4.79 9.48 4.60 7.74 4.21
-2 8.93 2.53 8.65 2.85 8.24 3.05 8.10 3.09 7.94 3.30 7.27 3.54

AHUW126A1 2 9.81 2.69 9.40 2.80 8.79 3.06 8.59 3.06 8.50 3.41 8.17 3.46
(HU121 U31) 7 12.48 2.66 12.00 2.67 11.28 3.20 11.00 3.18 10.3 3.41 9.85 3.58
10 13.49 2.81 13.32 2.99 12.62 3.12 12.4 3.37 11.19 3.69 10.1 3.50
15 14.20 2.50 14.06 2.53 13.34 2.87 12.8 3.16 11.64 3.50 9.40 3.13
18 14.61 2.68 14.51 2.65 13.77 2.94 13.00 3.22 11.92 3.55 8.98 2.90

Outdoor LWT 30°C LWT 35°C LWT 40°C LWT 45°C LWT 50°C LWT 55°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI
Outdoor Unit

-15 11.75 4.97 10.86 4.90 9.54 5.08 9.10 4.97 8.81 5.34
-7 14.03 4.49 13.11 4.85 11.89 5.15 11.40 5.17 10.71 5.24 8.88 4.87
-2 10.62 3.01 10.19 3.30 9.54 3.61 9.32 3.63 9.14 3.95 8.42 4.13

AHUW146A1 2 11.09 3.04 10.69 3.22 10.09 3.58 9.88 3.59 9.78 4.00 9.46 4.04
(HU141 U31) 7 14.46 3.08 14.00 3.15 13.12 3.77 12.80 3.80 11.97 4.08 11.50 4.20
10 15.11 3.17 14.94 3.39 14.27 3.63 14.10 3.83 12.49 3.97 11.60 4.06
15 15.93 2.81 15.65 2.81 14.96 3.21 14.50 3.56 13.35 4.00 10.90 3.62
18 16.38 2.85 16.15 2.95 15.44 3.31 14.80 3.63 13.87 4.10 10.40 3.35

LWT : Leaving Water Temperature


TC : Total Capacity (Averaged value including defrost effect, kW)
PI : Power Input(kW)

Notice : Measuring procedure follows EN-14511


Notice : Above table values may not be matched according to installation condition

14 _ Air-to-Water Heat Pump


7. Performance Data
Outdoor LWT 30°C LWT 35°C LWT 40°C LWT 45°C LWT 50°C LWT 55°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI
-15 13.35 5.75 12.30 5.73 10.73 5.71 10.20 5.70 10.00 5.88
-7 15.93 5.96 14.80 5.61 12.56 5.34 12.10 5.42 11.83 5.84 9.98 5.51
-2 12.38 3.51 11.76 3.73 10.82 4.06 10.50 4.17 10.30 4.63 9.56 4.72

AHUW166A1 2 12.28 3.37 11.90 3.62 11.33 4.00 11.10 4.13 11.03 4.60 10.70 4.62
(HU161 U31) 7 16.40 3.49 16.00 3.81 14.95 4.29 14.60 4.45 13.62 4.77 13.10 4.82
10 17.08 3.62 16.93 3.87 16.29 4.25 16.10 4.38 14.07 4.31 13.10 4.62
15 18.03 3.18 17.59 3.16 16.94 3.64 16.70 4.05 15.44 4.60 12.40 4.11
18 18.55 3.40 18.15 3.32 17.49 3.77 17.00 4.14 16.27 4.77 11.90 3.80

Outdoor LWT 30°C LWT 35°C LWT 40°C LWT 45°C LWT 50°C LWT 55°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI
-15 10.33 4.34 9.56 4.27 8.42 4.44 8.04 4.36 7.66 4.68
-7 12.42 4.32 11.66 4.31 10.49 4.54 10.02 4.61 9.37 4.58 7.73 4.23
-2 9.22 2.64 8.87 2.90 8.32 3.12 8.14 3.16 7.99 3.40 7.31 3.58

AHUW128A1 2 9.74 2.70 9.46 2.83 8.81 3.11 8.63 3.13 8.55 3.49 8.21 3.50
(HU123 U31) 7 12.54 2.71 12.00 2.72 11.49 3.27 11.28 3.31 10.50 3.54 9.94 3.64
10 13.40 2.83 13.25 3.02 12.63 3.22 12.43 3.41 11.20 3.61 10.10 3.53
15 14.04 2.48 13.82 2.49 13.18 2.84 12.77 3.14 11.70 3.51 9.45 3.15
18 14.44 2.62 14.26 2.61 13.61 2.92 13.02 3.20 12.10 3.59 9.05 2.91

Outdoor LWT 30°C LWT 35°C LWT 40°C LWT 45°C LWT 50°C LWT 55°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI
-15 12.04 5.09 11.11 5.07 9.74 5.17 9.29 5.12 8.82 5.26
-7 14.10 4.96 12.72 4.98 11.57 5.09 11.00 5.06 10.60 5.20 8.81 4.86
-2 10.88 3.14 10.38 3.36 9.60 3.64 9.34 3.69 9.18 4.00 8.40 4.14

AHUW148A1 2 11.06 3.09 10.89 3.28 10.10 3.60 9.90 3.66 9.83 4.07 9.43 4.05

Outdoor Unit
(HU143 U31) 7 14.40 3.16 14.00 3.24 13.37 3.82 13.16 3.92 12.30 4.20 11.46 4.22
10 15.21 3.26 15.06 3.49 14.46 3.79 14.26 3.95 12.90 4.04 11.55 4.06
15 15.86 2.80 15.53 2.80 14.89 3.21 14.56 3.56 13.40 4.02 10.85 3.62
18 16.32 2.92 16.02 2.94 15.38 3.31 14.87 3.64 14.10 4.14 10.43 3.35

Outdoor LWT 30°C LWT 35°C LWT 40°C LWT 45°C LWT 50°C LWT 55°C
Model
Temperature TC PI TC PI TC PI TC PI TC PI TC PI
-15 14.09 5.96 12.98 5.98 11.37 6.01 10.83 6.02 10.10 5.92
-7 15.93 6.09 14.92 5.95 12.86 5.74 12.17 5.67 12.00 5.91 9.99 5.54
-2 12.72 3.74 12.08 3.92 11.04 4.20 10.69 4.29 10.50 4.63 9.57 4.74

AHUW168A1 2 12.61 3.60 12.22 3.82 11.55 4.15 11.33 4.26 11.30 4.73 10.75 4.64
(HU163 U31) 7 16.40 3.71 16.00 3.81 15.56 4.42 15.41 4.62 14.40 4.95 13.09 4.84
10 17.49 3.83 17.34 4.10 16.73 4.51 16.53 4.65 15.20 4.69 13.11 4.64
15 18.05 3.19 17.61 3.18 16.95 3.66 16.68 4.07 15.50 4.62 12.36 4.13
18 18.57 3.42 18.17 3.34 17.50 3.79 17.04 4.16 16.30 4.79 11.91 3.82

LWT : Leaving Water Temperature


TC : Total Capacity (Averaged value including defrost effect, kW)
PI : Power Input(kW)

Notice : Measuring procedure follows EN-14511


Notice : Above table values may not be matched according to installation condition

Air-to-Water Heat Pump _ 15


8. Noise Criteria
Overall
Notes:
1m - Sound measured at 1m away with 1.5m height.
Microphone - Data is valid at free field condition.
- Data is valid at nominal operation condition.
- Reference acoustic pressure acoustic 0dB-20Pa.
- Sound level will vary depending on a range of factors such as
1.5m the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard.

(dB(A)±3) (dB(A)±3)
1Φ, 220-240V, 50Hz 3Φ, 380-415V, 50Hz
Model Cooling Heating Model Cooling Heating
AHUW096A1 (HU091 U41) 52 52 AHUW128A1 (HU123 U31) 54 53
AHUW126A1(HU121 U31) 54 53 AHUW148A1 (HU143 U31) 54 53
AHUW146A1(HU141 U31) 54 53 AHUW168A1 (HU163 U31) 54 53
AHUW166A1(HU161 U31) 54 53

Sound pressure level


n Cooling(1Ø)

AHUW096A1 (HU091 U41) AHUW126A1(HU121 U31) AHUW146A1(HU141 U31)


80 80 80

70 70 70
Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )


Octave Band Sound Pressure Level (dB re 20Pa )

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


Outdoor Unit

40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30

NC-30 NC-30 NC-30

20 NC-25 20 NC-25 20 NC-25

Approximate Approximate Approximate


NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AHUW166A1(HU161 U31)
80

70
Octave Band Sound Pressure Level (dB re 20Pa )

NC-65
60
NC-60

NC-55
50

NC-50

NC-45
40

NC-40

NC-35
30

NC-30

20 NC-25

Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

16 _ Air-to-Water Heat Pump


8. Noise Criteria
n Heating(1Ø)
AHUW096A1 (HU091 U41) AHUW126A1(HU121 U31) AHUW146A1(HU141 U31)
80 80 80

70 70 70
Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30

NC-30 NC-30 NC-30

20 NC-25 20 NC-25 20 NC-25

Approximate Approximate Approximate


NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

80
AHUW166A1(HU161 U31)

70
Octave Band Sound Pressure Level (dB re 20µPa )

NC-65
60
NC-60

NC-55
50

NC-50

NC-45
40

NC-40

NC-35
30

NC-30

Outdoor Unit
20 NC-25

Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000

Approximated SPL at specific distance : SPL[dB] = A + 20xLog(B/C)


where A[dB] : SPL at 1m distance
B[m] : 1m
C[m] : specific distance

Air-to-Water Heat Pump _ 17


8. Noise Criteria
n Cooling(3Ø)
AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31)
80 80 80

70 70 70

Octave Band Sound Pressure Level (dB re 20Pa )


Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )


NC-65 NC-65 NC-65
60 60 60

NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50

NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40

NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30

NC-30 NC-30 NC-30

NC-25 NC-25 20 NC-25


20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

n Heating(3Ø)
AHUW128A1 (HU123 U31) AHUW148A1 (HU143 U31) AHUW168A1 (HU163 U31)
80 80 80

70 70 70
Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35
Outdoor Unit

NC-35
30 30 30
NC-30 NC-30 NC-30

20 NC-25 20 NC-25 NC-25


20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

Approximated SPL at specific distance : SPL[dB] = A + 20xLog(B/C)


where A[dB] : SPL at 1m distance
B[m] : 1m
C[m] : specific distance

18 _ Air-to-Water Heat Pump


Part 3. Accessories

1. Dry Contact (PQDSA)


2. Remote Temperature Sensor (PQRSTA0)
3. PI485 (PMNFP14A0)
4. Sanitary Water Tank Kit(PHLTA/PHLTC)
5. Solar Thermal Kit(PHLLA)
1. Dry Contact (PQDSA)
1.1 Overview
LG Dry Contact is a solution for automatic control of air conditioning system at the ownerʼs behest.
In simple words, itʼs a switch which can be used to turn the unit On/Off after getting the signal from external sources like
key-in lock, door or window switch etc specially used in Hotel rooms.

Itʼs a small PCB that either can be fit inside the control box of Indoor unit or can be outside the unit in a plastic case if there
is no sufficient space inside the Indoor unit.

Apart from simple installation, it can also be linked to Central Controller via Indoor unit PI485 pcb. For this, all connecting
wires & an additional small pcb for looping is also provided along with Dry Contact.

Dry Contact can be used in two ways.


1. It can be used to actually turn On/Off the system on receiving the signal from the source.
In this case, user doesn't need to use remote controller anymore to turn On/Off the system.
However all the further settings like temperature, fan speed, mode etc can be done through remote controller only.
2. Other way is almost similar as above but in this case, after getting the On signal from the external source, user has to
turn On the system from remote controller only. Dry contact just activates the system.
However system can be turned Off directly from the external source. So only On mode is different here.

So in both of above conditions, system canʼt be operated without signal from external source which prevents unnecessary
use of system & facilitates its operation only when its required.

These settings can be selected from the remote controller whose details have been explained in the later part of this manual

So depending upon the requirement, Dry Contact offers a variety of applications to suit the customerʼs requirement in the
best possible way.
Power
Connector

Indoor PCB
Connector
Accessories

Dry Contact Controller


Connector

Air-to-Water Heat Pump _ 1


1. Dry Contact (PQDSA)
1.2 Part Description

1 CN-POWER : AC 220V Connector


2 CN-CC : Indoor PCB Connector
1
3 CN_DRY (L) : DRY CONTROLLER Connector
4 CN_DRY ( SIG ) : DRY CONTROLLER Connector
5 CN_DRY (ERROR CHECK) : ERROR Check Display Connector
2 6 CN_DRY( OPER STATE): Operation Display Connector

3 4 5 6

1.2.1 Accessory

Cable 1EA
(for Central controller)

Connecting PCB
(6871A30056A)
*for Central Controller

Dry contact
(For installation, 4EA)

Cable 3EA
(for connecting with indoor unit)
Dry contact - 4EA
(For assembly the case)

User/Installation
Accessories

Manual

[Structure of each cable]

NOTE

• These cable using for connection between Dry contact and Indoor unit.
• So before using these things Please check the connector type first and use cables on proper indoor unit.

2 _ Air-to-Water Heat Pump


1. Dry Contact (PQDSA)
1.3 Installation Guide
1.3.1 Step 1
Connect CN-CC with Indoor PCB by the cable(provided)
- Connection of Dry contact only

DRY CONTACT
Indoor PCB
PCB 4 4
3 3
CN-CC CN-CC 2 2
1 1

2 1
2 1 AC 220V

- Connection of Dry contact & LG Central Controller in case of single constant models.

Connection PCB
(6871A30056A)

DRY CONTACT
Indoor PCB
PCB 4 4
3 3
CN-CC CN-CC 2 2
1 1

2 1
2 1 AC 220V
BR1
C01A
OSC01B

IC01A

PI485 PCB : Special purchase for


L02D
L01D

S1
SWITCH
Central Control
(Ex : PHNFP14A0 or PSNFP14A0...)
L1 2 3 4
LED01G
LED02G
LED03G
LED1

ON
U03Y U04Y U02Y

TANS01Y

CN_COMM
C04Y

ZNR01Y
C03Y

* Single Only
- When you install single product this PCB have to add.

Accessories

Air-to-Water Heat Pump _ 3


1. Dry Contact (PQDSA)
1.3.2 Step 2
Connect CN_DRY with Control Unit. (Fix SUB PCB into the proper location.)
- To apply power source through PCB

DRY CONTACT
PCB

4 4 Operation Display
CN-CC 3 3 Error Check Display
RY2 2 2
RY1 1 1 Dry contact
CN_DRY Controller
N L
2 1
2 1
INPUT
AC 220V
LG does not
supply this section

- To apply power source directly to external source

DRY CONTACT
PCB

4 4 Operation Display
CN-CC 3 3 Error Check Display
RY2 2 2
RY1 1 1 Dry contact
CN_DRY Controller
N L
2 1
2 1
INPUT
AC 220V
LG does not
supply this section
Accessories

4 _ Air-to-Water Heat Pump


2. Remote Temperature Sensor (PQRSTA0)
2.1 Part Description
Remote temperature sensor can be installed any place a user wants to detect the temperature.

2.1.1 Remote Sensor

70mm

Remote Sensor
120mm

Connection Wire

2.1.2 Parts

Connection wire Fixing screw for Installation Manual


15m(1EA) Remote Sensor(2EA)
Accessories

Air-to-Water Heat Pump _ 5


2. Remote Temperature Sensor (PQRSTA0)
2.2 Installation Method
2.2.1 How to use
1. After deciding where the remote temperature sensor is installed, decide
the location and height of the fixing screws.
(Interval between the screws : 60mm) Fixing screws 60mm

2. Insert the connector of the connection wire into the space for the
connector in place of the room temperature sensor. (CN_ROOM)
3. Separately, set the option code of the attached controller on the indoor unit.
In detail, refer to "installer setting mode" in the owner's manual.

2.2.2 How to connect the remote temperature sensor and the connection wire

The Connection wire does not matter if you change the color of the wire because of non-polar

2.2.3 How to install the remote temperature sensor on the wall


Integrate the remote temperature sensor with the screws as the order of arrows.

Fixing the
Remote Sensor
Accessories

CAUTION

1. Choose the place where the average temperature can be measured for the place the indoor unit operates.
2. Avoid direct sunlight.
3. Choose the place where the cooling/heating devices do not affect the remote sensor.
4. Choose the place where the outlet of the cooling fan do not affect the remote sensor.
5. Choose the place where the remote sensor isnʼt affected when door is open.

6 _ Air-to-Water Heat Pump


3. PI485 (PMNFP14A0)
3.1 Part Description
1

2
3
4

ON KSDO4H
5

L1 2 3 4
6

7
8
9
10
11

h The location of parts might be different in case of PMNFP14A1.


PMNFP14A0 : For connecting 1 ~ 16 Indoor Units

PI485 GATEWAY(M)

1 CN_PWR: AC 220V Connector


2 +10V: DC 10V Terminal
3 GND: Ground
4 BUS_A: *RS-485 (+) Terminal
(Refer to note)
5 BUS_B: RS-485 (-) Terminal
6 CN_OUT: Outdoor Unit Connector
7 LED1:RS-485 Status LED
8 DIP Switch: Product Selection (Refer to the 「DIP Switch Configuration」)
9 LED01G, 02G, 03G: Communication Status LED
10 Reset Switch: PI485(M) Reset
11 CN_DRY: DRY Contact
Accessories

NOTE

RS-485 is one of the international interface standards for serial communication.

Air-to-Water Heat Pump _ 7


3. PI485 (PMNFP14A0)
3.2 Accessory Parts

Multi-V

ON KSDO4H

L1 2 3 4

PI485 : PMNFP14A0(1EA)
or PMNFP14A1(1EA) BRACKET (1EA) SCREW (4EA)
or PGNFP14A0(1EA)

Multi-V MPS Multi

WIRE ASSY 1(1EA) WIRE ASSY 2(1EA) WIRE ASSY 3(1EA)

Others : Tie Wrap (3 EA) - Cable Tie


Clamp (1 EA)
Accessories

8 _ Air-to-Water Heat Pump


3. PI485 (PMNFP14A0)
3.3 Installation Guide
3.3.1 Installation Steps
1. 6 Connect CN_OUT with Outdoor Unit by the cable (provided)
2. 4 5 Connect RS-485 BUS_A(+) and BUS_(B)(-) with other network products (ex. Central Controller , I-
Gateway.....)
3. 2 3 In case of using Simple Central Controller, connect VCC(+10V) and GND.
No need to connect otherwise.
4. 8 Select DIP Switch Configuration(Refer page 8)
5. 1 Connect CN_PWR with Outdoor PCB Power connector (Refer page 9, 10)
6. After Power is ON, check the Communication LED 9
- LED1G(Red)
• Normal : LED blinks for 5 times and then gets OFF
This process is repeated after every 3 minutes
• Error : Check the Indoor Unit's address & wiring connections
- LED2G(Yellow), LED3G(Orange)
• Normal : LED blinks continuously
• Error : Check the DIP Switch setting & wiring connections
7. 7 Check RS-485 Communication Status LED:
• Normal : LED's blinks 2 times in every 10~30 seconds
• Error : Check the wiring connections
8. Finally if all of the above steps are OK, then tie the cables by tie wraps & clamp

CAUTION

Install the PI485 after checking the hole for screw.

Accessories

Air-to-Water Heat Pump _ 9


4. Sanitary Water Tank Kit(PHLTA/PHLTC)
- Must be sued for communication of sanitary water tank and indoor unit
- PHLTA For 1phase Indoor model (AHNW**6**A1)
- PHLTC For 3phase Indoor model (AHNW**A**A1, AHNW**8**A1)
h PHRSTA0 : Sanitary water tank sensor (Thermistor) only

4.1 Part Description


1 Sensor (Thermister) : This sensor (PHRSTA0) can be supplied separately.
2 Sensor Adaptor
- It can be attached on the sanitary water tank
- Thermister is inserted in the sensor adaptor
- Connection 1/2"(12.7mm) BSP
3 MCCB (Circuit breaker) 40A
4 Magnetic switch
5 Installation manual
6 1 phase IDU model bracket (PHLTA only)
7 3 phase IDU model bracket (PHLTC only)

1 2 3 4

5 6 7

(PHLTA only) (PHLTC only)


Accessories

10 _ Air-to-Water Heat Pump


5. Solar Thermal Kit(PHLLA)
- Must be used for communication of solar thermal component and indoor unit.

5.1 Model
- PHLLA : Sensorʼs limit temperature 100℃

5.2 Part Description


1 Sensor (Thermister)
2 Sensor Adaptor
- It can be attached on T type pipe fitting attatched in the pipe of solar thermal component
- Thermister is inserted in the sensor adaptor
- Connection 1/2"(12.7mm) BSP
3 T type pipe fitting (option)

1 2 3

Accessories

Air-to-Water Heat Pump _ 11


P/No.: 3828A20892W

Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com

All rights reserved The air conditioners manufactured by LG have received


Printed in Korea December / 2012 ISO9001 certificate for quality assurance and ISO14001
The specifications, designs, and certificate for environmental management system.
information in this brochure are subject to
change without notice.