ATV310 Getting Started Parameters EN EAV96136 08
ATV310 Getting Started Parameters EN EAV96136 08
EAV9613608
Reference mode F005 Invalid industrialization zone 203 Logic inputs type 216.1 AO1 type 405 Stop key priority
Reference menu
402 External reference value F006 Current measurement circuit [00]* Positive [10U] Voltage: 0-10 Vdc [00] No: Stop inactive
1 3
[-00] Drive ready F027 IGBT overheat [05] HSP reached 306 Rated motor frequency [183] Integrated jog dial
[-01] Drive running F028 Autotuning fault [06] I threshold reached 10 to 400Hz (50Hz*) 500- FUNCTION MENU
[-02] Acceleration F029 Process underload fault [07] Frequency reference reached 307 Rated motor speed 501- RAMP MENU
[-03] Deceleration F030 Undervoltage [08] Motor thermal reached 0 to 24000rpM (depending on drive rating) 501.0 Acceleration
[-04] DC injection braking in progress F031 Incorrect configuration [21] Process underload fault 308 Maximum frequency 0.0 to 999.9s (3.0s*)
[-05] Current limitaion state F032 Invalid configuration [22] Process overload fault 10 to 400Hz (60Hz*) 501.1 Deceleration
Drive status
[-06] Freewheel stop control or freewheel state F033 AI1 current loss [123] Loss of 4-20mA signal 309 Motor control type 0.0 to 999.9s (3.0s*)
[-07] Auto-adatated deceleration F034 Download invalid configuration 206- LO1 CONFIGURATION MENU [00] Performance: Vector control 501.2 Ramp shape assignment
[-08] Controlled stop on mains phase loss F035 Pre-charge resistor protection fault 206.0 LO1 Assignment [03]* Standard: U/F 2 points [00]* Linear
[-09] Auto-tuning in progress Configuration mode [00]* Not assigned [06] Pump: U²/F [01] S shape
[-10] Fast stop state 301 Standard motor frequency [01] No error detected 310 IR compensation [02] U shape
[-11] No line power state [00] 50Hz IEC [02] Drive run 25 to 200% (100%*) 501.3 Ramp switching commutation
[-12] Drive in back state [01] 60Hz NEMA [04] Frequency threshold reached 311 Slip compensation [00]* Not assigned
2 4
performed
Maintenance menu
D22 (0.25-1.5In) (depending on drive rating) 210 Process underload time delay 502- STOP CONFIGURATION MENU
204.0 AI1 type 0 to 100 s (0 s*) 319 Motor parameter choice 502.0 Type of stop
905 Drive voltage rating [00]* Nominal motor power [00]* Ramp stop
N4 [5U]* 0-5V 211 Process underload threshold
20 to 100% of nominal motor current (60%*) [01] Nominal motor cos phi [03] DC injection stop
906 Specific Product Number [10U] 0-10V [08] Fast stop
[0A] x-y mA 212 Process underload fault duration 320 Vector control 2 points
907 Card 1 Software Version [00]* No [13] Free wheel stop
908 Card 2 Software Version [LIU] Logic inputs 0 to 6min (0min*)
213 Motor frequency threshold [01] Yes 502.1 Freewheel stop assignment
909 Run elapsed time display 101 Store customer parameter set [00]* Not assigned
910 Power On time display [00]* Disabled 0 to 400Hz (50Hz* or 60Hz) 321 Max voltage of constant power
[L1L] LI1 active Low to stop
918 Last fault 3 [00] Start/stop [L2L] LI2 active Low to stop
919 State of drive at fault 3 [130] Output frequency [01] Terminal [L3L] LI3 active Low to stop
[04] PID regulation [131] Ramp output [163] Remote display
920 Last fault 4 [09] Speed [L4L] LI4 active Low to stop
[164] Modbus
Control menu
921 State of drive at fault 4 [135] PID reference [LUL] LIU active Low to stop
200- I/O MENU [136] PID feedback [183] Integrated display with Jog dial
999 HMI Password 201 Type of control 402 External reference value 502.3 Ramp divider
F000 Fault list [137] PID error 1 to 10 (4*)
[00]* 2-wire control [139] Output power -400 to 400Hz
I/O menu
F001 Precharge [01] 3-wire control 403 Integrated display jog dial reference 502.4 DC injection assignment
F002 Unknown drive rating [140] Motor thermal state [00]* Not assigned
202 2-wire type control [141] Drive thermal state 0 to 100%
F003 Unknown or incompatible power board [00] Level 404 Reverse inhibition [L1H] to [L4H] LI1 to LI4 active High
F004 Internal serial link [01]* Transition [00]* No [LUH] LIU active High
[02] Forward priority [01] Yes
The (*) indicates a parameter factory setting.
www.se.com 1/2
Easy Altivar ATV310 complete parameters list
502.5 DC injection level 512.3 2 High speed assignment 609 4-20mA loss Behaviour
loss
502.6 IDC injection time for DCLI 0 to 400Hz (30Hz*) 0 to High speed (0Hz*) [L1H] to [L4H] LI1 to LI4 active High [01] Freewheel stop
frequency
interrup. inhibit.
0 to 400Hz (40Hz*)
Jump
502.8 Injection standstill braking time 0 to 600s (0s*) [L1H] to [L4H] LI1 to LI4 active High [L1H] to [L4H] LI1 to LI4 active High
0.1 to 30 s (0.5 s*) 508 Skip frequency 59.24 Maximum frequency detection Hysteresis [LUH] LIU active High [LUH] LIU active High
503 Reverse direction 0 to 400Hz (0Hz*) 0 to 50Hz (0Hz*) 512.5 High speed 2 611 Modbus detected fault management
reverse direction
[00]* Not assigned 59- PID MENU 59.25 PID feedback supervision Low speed to Max frequency (50 or 60Hz*) [00]* Detected fault ignored
59.00 PID feedback assignment
Function
[L1H] LI1 active High [00]* Not assigned 512.6 High speed 3 [01] Freewheel stop
[L2H] LI2 active High [00]* Not assigned [01] Free wheel Low speed to Max frequency (50 or 60Hz*) [08] DC injection stop
[L3H] LI3 active High [01] Terminal [04] Fallback speed 512.7 High speed 4 612 Degraded line supply operation
59.01 PID proportional gain [00]* No
Degr.
[L4H] LI4 active High 59.26 Fallback speed Low speed to Max frequency (50 or 60Hz*)
line
[LUH] LIU active High 0.01 to 100 (1*) 0 to High speed (0Hz*) 513 Cooling fan control [01] Yes
504- AUTO DC INJECTION MENU 59.02 PID integral gain 510- PUMP SUB-MENU [00] Fan runs when drive runs 613 Reset power run
Fan
DC injection function
504.0 Automatic DC injection 0.01 to 100 (1*) 207 Process overload time delay [01]* Thermal control [00]* No
59.03 PID derivative gain [03] Reset drive running time
7
209 Process overload fault duration [L1H] LI1 active High
5
0 to 120% of nominal motor current (70%*) 59.05 Activation internal PID reference 0 to 6 min (0 min*) [L2H] LI2 active High of HMI
504.2 Automatic DC injection time [00]* No 210 Process underload time delay [L3H] LI3 active High [00]* Deactivated
0.1 to 30s (0.5s*) [01] Yes 0 to 100 s (0 s*) [L4H] LI4 active High [01] Active
505.0 Jog assignment 59.06 2 preset PID assignment 211 Process underload threshold [LUH] LIU active High 700- COMMUNICATION MENU
[00]* Not assigned [00]* Not assigned 20 to 120% of nominal motor current (60%*) 602- AUTOMATIC RESTART MENU 701 Modbus address
Jog function
[L1H] LI1 active High [L1H] LI1 active High Off to 247 (off*)
Automatic restart
510.0 Selecting operating mode [01] Yes
[L4H] LI4 active High [L4H] LI4 active High [00]* Single frequency conversion mode 602.1 Max. automatic restart [28] 9.6 kbps
[LUH] LIU active High [LUH] LIU active High [01] Single frequency conversion combined [00]* 5 min [32]* 19.2 kbps
505.1 Jog frequency 59.07 4 preset PID assignment with auxiliary pump mode [01] 10 min [36] 38.4 kbps
0 to10Hz (*5Hz) [00]* Not assigned 510.1 Starting frequency of the auxiliary pump [02] 30 min 703 Modbus format
506- Speed up and down [L1H] LI1 active High 0 to 60Hz (50Hz*) [03] 1 hour [02] 8o1
506.0 Up speed command [L2H] LI2 active High 510.2 Time delay before starting auxiliary pump [04] 2 hours [03]* 8E1
[00]* Not assigned [L3H] LI3 active High 0 to 999.9s (2s*) [05] 3 hours [04] 8n1
[L1H] to [L4H] LI1 to LI4 active High [L4H] LI4 active High 510.3 Auxiliary pump ramp reaching [06] Infinite [05] 8n2
[LUH] LIU active High [LUH] LIU active High 704 Modbus time out
Motor potentiometer function
on
506.1 Down speed command 59.08 2 preset PID reference 0.1 to 30s (10s*)
the fly
510.4 Auxiliary pump stop frequency [00]* Function inactive
[00]* Not assigned 0 to 100% (25%*) 0 to 60Hz (0Hz*) [01] Function active 705- INPUT SCANNER MENU
[L1H] to [L4H] LI1 to LI4 active High 59.09 3 preset PID reference 510.5 Auxiliary pump stop time delay 604- MOTOR THERMAL PROTECTION MENU 705.0 Com scanner read adress parameter 1
[LUH] LIU active High 0 to 100% (50%*) 0 to 999.9s (2s*) 604.0 Motor thermal current 0C81*
506.2 Store 59.10 4 preset PID reference 510.6 Auxiliary pump stop ramp 0.2-1.5In (According to drive rating*) 705.1 Com scanner read adress parameter 2
[00]* No 0 to 100% (75%*) 0 to 999.9s (2s*) 604.1 Motor protection type 219C*
[01] RAM 59.11 Internal PID reference 510.7 Zero flow detection period [01]* Self-ventilated 705.2 Com scanner read adress parameter 3
[02] ROM 0 to 100% (0%*) 0 to 20min (0min*) [02] Motor-ventilated 0000
506.3 Clear the function 59.12 PID reference ramp 510.8 Zero flow detection activation threshold 604.2 Overload fault management 705.3 Com scanner read adress parameter 4
Communication menu
[00]* Not assigned 0 to 99.9s (0s*) 0 to 400Hz (0Hz*) [00] Detected fault ignored 0000
[L1H] to [L4H] LI1 to LI4 active High 59.13 PID min value reference 510.9 Zero flow detection offset [01]* Free wheel stop
0 to 100% (0%*) [08] DC injection stop 706- OUTPUT SCANNER MENU
[LUH] LIU active High 0 to 400Hz (0Hz*) 706.0 Com scanner write adress parameter 1
59.14 PID max value reference 604.3 Motor thermal state memo
8
[159] Acceleration and decele-
6
0 to 100% (100%*) 511- CURRENT LIMITATION MENU [00]* thermal state not stored at power off 2135*
ration with command 511.0 2nd current limitation commutation 706.1 Com scanner write adress parameter 2
active high 59.15 PID predictive speed [01] thermal state is stored at power off
0.1 to 400Hz (0.0*) [00]* Not activated 605 Output Phase loss 219A*
506.4 Reactivity of +/- speed [L1H] LI1 active High 706.2 Com scanner write adress parameter 3
[00] Deactivated
Current limiration function
Phase loss
0 to 100% (0%*) 0.0 to 999.9s (5s*)
59.16 PID correction reverse [L3H] LI3 active High 606 Input Phase loss 706.3 Com scanner write adress parameter 4
507- PRESET SPEED MENU [L4H] LI4 active High [00] Detected fault ignored 0000
507.0 2 Preset speeds [00]* No, no negative speed
[01] Yes, no negative speed [LUH] LIU active High [01]* Detected fault with freewheel stop 707- INPUT SCANNER ACCESS MENU
[00]* Not assigned [L1L] LI1 active Low [08] DC injection stop 707.0 Com scanner read adress value 1
[L1H] LI1 active High [02] No, allow negative speed
[03] Yes, allow negative speed [L2L] LI2 active Low 607- UNDERVOLTAGE MENU 0C81*
[L2H] LI2 active High [L3L] LI3 active Low 607.0 Undervoltage detected fault management 707.1 Com scanner read adress value 2
Preset speed function
Undervoltage
[L4H] LI4 active High [LUL] LIU active Low [01] Detected fault and R1 relay set 1 707.2 Com scanner read adress value 3
[LUH] LIU active High [L1H] to [L4H] LI1 to LI4 active High
[LUH] LIU active High 511.1 Current limitation 607.1 Undervoltage prevention 8000
507.1 4 Preset speeds 0.25 to 1.5In (1.5In*) [00]* No action (freewheel) 707.3 Com scanner read adress value 4
same as 2 Preset speeds 59.18 PID manual reference
[00]* No 511.2 Current limitation 2 [02] Stop following an adjustable ramp 8000
507.2 8 Preset speeds 0.25 to 1.5In (1.5In*) 607.2 Undervoltage ramp deceleration time 708- OUTPUT SCANNER ACCESS MENU
same as 2 Preset speeds [01] Terminal 0.0 to 10.0s (1.0s*)
[183] Integrated jog dial 512- SPEED LIMIT MENU 708.0 Com scanner write adress value 1
507.3 Preset speed 2 512.0 Low speed 607.3 Precharge resistor protection level
0 to 400Hz (10Hz*) 512.1 Low speed operating time CMD value*
Speed limitation
0Hz to high speed (0Hz*) 430 to 560 VDC (0 V* with protection removed) 708.1 Com scanner write adress value 2
507.4 Preset speed 3 0.1 to 999.9s (0s*) 608 IGBT test
512.1 Low speed operating time
function
0 to 400Hz (15Hz*) 59.19 PID: wake up level [00]* No test LFRD value*
507.5 Preset speed 4 0 to 100% (0%*) 0.1 to 999.9s (0s*) 708.2 Com scanner write adress value 3
512.2 High speed
IGBT [01] Starting test
0 to 400Hz (20Hz*) 59.20 PID: Wake up threshold 8000
507.6 Preset speed 5 0 to 100% (0%*) Low speed to Max frequency (50 or 60Hz deter- 708.3 Com scanner write adress value 4
0 to 400Hz (25Hz*) mined by 301 parameter value) 8000