Professional Documents
Culture Documents
Release Notes v4.0.1 - EcoStruxure Building Operation 2022
Release Notes v4.0.1 - EcoStruxure Building Operation 2022
Release Notes
EcoStruxure™ Building Operation 2022
v4.0.1
This document is written for and on behalf of Schneider Electric and is supplied on the express terms that it is to be treated as
confidential and that it may not be copied, used or disclosed to others except as authorized in writing by this Company. This
document is intended for internal use only.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 1 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
This version of EcoStruxure™ Building Operation 2022 Release provides new features and
enhancements. It also includes fixes for several previously reported field defects.
This EBO software release is fully compatible with SpaceLogic IP Controller firmware v4.00.01
and therefore this document should be read in conjunction with the SpaceLogic IP Controller
v4.00.01 release note.
Important note:
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 2 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Table of contents
ABOUT THIS RELEASE ......................................................................................................................................................... 2
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 3 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
2.21 I/A Series WorkPlace Tech Editor support for Visio vsdx format application files ......................... 48
4. FIELD REPORTED DEFECTS FIXED IN ECOSTRUXURE BUILDING OPERATION V4.0.1 RELEASE ..................... 59
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 4 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
6.6 LonWorks............................................................................................................................................... 85
6.9 Archiving................................................................................................................................................ 87
6.16 SmartDriver............................................................................................................................................ 88
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 5 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 6 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
The EcoStruxure Building Operation Release 4.0.1 deliverable includes the following software
and firmware.
* This release is NOT supported on the original AS’s often referred to as AS classic (part
number - SXWAUTSVR10001) .
BMS Software Support Policy establishes a clear expectation for product support timelines. There
are two main levels of software support, Full support when the software is in its active phase and
Limited support for a period of two years after the active phase. For more information, refer to
the software support policy document on Exchange.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 7 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Ending Version
Upgrade Path
1.8 1.9 2.0 3.0 3.1 3.2 4.0
1.5 Via 1.7 Direct Direct Via 2.0 Via 2.0 Via 2.0 Via 2.0
Out of Support 1.6 Via 1.7 Direct Direct Via 2.0 Via 2.0 Via 2.0 Via 2.0
1.7 Direct Direct Direct Via 2.0 Via 2.0 Via 2.0 Via 2.0
Starting Version
* Versions 1.5, 1.6, and 1.7 are not supported. We suggest that systems with these releases
be upgraded to the latest release.
v2.0.1/2/3 Supported Not supported Not supported Not supported Not supported Not supported
v2.0.4 Supported Supported Not supported Not supported Not supported Not supported
v3.0.x Not supported Supported Not supported Not supported Supported Supported
* New v4.0 features are not supported when used with EBO v3.x.x.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 8 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Warning: Downrev is not supported between versions once the application is loaded on to the
controller.
It is imperative that any upgrades be accomplished only after reading and understanding this
document, especially those areas that are related to the upgrade process.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 9 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Release v4.0.1 of EcoStruxure Building Operation 2022 provides many new features for the
user in the following areas:
The details for each of these feature enhancements can be found in Section 2.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 10 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Existing modules:
• Blind High Voltage (4 groups) with power distribution
• DALI 4 groups (1 channel) with power distribution
• Sensor expansion module for infrared motion detection and
luminosity measurements
• Blind Low Voltage (2 groups) with power distribution
• Lighting 0 to 10v with power distribution
• Standard Motor Interface (SMI) high voltage with power
distribution (4 groups)
• Standard Motor Interface (SMI) low voltage with power
distribution (2 groups)
• DALI without power distribution (2 groups)
• Light 0v to 10v without power distribution (2 channel)
• Relay module high voltage with power distribution (4 channel)
• Relay Module (10 channels)
For additional information please refer to the user documentation which can be found on
Exchange.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 11 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Multi-version system
A multi-version system supports I/NET, Sigma, MicroNet, and NETWORK 8000 ASD and LCM on
automation servers running an earlier version than 4.0.
For example, you have a multi-version system with an Enterprise Server with version 3.2 with an
automation server of version 3.2 attached. The Enterprise Server does not contain any unsupported
protocols, objects, or devices but the automation server does. In this case you can upgrade the
Enterprise Server to 4.0 but not the automation server. However, the automation server can still be
attached to the Enterprise Server. These protocols, objects, or devices will still work on the
automation server.
Considerations
• You cannot upgrade EcoStruxure Building Operation servers containing not supported protocols,
objects, or devices.
• Import and creation of not supported protocols, objects, or devices are blocked by error messages.
• Not supported objects still appears in the New menu but the creation of the objects is blocked.
• Before an upgrade all not supported protocols, objects, and devices must be deleted.
Exception
There is an exception that is NETWORK 8000 interface and objects that can be created in a NETWORK
8000 interface such as NETWORK 8000 points, alarms, and controls including Optimal Start-Stop.
These objects are still supported and improved to allow global bindings on all NW8K objects.
Report Server/WebReports is not supported in EcoStruxure Building Operation 4.0 or higher. For
more details please refer to engineering section 6.20.1.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 12 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
The Create object dialog also has a new look and support for keyboard navigation. Selecting to create
a new object will take you to the create object dialog where you can select from available objects.
Example:
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 13 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
After selecting the object to create, the Create object dialog offers you options to “Edit in wizard”
like previous versions, to “Create and edit” which automatically selects the new object in the system
tree and opens it in the workspace, or “Create”. The options might differ depending on which object
type is selected.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 14 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
EBO 2022 includes a new implementation of the SVG import. The main issue addressed was the lack
of support of the SVG <defs> and <use> elements which are used in many SVG graphics. TGML has
now two new elements that correspond to these SVG elements: Definitions and Use.
The elements Definition and Use can be created in the Graphics editor as any other TGML element,
but the purpose of these elements in EBO 2022 is to support the SVG import which creates these
elements automatically. Other usage is not supported in EBO 2022.
Zoom level
The Group, Component and Layer elements have a new attribute called ZoomLevel. The ZoomLevel
determines at which zoom level groups, components, and layers are visible.
The default value is 0.0 which means the zoom-level feature for this element is disabled. Zoom level
1.0 is the original size of the graphics.
Note that the zoom level is changed when graphics are stretched or shrunk to fit in the window.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 15 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
• Create standard objects in the Application folder and sub-folders by selecting the desired
standard object in the New Object dialog.
Sub-folders of the Application folder can contain standard objects but not i2 or b3 objects. If you
attempt to create an i2 or b3 object in a sub-folder of the Application, you will get an error message.
2.5.5 Possibility to merge Extended Trend Logs back into original Trend Logs
for Timescale DB setups
If External Log Storage is configured, records in an Extended Trend Log can be merged to the original
log in the TimescaleDB. Then all historical data is available in one trend log. The Extended Trend Log
is then not necessary. Right-click on the Extended Trend Log and choose External Log Storage-
>Merge with source log.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 16 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 17 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Users no longer have to close the dialog to apply a binding template. Now in the dialog “Edit binding
template” there is a button to apply the template.
In addition, errors and warnings generated by the server when it performs change sets during a user
session will also be shown in Session notifications. This goes for direct (normal) changes, not changes
done via import operations or upgrade.
The information in Session notifications is only from the ongoing Windows session and the previous
Windows session on the same computer. The information is only for the Windows logged-in user.
Some of the information provided in Session notification is only available in English, so you may see
some of the information translated and other messages in English
A new policy controls whether this feature should be active for a user group.
Note that only the Administrator group in the local domain has this policy “On” by default. This
means that other users will not see these session notifications if they do not enable this policy for
the user group.
If this policy is active there is a user setting where the user can select if the session notifications
should be shown or not. If the policy is enabled and the user has turned it on, the Session notifications
”balloon” shows up beside the user icon.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 18 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
If there is an unread message of type error or warning this is shown this way.
When you click on the Session notification button this dialog will be opened:
There is a known defect. Occasionally a message box can hide under this dialog at it will seem that
WorkStation hangs.
If that happens, resize the dialog so that you are able to see the message box and respond accordingly
to close.
This dialog can be docked into your workspace, but note that the docking cannot be persisted, so it
will be temporary.
AutomationClient
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 19 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Method TryGetServerVersion has been added to get version information on a server before doing
Open. This method uses ping to quickly determine if a server can be accessed.
ISession interface
The interface has been updated with methods IsDatabaseMode and SetDatabaseMode . With these
methods one can handle the database/online mode the same way as it is done in WorkStation.
IProgram interface
The interface has been updated with methods that use a string as content instead of a file:
CreateFunctionBlockProgramString , CreateMPxFunctionBlockProgramString ,
GetFunctionBlockProgramString , SetFunctionBlockProgramString .
IObjectManagement interface
The interface has been updated with method MoveObject to move objects within a server whilst
keeping references.
ICommand interface
The interface has been updated with WarmStart, ColdStart and FactoryReset commands ICommand.
Support for generic download, with operation details, has been added: DownloadSync .
IFileObject interface
This new interface contains methods that pertain to File Objects IFileObject .
ICustomType interface
Because the system now supports nested Custom Types; the method GetCheckoutObjects was
added since the result can be more than one object to checkout. The old version GetCheckoutObject
has been deprecated, but is still supported.
IObjectDiscovery interface
The interface has been updated with methods that inquire an objects type inheritance: ObjectIsA
and GetObjectTypeInheritance .
ICustomType interface
BUGFIX: The underlying code was not properly initialized when using certain methods in the
interface.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 20 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
rule saying that all folders named Trend shall use the Content Type. You can use * and ? as wildcards
(Example: “Trends*”).All old and new folders/containers will be evaluated against the rule and then
the Content Type reference will be set. Example:
The rules can be prioritized between each other in case it can be multiple matches:
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 21 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
function block programs. Builder provides a workspace where programming actions are available
using robust drag and drop capability or with no or minimal mouse interaction using keyboard
navigation.
Builder also provides some key capabilities not available before such as:
• Users can edit and save unfinished programs, while the last deployed program is still
running. To “activate” a program in Builder that has just been created or has been edited,
the Deploy command must be used. It is the deployed/running program version that can be
used outside Builder to bind signals and other objects to it.
• Programming can incorporate the use of “remote bindings” that make it possible to create
“wireless” bindings across the program.
• New blocks that provide Relinquish capability to allow the program to send a “null” when
triggered.
• Optional line styles allow the user to choose from curved, orthogonal, or straight lines.
• Provides automatic binding of objects when using the “New object” menu.
And more…
The old function block editor and Workstation live view, now referred to as “classic”, are still
available and can be accessed by the switch button “Show Classic Mode”. It is recommended to use
classic mode for old programs that do not redraw well when viewed with Builder.
It is not recommended to switch between using the classic editor and Builder for the same program.
Switching between editors can have unwanted behavior (e.g., strange block placements and
bindings) and some features created with Builder might disappear if edited with classic (e.g., remote
bindings, etc.).
It is possible on a user level or via policies for a user group to deactivate the new Builder for Function
Block altogether so only classic mode is available.
You set which segments will be managed by a zoning preset. Then you create preset configurations
that describe which of the managed segments shall be grouped.
Each preset configuration has a numeric index that you set to identify the configuration. The zoning-
presets property Active preset, which can be bound to for example programs, determines which of
the configurations shall be active and when you set a value that corresponds to a configuration index,
a zoning operation is executed.
No zoning operation is executed if the value of Active preset does not match a preset configuration.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 22 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
The configuration type “Standalone preset” is an empty configuration that will ungroup all segments
that are managed by the zoning preset.
The Zoning presets functionality is not affected by the group policy Zoning setting.
In the Last will tab, there is a new property “Last will retained” which is default “No”. In EBO 3.2 it
was not configurable but was “Yes” in the code. Default values for Starting and Stopping are now
empty.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 23 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
In the Other tab, you can configure unit conversion to SI and scale to SI prefix.
Note
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 24 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
The identifier can also be the configured value in the Foreign Address property. Normally the Foreign
Address is regenerated during import, but values under the MQTT client, will be exported and
imported with the same Foreign Address.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 25 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
To enable this there are quite a few steps to go. The configuration in the ADFS is described in another
document since it is out for validation when this is written.
Note
Federated Authentication cannot be configured in PCT 1.3.1. Currently there is no plan to support it
either so it can only be done in live environment. In PCT there will be a system alarm of missing
functionality.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 26 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Create a User Account Group and type the name of the external entity. Set permissions.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 27 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
In the Identity Provider Settings, type the address to the Identity provider and the URL to the SSO
Service and Single Logout Service. Also, paste the public key to the certificate.
Finally, configure the Security settings valid for the specific authentication.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 28 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
- When deleting a nested custom type in the Type Library, the parent custom type needs to
be deleted first and the inner custom types thereafter.
- When exporting a nested custom type, its inner custom types are also exported.
Note that nested custom types cannot be used in older versions of EBO.
2.10.2 Imported device type
In EBO 2022 an engineer can import new Zigbee device types to the Type Library (earlier called
Custom Type Library).
Zigbee device types behave as read-only custom types and can thus only be added through type
library import. Since the device types are read-only you cannot edit them, which also means that
some custom type operations are disabled.
Zigbee device types can be instantiated the same way you instantiate custom types but also using
the new menu. Note that these types cannot be instantiated or created from the New command
when logged into an EC.
2.10.3 Detect tampering of user-defined type in export file
One of the foundations of user-defined types (for example graphics and custom types) is that they
are immutable. An immutable type can never be changed and is guaranteed to have a unique
identifier.
Since we want to guarantee that all user-defined types are immutable, we have introduced a way in
EBO 2022 to detect tampering. This means that EBO 2022 can detect if a user-defined type has been
manipulated in an export file. If the type has been modified, then the import will be stopped since
we otherwise would get two different types with the same identity.
2.11 Semantics
Semantics is a concept where contextual information can be added to the system. It can be classes
on points or locations and equipment and relations between entities.
EBO is using a semantic (graph) database (GraphDB) which is installed together with EC and ES as a
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 29 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Windows Service. EBO has also added some additions to enable functionality in views, e.g. showing
related alarms.
In an EBO system you usually only use one instance of the semantic database, so when setup an EC,
you disable Semantics in the ES:s. See more below.
To use Semantics, the user group must have the correct policy set, and to use the Engineering view,
the user must also have Write permission.
Note
There is no support for Semantics in PCT 1.3.1 and PCT 1.3.2. Support for Semantics is planned to be
included in PCT 1.3.3.
2.11.1 Installation
When installing EC or ES, the GraphDB is installed under the hood as a Windows Service. It is possible
to set port to the database and disable Semantic in the installation. The database will be installed
regardless, but the service will be stopped. The URL in the settings should be deleted.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 30 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
To enable Semantic again after installation, you need to open Windows Services and start the
GraphDB Service. Then set the URL in the Semantic Settings. After a while, the EBO server will detect
that GraphDB is running and make the proper configurations. Under the hood, the ontology should
be uploaded to the semantic database.
Note: It is highly recommended to change the default admin password (“root”) on the GraphDB
directly after installation. A system alarm will be triggered and active until the password is changed.
The system itself will use a service account with an auto- generated password, so the admin account
is not used by EBO.
Links to the configuration parameters and the GraphDB itself can be found in the Control Panel.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 31 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
To add a semantic item, click on the + sign or drag a semantic type from the Brick tab. If no label is
set, a GUID will be shown instead.
You can also drag an object from the tree or list view and drop it in the work area.
If a naming convention with Brick types is imported in ~\System\Engineering, the class will
automatically be set when dragging to the work area. NOTE: Ensure that no header is present and all
entries in the type-column must contain “:” e.g. “brick:Alarm” in the csv-file.
Relations to existing alarms and trend logs are automatically set when setting a class to a point,
however, if you add or delete alarms and trend logs after, you need to manually update the relations
by using the command “Update the Semantic model”, which can be found in the context menu of
~\System\Semantic.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 32 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
If you have imported an ontology directly to the semantic database, there is a command on the same
object, Enrich model, which will set relations between points and alarms and trend logs.
You can also create a panel including a Semantic pane and apply a filter.
Alarms and Events can be filtered by item, type, label, and reference. It can be filtered on the direct
item or below in the hierarchy.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 33 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Search has a new tab where semantic search can be performed, e.g. find all temperature sensors
where Value is higher than 27:
You can also filter on Semantics in Alarms and Events in Notification Reports.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 34 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
The semantic features in WebStation are available when there is a connection to a semantic database
and the user-group policy Semantic permissions is set to Read-only or Write.
The semantic type information (for example Air Temperature Sensor) is shown together with the
property value when the property is connected to a Brick Point in the semantic database.
Semantic information is shown as a breadcrumb in the header of Alarm details when the monitored
value, or property of the alarm object, is connected to a Brick Point in the semantic database.
The breadcrumb is a simplified presentation of how the monitored value is related to “parent items”
in the semantic database, for example, which equipment or space this value belongs to.
You can navigate with the breadcrumb which opens the semantic view.
The semantic navigator is available when the workspace includes a Semantic pane. With this
navigator, you can navigate in the semantic model. A semantic view is displayed when you select an
item in the navigator.
The navigator includes a filter editor and you can create your own temporary filter in the navigator
(like a quick search). Filters are created automatically when you navigate and the temporary filter
you created will be replaced when you navigate.
If you want the navigator to always start with a certain filter, you create a workspace with a semantic
pane and specify an initial semantic filter for this pane.
The semantic view lists the “child items” of the selected item. The semantic view has also a graph
that visualizes the relations to the “parent items” and a breadcrumb in the header with a simplified
view of the parent relations.
Alarms, Schedule, and Trend chart are available in separate tabs in the semantic view when the child
items have relations to alarms, schedules, and trend logs. These relations are created automatically
when you connect a property value to a Brick Point in Workstation.
You can create semantic filters in alarm- and event views and save them as favorites. When you
create a filter, Column filter represents the “regular” EBO filters. Item, Item of type, Item with label,
and Item with reference are semantic filters.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 35 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
When you use semantic filters in Alarm and Events, the result will be alarms and events related to
semantically described EBO objects, which means EBO objects connected to semantic items.
The semantic items are typically Brick Points that are connected to properties of Value objects or
Alarm objects.
When you use semantic filters in Search objects, the result will be semantically described EBO
objects, i.e. typically Value objects with a connection to Brick points.
If the condition “Include semantic references” is set (you do this in Workstation), the search result
will include trend logs, schedules, and alarm objects that are bound (with EBO references) to the
semantically described EBO objects.
Metadata with semantic information is implemented for GetContainerItems and GetItems and the
metadata is included in the response when the EWS input attribute “metadata” is set to “true”.
The metadata describes the connection between the EWS item in the request and the nodes/items
in the semantic database. This description includes the Brick-type information (“semantic
information”) of the connected node, for example “Air Temperature Sensor”.
The semantic database is exposed as an EWS container called “Ontology Graph” that makes it
possible to navigate in the semantic database with EWS. Ontology Graph is exposed directly under
the server container item.
The connected EBO properties and objects are represented by “address nodes” in the semantic
database (namespace nspg). If you know how to construct SPARQL queries to a semantic database,
you can retrieve these addresses and use them as EWS Id in the following EWS methods:
- GetHistoryItem
- Subscribe
- GetItems
- GetValues
- SetValues
- ForceValues
- UnforceValues
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 36 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Secure Boot AS-P supports the new Scalable AS Pricing Concept. In all other perspectives AS-P Secure
Boot and the existing AS-P is compatible.
Secure Boot AS-P is not compatible with EBO 3.2 and earlier releases.
Enhance
d
Standard
Standalone
With EcoStruxure Building Operation 2022, the Zigbee Adapter will enable Zigbee 3.0 wireless
connectivity for the SpaceLogic RP-V controller. It can communicate over the Zigbee wireless
protocol with more wireless devices, including SpaceLogic Zigbee Expansion Modules (RP-C-EXT-ZB-
DALI Zigbee-to-DALI module and RP-C-EXT-ZB-0-10V Zigbee-to-0-10Vmodule)and PowerLogic Power
Tag Energy Sensors, and as a certified Zigbee device, will allow interoperability with third-party
Zigbee devices.
With an open Zigbee device support capability, support for new Schneider Electric and third-party
Zigbee devices can now be added to EcoStruxure Building Operation 2022 or later through a service
that is provided by the Digital Buildings Center of Excellence. See the Zigbee Adapter Specification
Sheet for more information on the new features and the supported wireless devices for the
SpaceLogic RP controllers and/or SpaceLogic servers.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 37 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Warning: Do not move the adaptors between RP-C’s or AS-P’s, as for this release, once plugged in
and recognized by the device they will not be recognized again if moved between devices, without
deleting the complete Zigbee network.
2.15.2 Support for Enrolment under SE8000
Motion Sensor, Window/Door Sensor, and Water Leakage Sensor can be enrolled to a SE8000.
The sensors will then report values to the SE8000 instead of to the AS.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 38 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 39 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
2.16.3 Property level permissions – decide down to property level who has
access
It is now possible to set permissions on properties, e.g. in programs etc. Open the dialog by clicking
on the wheel.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 40 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
• Stop Communication
• Both send alarm and stop communicating
If you are using the default certificates distributed with the EBO installation, these certificates will
always fail the validation since they are self-signed and cannot be validated against a CA certificate.
In order to supply certificates that can be validated you need to perform some steps in the Device
Administrator for the SpaceLogic servers
And some manual steps in Windows for the Windows servers.
You need to create server certificates that have been signed by a CA certificate.
For servers exposed to public networks usually a commercial certificate is being used, obtained from
a trusted certificate authority.
For servers on private isolated networks, self-signed CA certificates can be used.
In the Device Administrator CA certificates can now be downloaded to the Smart-X server.
For Windows servers, you instead add them to the Windows certificate store.
The server certificate that has been signed with the CA certificate is also downloaded via Device
Administrator to SpaceLogic servers.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 41 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
In Workstation, you find it under Schedules in the Create dialog. In WebStation you right-click on an
existing schedule and choose Create Multi schedule viewer, which also adds this schedule to the list
of schedules. Then you can add other schedules in the Create object dialog.
The viewer is a Day view. You can choose which day to show in the tool bar and in the header.
You can also edit the schedules, single or multiple schedules, using the mouse (click-drag).
You can open the “regular” schedule editor by right-clicking the name of a schedule.
The multi schedule viewer object can be renamed and deleted in WebStation.
Note that the Alarm Count widget has a built-in filter. Column: Alarm state, Condition: Alarm. You
can add more conditions, such as a Priority filter, but the conditions should not include the alarm
state.
A filtered alarm view is opened when you click on a bar, slice or node in Alarm Pareto charts, Alarm
pie, or Alarm Sankey charts.
Attachments for active alarms are available in the toolbar (the attachment symbol).
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 42 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
2.17.5 More options for setting up trend logs – all settings are available when
creating
We have added a second step in the creation flow when trend logs are created in WebStation to
make it easier to configure the new trend logs. The property dialog for the selected type of trend log
is now automatically displayed when the user clicks OK in the creation dialog. The trend log object is
created when the user clicks OK in the property dialog.
You can now edit the label of the segment group in the zoning tool and the default label now includes
the name of the controller and the name of the active master, similar to how it is presented in
Workstation.
Segment folders has a new property called Group label. The label of the group is stored in this
property in the active master segment.
In the previous version we used a TGML attribute to enable zoning in Graphics. This setting is now a
property in the Graphics object and the TGML attribute has been removed. The default value of the
Zoning property is False.
You don’t have to update your zoning settings if you used the old zoning attribute in EBO 3.2.
Graphics that were enabled for zoning in EBO 3.2 will also work in EBO 4.0.
The integrated zoning tool is now hidden by default but there is a toolbar button to open and close
the tool.
The toolbar now includes buttons for Group and Remove selected segments. You select the segments
that are represented in the graphics with mouse-click (single select) and shift-mouse-drag (rubber-
band select).
The Remove operation will result in a ungroup operation when all the group members are removed
from the group or when you remove the active master in a group with only one master-capable
segment.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 43 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
• List view settings. WebStation can now show properties ("columns") that have been
configured as Content Types for a folder in Workstation.
• Support for logarithmic scale in charts.
• Possibility to disable multi-select alarms. Property: “Disable multi-select” in the Alarm
Control Panel object.
• Dashboard heatmap: Improved visualization of missing values (new property in heatmaps).
• Dashboard gauges: The color of the indicator follows the color of the guides when the color
of the indicator is Null.
• Possible to select and clone widgets in dashboards (new tool in toolbar).
• Possible to select and rebind widgets in dashboards by specifying a target folder (new tool
in toolbar). Objects with matching object-/property names in the target folder will be
proposed as the new binding.
• WebStation supports federated authentication, which includes signing in Electronic
Signature.
• Event details are opened as a pop-up when the browser window is small.
• Possible to do multi-select edit in search.
• Possible to move events in schedules to another day within the same week (not supported
on mobile devices such as phones).
• Better visualization of active schedule events when you have overlapping events with
different priorities.
• Possible to configure a unit for a value in Properties.
• Possible to add a value to Watch in Properties.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 44 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
This release provides two new configuration settings that cause the EBO Server to ignore I-Am
messages from devices not hosted in the EBO Server’s database. Both settings control the Ignore
unhosted devices property.
The first configuration setting is found in the Basic tab of the BACnet Interface. The setting defaults
to No (do not ignore unhosted devices).
The second setting is found in the Device Discovery tab of the EBO Server, when BACnet Devices is
selected. The setting is visible only when the Ignore unhosted devices is set to Yes.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 45 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
The first configuration setting is found in the Advanced tab of the BACnet Interface. The setting
defaults to 60 minutes.
The second configuration setting is found in the Advanced tab of the BACnet Device proxy. The
setting defaults to Normal (poll at the default 1-minute interval). When the setting is changed to
Extended, the system will poll this device at the rate defined by the Extended online poll interval.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 46 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 47 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
A new BACnet Interface type is now provided (SC Network) for configuration of all BACnet/SC
communication parameters. In this release, EBO Servers may host up to 10 other BACnet/SC
devices. The routing of BACnet messages between BACnet/SC and non-BACnet/SC networks is also
supported(providing backward compatibility between BACnet/SC and BACnet IP and MTSP
networks).
BACnet certificate installation and management are supported via Device Administrator.
2.21 I/A Series WorkPlace Tech Editor support for Visio vsdx format
application files
I/A Series MNL and MNB applications are now stored in Microsoft Visio .vsdx file format. As a result,
Visio 2010 is not supported in EBO 2022.
• When you edit an application after upgrade to EBO 2022, you will be prompted and required
to upgrade to .vsdx file format on first save.
• There is no need to convert applications all at once. Applications can remain in a server as
.vsd files indefinitely until they need modification.
• When you save an application as a .vsdx file, it cannot be reverted to a .vsd file.
• When you save an application as a .vsdx file, users who have not upgraded WorkStation
WorkPlace Tech Editor to a version that supports .vsdx format will not be able to view, edit
or monitor the application.
Note:
In case of issues compiling or saving applications in WorkPlace Tech Editor, update Visio with the
latest Microsoft Office updates.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 48 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Note: Offset calibration will not be accurate if there is damper leakage. If possible, you can minimize
the impact of damper leakage by performing calibration at a time when the air-handler is off.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 49 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
• On upgrade to EBO 2022, inputs configured with a reference and a constant prior to the
upgrade are Forced to the value from the pre-upgrade constant. The upgrade log includes
warnings indicating any inputs that upgraded to a forced state.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 50 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 51 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 52 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 53 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 54 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 55 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 56 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 57 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 58 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 59 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 60 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 61 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 62 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 63 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 64 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
#
Installation Defect PSS
Summary ID Ticket ID
EBO: Multiple C++ packages are no longer supported by Microsoft but are 78641814,
required for EBO 47093 78624413
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 65 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 66 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 67 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 68 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 69 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 70 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
ES server taking over 10 mins to stop when using HTTPS/443 after upgrading 68547203,
45403
to v3.1 77455262
98,
ES Crashes during shutdown in Runtimedbmanager 31613 70905009
98,
CDA: AS crash - BACnet ASSERTION FAILED 44747 82686550
98,
CDA crash in Xenta handling of ObjectHandle acquisition 45246 61665432
70754945,
71007523,
Edit a Xenta will crash Menta if AS-P is running in PCT 45260 79540214
ES Crash when INET IPortAPI64 DLL installed 45500 71484912
98,
74593227,
CDA: AS crash in WebStationSessionObserver 46141 75103154
ES keeps crashing after every service restart 46214 74433998
AS-P crashed when using a faulty script program. 46730 76537306
ASP keeps restarting every 8 minutes the Memory usage increases and the
AS crashes, no core dumps 46814 76899464
Restore backup, the AS-P crash the moment the ethernet cable is connected 47134 78882475
AS-P acting as gateway between Modbus and BACnet keeps crashing 47150 78502857
80731517,
AS-P crash after adding an XML Webservice interface. 47470 81888118
Report Notification Crashes ES server 47662 80660859
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 71 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
80987804,
80906797,
81165978,
81195379,
81432502,
SmartDriver unloads after warm start or power cycle 46607 81761638
81354753,
Slow FBP cycle time on AS-P after apply hotfix 47571 79997870
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 72 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Unable to upgrade ASP due to custom type links to the controller objects 45674 72455263
79051530,
Issue with EWS after upgrade to EBO 3.2.2 from EBO 2.0 47294 75923487
Following an upgrade from EBO 3.0 to 3.1, the AS-P fails to start. 43846 67293221
ES and EC slow to open Server tree after upgrade to version 3.2.2 46860 77160071
Deploy of upgraded db (HAL: SL78) failed: error 'Package installation failed’ and
Download failed 45458 72326992
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 73 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 74 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Events from both the ES and AS is shown in the Event view when opened from
Webstation 46451 75403357
There is a limit of 27 charcters in Webstation for how long the shown text in
MENU objects can be 46628 75832596
Wrong trendchart is opened in Webstation 46630 75150118
TGML component "drawer" not working properly when zooming in WebStation 46637 76103118
76107383,
Webstation does not highlight the correct item in the navigation tree of a menu. 46652 80169580
User with read ONLY access is able to modify the filter of standard event/alarm
views in Webstation 46665 76580567
Blank page is displayed ,when any fields from the filter list is selected for the first
time in webstation 46676 99
Webstation: Right click - Zoning in Graphic hangs when there are unresolved
bindings 46749 76190566
Webstation: Cannot display more than one floating window from Panel 46809 77188924
Multi trend log list doesn’t display log identity in webstation. 47028 77903318
Workstation/Webstation hangs waiting for Modbus TCP values in Graphic 47032 77079702
Unable to set force to NULL in Webstation 47075 78261525
Pop-up buttons in TGML does not work in WebStation 47099 78347953
Webstation: Exported trends in Excel show "Value edited" instead of actual
value 47102 78399116
78857860,
Webstation: Error message viewing Schedule spanning Daylight Saving shift 80472796,
time 47126 81425811
EBO: Webstation Graphics are presenting 1 or 0 instead of correct active text. 47166 78604073
A bound TGML elliptical Arc, does not display correctly in webstation. 47303 79884043
TGML script using SkiponFallBack is not working as it should in Webstation 47334 79834497
Webstation : Alarms originating from AS are not visible in ES’s Alarm view
object when logged on to EC even if the user has the software permissions to
view AS alarms 47418 99
Webstation: When one of the AS-x under an ES goes offline, the navigation
menu under the ES throws the offline error in Webstation and user is not able to
navigate to other ASs that are online 47592 81070321
81564407,
WebStation: Alarm acknowledgment when Comments are enabled are 81928798,
acknowledged without having to enter any comment. 47633 83294868
Using webstation with PCT, scrolling to the bottom of alarm details window,
closes the view. 47636 81742731
Alarm View “content window” replaced by Alarm’s attachment in Webstation 47659 81254552
Panel will not load correctly in WebStation if linked to other panel via shortcut in
Menu object 48084 84158974
Multi Schedule View : Blank screen in webstation while adding exception events
in the Multi Schedule View. 48239 97
The calendar date range view is not shown correctly in the Webstation 48298 85004987
Mouse cursor offset when editing a FloatingWindow schedule with an increased
window height in WebStation 48322 84970873
Extended trend logs (ETL) display no data in Webstation if user only has read
only access. 48347 85090404
BaSE Replica - Webstation issue - Type error 48385 97
No values are shown in graphics connected to ES using Webstation 48425 84380402
WebStation - List Views - Type Column does not contain clear text 48500 97
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 75 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 76 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 77 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Auto suggest automatically insert wrong text into EBO string value object 47035 78049420
Add/Remove columns not working when you have Folder added under an
46243 74737753
BACnet Interface\Application Folder.
The new naming standard feature only matches on point name and not on point
45611 72224252
description.
Insight Sensor - Ambient Light column name in Listview mode (workstation)
when you select to add AmbientLight/Value/MotionDetected 48458 97
In workstation, the menu object view when renamed is incorrect when the main
menu is part of navigation pane in a panel 48587 97
Menu object - when an object is places under the Menu, it can be re-named in
the workspace pane, however the names in the System Tree pane are not
updated. 46829 77200463
Having a main menu on one server and submenues to the main menu on
another server is not working correct. 46100 73619346
"Copy properties from..." option does not copy values from FBP module 46627 99
Schedule toolbar option for adding event is not following the user permission
correctly 42341 59103310
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 78 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 79 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Andover Continuum Controllers are vulnerable to the Treck TCP /IP issues. Sites using Continuum
controllers are strongly encouraged to apply standard network mitigations, including network
segmentation, to address these vulnerabilities. See “Mitigation Strategies” below for additional
mitigations suggestions.
Two Denial of Service attacks were found in the version of the FlexNet Published used for Vista sites.
The Vista product went End of Service on 1-31-2021 so it is no longer possible to provide a fix these
issues. Sites using Vista are strongly encouraged to follow standard network mitigations to address
these issues. See a list of some mitigation strategies below.
The Xenta 511 and 911 controllers have a weakness in their web interface that allows a user logged
in as root to use a web browser to traverse the devices directory tree and view the devices root
password. The fact the user is already root means this is a low risk vulnerability. Following standard
user account practices is important in addressing this issue. Xenta controllers should never be
connected directly to the Internet and Xenta sites are strongly encouraged to follow standard
network mitigations to help minimize risk. See a list of mitigation strategies below.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 80 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
• Never allow mobile devices that have connected to any other network besides the
intended network to connect to the safety or control networks without proper
sanitation.
• Minimize network exposure for all control system devices and systems and ensure that
they are not accessible from the Internet.
• When remote access is required, use secure methods, such as Virtual Private Networks
(VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most
current version available. Also, understand that VPNs are only as secure as the
connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best
Practices document https://www.se.com/us/en/download/document/7EN52-0390/.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 81 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 82 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
• WebStation operation
o There are currently available some cybersecurity software products that make
use of what is known as “aggressive” caching. This action will prevent
redirection and will prevent a user from being able to log into an Enterprise
Server or Automation Server that is downstream of a device that uses this
software. Such caching will need to be disabled for WebStation to operate
correctly.
• Long user initiated operations
o A user triggered operation, like hosting a big system via EWS or the manual
start of a huge backup, that takes more than 90 minutes to complete by the
server will result in an error message “Wrong user ID or password” and then
WorkStation will be restarted. The message is somewhat benign since the
actual operation started by the user will be successfully completed by the
server.
• Resource limitations to consider during engineering
o When designing and engineering a system, make sure not to over-engineer a
server. Make sure to follow stated architectural guidelines and do not add, for
example, too many trend logs in an AS where resources are the most limited.
Adding too much content and logs can cause performance reduction and even
a crashed server if disk ends up being full. Reference the Architectural
Guidelines from Exchange for further information.
6.2 Backup
6.2.1 Backup validation
Please note that the default behaviour for database backup validation is changed. The
configuration database will always be validated, but the historical databases on Enterprise
Server and Enterprise Central will not. This change is made for performance reasons. We
think this is acceptable because we have seen an insignificant number of actual cases of
issues with databases getting corrupt on a PC in a way that can be detected by the current
SQL validation during the lifetime of this product.
6.2.2 How to activate full validation of historical data
To activate full validation of historical data in backups for Enterprise Server and Enterprise
Central respectively, go to C:\Program Files (x86)\Schneider Electric EcoStruxure\Building
Operation 3.0\Enterprise Server\etc\config and change the Enterprise Server and Enterprise
Central config file line value for NspServer.BarManager.FullValidation from false to true.
Please note that this can have severe performance implications, especially if you are using a
mechanical hard drive for your database.
• When upgrading an Automation Server, the Device Administrator will indicate the
upgrade has completed successfully before it is possible to log on. The time difference
can be quite long for a large size database.
• Due to changes that were made in several areas of the Linux server operation, there are
more frequent spikes to the CPU utilization percentage. The average CPU utilization is
not substantially increased but there will be spikes that could generate false alarms if
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 83 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
alarms are attached to the CPU percentage. It is recommended that CPU percentage
alarms include a time delay of at least 60 seconds.
• DFU upgrade: It has been seen that using DFU mode to upgrade an AS-B can fail,
generally repeating a second time will resolve, if not unplug the USB lead, restart Device
Administrator, and repeat the upgrade again.
• Downgrading a system is not supported; however, there are occasionally circumstances
that may cause a person to abort an upgrade and revert their system to the previous
version by downgrading servers and restoring back up files. Downgrading must be done
locally via USB and following a DFU reset of the Automation Server. The DFU reset may
also result in the Automation Server falling back to the default IP address which will then
need to be changed.
6.4 WorkStation
• If a binding name is changed in the graphics or script editor, any binding that might exist for
that component is removed.
• If a value is displayed in the spreadsheet view with localized units, then any copying of that
value to another location will also copy the localized units.
• An event view can only show 100,000 entries. If there are entries that are older than 100,000
entries, a filter will need to be created that allow the entries of interest to be included in the
view.
6.5 WebStation
6.5.1 Graphics Viewer
• Global variables that are already defined in IE, Firefox, and Chrome will not work.
Example: top,x,y, width, height
• Functions that are called and that actually are properties show a script error.
Example: array.length() instead of array.length
• Scripts that do 'drag', need to call preventDefault() on mousedown. This disables
standard touch/drag panoration
• Use of java classes is unsupported.
• Please use 'var' when declaring variables inside your TGML scripts instead of assigning
global variables. This enables you to use global scripts (UseGlobalScripts flag in TGML
root element) that make it possible to share functions between Script nodes. Having
UseGlobalScripts set to True will also improve performance substantially in
WebStation. See section 6.3.
• There is a simple tool in the Statistics tab of the Graphics Editor that will tell you if your
image has some of these common issues.
6.5.2 Workspace and Panels
• The use of toolbars in WebStation is restricted. The Statusbar, Historybar, and
Addressbar have no effect in WebStation. Hidden and Not available have the same
results (Hidden).
6.5.3 General information
• Status overlays on the icons in the System tree are not available in WebStation.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 84 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 85 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
6.7 b3 Devices
• When selecting and downloading from the application folder, it is necessary to select
and download in the appropriate order to satisfy all of the referencing accomplished
in the bindings. Downloading the entire device avoids this type of problem.
• When creating BACnet schedules, it is important to add those items to be controlled
by the schedule to the Object Property Reference List and NOT to use the binding tool
to bind those items to the schedule’s value.
• In order for extended log data to capture b3 log data successfully, they must be
configured in a very specific way: a) Smart Logs = False b) The intrinsic b3 logs must be
evenly divisible by the maximum transfer interval of the ETL Reference on Exchange
Knowledgebase.
6.8 Trends
• When a COV trend log is created in an Automation Server to monitor an object from a
field bus device, attention should be given to the capability of the field device. If the
field device supports COV, as many BACnet devices do, then the BACnet device will
supply the Automation Server with data via COV, but it will do so at an interval that
corresponds to the devices interval not to the delta as established by the trend log. If
the device does not support COV, then the trend will function as a polling trend with
an interval of 500ms. In those cases, users should create an interval log to avoid
unnecessary field bus communication.
• In order for extended log data to capture b3 log data successfully, they must be
configured in a very specific way: a) Smart Logs = False b) The intrinsic b3 logs must be
evenly divisible by the maximum transfer interval of the ETL Reference on Exchange
Knowledgebase.
• Each SpaceLogic server in an installation has two properties relating to trend logs:
Trend storage capacity and Trend storage usage. Whenever the usage exceeds the
capacity, a system alarm will be generated. There is also an indication whenever a
trend log of any type is created of how many records the new log will consume and
what the available storage is.
• Previous versions of the Architectural Guidelines contained erroneous information
concerning BACnet trend logs. All SpaceLogic server devices have a limit of BACnet
trend log size limit of 1,000 records. The 1.9.0 Architectural Guidelines have been
updated to include this limit.
• Manual trend logs are truncated - Old manual trend logs are truncated to 100 000
records in EcoStruxure Building Operation 2.0 and EcoStruxure Building Operation 3.x.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 86 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
6.9 Archiving
When archiving using the CSV format, the maximum size limit for the archive will be
65,536, which is the maximum allowed in an Excel spreadsheet.
6.10 Web Services
• Script Web Service
o When capturing date / time data through a script program in an Automation
Server, that time will be localized by the WorkStation to the time zone of the
WorkStation whenever the data is displayed. Consequently, the Automation
Server’s script program should include the logic to adjust the date/time value to
UTC.
o Script programs do not recompile based upon bindings. Consequently, you may
enter a program, save it, establish bindings, and save the bindings. Yet, it will only
appear to be running without many of its outputs actually being set. It is necessary
to force a recompile of the programs to allow the web service information to be
incorporated into the actual byte code of the program.
• EcoStruxure™ Web Service (EWS)
o When configuring trend logs and extended trend logs, it is important to be aware of
their relative sizes and polling intervals. The trend log must have a size big enough
to store all values from a single poll - typically at least twice the size of values
received in one poll. Otherwise, the extended trend log will not be able to keep up
with the trend log. There must be sufficient time for the extended trend log to read
the values from the trend log before they are overwritten.
o EWS connections to servers and clients that support MD5 and not SHA2 (SHA-256)
HASH algorithms will require the MD5 is enabled in the EcoStruxure Building
Operation Server. The documentation of each connecting EWS solution should be
reviewed to determine which HASH algorithms are supported when configuring
EcoStruxure Building Operation servers. MD5 is the least resilient HASH algorithm
and SHA2 (SHA-256) is the most resilient HASH algorithm that EcoStruxure Building
Operation supports. The option can be found in WorkStation Control Panel ->
Security Settings -> Disable MD5 Hash.
o When configuring a multi-server system, it is best to establish the EWS interface
after all server renaming takes place. A client that uses cookies will suddenly trigger
error messages such as "access denied", and no more data will be communicated
when the server is renamed or moved into a multi-server configuration in a running
system. The cookies, and all other communication parameters, are valid so the client
does not detect any communication problems and continues to use that cookie.
When this occurs, it will be necessary to restart the reconfigured server.
6.11 Editors
• If When two engineers are simultaneously editing the same program (Function Block or
Script) or using WorkPlace Tech Editor, they will have no idea that someone else may be
editing the same object. The final save of the object in question will be the final copy
that is in the server.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 87 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
6.12 Authentication
• When setting up a site with a Windows Active Directory, make sure the Enterprise
Server is running with rights to read at least those AD-groups that are intended to be
used for authentication via EcoStruxure Building Operation.
6.13 Schedules
• In order to accommodate as many resolution settings as possible for the graphic
display of the WorkStation Schedule editor, it was decided that the smallest event
duration for that editor would be 5 minutes. If an event duration of less than 5 minutes
is desired, the user is directed to use either the text editor that is located on the
Advanced tab of the graphical schedule editor or to use WebStation.
6.14 Import / Export
• In keeping with the general policy of maintaining support for a period of time after
releases are delivered to the market, the 4.0.x release will not guarantee backward
compatibility to files that were exported prior to release 1.8. For more information ,
refer to the software support policy document on Exchange.
• Export files are, in general, NOT backward compatible. A Script or Function Block
Program that is exported from v3.2.x is NOT guaranteed to import successfully into an
earlier release.
o Starting in version 3.0.x, import files exported from a newer release than
where they are imported will be denied. An export file from 3.2.x cannot be
imported in 3.0.x. An export file from 3.0.x can however still be imported in
2.0.x, but it's not recommended, and it may fail to import successfully.
o In version 3.1.x, or earlier, import files exported from versions older than 1.3,
will be denied.
o Starting in version 3.2.x, import files exported from versions older than 1.8.x,
will be denied.
• If you make use of a library of exported files, then you should import them into a
supported version and re-export them for maintenance in your library.
• Import of export files created from version 1.7, or earlier, with StruxureWare Building
Operation bindings to Lon variable fields outside the scope of the export file, will not
convert those bindings when you import the file into version 1.8, or later. They need
to be corrected manually after the import. Please use Binding Diagnostics in the
Engineering section of the Control Panel to detect references that are not properly
converted.
6.15 Search
• If a saved Search-object from previous versions, has contained a type that no longer
exist in the server, e.g. an E-mail-notification that is converted to an Alarm Triggered
Notification, then the search operation will not find any object and will need to be
manually re-configured in order to present the expected result.
6.16 SmartDriver
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 88 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
By default, SmartDriver drivers are loaded at startup. If a faulty SmartDriver driver causes the
EcoStruxure BMS server to crash repeatedly i.e. more than thrice, the EcoStruxure BMS server
disables the SmartDriver drivers. This prevents further crashes.
This crash counter is reset after 10 mins. The user can then re-enable the smart driver and perform
a warm start operation on the ASP. The smartdrivers will be operational again.
If the SmartDriver drivers are enabled to load at startup and the EcoStruxure BMS server is crashing
again, then the SmartDriver drivers are disabled again. The problem with the SmartDriver driver
needs to be fixed before the SmartDriver drivers can run again without crashing the server.
6.17 EWS
6.17.1 Domain login
It is possible to use the format <domain/username> as a username to login to a specific
domain when using EWS. Using the standard format <username> will use the default
domain. When logging on to an AS which is a subserver to an ES and the AS has its default
domain on the ES you will have to login using the format <domain/username>.
6.18 BACnet
6.18.1 Synchronize Bindings of Value and Default Priority Level
Previous EBO versions allowed users to modify the Value property of a BACnet object when a binding
exists on the default Command priority (typically, 16), and vice-versa. As some customers found this
confusing, the system now makes each property read-only when the other contains a binding.
For users who wish to maintain the previous behaviour, a new system setting was added. This setting
is found in <Server>-System-Interface manager-BACnet called ‘Synchronize bindings of value and
default priority level’. When changed from True (default) to False, the system behaves as before. The
setting applies to all BACnet objects in all types of devices – EBO, IP Field Controller, 3rd-party, etc.
The following behaviour occurs when you force a value in the pre-v3.2 EcoStruxure BMS:
• The Force button is shown
• The value is highlighted in orange
With the 3.2 release, force behaviour now also includes the following:
• The forced hand icon is visible in the Watch Window
• The forced text is also displayed in the List View
• The standard blue border displays around the control object in the graphic
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 89 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
There are two variants of Zigbee Device import files. Automation Server (AS) files and RP Controller
(RP) files. If you intend to setup a Zigbee Physical device under AS choose file names with prefix AS.
If your Zigbee device runs under a RP choose file names with prefix RP. Zigbee Device Import Files
can be downloaded from Schneider BMS Application site.
Above picture shows two variants of same Zigbee physical device as you can find then on Schneider
BMS site. Note the prefix difference AS or RP.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 90 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Type Library
Warning: Engineering with Custom Types pane must be chosen to make Type Library visible.
6.19.4 New way to associate Zigbee physical device with logical device
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 91 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Drag the logical device from the Type Library to the Zigbee network in the System Tree.
Choose the physical device in Device Discovery and drag it to the logical device in System Tree. Click
on the save icon.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 92 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
6. Choose the corresponding Zigbee Device version 4.0 from the Type Library pop-up list.
7. Click ”OK”.
8. Click on the save icon.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 93 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
9. To verify that your configured Zigbee device has been updated to EBO 4.0.
-Select the Zigbee device.
- Click on the “Properties” Tab.
- Verify that the “Type” property has v.4.0 in last part of the id string.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 94 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
If the Zigbee network is not set to automatic in the creation wizard it will be necessary to manually
set one.
If all is well the Network status should be ‘Online’.
When the sensor is in paring mode use EBO to discover the devices:
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 95 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Note: it can take some considerable time for all the properties of the SE Green Power sensor to be
obtained, an upload generally speeds things up.
Also, some object properties are not implemented such as the Green Power and Basic objects.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 96 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
If you decommission the Zigbee device by pressing the service button on the GP sensor or via the
EBO command ‘Leave’ while it is commissioned but not connected with its host controller, it will not
be possible to re-commission it to the same EBO or RP host.
This is due to cyber security requirements.
The work-around to re-using a GP sensor that has been blocked is to delete the Zigbee network on
the host AS or RP device and re-create it.
It is essential that the hardware to run this solution on is ordered to meet the expected and future
EcoStruxure Building Operation logging requirements.
Ensure that the minimum hardware and software requirements for the TimescaleDB
(www.timescale.com) and PostgreSQL (www.postgresql.org) is exceeded.
High performance SSD storage is required and expect that additional CPU/RAM capacity will be
required for large EcoStruxure Building Operation systems.
As an example, a minimum 64GB RAM is recommended for systems with 100 Building Operation
servers.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 97 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Where the server has been operating for at least 2 months since the last restart, should the system
memory usage be above 50% for a 1.5/1.6 release, 55% for a 1.7 release, 60% for a 1.8 release, 65%
for a 1.9 release, 70% for a 2.0/3.0/3.1 release then you may need to make engineering adjustments
to reduce your system memory usage or consider upgrading older AS devices to AS-P or AS-B which
have larger memory capacities.
The numbers above are indicative only and will vary depending on system configuration and the use
of field devices.
Key differences:
• Save does not activate a program, it only saves the edited program. Deploy is needed to
make it run. This is not supported in classic mode (i.e., saving unfinished programs).
• Text macros written in the Comment objects are not supported in Builder.
• Builder requires Labels for all Blocks (with the exception of Operators).
New Capability:
• Relinquish blocks: three new output blocks that support sending out “null”. Supported
in both Builder and classic editor.
• Live values can also be shown as tooltips when hovering over a binding.
Other Considerations:
• Builder can be used for old servers and devices as long as they are a part of a multi-
version system and WorkStation 4.0 is used to log in to the top server.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 98 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
• If your programs are using Public PV blocks you will receive a warning when saving to
avoid writing the original initial values. See image below.
• If when deploying a program, one would get a cryptic error code (see example below). A
tip is to open the same program in Classic editor (load the edited version when asked)
and switch to the Simulation mode. This might give a more detailed error description.
NOTE: Do not save from Classic though.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 99 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
APPENDIX A – Procedures
A1. Installing EcoStruxure Building Operation
For installation of EcoStruxure Building Operation v4.0.1 WorkStation, Enterprise Server, Enterprise
Central , please reference the Web Help for that topic.
A system upgrade can include an Enterprise Server Enterprise Central, one or more automation
servers and Workstations, and the supporting administrator software, such as Device Administrator.
For more information , see System Upgrade Overview
It is imperative that any upgrades be accomplished only after reading and understanding this
document, especially those areas that are related to the upgrade process.
During upgrade from any of the previous releases, there is a limited level of runtime compatibility
during the upgrade process. You can find more information on Webhelp here.
If your EcoStruxure BMS contains an Enterprise Central, use the Enterprise Central Upgrade
Workflow.
Note:
Depending upon the size of the system and the quantity of trends, it is possible that the database on
the Enterprise Server/ could be quite large. When upgrading, always make certain that you have at
least twice as much disk space available as the size of your database. It should also be expected that
the Enterprise Server may appear to “hang” for as much 20 to 30 minutes upon the first initial start-
up after the upgrade, but only on the first start.
Note:
If the installation path is longer than the default path, an error will occur during installation. See
defect 48808.
If ES-upgrade hangs and shows error “-4”, then a restart of the PC will solve the problem.
CPU-load can be high some minutes in the AS after upgrade depending on how large historical db.
there is.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 100 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
To upgrade a single automation server or a series of standalone automation servers , use the
Automation Server System Upgrade Workflow.
You use Device Administrator to upgrade the automation server. You must upgrade Device
Administrator before you upgrade the automation server.
Note:
In case of issues compiling or saving applications in WorkPlace Tech Editor, update Visio with the
latest Microsoft Office updates.
If you use External Log Storage, new scripts must be run in the PostgreSQL/TimescaleDB database
for EBO 4.0. The script “pg_install_db.sql” can handle schema upgrade from 3.0 and forward.
For more info, read WebHelp Topic: “Setting up a Database Schema in the PostgreSQL Database”.
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 101 of 102 Company Confidential
Internal
[ Release Notes ] EcoStruxure™ Building Operation 2022 v4.0.1
Change History
Revision Date Revision Description/Change
/Author
A 2021-12-20 R. Yanappa Final version
B 2022-01-13 R. Yanappa Rev B with minor corrections
Schneider Electric
Boston ONE Campus, 800 Federal Street, Andover, MA 01810 Telephone +1 978-794-0800 www.schneider-electric.com
RN_EBO 2022_v4.0.1 Rev B – January 2022 Page 102 of 102 Company Confidential
Internal