Professional Documents
Culture Documents
ADR-10000-I&M MANUAL - 8.1 253359436-A - Ed01
ADR-10000-I&M MANUAL - 8.1 253359436-A - Ed01
ADR-10000-I&M MANUAL - 8.1 253359436-A - Ed01
ADR – 10000
Versions 8.1
253 359 436 September 2010 Creation of original user guide All pages
3 000 358 607 R11 000 01
Contents
About This Manual..................................................................... xi
Overview..............................................................................................................xi
Intended Audience...............................................................................................xi
Document Organization ......................................................................................xii
Document Conventions ......................................................................................xii
Related Documentation ..................................................................................... xiii
Obtaining Technical Documentation.................................................................. xiii
Technical Assistance xiv
Introduction..............................................................................2-1
ADR-10000 Platform Overview ........................................................................ 2-1
ADR-10000 I/O Protection Options .................................................................. 2-2
ADR-10000 Shelf with CWDM Networking Capabilities ................................... 2-6
Maintenance .............................................................................8-1
Overview........................................................................................................... 8-1
Required Test Equipment, Tools, and Materials............................................... 8-1
Preventive Maintenance ................................................................................... 8-2
Traffic Monitoring System ................................................................................. 8-6
Onsite Troubleshooting................................................................................... 8-10
Replacing Cards and Modules........................................................................ 8-17
Replacing RAP Components .......................................................................... 8-23
In this chapter:
Overview............................................................................................................ xi
Intended Audience ............................................................................................. xi
Document Organization....................................................................................xii
Document Conventions..................................................................................... xii
Related Documentation....................................................................................xiii
Obtaining Technical Documentation ...............................................................xiii
Technical Assistance........................................................................................ xiv
Overview
The ADR-10000 Installation and Maintenance Manual (IMM) describes how to
set up, configure, and install ADR-10000 shelves and their components and
accessories.
The manual also provides task-oriented instructions for LED indications,
troubleshooting hardware-related problems, and replacing hardware
components (cards, modules, accessories).
Intended Audience
This manual is intended for installation and other qualified service personnel
responsible for installing the system and its accessories.
The instructions require you to understand and follow the safety practices
included here, as well as any applicable national regulations and those enforced
at your site. They also require that you understand the physical, optical, and
electrical requirements of the installation site.
Document Conventions
When applicable, this manual uses the following conventions.
Convention Indicates Example
Bold Names of windows, In the Alarms menu...
dialog boxes, menus,
buttons and most other
GUI elements
Menu > Option Selection from a menu, or Select Update > View
leading to another Objects
command
Italics New terms and Examples in text
emphasized text
Borders around text Notes, cautions, and See examples below
warnings
Obtaining Technical
Documentation
To obtain technical documentation related to the ADR-10000 or any other
Sagemcom product, please contact:
Telephone 33 1 57 61 16 16
Telefax 33 1 57 61 16 60
Email hotline.arp@sagemcom.com
Don't forget to provide yourself with your customer number which is written on
your invoice
In this chapter:
Overview..........................................................................................................1-1
Warning Definition ..........................................................................................1-3
Qualified Personnel Warning...........................................................................1-4
Installation Warning ........................................................................................1-5
General Safety Requirements ..........................................................................1-5
Jewelry Removal Warning...............................................................................1-7
Grounding Requirements.................................................................................1-8
Power Supply Requirements..........................................................................1-11
UL/TUV Statutory Warnings and Requirements...........................................1-18
ITU-T/Telcordia Statutory Warnings and Requirements...............................1-20
Laser Safety Requirements ............................................................................1-22
Protection against Electrostatic Discharge.....................................................1-26
Environmental and Health Concerns .............................................................1-29
Overview
This chapter describes the ADR safety guidelines. The safety rules and
warnings in this chapter must be read before beginning any platform
installation or maintenance work. These safety guidelines must be adhered to
carefully.
Figure 1-1: Optical rack grounding bar and rack frame grounding post
Figure 1-2: Grounding the optical rack to the site grounding bar
Warning Label
The following warning label is affixed alongside the ADR power input
connectors and the xRAP circuit breakers.
ITU-T/Telcordia Statutory
Warnings and Requirements
This section outlines the ITU-T and Telcordia statutory warnings and
requirements applicable to ADR platforms. The source for these requirements
can be found in IEC 60950-1/3.2.1.2.
WARNINGS:
Ethernet ports must be cabled with shielded cables and the shield
grounded at both ends.
Intra-building ports of the Equipment or subassembly are suitable
for connection to intra-building or unexposed wiring or cabling only.
Intra-building ports of the Equipment or subassembly MUST NOT
be metallically connected to interfaces that connect to the OSP or its
wiring. These interfaces are designed for use as intra-building
interfaces only (Type 2 or Type 4 ports as described in
GR-1089-CORE, Issue 4) and require isolation from the exposed
OSP cabling. The addition of Primary Protectors is not sufficient
protection in order to connect these interfaces metallically to OSP
wiring.
Laser Information
See the ADR System Specification for information regarding the laser
transmitters of the various optical cards available for the ADR platforms.
General
Most types of electronic equipment, assemblies, and components can be
damaged by electrostatic discharges. An electrostatic discharge between two
objects occurs when an object carrying static electrical charges touches, or is
brought near enough to the other object.
Static electrical charges appear as a result of friction between surfaces of
insulating materials or separation of two such surfaces, and may also be
induced by electrical fields. Routine activities such as walking across an
insulating floor, friction between garment parts, friction between objects, and
so on, can easily build charges up to levels that may cause damage, especially
when humidity is low.
In many cases, the build-up of charges can be avoided by using special
materials, for example, garments and packaging made of antistatic materials or
materials that have high resistivity but are not insulators.
Personnel Training
During production and assembly, Equipment is handled in work spaces
especially prepared and certified to serve as a permanent EPA. However, in
many cases, the environment in which the same Equipment is installed or
maintained cannot be assumed to form an EPA with a permanently controlled
boundary.
Therefore, all the work requiring the handling of unprotected ESDS must be
considered as field work.
Field work in this context includes such activities as service and maintenance,
installation, site inspection, and commissioning of components and assemblies
classified as ESDS, together with the packaging and unpackaging activities
associated with such activities.
All the staff involved in field work must be trained to perform field work in the
same way as work performed in permanent EPAs with respect to the material
quality and personal responsibilities, training, labeling, and packaging.
In this chapter:
ADR-10000 Platform Overview ......................................................................2-1
ADR-10000 I/O Protection Options ................................................................2-2
ADR-10000 Shelf with CWDM Networking Capabilities ..............................2-6
Similar I/O protection options are supported for ADR-10000 shelves installed
in a vertical position.
A typical ADR-10000 shelf with an OCU (and two TPUs) is shown in the
following figure.
In this chapter:
Overview..........................................................................................................3-1
Tools and Test Equipment ...............................................................................3-4
Unpacking and Performing Visual Inspection.................................................3-5
ADR Rack Installation Options .......................................................................3-6
Preparing Cables and Fibers ............................................................................3-7
ADR-10000 Accessories................................................................................3-18
Equipment Installation...................................................................................3-28
Rack Installation ............................................................................................3-37
Installing Ancillary Units in Racks................................................................3-42
Overview
The following sections describe the conditions required for installing the
equipment at the site.
Site Preparation
Perform a preliminary survey of the installation site, taking into consideration
the following issues:
| System environmental requirements
| Physical location of the ADR-10000 shelves
| Location of power sources
| Types of interfaces used at the site (optical, electrical, management, alarm
monitoring, and so on)
| Work and equipment safety requirements
Physical Location
Choose the physical location of the ADR-10000 shelves, taking the following
aspects into consideration:
Power Sources
ADR equipment must be powered only by DC sources in compliance with the
applicable sections of ETSI 300 132-2 and FTZ 19PFL1, and the SELV of EN
60950-1 requirements. The nominal supply voltage is -48 VDC (positive lead
grounded); the allowed supply voltage range is -40 VDC to -57.6 VDC. For
redundancy, two separate DC power sources should be available.
The power consumption of the ADR-10000 is:
| Typical: 800 W
| Maximum: 1100 W
3. Search the shipping boxes for any additional small items that may be
present.
NOTES:
| Not all ADR platforms can be installed in all types of
racks. This section includes a general list of the rack
options available. The installation instructions for each
platform include a list of the racks appropriate for that
platform.
| The installation instructions in this manual are written on
the basis of an installation using an SAGEMCOM
enhanced rack. Some of these instructions may not be
relevant if you are using a standard rack supplied by other
vendors.
| Before any installation plan can be completed, a site
survey by SAGEMCOM technical support team is
required, to verify rack accessibility and accessory
compatibility at that site. If you are working with standard
racks from other vendors, the site survey is also essential to
determine what changes are required to adapt the rack to
ADR platform installation requirements.
DC power cables should be prepared on site. Two types of DC power cables are
needed:
| RAP input power cables
| Shelf power cables
Alarm Cables
Alarm cables used are included in the shipment according to the site
specifications. Alarm indications are carried by the following cables:
| Shelf alarm indication cable. One shelf alarm indication cable is required
for each ADR-10000 shelf installed in the rack. One end of the cable is
always connected to the ALARMS connector on the ECU300/ECU300-F
card. Connection of the other end depends on the cable type, as follows:
xRAP-B alarm cable. Connects to one of the SHELF connectors on the
xRAP-B.
xRAP-D alarm cable. Connects to one of the SHELF connectors on the
xRAP-D.
Client alarm cable. Connects to the client's alarm collecting facility.
| Bay alarm cable. One bay alarm cable is required for each rack. This cable
carries the alarm indications and monitoring lines of the bay (rack). One
end of the cable is connected to the RAP, the other end is open and
connects to the client's alarm collecting facility. Two types of this cable are
available:
xRAP-B bay alarm cable. Connects to the ALARMS connector on the
xRAP-B.
xRAP-D bay alarm cable. Connects to the ALARMS connector on the
xRAP-D.
When a TPU is used, additional patch traffic cables between PIMs and TPMs
are required, as described in the following table.
Table 3-5: Patch traffic cables connecting I/O modules to the TPU
TPM Interface Cable type Mating connector Qty/
type Module
TPM2_1 E1 balanced Twin multipair PIM: Twin 50-pin SCSI 1
(2.048 Mbps) cable (25 pairs female
of shielded TPM: 100-pin SCSI
120 Ω twisted female
pairs)
TPM2_3 E1 balanced Twin multipair PIM: Twin 50-pin SCSI 4
(2.048 Mbps) cable (25 pairs female
of shielded TPM: 100-pin SCSI
120 Ω twisted female
pairs)
TPM2_42_2 E1 balanced Twin multipair PIM2_42: 100-pin SCSI 2
(2.048 Mbps) cable (25 pairs male
of shielded 120 TPM: Twin 136-pin
Ω twisted VHDCI male
pairs)
TPM2_63_2 E1 balanced Triple multipair PIM2_63: Triple twins 1
(2.048 Mbps) cable (25 pairs of 50-pin SCSI male
of shielded TPM: Twin 136-pin
120 Ω twisted VHDCI male
pairs)
E1 balanced Twin multipair PIM2_42: 100-pin SCSI 1
(2.048 Mbps) cable (25 pairs male
of shielded 120 TPM: Twin 136-pin
Ω twisted VHDCI male
pairs)
1
SIM1_8 configured as STM-1 electrical module with ETR-1 electrical SFP transceivers.
Optical Fibers
Optical fibers can be prepared on site.
Use only 2 mm optical fibers to connect to optical interfaces. For each optical
interface, SAGEMCOM supplies patch cords with mating optical connectors
already attached to the fiber. Therefore, only the optical termination on the
ODF side, which is installation-dependent, must be installed on site.
The optical fibers should enter the rack from the top, be threaded through cable
guides running along the rack side rails, and end at the FST. The tray must
contain enough fiber length for extracting modules from the ADR-10000 and
for replacing fiber in case of damage (splicing repairs). When routing fibers,
make sure to observe the minimum bending radius (35 mm).
The following table lists the type of fibers and mating connectors needed to
prepare fibers for each ADR-10000 module/card.
Table 3-6: Optical fibers and mating connector data
I/O Interface type Fiber type Mating Qty/
module/card connector Module/Card
SIM1_4/OB STM-1 optical 1 pair of fiber LC male 8 fibers
SIM1_4/O patch cords per
interface
SIM1_8 2 STM-1 optical 1 pair of fiber LC male 16 fibers
patch cords per
interface
SIM4_2 STM-4 optical 1 pair of fiber LC male 4 fibers
patch cords per
interface
SIM4_4 STM-4 optical 1 pair of fiber LC male 8 fibers
patch cords per
interface
SIM16_1 STM-16 1 pair of fiber LC male 2 fibers
patch cords per
interface
SIM16_4 STM-16 1 pair of fiber LC male 8 fibers
patch cords per
interface
SIM64_XFP STM-64 1 pair of fiber LC male 2 fibers
patch cords per
interface
2
SIM1_8 configured as STM-1 optical module with OTR-1 optical SFP transceivers.
The following table lists the type of Ethernet electrical traffic cables and the
mating connectors needed for the MCSM module.
Table 3-12: MCSM Ethernet electrical cables and mating connector data
MCSM Port Interface type Cable type Mating Qty/
module no. connector module
MCSM 9-16 10/100BaseT CAT5E SFTP RJ-45 8
4-pair
xRAP-B
The xRAP-B is a power distribution and alarm panel for ADR shelves installed
in racks. The xRAP-B performs the following main functions:
| Power distribution for one or two ADR-10000 shelves. The nominal DC
power voltage is -48 VDC, ranging to -57.6 VDC. Since ADR-10000
shelves can use redundant power sources, the xRAP-B supports connection
to two separate DC power circuits. The internal circuits of the xRAP-B are
powered whenever at least one power source is connected. The presence of
DC power within the xRAP-B is indicated by a POWER ON indicator.
The xRAP-B has two 5-pin DC output connectors for supplying power to
any shelf in the ADR-10000 family of products. The maximum power that
can be supplied to each ADR shelf is up to 2250 W, in accordance with the
shelf type and version. The xRAP-B uses a single 50 mm2 power cable to
supply up to 4500 W in total to two ADR platforms.
Each DC power circuit of each shelf is protected by a circuit breaker that
also serves as a power on/off switch for the corresponding circuit. The
required circuit breakers are included in the installation parts kit supplied
with the ADR-10000 shelves, and therefore their current rating is in
accordance with the order requirements.
The circuit breakers are installed during the xRAP-B installation. To
prevent accidental changing of a circuit breaker’s state, the circuit breakers
can be reached only after opening the front cover of the xRAP-B. The
circuit breaker state (ON or OFF) can be seen through translucent covers.
| Bay alarm indications. The xRAP-B includes four alarm indicators, one
for each alarm severity. When alarms of different severities are received
simultaneously, the corresponding alarm indications light simultaneously.
A buzzer is activated whenever a Major or Critical alarm is present in ADR
shelves installed in the rack.
| Connecting alarms from two ADR shelves, each shelf with maximum four
alarm inputs and four alarm outputs (via dry contacts) to the customer's
central alarm monitoring system.
The following figure shows the front panel of the xRAP-B, and the table lists
the functions of the front panel components corresponding to the figure callout
numbers.
The xRAP-B connectors are located on the circuit board, as shown in the
following figure. The table lists the connector functions. The index numbers in
the table correspond to those in the figures.
3
Alarm input lines arrive through the ALARM connector and are connected to the corresponding SHELF connector.
The xRAP-D has four 5-pin DC output connectors for supplying redundant
power to any shelf in the ADR-10000 family of products. The maximum
power supplied to each ADR shelf is up to 2250 W, in accordance with the
shelf type and version.
The nominal DC power voltage is -48 VDC, ranging to -57.6 VDC. The
internal circuits of the xRAP-D are powered whenever at least one power
source is connected. The presence of DC power within the xRAP-D is
indicated by a POWER ON indicator.
Each DC power circuit of each shelf is protected by a circuit breaker that
also serves as a power on/off switch for the corresponding circuit. The
required circuit breakers are included in the installation parts kit supplied
with the ADR-10000 shelves, and therefore their current rating is in
accordance with the order requirements.
NOTE: Note that the xRAP-D supports the same alarm and
power functions as the xRAP-B and xRAP-HP. When
replacing an existing xRAP-HP with an xRAP-D you must
also use the appropriate xRAP-D accessory kit, including
cables.
The following figure shows the front panel of the xRAP-D, and the table lists
the functions of the front panel components corresponding to the figure callout
numbers.
The xRAP-D connectors are located on the circuit board, as shown in the
following figure. The table lists the connector functions. The index numbers in
the table correspond to those in the figures.
Alarm signals arrive at a SHELF connector on the xRAP unit from two
different connector sources on the ADR shelf using a Y-Cable.
| A 9-pin connector on the ADR shelf labeled xRAP is used for the four
ADR severity alarms. (CRITICAL, MAJOR, MINOR, and WARNING)
| A 50-pin connector on the ADR shelf labeled ALARMS is used for any
external alarms defined by client request.
Equipment Installation
The following sections provide general instructions for the installation of the
ADR-10000 and auxiliary equipment.
The procedures for equipment replacement and upgrades are similar to those
described for installation of the equipment, and when relevant, notes regarding
live replacement or upgrade are inserted in these procedures.
The information appearing in these sections should be used in conjunction with
specific site installation plans in the particular customer network. If you are
interested in obtaining design or installation assistance from SAGEMCOM
Networks Solutions Division’s Customer Support team, or wish to prepare a
network installation plan, contact your SAGEMCOM sales representative.
The ADR-10000 shelf, cards, modules, and ancillary equipment are described
in the ADR-1000 Product Line Reference Manual.
Preliminary Preparations
The installation procedures provided in this chapter assume that:
4
The number of supported shelves depends on their total power consumption.
5
The same type of circuit breaker is used in all xRAP versions. The value of the circuit breaker is defined by the
power consumption requirements of the shelf and not by the type of xRAP.
6
Critical, Major, Warning, and Minor alarms toward the customer central monitoring system.
7
External Alarms input via Opto coupler.
8
Using dip switches.
9
External Alarms output via dry contacts.
10
Using dip switches.
11
Bridge option to work with a single 50mm2 power cable available.
NOTE:
If you are not installing an FST for a particular ADR-
10000 shelf, it is recommended that you leave empty
space in the rack in case optical modules are added to the
shelf in the future.
If you are not installing a TPU for a particular ADR-
10000 shelf, it is recommended that you leave empty
space in the rack so that the protection unit can be added
in the future, if required, without interrupting operation.
CAUTION:
If additional equipment is used in the rack, a heat buffer or
a buffer plate must be installed between any such
additional equipment and the ADR-10000 shelf to
minimize the transfer of heat from shelf to shelf. This heat
buffer must be purchased from SAGEMCOM.
During the installation of equipment in the rack, make
sure all the optical connectors are closed by protective
caps. Do not remove the cap until an optical fiber is
connected to the corresponding connector.
Several installation options are illustrated in Installation Options (on page 4-1).
8. Install cards and modules in the optional Installing TPU Modules (on
TPU, including: page 5-19)
| TC/TCF module
| Single-slot TPMs
| Double-slot TPMs
| Triple-slot TPMs
9. Install blank covers where I/O modules, —
cards, and TPMs are not used.
10. Route and connect all cables and fibers Connecting Fibers and Cables
for ETSI A racks, including: in ETSI A Racks (on page 6-1)
| Power and alarm cables
| Optical fibers to optical modules
transceivers
| Electrical interface cables to
electrical modules (includes
installation of the optional xDDF-21
channel patch panel)
| Electrical traffic through the TPU
| Data cables to
EISMB/MCSM/DIOM modules
| Timing cables
| Management cables
ADR-10000 shelf
5. Install the ADR-10000 shelf in the rack. Installing the ADR-10000 Shelf
Note: If your site installation plan in Racks (on page 4-7)
includes TPU protection, the ADR-
10000 is supplied with the TPU already
installed. If you need to connect a TPU
unit to an existing ADR-10000 shelf, see
Installing a TPU on the ADR-10000
Shelf.
6. Install the air filter. Installing the Air Filter
7. Install the common cards in the ADR- Installing ADR-10000 Cards
10000 shelf, including: (on page 5-1)
| FCU300
| ECU300/ECU300-F
| MXC300 with NVM flash card
11. Route and connect all cables and fibers Connecting Fibers and Cables
for ETSI A racks, including: in ETSI A Racks (on page 6-1)
| Power and alarm cables
| Optical fibers to optical modules
transceivers
Electrical interface cables to electrical
modules (includes installation of the
optional xDDF-21 channel patch panel)
| Electrical traffic through the TPU
| Data cables to
EISMB/MCSM/DIOM modules
| Timing cables
| Management cables
7. When applicable, install the EMS-ADR management station (see the EMS-
ADR User Manual).
8. Install the power distribution and alarm panels – xRAP-B (on page 3-18),
xRAP-D (on page 3-22) and other equipment needed in each rack.
9. Install the ADR-10000 shelves in the appropriate rack.
10. For each ADR-10000 shelf where optical modules are used, install an FST
above the ADR-10000 shelf and route the optical fibers to the FST (see
"Installing the FST" on page 3-70).
11. Install the ECU300/ECU300-F, FCU300, MXC300, and I/O cards in the
shelf (see "Installing ADR-10000 Cards" on page 5-1).
12. Install the prescribed I/O modules in the shelf.
13. If applicable, install the TC card and the prescribed TPMs in the TPU.
14. Depending on the modules in your ADR-10000 shelf:
Route the optical fibers from the FST to the relevant module
connectors.
Route the E1 electrical cables to the patch panel location.
Route the data cables to the data modules (EISMB/DIOM/MCSM).
Install a patch panel for each ADR-10000 shelf where electrical E1
modules are used and 120 Ω/75 Ω conversion is required. You will
need a separate patch panel for each PIM2_21 module in the shelf.
NOTE: In some cases, you may need to add a TPU after the
ADR-10000 has already been installed. Instructions for this
procedure are provided in Attaching TPUs/OCU to the ADR-
10000 shelf (on page 5-25).
Rack Installation
Installing Equipment Racks
1-45/64” 1-45/64”
18-1/2” 14-1/2”
3-11/16” 3-11/16”
25-7/8” 21-7/8”
a. 23” wide bay mounting hole drilling template b. 19” wide bay mounting hole drilling template
SCREW M12X50
FLAT WASHER
SPACER
SQUARE WASHER
ANCHOR BRACKET
OPEN DUCT
LOCK WASHER
FLAT WASHER CEILING
FLAT WASHER
640 MAX
50 MIN
NUT M8
FLAT WASHER
SCREW M8X20
Rack Grounding
Immediately after installing the rack, connect its grounding stud to the
prescribed grounding point on the site grounding bar. Use a grounding lead that
meets the Rack grounding requirements listed in section Before You Start.
605.5
667
600
500
Maximum distance
between levels
2021
1912
499mm
625
515
44
Z 538
Mounting angle
355
Foremost position
Detail Z
44500
515
538
Before connecting DC power cables, refer to DC Power Cables (on page 3-11).
The installation of an xRAP-D unit includes the following steps:
1. Prepare DC power cables.
2. Install the xRAP-D in the prescribed location, either at the top of the rack or
on the extendable installation rails.
3. Ground the xRAP-D to the rack grounding stud.
The preceding figure portrays the electrical connections on the left side of
the xRAP-D, the side that connects to the user's main power supply for the
ADR shelves being powered. The right side of the xRAP-D contains a
mirror image of the connections illustrated in the preceding figure. The
right side connects to the user's (optional) backup protective power supply
for the shelves.
3. Bring the two leads of one DC source input power cable to the appropriate
xRAP-D opening.
4. Attach the lug of the red lead to the positive stud terminals, marked (+) on
the power terminal board. Note that the xRAP-D works with two sets of
positive terminals, used with two 25 mm2 power cables.
5. Secure the lug using a flat washer, a spring washer, and a nut. Tighten the
nut with a torque of 450 N cm to 550 N cm.
6. Attach the lug of the black lead to the negative stud terminal marked (-) on
the power terminal board. Note that the xRAP-D works with two sets of
negative terminals, used with two 25 mm2 power cables.
7. Repeat Step 6 for the black lead lug.
8. If an additional power source (source B) is used, repeat Steps 3 to 8 for
source B.
9. Route the DC input power cables towards the cable retainers at the rear of
the xRAP-D (see To ground the xRAP-D (on page 3-47)), and attach them
to the retainers with cable ties.
2. Find the replacement spacer screws included in the protective cover kit.
Note that four replacement spacer screws are included with the xRAP-D. A
replacement spacer screw is illustrated in the following figure.
4. Find the small L-shaped protective covers included in the kit. Four
protective covers are included for the xRAP-D. The protective covers are
illustrated in the following figure.
6. Secure the protective covers in place by screwing on the wing nuts supplied
in the kit onto the tops of the spacer screws on each side.
7. Find the protective bottom panel in the kit. The bottom panel for the
xRAP-D is illustrated in the following figure.
8. Secure the bottom panel into place with the four screws supplied in the kit.
2. Insert the end of the DC power cable terminating with a 5-pin D-type male
connector near the SOURCE A power connectors and connect it to
connector Shelf 1 (see preceding figure).
3. Fasten the screws of the D-type connector.
4. If you are connecting an additional shelf to the xRAP-D, repeat the above
steps for the second shelf. Note that a maximum of 55A is supplied from
the power sources to each ADR platform. Power is supplied independently
to each ADR platform connected to the xRAP unit. Power is not shared
between ADR platforms.
5. If an additional power source is used, repeat the above steps to connect the
shelves to source B.
6. Route the DC power cables towards the cable retainers at the rear of the
xRAP-D and attach them to the retainers with cable ties (see To ground the
xRAP-D (on page 3-47)).
7. Route each shelf power cable along the rack side rails down to the
corresponding shelf position, and securely attach the power cable to the
rack inner wall using cable ties. Attach a tag to each power connector in
accordance with its function.
4. Make sure the voltage is within the allowed range (-40 VDC to -57.6 VDC)
and that it has the correct polarity.
5. Return all xRAP-D circuit breakers to OFF.
6. Disconnect the xRAP-D input power sources.
7. Reinstall the xRAP-D front cover and fasten it using the two captive
screws.
During the following procedure, refer to the figures illustrating the connectors
in Connecting DC Input Power Cables to the xRAP-D (on page 3-48).
Before connecting DC power cables, refer to DC Power Cables (on page 3-11).
The installation of an xRAP-B unit includes the following steps:
1. Prepare DC power cables.
2. Install the xRAP-B in the prescribed location, either at the top of the rack or
on the extendable installation rails.
3. Ground the xRAP-B to the rack grounding stud.
4. Connect DC input power cables to the xRAP-B.
5. Attach protective covers to the sides and bottom of the xRAP-B unit.
(From V7.15 only, required for NEBS; optional for all others.)
6. Connect the DC power cables of the ADR-10000 shelves to the xRAP-B.
7. Install circuit breakers.
8. Check DC voltage polarity.
9. Connect the alarm cables.
For a description of the xRAP-B, refer to the ADR-10000 Product Line
Reference Manual.
The DC input power cables connect between the two DC power sources and the
xRAP-B source A and source B inputs. When working with the xRAP-B, two
cables are required, one for each source.
2. Open the two captive screws fastening the xRAP-B front cover and remove
the cover.
3. Bring the two leads of one DC source input power cable to the appropriate
xRAP-B opening.
4. Attach the lug of the red lead to the positive stud terminals, marked (+) on
the power terminal board. Note that the xRAP-B works with a single set of
positive terminals, used with a 50 mm2 power cable.
5. Secure the lug using a flat washer, a spring washer, and a nut. Tighten the
nut with a torque of 450 N cm to 550 N cm.
6. Attach the lug of the black lead to the negative stud terminal marked (-) on
the power terminal board. Note that the xRAP-B works with a single set of
negative terminals, used with a 50 mm2 power cable.
7. Repeat Step 6 for the black lead lug.
8. If an additional power source (source B) is used, repeat Steps 3 to 8 for
source B.
9. Route the DC input power cables towards the cable retainers at the rear of
the xRAP-B (see the figure in To ground the xRAP-B (on page 3-60)), and
attach them to the retainers with cable ties.
2. Find the replacement spacer screws included in the protective cover kit.
Note that two replacement spacer screws are included with the xRAP-B. A
replacement spacer screw is illustrated in the following figure.
4. Find the small L-shaped protective covers included in the kit. Two
protective covers are included for use with the xRAP-B. The protective
covers are illustrated in the following figure.
6. Secure the protective covers in place by screwing on the wing nuts supplied
in the kit onto the tops of the spacer screws on each side.
7. Find the protective bottom panel in the kit. The bottom panel for the
xRAP-B is illustrated in the following figure.
2. Insert the end of the DC power cable terminating with a 5-pin D-type male
connector near the SOURCE A power connectors and connect it to
connector Shelf 1 (see preceding figures).
3. Fasten the screws of the D-type connector.
4. If you are connecting an additional shelf to the xRAP-B, repeat the above
steps for the second shelf. Note that a maximum of 55A is supplied from
the power sources to each ADR platform. Power is supplied independently
to each ADR platform connected to the xRAP unit. Power is not shared
between ADR platforms.
5. If an additional power source is used, repeat the above steps to connect the
shelves to source B.
6. Route the DC power cables towards the cable retainers at the rear of the
xRAP-B and attach them to the retainers with cable ties (see the figure in
To ground the xRAP-B (on page 3-60)).
7. Route each shelf power cable along the rack side rails down to the
corresponding shelf position, and securely attach the power cable to the
rack inner wall using cable ties. Attach a tag to each power connector in
accordance with its function.
4. Make sure the voltage is within the allowed range (-40 VDC to -57.6 VDC)
and that it has the correct polarity.
5. Return all xRAP-B circuit breakers to OFF.
6. Disconnect the xRAP-B input power sources.
7. Reinstall the xRAP-B front cover and fasten it using the two captive
screws.
NOTE: The FST has two opening positions. The tray latches
with a click at the halfway position. Pull it again to open it
fully so that you can thread the fibers.
6. Thread the fibers into the FST, as illustrated in the following figure.
2. Hold the end of the swing-out tray and pull it out to gain access to the ODF
components.
3. Open the two cover thumb nuts and remove the protective cover from the
ODF splice support.
4. Insert the external fibers cable through the protective tube.
5. Route the fiber ends through the cable guides to the splice support area.
6. Identify the adapter panel pigtail to be spliced to each user fiber.
7. Insert splicing sleeves over the pigtail, splice the user fiber to the pigtail,
and slide the splicing sleeve over the splice.
8. Place the splicing sleeve in one of the slots in the splice support.
9. After splicing all the fibers, reinstall the protective cover removed in Step 3.
10. Push the swing-out tray back into the unit.
11. Close the ODF front cover by pushing it up till it clicks to the unit.
12. Refer to Attaching rack mount brackets (on page 3-71) and secure the user
fibers with cable ties to the fiber fastening bracket at the rear of the ODF.
NOTE: The OPP has two opening positions. The tray latches
with a click at the halfway position. Pull it again to open it
fully so that you can thread the fibers.
6. Thread the fibers into the OPP, as illustrated in Threading and connecting
optical fibers in the OPP (on page 3-75).
7. Identify the duplex connector position on the duplex connector panel (on
page 3-75).
8. Connect each equipment fiber to the corresponding network fiber according
to the site cabling diagram and the detailed cabling diagrams or tables of
each shelf.
9. Run the fibers up to the level of the corresponding optical connector.
10. Return the OPP to the rack until it latches in place with a click.
In this chapter:
Installation Options..........................................................................................4-1
Installing the ADR-10000 Shelf in Racks .......................................................4-7
Grounding the ADR-10000 Shelf ..................................................................4-22
Installation Options
ADR-10000 shelves can be installed in ETSI A racks or a 19" 600 mm deep
racks (in consultation with and approved by SAGEMCOM's Mechanical
Department). These racks can be installed on wooden, concrete, or suspended
floors, or suspended from overhead mountings.
The ADR-10000 can be installed in the rack in an horizontal or vertical
position. In addition, the ADR-10000 can be expanded with one or two TPUs
and an OCU. Different brackets and mechanical adapters are available for
attaching the ADR-10000 to the rack in each of these positions.
ADR-10000
ADR-10000
Figure 4-4: Typical horizontal installation of three ADR-10000 shelves with TPUs in
2600 mm ETSI A rack
ADR-10000
4. Fasten the lower bracket to the shelf with two long screws and nine short
screws from the installation kit.
2. Insert the filter frame pin guides into the corresponding holes in the frame
support.
3. Attach the frame support to the filter frame.
4. Attach the filter frame to the shelf and fasten it with four long screws from
the installation kit.
4. Fasten the upper bracket to the shelf with seven screws and washers from
the installation kit.
In this chapter:
Installing ADR-10000 Cards ...........................................................................5-1
Installing ADR-10000 Modules.....................................................................5-10
Installing TPU Modules.................................................................................5-19
Attaching TPUs/OCU to the ADR-10000 Shelf............................................5-25
CAUTION:
If you feel resistance when inserting cards, immediately
retract the card and repeat the process.
Do not use excessive torque when tightening the fastening
card screws.
c. Orient the NVM card against the dedicated slot on the MXC300, and
then insert its rear end (the end with the connector) in the card guides.
Push the card in until it is locked in place.
d. Place the NVM cover on the slot, and fasten it with its two captive
screws.
8. Push the front panel of the MXC300 in until the extractor handles start to
move inside, the card mates the chassis connectors, and the front of the card
is flush with the front of the shelf. If you feel resistance before the
connectors are mated, pull the card out and repeat the procedure.
9. Turn the two extractor handles simultaneously to the horizontal position to
lock the card in place.
10. Secure the MXC300 in place by tightening the two captive screws.
WARNING:
To reset the system using the RESET button, you must
first remove the NVM cover.
To extract the NVM, press the release pushbutton using
the cover as a tool.
4. Push both brown levers located on the card's extractor handles to release the
handles.
5. Insert the rear end of the quad I/O card into the card guides.
6. Push the card in until it mates the chassis connectors and the front of the
card is flush with the front of the ADR-10000 shelf. If you feel resistance
before the connectors are mated, pull the card out and repeat the procedure.
7. Press both handles simultaneously to lock the card in place.
8. Secure the quad I/O card in place by tightening the two captive screws.
9. Install the SFP/XFP transceivers according to Installing SFP/XFP
transceivers in optical modules and cards (on page 5-15).
6. Attach the adapter to the right side of the quad I/O slots with two screws
from the installation kit as shown in the figure above.
7. Identify the left card adapter according to the following figure.
8. Attach the adapter to the left side of the quad I/O slots with two screws
from the installation kit as shown in the figure above.
5. Push both brown levers located on the card's extractor handles to release the
handles.
6. Insert the rear end of the SIM64_XFP into the card guides.
7. Push the card in until it mates the chassis connectors and the front of the
card is flush with the front of the ADR-10000 shelf. If you feel resistance
before the connectors are mated, pull the card out and repeat the procedure.
8. Press both handles simultaneously to lock the card in place.
9. Secure the SIM64_XFP in place by tightening the two captive screws.
10. Install the XFP transceiver according to Installing SFP/XFP transceivers in
optical modules and cards (on page 5-15).
CAUTION:
When installing optical modules, make sure all SFP
transceiver slots are closed by protective caps. Do not
remove the cover until an SFP is inserted.
For your safety, to comply with electro-magnetic
6. Fasten the module to the chassis by tightening the two fastening screws. Do
not use excessive torque when tightening the screws.
7. If you are installing an optical module with SFP transceivers, proceed to
Installing SFP/XFP transceivers in optical cards. (on page 5-15)
After inserting all the modules, check for correct installation against the module
insertion diagram. Install blank panels over all free slots.
7. Fasten the module to the adapter by tightening the two fastening screws. Do
not use excessive torque when tightening the screws.
8. Install the SFP transceiver according to Installing SFP/XFP transceivers in
optical cards (on page 5-15).
CAUTION: All slots that are not in use must remain covered. If
you have to replace a module or card, remove the SFP/XFP first.
Because the PIM 2_63s and MCSMs occupy a pair of slots each, before you
can install them you must first remove the guide between the pair of slots.
8. After inserting all the modules, check for correct installation against the
module insertion diagram. Install blank panels over all free slots.
When you order an ADR-10000 system with one or two TPUs, the shelf is
supplied with the TPUs installed and their fastening brackets attached to each
one. The same applies to OCU shelves.
If your ADR-10000 shelf does not include TPU protection, it is possible to
upgrade your system and add one or two TPUs and an OCU at a later stage,
provided you have left space on the rack for this possibility. You need at least
150 mm space above/under the ADR-10000 for each TPU/OCU.
The TPUs can be installed without disconnecting any of the ADR-10000 cables
and fibers and without affecting traffic not going via a TPU.
12. Insert the three long screws, supplied with the installation kit, into the
appropriate holes, as illustrated in the following figure, and secure the TPU
in place.
13. Insert the TC module in the TPU, as described in Installing the TC/TCF
Module in the TPU Shelf (on page 5-19).
14. Insert the TPMs in the TPU, as described in Installing Single-Slot TPMs in
the TPU (on page 5-20) and Installing Double-Slot TPMs in the TPU (on
page 5-22).
Figure 5-25: Installing the ADR-10000 pin guides and removing the lower
connector cover
6. Open the two captive screws fastening the lower TPU connector cover to
the shelf. Remove the cover.
14. Open the two captive screws fastening the second connector cover to the
TPU. Remove the cover.
15. Take the jumper connector from the installation kit and insert it into the
connector house.
16. Fasten the jumper connector in place with three screws from the installation
kit.
17. Turn the TPU back to regular position.
19. Insert the three long screws supplied in the installation kit into the
appropriate holes, as illustrated in the following figure, and secure the TPU
in place.
Figure 5-29: Removing the connector cover and fastening bracket from the
first TPU/OCU
6. Open the six screws securing the fastening bracket to the first TPU/OCU
shelf installed on the expanded ADR-10000 (see the previous figure).
7. Open the two screws fastening the bracket to the rack. Remove the bracket.
8. Orient the second TPU upside down, on a clean flat surface.
9. Identify the two threaded holes for the pin guides at the bottom of the
second TPU.
10. Take two pin guides from the installation kit and screw them securely into
the TPU.
Figure 5-31: Inserting the TPU/OCU connector onto the first TPU/OCU in the
ADR-10000
Expanded
ADR-10000
Figure 5-32: Lowering the second TPU/OCU onto the expanded ADR-10000
13. Insert the three long screws supplied in the installation kit into the
appropriate holes, as illustrated in the following figure, and secure the
second TPU/OCU in place.
Figure 5-33: Securing the second TPU/OCU onto the expanded ADR-10000
In this chapter:
Connecting Fibers and Cables in ETSI A Racks .............................................6-1
1. Connect the connector at the end of the power cable to the POWER
connector of the MXC300 in slot MXC-A, and fasten it with its two screws.
2. Grasp the connector at the other end of the power cable, and thread it
through the opening in the left bracket of the ADR-10000 shelf.
3. Repeat steps 1 and 2 for the second power cable to be connected to the
corresponding MXC300 in slot MXC-B.
4. Bend the cables and thread them through the side cable guides of the rack.
Pull the cables until the cable connectors are positioned against the
appropriate connectors on the RAP.
5. Use cable ties as required to fasten the cable to the rack side rails.
6. Connect the free ends of the power cables in accordance with the rack
installation plan and the cable tags to the DC power connectors on the RAP.
NOTE: The FST has two opening positions. The tray latches
with a click at the halfway position. If you cannot release the
fiber in the halfway position, pull the tray again to open it
fully.
3. Insert the end of the fiber in the appropriate slot of the conduit running
along the front support of the rack, and route it to the appropriate level.
4. At the desired level lead the end through the appropriate slot of the conduit,
and pass the fiber through one of the slots in the fiber guide.
7. Secure the cable connector to the module connector with the two cable
connector screws. Tighten the screws manually; if the screws cannot be
reached with your bare hand, use an adjustable-torque flatblade screwdriver
(maximum blade size 0.6). Set the tightening torque to 40 N cm to 44 N cm.
The following table shows the slot association for 1:1 protection scheme in the
ADR-10000.
Table 6-2: ADR-10000 1:1 I/O protection
TPU slots I/O slot allocation
Protection Main
M1-1 I1 I5
M1-2 I2 I6
M1-3 I3 I7
M1-4 I4 I8
M3-1 I9 I13
M3-2 I10 I14
M3-3 I11 I15
M3-4 I12 I16
The following table shows the slot association for 1:2 protection scheme in the
ADR-10000.
Table 6-3: ADR-10000 1:2 I/O protection
TPU slots I/O slot allocation
Protection Main
M1-1, M1-2, and I1 and I2 I5 and I6
M1-3 I7 and I8
M3-1, M3-2, and I9 and I10 I13 and I14
M3-3 I15 and I16
The following table shows the slot association for 1:3 protection scheme in the
ADR-10000.
Table 6-4: ADR-10000 1:3 I/O protection
TPU slots I/O slot allocation
Protection Main
M1-1 and M1-2 I1 I2, I5, I6
M1-3 and M1-4 I3 I4, I7, I8
M3-1 and M3-2 I9 I10, I13, I14
M3-3 and M3-4 I11 I12, I15, I16
The following table describes the slot assignment of the TPM2_42_2 in the
TPU and the PIM2_42 in the ADR-10000 shelf.
Table 6-5: TPM2_42_2 and PIM2_42 slot assignment in the ADR-10000
TPU slots I/O Slot Allocation
Protection Main
M1-1 and M1-2 I1 I5 and I6
M1-3 and M1-4 I3 I7 and I8
M3-1 and M3-2 I9 I13 and I14
M3-3 and M3-4 I11 I15 and I16
Tool Kit
SAGEMCOM offers a tool kit to facilitate extraction/insertion of connectors
and optical SFP transceivers connected to ports in very high density cabling
environments.
2. Move extractor forward to attach the far groove to the module's handle.
To extract an LC connector:
1. Insert the fiber near the boot under the extractor's wide end tab.
4. Move the fiber backward till its connector is beyond the extractor's tab.
To insert an LC connector:
1. Insert the fiber near its boot, under the extractor's narrow end tab. Orient
connector's clip in front of the tool's teeth.
4. Gently pull the extractor back until its edge is beyond the boot.
3. Push the extractor forward to fit SFP's middle partition into extractor's edge
slot.
5. Pull the extractor slightly backward. Make sure that the clip is grasped and
moves with the tool.
6. Slide the lever forward to lock the SFP's clip, and press slightly.
Figure 6-32: Locking the clip between lever and extractor's teeth
3. Pull the extractor with the connector backward and release the connector.
2. Pull the cable backward until the connector's edge is stopped by the tab.
4. Gently pull the extractor backward and release it from the cable.
In this chapter:
Overview..........................................................................................................7-1
Test Equipment ................................................................................................7-2
Site Commissioning Tests ...............................................................................7-3
Network Commissioning Tests........................................................................7-6
Overview
The commissioning tests are performed after completing the installation and
preliminary configuration of a new network. These procedures confirm that the
network has been properly installed and is operating in accordance with the
design specifications.
This chapter provides general commissioning procedures for the ADR-10000,
and provides a basis for preparing tests in specific networks.
The commissioning procedures include:
| Site commissioning tests, performed at the site level to ensure proper
functionality of the site.
| Network commissioning tests, performed at the network level. These
include:
SDH commissioning tests, to ensure proper SDH functionality of the
integrated network
Data network commissioning tests, to ensure proper data functionality
of the integrated network
Optical network commissioning tests, to ensure proper optical
functionality of the integrated network
Test Equipment
The following test equipment is required for the commissioning procedures:
| Optical power meter (OPM)
| Optical spectrum analyzer (recommended for measurements at points
carrying multiple wavelengths, for example, inputs and outputs of optical
amplifiers)
| Optical BER tester
| Set of optical attenuators with various values
| Variable optical attenuator
| FC-to-LC and FC-to-SC adapters
| FC/FC optical patch cords
| Multimeter
Suitable equipment is available from a wide range of manufacturers, and
therefore no specific test equipment models are listed. You can use any
equipment that meets the applicable international standards and has satisfactory
measurement accuracy over the range of operating parameters and
environmental conditions that apply to the specific network. If necessary,
contact SAGEMCOM's Field Engineering Department for specific
recommendations.
NOTES: Make sure that the boot version of each card and
module matches the embedded version.
If the equipment is already connected to a management
station, use the Inventory window to collect the information
and print the relevant data. Refer to the SAGEMCOM
management system user manual for detailed instructions.
2 Mbps tests
For 2 Mbps tributaries, configure the test equipment as follows:
Framing Unframed
Coding HDB3
Pattern 2 * 10-15 PRBS
Signal rate 2 Mbps
Timing Received clock
Inject error Code error
34 Mbps tests
For 34 Mbps tributaries, configure the test equipment as follows:
Framing Unframed
Coding HDB3
Pattern 2 * 10-15 PRBS
Signal rate 34 Mbps
Timing Received clock
45 Mbps tests
For 45 Mbps tributaries, configure the test equipment as follows:
Framing Unframed
Coding 45 frame = C-bit
X-bit = 11
Pattern 2*10-15 PRBS
Signal rate 45 Mbps
Timing Received clock
Inject error Code error
SDH tests
For SDH tests, configure the test equipment according to the interface type
being tested, as follows:
Signal rate STM-1, STM-4, or STM-16
Mapping Any mapping (preferably bulk)
Framing Off
Pattern 2 * 10-15 PRBS
Timing Received clock
Inject error Code error
NOTE:
Measured latency is for both the forward and return paths.
For a single path, the latency will be 50% of the measured
value.
The latency test is dependent on the throughput results.
For example, if 10 Mbps is tested and the throughput is
4%, the latency test should be for 4 Mbps (2 * VC-12 = 4
Mbps).
Inject traffic according to the assigned bandwidth (VC-12
= 2.048 Mbps).
Latency
Optical
loopback
TX T
TX
BER
tester R
RX P RX
Attenuator
Mux Demux
TRP ...........
...........
TX
BER
tester
RX
Variable ...........
attenuator ...........
Demux Mux
In this chapter:
Overview..........................................................................................................8-1
Required Test Equipment, Tools, and Materials .............................................8-1
Preventive Maintenance...................................................................................8-2
Traffic Monitoring System ..............................................................................8-6
Onsite Troubleshooting..................................................................................8-10
Replacing Cards and Modules .......................................................................8-17
Replacing RAP Components .........................................................................8-23
Overview
This chapter provides maintenance procedures for ADR-10000 equipment.
13. Check that there are no alarm indications on the cards and X
modules.
14. Check that all RAP LEDs turn on and that the buzzer sounds X
when the POWER ON pushbutton on the RAP panel is
pressed.
15. Check that all card and module LEDs turn on when the LED X
TEST pushbutton on the ECU300/ECU300-F panel is pressed.
16. Perform a visual check of LED indications. X
17. Check the proper operation of the OW system (if applicable to X
the NE).
3. Cold water rinse: Under normal service conditions, the foam media used
in the filters require no oily adhesives. Therefore, collected dust and dirt
can be washed away using a standard hose nozzle with plain water. Stand
the filter until completely dry and free of moisture, and return to service.
4. Immersion in warm soapy water: Where stubborn airborne dirt is present,
the filter may be dipped in a solution of warm water and mild detergent.
Then simply rinse in clear water, stand until completely dry and free of
moisture, and return to service.
The recommended method is No. 4, as it ensures thorough cleaning of all types
of contaminants under any reasonable service conditions.
The main components of the monitoring system interface are located on the
ECU300-F front panel. These components, except for the monitoring point and
monitoring indicator, are common to all modules. In addition, the system has a
monitoring point and monitoring indicators on the front panel of the modules.
The PIM2_21, PIM2_63/B, and PIM345 have only one monitoring indicator
used for all their channels. STM-1 modules do not have a monitoring point, and
use the monitoring point on the ECU300-F card.
Selecting a module
The MODULE selector chooses the monitored module slot number. The
selected module is displayed on the 2-digit display to the right of the selector.
Pressing the selector upward increments the slot number; pressing it downward
decrements the slot number. The selection is cyclic. Possible selections are QA
and QB for the aggregate cards (I/O cards), and I1 to I16 for the I/O modules. If
the selected module is an STM-1, the MON indicator on the ECU300-F lights.
Selecting a channel
The CHANNEL selector chooses the specific monitored channel (port) on the
module selected. The selected channel is displayed on the 2-digit display to the
left of the selector. Pressing the selector upward increments the channel
number; pressing it downward decrements the channel number. The selection is
cyclic. Possible selections are from 00 to the module's maximum number of
channels. For example, in a PIM2_21 (which has 21 ports), the selection goes
from 00 to 21. When the value 00 is selected, the system blocks the monitoring
to the selected module.
In addition to the number of the selected channel shown on the display, a MON
indicator lights near the selected port on the module. If an STM-1 module is
selected, the MON indicator on the ECU300-F lights in addition to the LED
near the selected port on the module.
Stabilization time
The monitoring system has a stabilization time of approximately 1.5 seconds.
This means that after a new value is selected with the MODULE or CHANNEL
selectors, the display starts blinking for the stabilization time, and only after
that the new selection is displayed.
Monitoring options
The system can monitor a number of channels in different modules
simultaneously. This feature is useful when traffic passing through different
modules in the ADR-10000 has to be analyzed.
After monitoring channels of different modules, all selected channel numbers
of these modules are saved in the ECU-F's memory.
You can connect test equipment to various modules or connect test equipment
with multiple inputs to simultaneously monitor the traffic passing through the
channels in these modules.
Onsite Troubleshooting
The purpose of onsite troubleshooting is to identify the hardware causing the
malfunction and return the equipment to normal operation as soon as possible.
Troubleshooting is usually initiated in response to one of the following
conditions:
| Alarm or performance degradation reported by the management station.
| Alarm or malfunction detected on site by maintenance personnel, either as a
result of a troubleshooting activity initiated by the management center
personnel or as a result of a periodic inspection or preventive maintenance
action. Many problems can be detected via the various indicators available
on the ADR-10000 system components.
This chapter assumes familiarity with the ADR-10000, with SDH, data, and
with the NMS and EMS-ADR management stations. Refer to the respective
user manuals for details on the various capabilities of the management stations,
and for instructions on performing the desired activities.
The following sections provide procedures for performing onsite
troubleshooting for various trouble categories, as well as for specific
subsystems, and so on. For each category, you will find a troubleshooting table
that provides the instructions for identifying the trouble.
CAUTION:
Do not extract/insert an MXC300 while the DC cables are
connected to it.
If the FAIL (red), MAIN (blue), and TMU (orange) LEDs
blink simultaneously, the MXC300 is not mounted
correctly or not all four screws are properly locked.
Before attempting to remove the card, monitor its NVM
(yellow) indicator; remove the card only after this
indicator has been off for at least 2 minutes.
3. Open the MXC300 upper left screw first, then the upper right screw, and
then the two lower screws.
4. Hold both extractor handles and pull them simultaneously outward until the
card is released from the backplane.
5. Keep holding the handles, and gently pull the card out of the shelf.
6. If necessary, transfer the NVM from the replaced MXC300 card to its
replacement (see Replacing the NVM on MXC300 cards).
NOTE: Make sure that all four screws in the MXC300 are
properly tightened. Failing to do so may result in improper
operation of the shelf.
If the FAIL (red), MAIN (blue), and TMU (orange) LEDs
blink simultaneously, the MXC is not mounted correctly or
not all four screws are properly locked.
4. Insert the replacement circuit breaker into the circuit breaker sockets of the
corresponding xRAP-D/xRAP-B power terminal board, as shown in the
following figures.
5. Reinstall the xRAP-D/xRAP-B front cover and fasten it with its two captive
screws.
In this appendix:
Overview......................................................................................................... A-1
ECU300/ECU300-F Card Connectors............................................................ A-1
MXC300 DC Input Power Connectors ........................................................... A-7
PIM2_21 Connection Data ............................................................................. A-8
PIM2_42 Connection Data ........................................................................... A-11
PIM2_63/B Connection Data........................................................................ A-17
EISMB/DIOM/MCSM Connectors .............................................................. A-21
xRAP-D/xRAP-B Connectors ...................................................................... A-22
Overview
This appendix provides connection data for the user connectors located in ADR
shelves and associated ancillary equipment supplied by SAGEMCOM. Optical
and coaxial connectors are described in the ADR-10000 Reference Manual.
Any connectors not described in this appendix are reserved for use by
SAGEMCOM’s Network Solutions Division technical support personnel and/or
for future expansion, and therefore no user equipment may be connected to
them.
ECU300/ECU300-F Card
Connectors
ALARMS Connector
The ALARMS connector is a 36-pin SCSI female connector that carries three
groups of lines:
Pin 18 Pin 1
Pin 36 Pin 19
F-CHANNEL Connector
The F-CHANNEL connector is a 9-pin D-type male connector that provides a
serial RS-232 communication channel supporting SLIP. This connector is
intended for connection to a Craft terminal. The connection is made to one of
the serial RS-232 ports of the PC serving as a Craft terminal, using a crossed
cable.
The following figure identifies the connector pins as seen when looking into the
connector. The table lists the connector pin assignment, together with the
corresponding pin in the Craft terminal serial RS-232 port (assuming that this
port uses a 9-pin connector).
ETHERNET Connectors
The two ETHERNET connectors located on the ECU300/ECU300-F panel,
designated MANAGEMENT MAIN and PROT/LCT, are 8-pin RJ-45
connectors that provide two Ethernet 10BaseT management interfaces (one for
each MXC300 card installed in the ADR-10000 shelf).
At any time, only the interface connected to the MXC300 serving as the current
main card is active; the interface connected to the MXC300 serving as the
protection card is in standby to provide protection for the out-of-band
management traffic.
Each ETHERNET connector is wired as a station port intended for direct
connection through a straight cable to a port of a 10BaseT Ethernet hub.
Pin 25 Pin 1
Pin 50 Pin 26
Pin 25 Pin 1
Pin 50 Pin 26
LOWER
Figure A-6: PIM2_21 E1 connectors pin identification
Table A-6: PIM2_21 receive lines (upper) connector pin assignment
Pin Name Function Direction Wire color
1 RTIP1 Receive, tributary 1, wire A Input Brown
2 RTIP2 Receive, tributary 2, wire A Input Red
3 RTIP3 Receive, tributary 3, wire A Input Orange
4 RTIP4 Receive, tributary 4, wire A Input Yellow
5 RTIP5 Receive, tributary 5, wire A Input Green
6 RTIP6 Receive, tributary 6, wire A Input Blue
7 RTIP7 Receive, tributary 7, wire A Input Violet
8 GND Shield — Brown/green-ring
9 RTIP8 Receive, tributary 8, wire A Input White
10 RTIP9 Receive, tributary 9, wire A Input Pink
11 RTIP10 Receive, tributary 10, wire A Input Brown/white-ring
12 RTIP11 Receive, tributary 11, wire A Input Orange/white-ring
13 RTIP12 Receive, tributary 12, wire A Input Green/white-ring
14 RTIP13 Receive, tributary 13, wire A Input Violet/white-ring
15 RTIP14 Receive, tributary 14, wire A Input Red/brown-ring
16 GND Shield — Light-gray/green-ring
17 RTIP15 Receive, tributary 15, wire A Input Orange/brown-ring
Table A-9: PIM2_42 receive/transmit lines lower connector (22-42) pin assignment
Pin Name Function Direction Wire color
1 CGND Shield — Brown/green-ring
2 CGND Shield — Light Gray/green-ring
3 RTIP22 Receive, tributary 22, wire A Input Brown
4 RRING22 Receive, tributary 22, wire B Input Brown/gray-ring
5 RTIP23 Receive, tributary 23, wire A Input Red
6 RRING23 Receive, tributary 23, wire B Input Red/gray-ring
7 RTIP24 Receive, tributary 24, wire A Input Orange
8 RRING24 Receive, tributary 24, wire B Input Orange/gray-ring
9 RTIP25 Receive, tributary 25, wire A Input Yellow
10 RRING25 Receive, tributary 25, wire B Input Yellow/gray-ring
11 RTIP26 Receive, tributary 26, wire A Input Green
12 RRING26 Receive, tributary 26, wire B Input Green/gray-ring
13 RTIP27 Receive, tributary 27, wire A Input Blue
14 RRING27 Receive, tributary 27, wire B Input Blue/gray-ring
15 RTIP28 Receive, tributary 28, wire A Input Violet
16 RRING28 Receive, tributary 28, wire B Input Violet/gray-ring
17 RTIP29 Receive, tributary 29, wire A Input White
18 RRING29 Receive, tributary 29, wire B Input White/gray-ring
19 RTIP30 Receive, tributary 30, wire A Input Pink
20 RRING30 Receive, tributary 30, wire B Input Pink/gray-ring
21 RTIP31 Receive, tributary 31, wire A Input Brown/white-ring
22 RRING31 Receive, tributary 31, wire B Input Red/white-ring
23 CGND Shield — Violet/green-ring
Pin 25 Pin 1
Pin 50 Pin 26
Pin 25 Pin 1
Pin 50 Pin 26
LOWER
Figure A-8: PIM2_63/B typical pair connectors pin identification
Table A-10: PIM2_63/B typical receive lines (upper) connector pin assignment
Pin Name Function Direction Wire color
1 RTIP1 Receive, tributary 1, wire A Input Brown
2 RTIP2 Receive, tributary 2, wire A Input Red
3 RTIP3 Receive, tributary 3, wire A Input Orange
4 RTIP4 Receive, tributary 4, wire A Input Yellow
5 RTIP5 Receive, tributary 5, wire A Input Green
6 RTIP6 Receive, tributary 6, wire A Input Blue
7 RTIP7 Receive, tributary 7, wire A Input Violet
8 GND Shield — Brown/green-ring
Table A-11: PIM2_63 typical transmit lines (lower) connector pin assignment
Pin Name Function Direction Wire color
1 TTIP1 Transmit, tributary 1, wire A Output Brown/yellow-ring
2 TTIP2 Transmit, tributary 2, wire A Output Orange/yellow-ring
3 TTIP3 Transmit, tributary 3, wire A Output Blue/yellow-ring
4 TTIP4 Transmit, tributary 4, wire A Output Light-gray/yellow-ring
5 TTIP5 Transmit, tributary 5, wire A Output Brown/blue-ring
6 TTIP6 Transmit, tributary 6, wire A Output Orange/blue-ring
7 TTIP7 Transmit, tributary 7, wire A Output Green/blue-ring
8 GND Shield — Pink/orange-ring
9 TTIP8 Transmit, tributary 8, wire A Output Light-gray/blue-ring
10 TTIP9 Transmit, tributary 9, wire A Output Brown/orange-ring
11 TTIP10 Transmit, tributary 10, wire A Output Yellow/orange-ring
12 TTIP11 Transmit, tributary 11, wire A Output Blue/orange-ring
13 TTIP12 Transmit, tributary 12, wire A Output Light-gray/orange-ring
14 TTIP13 Transmit, tributary 13, wire A Output Brown/violet-ring
15 TTIP14 Transmit, tributary 14, wire A Output Orange/violet-ring
16 GND Shield — Pink/blue-ring
17 TTIP15 Transmit, tributary 15, wire A Output Green/violet-ring
18 TTIP16 Transmit, tributary 16, wire A Output Light-gray/violet-ring
19 TTIP17 Transmit, tributary 17, wire A Output Brown/pink-ring
20 TTIP18 Transmit, tributary 18, wire A Output Orange/pink-ring
21 TTIP19 Transmit, tributary 19, wire A Output Green/pink-ring
22 TTIP20 Transmit, tributary 20, wire A Output Light-gray/pink-ring
23 TTIP21 Transmit, tributary 21, wire A Output Pink/violet-ring
24 GND Shield — Pink/white-ring
25 — Not connected — —
26 GND Shield — White/brown-ring
27 TRING1 Transmit, tributary 1, wire B Output Red/yellow-ring
28 TRING2 Transmit, tributary 2, wire B Output Green/yellow-ring
29 TRING3 Transmit, tributary 3, wire B Output Violet/yellow-ring
30 TRING4 Transmit, tributary 4, wire B Output White/yellow-ring
31 TRING5 Transmit, tributary 5, wire B Output Red/blue-ring
32 TRING6 Transmit, tributary 6, wire B Output Yellow/blue-ring
Figure A-10: xRAP-D and xRAP-B shelf DC input power connector pin functions
Pin 18 Pin 1
Pin 36 Pin 19