Professional Documents
Culture Documents
Final Thesis
Final Thesis
Final Thesis
Bachelor’s thesis
Ardeep Maharjan
ABSTRACT
ABSTRACT
The purpose of this Bachelor’s thesis was to conduct a structural analysis
of structural elements of a concrete multi-storey building with Autodesk
Robot Structural analysis and traditional manual calculation. The aim was
to compare the results obtained from the structural analysis of both
methods to discover if there is any alteration in the results. The thesis only
concentrates on structural elements of the building but not on the design
of Structural connections. The main aim was to examine the behaviour of
structure when the most critical load combination is applied on the
building.
The results of the thesis show that for the given applied load on the
structure the load combinations by traditional manual calculations is
almost impossible to executed due to many possible combinations which
leads to difficulties to find out the critical load. This also leads to the
overestimation of critical load by introducing a high value for safety
factors, resulting in oversizing of structural elements eventually increasing
the cost of the structure. Moreover, it is tedious and time consuming to
perform the calculation manually which makes using software for
structural analysis more beneficial and efficient. However, there are
certain drawbacks of a structural analysis by software as it is not
completely perfect yet; there are some calculations which are obligated to
calculate manually.
EC Eurocode
SW Self Weight
1 INTRODUCTION ........................................................................................................... 1
1.1 Introduction of Eurocodes .................................................................................. 1
1.2 Eurocode 2 .......................................................................................................... 1
REFERENCES.................................................................................................................... 48
Appendices
Appendix 1 Calculations
Appendix 2 Floor plans and Materials properties
1
1 INTRODUCTION
1.2 Eurocode 2
concrete etc. It consists of seven chapters and four appendices. The four
chapters are shown below.
This Thesis only deals with part 1-1 also called EN 1992-1-1 because it
concentrates on a multi-story reinforced concrete office building.
2 PROJECT DESCRIPTION
The slab of the new building was supported with the existing building with
the rectangular beam element embedded with 2T12 rebar with a spacing
of 150mm and chemical anchor with a diameter of 20mm connected in the
existing building on each floor. The exterior frame of the building was
made up of prefabricated reinforced concrete walls. The floor system was
different in different floors. The ground floor and the roof floor consisted
of extra insulation in order to protect the structure from unnecessary
moisture from the external environment along with hollow core slabs of
350mm, which was supported by Peikko’s delta beams on each floor.
Circular reinforced columns were used as the vertical member of the
structure whereas structural steel columns were used for the openings of
the doors on the ground floor and the celling room. A Pad foundation of
varying dimensions was used for the columns whereas strip foundations
were used as a supporting element for the external walls. The load of the
structure was transferred via columns to foundation piles embedded in the
bedrock.
The building was designed using Eurocode SFS EN-1990, EN-1991, EN-1992
standards as well as the Finnish National Annexes.
2.1 Materials used in building with exposer class and concrete cover
The concrete class, exposer class and concrete covers used in the building
were different at different places, which is given in Appendices.
Then according to the design life and special quality control of the concrete
production of the structural element the structural class of the structural
element can be altered. For example, this beam and column were designed
for 50 years of life and no special quality control is ensured. The structural
classes of the elements is shown in Table 3.
Values for minimum concrete cover for the given structural class and
exposure class can be determined by using Table 4 below.
5
Where,
∆𝑐,𝑑𝑒𝑣 = 10mm
3.2 Columns
There were ten prefabricated circular reinforced columns in both the first
floor and second floor with a diameter of 380mm whereas there were four
reinforced concrete columns of dimension 280mm*280 mm on the roof.
(C30/37) concrete class was used in the building with the concrete cover
of 25mm. Peikko’s precast hidden corbel was used in columns to support
delta beams. It consisted of a corbel plate bolted to a machined steel
column plate integrated into the column.
3.3 Beams
Delta beams were employed in the building to carry the loads from the
floor. Hollow core slabs were put on the flange of delta beams. Delta
beams of size D24-400 were used on third floor while D32-400 beams were
used on the rest of the structure. The slab was supported by the
rectangular beam element of 200mm*280mm embedded with 2T12 rebar
with a spacing of 150mm and chemical anchor with a diameter of 20mm
connected in the existing building side on each floor. The shape of the delta
beam is shown in Figure 4.
7
3.4 Floor
Imposed loads on the building were transferred to the delta beams via
floor slabs. Hollow core slabs were used as the structural floor element in
the building. Three types of floors with a different layer were used in this
structure. The dimensions and materials of the floor are shown in Table 6.
3.5 Foundation
Loads from the building were transferred to the ground via foundation. A
Strip foundation with the dimension of 1000mm*700mm was used for
exterior walls. The loads from the columns were first transferred to the
plinth of dimension 500mm*800mm then, it was transferred to the pad
foundation with variable dimensions from 1650mm*1900mm*700m to
1900mm*1900mm*700mm. The load bearing capacity of the soil was not
enough to support the structure load. Therefore, piles were used to
transfer the loads from the foundation to the bedrock. The column was
connected to the plinth by using a column shoe whereas the plinth was
connected to the pad foundation by anchor rods and lapping
reinforcement from the footing and plinth.
4 LOAD DESCRIPTION
Dead load is defined as Action that is likely to act throughout the given
reference period and for which the variation in magnitude with time is
negligible, or for which the variation is always in the same direction
(monotonic) until the action attains a certain limit value (SFS-EN 1990
2002, 2005)
In this project, the self-weight of the building was considered as the dead
load. The partial safety factors used for permanent actions according to
the Finnish National Annex is shown in Table 7 below.
Where,
𝜉 = 0.85
Live load is defined as Action for which the variation in magnitude with
time is neither negligible nor monotonic (SFS-EN 1990 2002, 2005).
The partial safety factors used for variable actions in the Finnish National
Annex is shown in Table 9 below.
The imposed load on the building doesn’t act simultaneously all the time;
hence, to decrease the cost of the building the applied load can be reduced
using a reduction factor:
5 𝐴0
𝛼𝐴 = 𝜓0 +
7 𝐴
Where,
𝜓0 = 0.7
𝐴0 = 10𝑚2
𝐴 = 𝐼𝑛𝑓𝑙𝑢𝑒𝑛𝑐𝑒 𝑎𝑟𝑒𝑎
10
The Finnish National Annex for imposed loads on the different part of the structure is
shown in Table 10.
The building was used for office purposes and library. There might be a
gathering of many people; hence, the imposed load on the building was
taken as 7.5 𝑘𝑁/𝑚2 upon request on each floor while 4 𝑘𝑁/𝑚2 was taken
at roof because the roof will be only used for maintenance purposes.
The value of coefficient ‘ψ’ for building is given in the National Annex for
SFS-EN 1990:2002. They are copied in the Table 11 below.
Table 11. The value of coefficient ‘ψ’ for building (SFS - EN1991-1-3
Eurocode 2003)
𝑠 = 𝜇1 ∗ 𝐶𝑒 ∗ 𝐶𝑡 ∗ 𝑠𝑘
Where,
𝐶𝑒 = Exposure coefficient
𝐶𝑡 = Thermal coefficient
The snow load shape coefficient can be calculated using Figure 7 below.
The roof is a flat roof with a projection of 3.3m and there were existing
higher buildings nearby. Therefore, the load arrangement should be used
for both the undrifted and drifted load arrangements. The snow load shape
coefficients that should be used for roofs abutting to taller construction
works are given in the following expressions in Figure 8.
Figure 9. Drifted load arrangement for structure near taller constructions (SFS-
EN1991-1-3 Eurocode 2003)
Where,
µs = Snow load shape coefficient due to sliding of snow from the upper
roof
For 𝛼 ≤ 15° µs = 0
µw = Snow load shape coefficient due to wind
𝑏 +𝑏 ℎ
µw = 1 2 ≤ 𝛾
2ℎ 𝑠𝑘
Where,
Drift length,
𝑙𝑠 = 2 ∗ ℎ
14
The wind load for the structure is given by EN 1991-1-4 under Finnish
National Annex SFS-EN 1991-1-4. The wind load can be calculated by
undergoing numerous steps as suggested by the Finnish National Annex.
Where,
The Mean wind velocity at height z above the terrain can be calculated
using following equation
𝑉𝑚 (𝑧) = C𝑟 (z) ∗ C0 (z) ∗ V𝑏,0
Where,
C0 (z)= Orography factor
Cr (z)= Terrain roughness factor
z
C𝑟 (z) = 𝐾𝑟 ∗ ln [ ]
𝑧0
Where,
Z0=Roughness height
Kr=Terrain factor depending on the roughness length z0
15
0.07
z0
K 𝑟 = 0.19 [ ]
𝑧0,𝑖𝑖
Where,
K 𝑟 = Terrain factor
𝐾1 = Turbulence factor (Recommended value from national annex is 1)
𝑣𝑏 = Basic wind velocity
𝜎𝑣
𝐼𝑣 =
𝑉𝑚
Where,
16
The peak velocity pressure can be calculated by using the equation below
1
𝑞𝑝 = [1 + 7𝐼𝑣 ] ∗ 𝜌 ∗ 𝑉𝑚2
2
𝑞𝑝 (𝑧) = C𝑒 (z) ∗ q𝑏
Where,
𝑞𝑏 =basic velocity pressure;
1
𝑞𝑏 = ∗ ρ ∗ v𝑏 2 ; ρ=Air density (1.25kg/m3)
2
The Exposer factor (C𝑒 (z)) can be calculated by using Figure 10 below
Figure 10. Illustration of Exposure factor for Co=a, Kr=1 (SFS-EN1991-1-4 Eurocode
2005)
17
Where,
𝐶𝑝𝑒 = Pressure coefficient for the external pressure
𝐶𝑝𝑖 = Pressure coefficient for the internal pressure
𝑝 = 𝐶𝑠 𝐶𝑑 𝑞𝑝 𝐶𝑝𝑒10 − 𝑞𝑝 𝐶𝑝𝑖
Where,
19
5 LOAD COMBINATION
The structure shall be designed so that it doesn’t face any kind of structural
damage during its intended period of life. There are different types of load
acting on the structure and most of the time these loads act in
simultaneously resulting in the overloading in the structure. Therefore, to
overcome such problem in future the most critical combination of load
must be considered while designing the structure. EN 1991 gives the load
combinations depending on whether the overall structure is considered as
a rigid body (EQU) or design of structural element (STR) need to be carried
out.
The load combination was executed by using the Finnish National Annex
as shown in table 16 and 17.
As shown in Table 17 above, the factor KFI was taken as 1 since the
structure belongs to the reliability class 2.
All the members of the structure from grid N3-N3 were defined as shown
in Figure 12 below.
All the loads applied on the structure were defined in the robot structural
analysis as shown in Table 18 below.
The self-weight of the elements modelled in the software was defined automatically by
software itself and the self-weight of concrete finishes and fillings was manually
introduced to the software, as it was not defined by the software.
There are altogether 1528 load combinations for the defined loading on
the structure. However, only 46 combinations are shown in Table 19.
The forces and moment on the column were calculated by RSA for load
combination 24. The values of normal forces and moments on the column
2 are shown in Figure 16.
The column was designed in the RSA as shown in Figure17 below,then the
properties of column was defined.
26
The normal force versus moment graph from RSA is shown in Figure 18.
After finding the maximum design moment on the column, the provided
reinforcement to overcome the given moment was defined and the
number of bars with diameters and spacing is shown in Table 20. It was
found that the total area of the provided reinforcement was 1357mm2.
Load combination, which gives the maximum moment and shear force on
the beam, is shown in Figure 20 below. It was found that the load
combination number 24 gives the maximum moment and shear force on
the beam number 16 with the moment value of 700.65kNm and shear
force value of 452.03kN as shown in Figure 21 below.
28
From the Figure 22, the load capacity for 6.2m D32-400 beam is
approximately 140kN/m. The maximum bending moment and shear
resistance is given by equation in Figure 23.
30
Figure 23. Forces and moments for UDL with pin support
Since the delta beam will be cast inside the concrete which results in a
substantial increase of moment resistance of beam. The extra moment
capacity due to concrete is calculated as shown in Figure 24 below:
𝑀 = 300.2𝑘𝑁𝑚
The structural load from the building was beyond the capacity of applicable
pad footing dimension; due to that reason the pad footing was not used in
the structure. To overcome that problem piles were introduced in the
structure to carry the load from the structure. Due to a lack of features to
design piles in RSA it cannot be executed.
7 MANUAL CALCULATION
32
During the erection of the wall due to imperfection, some of the load from
the wall was transferred into the structure instead of direct transfer of wall
through the footing of the wall. The transferred load from the wall must
also be considered. The load from the wall is shown in Figure 26 below:
Figure 26. Cases for permanent load from wall due to imperfection
The building is used for office purposes and library. There might be a
gathering of many people; hence, the Imposed load on the building was
taken as 7.5 kN/m2upon request on each floor while 4 kN/m2was taken at
roof because the roof will be only used for maintenance purposes.
The Imposed line load on the grid 3-3 was calculated and different possible
load cases were defined according to Eurocode as shown in Figure 27
below
The load cases for imposed loads are shown in Figure 27 and the reaction
obtained from those cases are noted in Table 25 below.
Snow load on the roof was calculated based on EN 1991-1-3 along with the
Finnish National Annex. The step by step process of calculation is shown in
Appendix 1. There is only one case of snow load that was taken into
consideration which is shown below in Figure 28.
The line load on the structure from snow load is shown in Figure 28 and
the reaction forces exerted by the support due to snow load 27 is shown
in Table 26 below
36
RA 98.96
RB 172.10
RC 143.08
RD 135.86
RE 59.17
The reaction forces on the support obtained from Figure 29 are shown in
Table 27 below.
RA RB RC RD RE
In this section, the method of column design is explained. There are two
types of design approaches discussed in Eurocode 2 for the design of RC
columns namely Nominal Stiffness method and Nominal Curvature
method. For this project, Nominal curvature method was adopted to take
into account of Second order effect in the column. The simple flow chart
for the design approach of Nominal curvature method is shown in Figure
32.
Figure 32. Flow chart for nominal curvature method (Frost 2011)
40
𝜃𝑖 = 𝜃0 𝛼ℎ 𝛼𝑚
Where,
1
𝜃0 =
200
2
𝛼ℎ = ; l= Length of member
√𝑙
1
𝛼𝑚 = √0.5 ∗ (1 + ) ; m= no. of vertical member
𝑚
ℎ 𝑙
𝑒0 = max [ , 20, 𝜃𝑖 0 ] 𝑙0 = 𝐸𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 ℎ𝑒𝑖𝑔ℎ𝑡
30 2
Figure 33. Buckling modes and corresponding effective lengths for isolated member
(SFS-EN1992 Eurocode 2004)
Slenderness limit:
Slenderness limit can be calculated according to EC2 as shown below,
41
20 ∗ 𝐴 ∗ 𝐵 ∗ 𝐶
𝜆𝑙𝑖𝑚 =
√𝑛
Where
1
A= (If hef is not known, A = 0.7)
1+0.2ℎ𝑒𝑓
B =√1 + 2𝜔 (If ω is not known B=1.1)
C = 1.7 – rm (if rm is not known, C = 0.7)
𝑁𝐸𝑑
𝑛=
𝑓𝑐𝑑 𝐴𝑐
𝑀01
𝑟𝑚 =
𝑀02
For the given load applied on the beam. The Maximum design moment is
calculated. Then the height of the beam is determined (L=h/10). After
calculating the height of the beam, Effective depth (d) is calculated as:
∅𝑚𝑎𝑖𝑛
𝑑=ℎ− − ∅𝑠𝑡𝑖𝑟𝑟𝑢𝑝 − 𝑐𝑛𝑜𝑚
2
Where,
∅𝑠𝑡𝑖𝑟𝑟𝑢𝑝 = 𝐷𝑖𝑎𝑚𝑒𝑡𝑒𝑟 𝑜𝑓 𝑠𝑡𝑖𝑟𝑟𝑢𝑝
∅𝑚𝑎𝑖𝑛 = 𝐷𝑖𝑎𝑚𝑒𝑡𝑒𝑟 𝑜𝑓 𝑚𝑎𝑖𝑛 𝑟𝑒𝑏𝑎𝑟
𝑐𝑛𝑜𝑚 = 𝑁𝑜𝑚𝑖𝑛𝑎𝑙 𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 𝑐𝑜𝑣𝑒𝑟
42
𝑀
𝐴𝑠 = 𝒵∗𝑓
𝑦𝑑
Now,
𝑓𝑐𝑡𝑚
0.26 ∗
∗𝑏∗𝑑
𝐴𝑠,𝑚𝑖𝑛 = 𝑚𝑎𝑥 [ 𝑓𝑦𝑘 ]
0.0013 ∗ 𝑏 ∗ 𝑑
In this way, the required reinforcement for flexure design is calculated. The
same sets of rules are applied to design this structure. The calculation for
this building can be found in Appendix 1.
For the given load applied on the beam, the maximum design shear force
is calculated. Before anything else, one should check if the beam requires
any shear reinforcement or the capacity of beam without shear
reinforcement is adequate. The capacity of beam without shear rebar, that
is given by Eurocode is presented below.
1
[𝐶𝑅𝑑,𝑐 ∗ 𝑘 ∗ (100 ∗ 𝜌1 ∗ 𝑓𝑐𝑘 )3 + 𝑘1 𝜎𝑐𝑝 ] ∗ 𝑏𝑤 ∗ 𝑑
𝑉𝑅𝑑,𝑐 = 𝑚𝑖𝑛 { }
𝑣𝑚𝑖𝑛 ∗ 𝑏𝑤 ∗ 𝑑
Where,
0.18
𝐶𝑅𝑑,𝑐 = 𝛾
𝑐
200
𝑘 =1+√ ≤2
𝑑
𝐴𝑠𝑙
𝜌1 = 𝑏
𝑤 ∗𝑑
43
𝑘1 = 0.15 (𝑅𝑒𝑐𝑜𝑚𝑚𝑒𝑛𝑑𝑒𝑑)
𝑁𝐸𝑑
𝜎𝑐𝑝 = < 0.2 ∗ 𝑓𝑐𝑑
𝐴𝑐
If the value of shear resistance is smaller than the applied shear force, then
the beam requires the shear reinforcement. The shear capacity of the
beam is smaller of tension capacity of shear reinforcement and
compression capacity of concrete strut.
Where,
𝑉𝑅𝑑,𝑠
𝑉𝑅𝑑 = 𝑚𝑖𝑛 [ ]
𝑉𝑅𝑑,𝑚𝑎𝑥
𝐴𝑠𝑤,𝑚𝑎𝑥 𝑓𝑦𝑤𝑑 1
≤ 𝛼𝑐𝑤 𝜐1 𝑓𝑐𝑑
𝑏𝑤 𝑠 2
In this way, the required reinforcement for shear is calculated. The same
sets of rules are applied to design this structure.
The slab can be designed according to the maximum applied load on the
structure in per square meter, from the obtained maximum load the right
dimension of the slab was chosen from the design chart shown in Figure
34 below. The maximum applied load on the building was 7kN/m2 imposed
load added with 7.55kN/m2 permanent load which gives 14.55kN/m2
As can be seen in Figure 34 above, a hollow core slab of 320mm with the
length of 7.8m can carry about 19kN/m2. Hence, the hollow core slab of
320mm with the maximum length of 7.8m were used in the building.
All the applied load on the building is transferred via foundation to the
ground. There are different types of foundation in existence, However, the
design of pad foundation and strip foundation is described in this thesis.
Every foundation must be designed in such a way that the bearing pressure
from the foundation mustn’t exceed the bearing strength of soil and the
foundation must be strong enough to overcome forces and moment
applied in the foundation. There are certain steps one should follow
according to Eurocode to design the foundation. The process is
summarized below.
At first, the total load from the foundation on the footing was calculated.
The base area of the footing is calculated using the given formula
After finding the area of the base, the structural design of the base is
executed for the maximum load to the base by the column.
Flexure Design
Maximum bending moment is on the face of the column on pad footing.
The ultimate load is taken due to the ultimate load on one side of the
footing section. The maximum design moment can be calculated in such a
case using the given formula
1
𝑀𝐸𝑑 = ∗ 𝑝𝑑 ∗ 𝑐 2
2
∅𝑚𝑎𝑖𝑛
𝑑=ℎ− − ∅𝑠𝑡𝑖𝑟𝑟𝑢𝑝 − 𝑐𝑛𝑜𝑚
2
46
Where,
∅𝑠𝑡𝑖𝑟𝑟𝑢𝑝 = 𝐷𝑖𝑎𝑚𝑒𝑡𝑒𝑟 𝑜𝑓 𝑠𝑡𝑖𝑟𝑟𝑢𝑝
∅𝑚𝑎𝑖𝑛 = 𝐷𝑖𝑎𝑚𝑒𝑡𝑒𝑟 𝑜𝑓 𝑚𝑎𝑖𝑛 𝑟𝑒𝑏𝑎𝑟
𝑐𝑛𝑜𝑚 = 𝑁𝑜𝑚𝑖𝑛𝑎𝑙 𝑐𝑜𝑛𝑐𝑟𝑒𝑡𝑒 𝑐𝑜𝑣𝑒𝑟
𝑀
𝐴𝑠 = 𝒵∗𝑓
𝑦𝑑
Now,
𝑓𝑐𝑡𝑚
0.26 ∗∗𝑏∗𝑑
𝐴𝑠,𝑚𝑖𝑛 = 𝑚𝑎𝑥 [ 𝑓𝑦𝑘 ]
0.0013 ∗ 𝑏 ∗ 𝑑
In this way, the required reinforcement for flexure design is calculated. The
same sets of rules are applied to design this structure. The calculation for
this building can be found in Appendix 1.
After calculation the design shear force is calculated using given formula
below for a round column
𝜋 𝑑𝑐𝑜𝑙 2
𝑉𝐸𝑑 = 𝑝𝐸𝑑 [𝑏𝑓 2 − ∗ ( + 2𝑑) ]
4 2
47
During the design of the beam, there were some challenges as RSA was
unable to design delta beam because of holes in the geometry. However,
the cross section of delta beam was designed from the section definition
tab in RSA. Instead of checking the capacity of beam via software the
capacity was checked from the Peikko’s standard pre-defined capacity.
Only the maximum moment and shear on the beam were obtained from
the software while shear resistance and moment resistance were checked
through a manual calculation.
48
For slab design, it was not required to check the calculation via software
because the strength of a hollow core slab was known which was used to
check if the applied critical load exceeds the capacity. For the foundation
design, piles were used because of inadequate load bearing capacity of the
soil. Since RSA doesn’t have the features to design piles,it was abandoned.
However, punching capacity of the foundation was checked and due to
sufficient height of the pad foundation, there was no need for punching
reinforcement. RSA was unable to calculate the reinforcement for
punching shear even if there was punching. It needs to be calculated by
manually.
REFERENCES
49
Bond, A., Harrison, T., Narayanan, R., Brooker, O., Moss, R., Webster, R., Harris, A.
(2006). How to design concrete structure using Eurocode 2. CCIP publications.
Narayanan, R., Goodchild, C. (2006). Concise Eurocode 2. The Concrete Centre and
British Cement Association.
SFS - EN1990 Eurocode (2002,2005). Basis of structural design. SFS Online. SFS Online.
Retrieved 26 August 2017 from https://online.sfs.fi
SFS - EN1991-1-1 Eurocode (2002). Actions on structures. Part 1-1: General actions.
Densities, self-weight, imposed loads for buildings. SFS Online. SFS Online. Retrieved 26
August 2017 from https://online.sfs.fi
SFS - EN1991-1-3 Eurocode (2003). Actions on structures. Part 1-3: General actions.
Snow loads. SFS Online. SFS Online. Retrieved 26 August 2017 from https://online.sfs.fi
SFS - EN1991-1-4 Eurocode (2005). Actions on structures. Part 1-4: General actions.
Wind actions. SFS Online. Retrieved 26 August 2017 from https://online.sfs.fi
SFS - EN1992 Eurocode (2004). Design of concrete structures. Part 1-1: General rules and
rules for buildings. SFS Online. Retrieved 26 August 2017 from https://online.sfs.fi
50
Appendix 1
LOADS ON THE STRUCTURE
51
52
kN
s k = 2.5
2
m
Characteristics snow load on the ground
Exposure coefficient
Ce = 1 Normal topography
Thermal Coefficient
Ct = 1
53
s = 0
Because α <15
Snow load shape coefficient at zone A due to projected structure
Coefficient b1
b1 = 7.06m
Coefficient b2
b2 = 9.04m
Height of projection
H = 3.2m
Coefficient b1
b1 = 7.06m
Coefficient b2
b2 = 6.6m
Height of projection
H = 3.2m
55
Drifted length
ls = 2 H = 6.4m
Snow load on zone A
kN
s A = wA Ce Ct s k = 6.289
2
m
Coefficient b1
b1 = 9.1m
Coefficient b2
b2 = 4.6m
Height of projection
H = 3.2m
Drifted length
ls = 2 H = 6.4m
s = 0
Because α <15
Snow load shape coefficient at zone D due to Tall structure
Weight density of snow
kN
= 2
3
m
Coefficient b1
b1 = 51m
Coefficient b2
b2 = 22m
Height of projection
H = 3.5m
1 = 0.8
Drifted length
ls = 2 H = 7m
Snow load on zone D
kN
s D = wD Ce Ct s k = 7
2
m
Snow load on zone E
kN
s E = 1 Ce Ct s k = 2
2
m
Combined snow load
Snow load on top of projected roof
kN
s proof = 2
2
m
Total snow load due to tall Building
kN
( 7 − 2)
2
m kN
x = ( 1.7 + 2.65)m = 3.107
7m 2
m
Snow load on shaded region
kN kN 1 kN kN
2.45m 2 + 4.35m 2 + 4.35m 3.107 = 20.358
2 2 2 2 m
m m m
Total snow load due to projection
Line load
kN kN
5.33 4.15m = 22.12
2 m
m
kN kN
6.28 4.15m = 26.062
2 m
m
59
kN kN
2 4.15m = 8.3
2 m
m
Total load on shaded region of zone F
kN
5.35 2.65m
2
m kN
x = = 2.215
6.4m 2
m
snow load on shaded region of zone F
kN 1 kN kN
2.65m 2.215 + 2.65m ( 5.35 − 2.215) = 10.024
2 2 2 m
m m
Combined load on Grid 3-3
kN kN
( 8.3 + 20.35) = 28.65
m m
kN kN
( 22.12 + 20.35) = 42.47
m m
kN kN
( 26.06 + 20.35) = 46.41
m m
60
z = 9.5m h b
Reference height
61
m
Fundamental value of basic wind velocity vb0 = 21
s
Direction factor Cdir = 1
Cseason = 1
Season factor
m
Basic velocity of wind vb = vb0 Cdir Cseason = 21
s
z0 = 0.3
Roughness height
z0ii = 0.05
Factor zoii
0.07
z0
Kr = 0.19 = 0.215
Terrain factor
z0ii
Cr = Kr ln
z
Terrain roughness factor = 0.744
z0 m
C0 = 1
Orography factor
m
vm = Cr C0 vb = 15.629
Mean wind velocity s
kg
Density of air = 1.25
3
m
Factor K1 K1 = 1
m
v = Kr vb K1 = 4.523
Standard deviation of turbulence s
v
Iv = = 0.289
Turbulence intensity vm
b = 22m
Crosswind dimension
d = l = 21m
Depth of structure h
= 0.452
d
Ratio of h and d
e = min( b 2 h ) = 19m
Length parameter e
e
= 3.8m
Length of zone A 5
4
e = 15.2m
Length of zone B 5
d − e = 2m
Length of zone C
63
For,
h
= 0.452
d
For,
h
= 0.452
d
e
= 4.75m
Length of Zone F on crosswind direction 4
e
= 1.9m
Length of Zone F on depth direction 10
e
= 1.9m
Length of Zone G on depth direction 10
e
= 9.5m
2
65
Length of Zone F on crosswind direction
2e
= 7.6m
Length of Zone H on depth direction 5
e
d − = 11.5m
Length of Zone I on depth direction 2
kN
weC = q p ( −0.5) = −0.231
Zone C 2
m
kN
weD = q p ( 0.727) = 0.336
Zone D 2
m
kN
weE = q p ( −0.354) = −0.164
Zone E 2
m
kN
weF = q p ( −1.8) = −0.831
Zone F 2
m
kN
weG = q p ( −1.2) = −0.554
Zone G 2
m
kN
weH = q p ( −0.7) = −0.323
Zone H 2
m
kN
weI = q p ( 0.2) = 0.092
Zone I 2
m
66
Cs = 1 Cd = 1
Structural factor
Net pressure ( )
P Cpe10 Cpi = Cs Cd qp Cpe10 − qp Cpi
kN
P( −1.2 0.2) = −0.647
Zone A 2
m
kN
P( −1.2 −0.3) = −0.416
2
m
kN
P( −0.8 0.2) = −0.462
Zone B 2
m
kN
P( −0.8 −0.3) = −0.231
2
m
kN
P( −0.5 0.2) = −0.323
Zone C 2
m
kN
P( −0.5 −0.3) = −0.092
2
m
kN
P( 0.727 0.2) = 0.243
Zone D 2
m
kN
P( 0.727 −0.3) = 0.474
2
m
kN
P( −0.354 0.2) = −0.256
Zone E 2
m
67
kN
P( −0.354 −0.3) = −0.025
2
m
kN
P( −1.8 0.2) = −0.924
Zone F 2
m
kN
P( −1.8 −0.3) = −0.693
2
m
kN
P( −1.2 0.2) = −0.647
Zone G 2
m
kN
P( −1.2 −0.3) = −0.416
2
m
kN
P( −0.7 0.2) = −0.416
Zone H 2
m
kN
P( −0.7 −0.3) = −0.185
2
m
kN
P( 0.2 0.2) = 0
Zone I 2
m
kN
P( 0.2 −0.3) = 0.231
2
m
68
69
Largest reaction at A
STR 6.10a
1.35 KFI GkA = 708.237kN
Largest reaction at B
STR 6.10a 3
1.35 KFI GkB = 1.587 10 kN
Largest reaction at C
QkCsnow = 143.08kN
Maximum support reaction at C from snow load
STR 6.10a 3
1.35 KFI GkC = 1.375 10 kN
Largest reaction at D
71
Combination factor ψ
= 0.7
STR 6.10a
1.35 KFI GkD = 966.006kN
Largest reaction at E
QkEsnow = 59.17kN
Maximum support reaction at E from snow load
QkAsnow = 98.96kN
Support reaction at A from snow load
Largest reaction at A
Minimum reaction at B
QkBsnow = 172.10kN
Support reaction at B from snow load
Minimum reaction at C
QkCsnow = 143.08kN
Support reaction at C from snow load
Minimum reaction at D
QkDsnow = 135.86kN
Support reaction at D from snow load
Minimum reaction at E
GkE = 385.81kN
Support reaction at E from permanent action
QkEsnow = 59.17kN
Support reaction at E from snow load
QkEimposed = 0kN
Minimum support reaction at E from imposed load
= 0.7
Combination factor ψ
Column Geometry
Diameter of column
dc = 400mm
Clear length of the column
lc = 5000mm
Concrete details
Characteristics strength of concrete
N
fck = 30
2
mm
Partial safety factor for concrete
c = 1.5
Coefficient α .cc
cc = 0.85
Maximum aggregate size
dg = 20mm
Design strength of concrete
fck N
fcd = cc = 17
c 2
mm
Link diameter
link = 8mm
Axial load and bending moments from frame analysis
Design axial load
NEd = 2121.20kN
The moment can be ignored because of small values.
Minimum concrete cover check
76
conservative factors
f = 1
Condition 3
Effective length
l0 = f lc = 5m
Column slenderness
4
dc 9 4
I = = 1.257 10 mm
4 2
Second moment of area of column
Radius of gyration
I
iy = = 0.1m
Ac
Slenderness ratio
l0
= = 50
iy
Slenderness limit for buckling about y axis
77
Factor A
A = 0.7
Factor B
B = 1.1
Factor C
C = 0.7
Relative normal force
NEd
n = = 0.993
A c fcd
Slenderness Limit
20 A B C
lim = = 10.818
n
lim Second order must be considered
Local second order bending moment about y-axis
Relative humidity
RH = 50
Column perimeter in contact with atmosphere
u = d = 1.134m
Factor α 1
0.7
1 = 35MPa = 0.944
f
cm
Factor α 2
0.2
2 = 35MPa = 0.984
f
cm
Relative humidity factor
1−
RH
RH = 1 + 1 2 = 1.778
100
0.1 200
3
Concrete strength factor
1M Pa
fcm = 16.8 = 2.725
fcm
Factor β
fck
= 0.35 + − = 0.167
200M Pa 150
Creep factor
(
K = max 1 1 + ef = 1.256 )
Curvature distribution factor
c = 10
Factor e2
2
fyd l0
e2 = Kr K = 14.291 mm
Es ( 0.45 d ) c
0.5 1 +
1
m = =1
m
−3
i = 0 h m = 4.472 10
The imperfection causes eccentricity
i l0
e0 = = 11.18 mm
2
The first order design moment
4
M0Ed = NEd e0 = 2.372 10 J
79
= 0.2
A c fcd 2
A sreq = = 982.69 mm
fyd
Choose 10 T12
NEd 2
A smin = max 0.1 0.002 A c = 487.876 mm
fyd
3 2
A smax = 0.04 A c = 5.027 10 mm
Selection of link
Minimum diameter
linkmin = max(6mm 0.25 ) = 6 mm
80
Link diameter
link = 8mm
Anchorage with a bend
Anchorage length
( )
max 10 link 70mm = 80 mm
Reduction of link
Sclred = 0.6 Sclmax = 144 mm
Choose
1 Level:
• Name : Level +5,00
• Reference level : 0,00 (m)
• Concrete creep coefficient : p = 1,54
• Cement class :N
• Environment class : XC1
• Structure class : S4
2 Column: Column2
2.1 Material properties:
• Concrete : C30/37
• fck = 30,00 (MPa)
Unit weight : 2501,36 (kG/m3)
Aggregate size : 20,0 (mm)
• Longitudinal reinforcement: : A500HW
• fyk = 500,00 (MPa)
Ductility class :C
• Transversal reinforcement: : A500HW
• fyk = 500,00 (MPa)
2.2 Geometry:
2.2.1 C
Diameter = 400,0 (mm)
2.2.2 Height: L = 5,00 (m)
2.2.3 Slab thickness = 0,00 (m)
2.2.4 Beam height = 0,00 (m)
2.2.5 Cover = 25,0 (mm)
2.4 Loads:
ea = 0,0 (mm)
Ma = N*ea = 0,00 (kN*m)
MEdmin = 42,42 (kN*m)
M0Ed = max(MEdmin,M0 + Ma) = 42,42 (kN*m)
2.5.2 Reinforcement:
2.6 Reinforcement:
Main bars (A500HW):
• 12 12 l = 4,98 (m)
3 Material survey:
• Concrete volume = 0,63 (m3)
• Formwork = 6,28 (m2)
• Steel A500HW
• Total weight = 67,36 (kG)
• Density = 107,21 (kG/m3)
• Average diameter = 10,5 (mm)
• Reinforcement survey:
Appendix 2
Floor plans
85
86
87