Seismic Load Definition in Staad - Pro
Seismic Load Definition in Staad - Pro
The seismic load generator can be used to generate lateral loads in the X and Z directions only. Y is the
direction of gravity loads. This facility has not been developed for cases where the Z axis is set to be the
vertical direction (See the SET Z UP command in TR.5 Set Command Specification).
General Format
DEFINE IS1893 2016 ( ACCIDENTAL ) LOAD
1893-2016-spec
wall-definitions
weight-data
Refer to Common Weight Data for information on how to specify structure weight for seismic loads.
where
Paramete Description
r
ZONE f1 Seismic zone factor. Refer to Table 3 (Clause 6.4.2) of IS:1893 (Part 1)-2016.
RF f2 Response reduction factor. Refer Table 9 (Clause 7.2.6) of IS: 1893 (Part 1) -
2016.
1 = hard soil
2 = medium soil
3 = soft soil
Note: Use either SS orSA to specify site conditions. If both parameters are
specified, SS is ignored.
Paramete Description
r
ST f5 Structure type of the seismic-resisting system. The program will calculate
natural period as per Clause 7.6.2 of IS:1893(Part 1)-2016.
Note: *ST 4 requires that wall data be entered in order to determine the natural
period.
This should be a value between 0 (zero) and 1.0, inclusive. For example, 7%
damping should be specified as 0.07.
PX f7 Optional period of structure (in sec) in X direction. If this is defined this value
will be used to calculate S /g for generation of seismic load along X direction.
a
PZ f8 Optional period of structure (in sec) in Z direction. If this is defined this value
will be used to calculate Sa/g for generation of seismic load along Z direction.
DT f9 Depth of foundation below ground level. It should be defined in current units.
If the depth of foundation is 30 m or more, the value of A is taken as half the
h
value obtained. If the foundation is placed between the ground level and 30 m
depth, this value is linearly interpolated between A and 0.5A . Refer to Clause
h h
GL f10 Y coordinate of ground level (or global Z coordinate for SET Z UP). A
reduced lateral force is applied to levels below this height, per Clause 6.4.5.
Note: Use either DT or GL to specify foundation depth. If both parameters are
specified, DT is ignored. See Node d below.
HT f13 Height of the building. Refer Clause 7.6.2 (a) and Fig. 5 of IS 1893 2016
DX f14 Base dimension of the building in X direction at the plinth level. Refer Clause
Paramete Description
r
7.6.2(b) or (c)
DZ f15 Base dimension of the building in Z direction at the plinth level. Refer Clause
7.6.2(b) or (c)