2.

0 MW

GENSET NO.2 GENSET NO.1


JGS - 320

G G
2.0 MW 1.0 MW

BTD - 4 BTD - 3
1250 KVA 1250 KVA 4000 A 4000 A

4000A 4000A
TP ACB TP ACB
100KA 100KA
2000A 2000A MOTORIZED MOTORIZED
TP ACB TP ACB
65KA 100KA

BUS BAR SECTION-D BUS BAR SECTION-C


Connected Load = 930 KW Connected Load = 4962 KW
LT - 3

Running Load = 748 KW LT - 1 ENERGY


2000A Running Load = 3424 KW
ANALYZER
TP ACB
2000A TPN & E Isc=65 KA Isc=100 KA 2500A TPN & E 100 KA Isc=100 KA 6000A TPN & E

BUS COUPLER
500A 400A 630A
1000A 400A 630A 400A 630A 400A 100A 630A 630A 4000A 4000A 150A
TP
TP TP TP TP TP TP TP TP TP TP TP TP TP TP
LBS
LBS MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB ACB ACB MCCB MCCB

A A

ENERGY ENERGY ENERGY ENERGY ENERGY ENERGY ENERGY ENERGY


ENERGY ENERGY ENERGY
ANALYZER ANALYZER ANALYZER ANALYZER ANALYZER ANALYZER ANALYZER ANALYZER
ANALYZER ANALYZER ANALYZER

2500 KVA 2500 KVA


CL-247 KW CL-247 KW CL-275 KW CL-170 KW CL-35 KW
SPARE SPARE
RL-198 KW RL-198 KW RL-244 KW RL-140 KW RL-28 KW
Soft Cotton Soft Cotton Colony Power House Power House
Cleaning Line Cleaning Line Aux. Aux.
&
MISCELLENOUS
LOAD 4000A 4000A 4000A 4000A
TP ACB TP ACB TP ACB TP ACB
CL-138 KW CL-138 KW CL-10 KW CL-260 KW CL-2177 KW CL- 2080 KW 85KA 85KA 85KA 85KA
RL-111 KW RL-111 KW RL-10 KW RL-133 KW RL-1468.5 KW RL-1438.5 KW

P.F.I LIGHTING P.F.I Chiller Spinning 2 Spinning 1


Hard Waste Hard Waste
650KVAR 350KVAR &
Chiller Aux.

LT - 2
4000A
TP ACB
BTD - 2 BTD - 1
4000 A 4000 A
85 KA

BUS COUPLER

4500A TPN & E

Running Load = 1468.5 KW


Connected Load = 2177 KW
BUS BAR SECTION-B
1250A 400A 2500A 1600A 2500A 2000A 300A 200A 1250A

4500A TPN & E


400A

Running Load = 1438.5 KW


400A

Connected Load = 2080 KW


BUS BAR SECTION-A
TP TP TP TP TP TP TP TP TP TP TP
LBS MCCB MCCB ACB ACB ACB ACB MCCB MCCB MCCB LBS

A A A
ENERGY ENERGY ENERGY ENERGY ENERGY
ENERGY
ANALYZER ANALYZER ANALYZER ANALYZER ANALYZER
ANALYZER

Isc=65 KA

Isc=65 KA
CL-150 KW CL-760 KW CL-1170 KW CL-125 KW
SPARE RL-135 KW RL-543 KW RL-760.5 KW RL-93.75 KW SPARE

Compressor AC Open End Open End MISCELLENOUS


+ Rotor LOAD
blowroom Filter Phase 2
+
Card Filter

CL-1170 KW CL-807 KW CL-75 KW


RL-760.5 KW RL-558 KW RL-56.25 KW
Open End LIGHTING
P.F.I AC Open End P.F.I
Rotor
750KVAR P2 + Drawing 700KVAR
Frames +
Drawing AC +
Cards + Blow
room AC