Professional Documents
Culture Documents
IEC Healthcare-2C 300-Bed Hospitals - Electrical Reference Architecture Guide ESXP2RA5EN (March 2019)
IEC Healthcare-2C 300-Bed Hospitals - Electrical Reference Architecture Guide ESXP2RA5EN (March 2019)
300-Bed Hospitals
IEC Electrical Reference Architecture Guide
schneider-electric.com/ecostruxure
Related Documentation
Digital Applications for Large Buildings & Critical Facilities - IEC design guide
Ref: ESXP2G001EN
https://www.schneider-electric.com/tools/registration/promo/ww/en/countryselect/A09116
• Insulation Monitoring
• Electrical Distribution Monitoring & Alarming
• Backup Power Testing
• Energy Usage Analysis
• Power Factor Correction
DC DC
AC AC
N +1 diesel
Generators
Main LV Main LV
switchgears switchgears
Centralised
UPS (N+1)
Operating
Ward feeder
Isolated
Smart
Panel
Healthcare
See Healthcare 300-Bed IEC Hospital “Power” Single Line Diagram
Acti9 Acti9
• Group 2 medical location Smartlink SI B
Smartlink SI B
The main solution provided to protect the Main Emergency
Isolated Smart Panel
patient from electric shock is managed through supply supply
the Insulation neutral system (IT) as
recommended in IEC 60364-7-710.
Away from the patient environment, in the
operating room and intensive care unit the TNS
network is well protected by the RCD 30 mA –
SI model for load sensitivity and the RCBO
compact model. RCD protection must be
installed for all TNS sockets and lighting TNS
systems as a minimum.
Lastly, to complete the electrical protection
design, the IEC standard recommends
installing the Isolated Smart Panel less than (x6)
25 m from the IT sockets.
• Group 1 medical location
The RCD 30 mA SI model is also recommended Acti9
Smartlink SI B
due the connected electronic devices. 24
Vdc
Vigilohm
• Group 0 medical location and other IM20-H
The RCD 300 mA /RCD 30 mA type B is Insulation
Monitoring
recommended for the application including Device
(x12)
3-phase motors.
• Isolated Smart Panel
Vigilohm
The design of the distribution board for the IMD IFL12H
Operating room and Intensive care unit is 100% Insulation Fault Locator
IEC standard-compliant: Acti9
Smartlink Modbus RS485
• IT and TNS network
See Healthcare 300-bed IEC Hospital "Distribution boards" - Isolated Smart Panel folio
• Double incomers with ATS 30 ms transfer
performance
• Total breaker discrimination
• Isolated transformer and monitoring system
• Insulation fault location
• Monitoring system.
See Digital applications for Large Buildings & Critical Facilities
- Part 1 Insulation Monitoring
Operating Ward dashboard
• Sustainability reporting
Greenhouse gas reporting is based on
equivalent tonnes of CO2 emissions,
saved trees, km driven, etc.
The Building Energy Rating is directly linked
to energy consumption per square meter.
Building Energy Rating dashboard Energy Equivalency gadget
Carbon emissions are reported and segmented
by source, scope and pollutant and can be
indexed to various metrics you specify.
See Digital applications for Large Buildings & Critical Facilities
- Part 1 Greenhouse Gas reporting
The Generator capacity report checks the Generator Load Summary report
redundancy performance depending on load
change. Load discrimination (Groups 2,1 and
0) is used to inform key decision of whether
to buy a new Generator or reinforce load
shedding automation.
• UPS monthly test:
The IEC 60364-7-710 standard recommends
monthly testing of the endurance UPS backup
system on battery within minimum 50%
connected load for 15 min. By incorporating an
auto test function, the Galaxy VS fulfills this
testing requirement.
In addition to this global auto test facility, a Lithium
battery system can identify precisely which cell
of the battery has failed when this occurs.
This optional accurate diagnosis reinforces
energy availability performance and
UPS Monthly Test report
operational efficiency.
• Operating room Isolated power report
For each Vigilohm IM20-H in the room,
the report shows:
•Impedance graph - Displays a comparison
of impedance measurements with the
impedance threshold. The impedance
threshold is a blue line and the actual
measurements are shown as a green line.
A red line shows occasions when impedance
has dropped below the threshold.
•Transformer load graph - Displays a
comparison of transformer load
measurements to the load threshold.
The threshold is a blue line and the actual
measurements are shown with a green line.
A red line shows occasions when the load
has risen above the threshold.
•Events table - Shows information for each
event that occurred in the date range.
•Data log table (optional) - Contains
measurements for impedance, load, and Isolated Power report
temperature in the selected date range. Red
values indicate measurements over the limit.
IEC Electrical Reference Architecture Guide 11
Schneider Electric Industries SAS
March 2019
ESXP2RA5EN