TOP VIEW

D C

concrete or
surge steel column
distribution fuse
arrester
transformer cut-out #6 solid
copper wire
1500 min.

steel
(e.g. c-channel)
500 min.
300 min.
grounding rod &
compression
secondary wires connector
4000

fence

concrete pad

1/2" stainless bolt & cable tray metering vault


clamp/1-bolt guy

door
B service entrance B'
pedestal meter

5000
A A'

D' C'

NOTE:
• Applicable for Distribution Transformer Bank: 3-100 kVA and below that have Secondary Instrument Rated Metering.
• The customer shall provide the secondary wires and its accessories but it is optional for the DU to provide the secondary banking wires only or all the
secondary wires(including its accessories) going to the service entrance pedestal of the customer when the customer could not provide the required
standard materials.
• Units are in millimeter (mm).

4M X 5M TRANSFORMER PAD FOR3-100 KVA AND BELOW


OUTDOOR ELEVATED PAD MOUNTED TRANSFORMER BANK
WITH SECONDARY INSTRUMENT RATED METERING

Drawn by: ABesana Noted by: ACapul/WJGo


EPAD 4x5-S
Checked by:HBolido/JJayme Approved by: RCLucero