Viesmann: Vitotronic 300-K
Viesmann: Vitotronic 300-K
Datasheet
Part numbers and prices: see the respective boiler pricelist
Vitotec folder, register 18
File in:
Application
Weather-compensated, digital cascade and heating circuit control & In conjunction with the Vitotronic 100, type GC1:
units: – For two-stage or modulating burners
& For multi-boiler systems with up to four boilers – For boilers with an integral Therm-Control start-up system,
& With sequential boiler strategy systems with a shunt pump or constant return temperature
& For one system circuit and up to two heating circuits with mixer control
(a maximum of 32 Vitotronic 200-H heating circuit control units & With capability to communicate via LON BUS (LON communica-
can be connected via the LON BUS) tion module and terminators are part of the standard delivery)
& With cylinder temperature control or control of a cylinder primary & With integral diagnostic system
system with a mixer assembly
5822 223-6 GB
– Plug the connectors directly into the front of the open control & Automatic summer/winter time changeover
unit & Automatic function for DHW heating and DHW circulation pump
– Connection of three-phase consumers via additional contac- & Time, day and standard switching times for central heating,
tors DHW heating and the DHW circulation pump are factory-set
Programming unit: & Switching times are individually programmable, i.e. up to four
& Rotary selector for the temperature in standard mode Setting heating programs
& Keys: The heating system frost protection (see frost protection function)
– Temperature for reduced mode applies to all heating programs.
– Program selection You can select the following heating programs with the program
– Holiday program keys:
– Party and economy mode & Heating and DHW
– Heating curves for the system flow temperature and the flow & Standby mode
temperature of the heating circuits with mixer Optional external changeover of heating program for all heating
– Heating circuit selection circuits together or for selected heating circuits only.
of a multi-boiler system with up to four boilers with the temperature drops below approx. +1 °C, i.e. the heating circuit
Vitotronic 100, type GC1, (modulating) and the flow temperature pumps will be started and the flow temperature will be main-
of the heating circuits with mixer tained at a minimum temperature of 10 °C.
& Control of the Vitotronic 100, type GC1, to effect the control of & The frost protection function will be switched OFF, when the out-
the boiler in accordance with a boiler sequence strategy (freely side temperature exceeds approx.+3 °C, i.e. the heating circuit
selected) pumps will be switched OFF.
& Electronic maximum and minimum temperature limit
– Level: −13 to 40 K
Specification
Cable length 5.8 m, fully wired
Protection IP 32 to EN 60529;
safeguard through appro-
priate design and instal-
lation
Outside temperature sensor Permissible ambient temperature
Installation location: – during operation 0 to +120 °C
& North or north-western wall of the building – during storage and transport -20 to +70 °C
& 2 to 2.5 m above the ground, for multi-storey buildings in the
(copper)
& Never route this lead immediately next to 230/400 V cables
Specification
Lead length 5.8 m, fully wired
Protection IP 32 to EN 60529; safe-
guard through appropriate
design and installation
Permissible ambient temperature
– during operation 0 to +90 °C
Specification – during storage and transport -20 to +70 °C
Protection IP 43 to EN 60529;
safeguard through appro-
priate design and instal- LON communication module
lation Integral PCB for data exchange with the Vitotronic 100, type GC1,
Permissible ambient temperature dur- Vitotronic 200-H, Vitocom 300 and for connection to a higher level
ing operation, storage and transport -40 to +70 °C building management system.
Terminator (2 pce.)
To terminate the LON BUS at the first and the last control unit.
Dimensions
A Vitotronic 300-K
B Mounting panel
Delivered condition
Vitotronic 300-K
Type MW1 Heating system with heating circuit with mixer
Part no. 7248 233 An extension kit (accessories) is required for each heating circuit
& Programming unit with mixer.
& LON communication module with two terminators Because of the low return temperatures associated with conden-
& Outside temperature sensor sing boilers, install only three-way mixers in the heating circuits.
& Flow temperature sensor
Specification
Cable length 5.8 m, fully wired
Specification Protection IP 32 to EN 60529; safe-
Cable length 4.2 m, fully wired guard through appropri-
Rated voltage 230 V~ ate design and
Rated frequency 50 Hz installation
Power consumption 4W Permissible ambient temperature
Protection class II – during operation 0 to +120 °C
Protection IP 42 to EN 60529; safe- – during storage and transport -20 to +70 °C
guard through appropri-
ate design and
installation
Mixer motor
Part no. 7450 657 Specification
The mixer motor is mounted directly onto the Viessmann mixer DN
20 to 50 and R ½" to 1¼". Rated voltage 230 V~
With system plug. Rated frequency 50 Hz
For wiring on site. Power consumption 4W
Protection class II
Protection IP 42 to EN 60529; safe-
guard through appropri-
ate design and
installation
Permissible ambient temperature
– during operation 0 to +40 °C
– during storage and transport -20 to +65 °C
Torque 3 Nm
Runtime for 90° ∢ 120 s
DN 40 and 50, without system plug and connecting cable this folder.
& Part no. Z004344
DN 65 to 100, without system plug and connecting cable
Plug sÖ
Part no. 7415 056
for heating circuit pump.
Plug gS
Part no. 7415 057
for mixer motors.
Sensor well
Part no. 7819 693
R ½" x 200 mm
For the cylinder temperature sensor, part of the standard delivery
of Viessmann DHW cylinders.
Immersion thermostat
5822 223-6 GB
Specification
Contact thermostat
Part no. 7151 729 Specification
May be used as a maximum temperature limiter for underfloor
heating systems (only in conjunction with metallic pipes). Cable length 4.2 m, fully wired
The temperature limiter is installed into the heating flow and Setting range 30 to 80 °C
switches the heating circuit pump OFF in case of excessive flow Switching differential max. 14 K
temperature. Breaking capacity 6(1.5) A 250V~
Setting scale inside the casing
DIN reg. no. DIN TR 77703
or
DIN TR 96803
or
DIN TR 110302
Information regarding room temperature hook-up (RS function) for remote control units
Never activate the RS function for underfloor heating circuits
(inertia).
Vitotrol 200
Part no. 7450 017 Installation in the main living room on an internal wall opposite
KM BUS subscriber radiators. Never install inside shelf units, recesses, immediately
The Vitotrol 200 remote control regulates the heating program for by a door or heat source (e.g. direct sunlight, fireplace, TV set,
one heating circuit and the required set room temperature in stan- etc.).
dard mode, from any room in the house. The integral room temperature sensor captures the actual room
The Vitotrol 200 is equipped with backlit heating program selec- temperature and effects any necessary correction of the flow tem-
5822 223-6 GB
tion keys as well as a party and economy key. perature as well as a rapid heat-up at the start of the heating
The fault display shows faults on the control unit. operation (if appropriately programmed).
WS function: Connection:
Installation anywhere in the building.
RS function:
Vitotrol 300
Part no. 7179 060
KM BUS subscriber
The Vitotrol 300 remote control regulates the required set room
temperature for one heating circuit in standard and reduced mode,
the heating program and the switching times for central heating,
DHW heating and the DHW circulation pump.
The Vitotrol 300 provides a backlit display as well as backlit heat-
ing program keys, a party and economy key, automatic summer/
winter time changeover, keys for holiday program, day and time.
WS function:
Installation anywhere in the building.
RS function:
Installation in the main living room on an internal wall opposite
radiators. Never install inside shelf units, recesses, immediately
by a door or heat source (e.g. direct sunlight, fireplace, TV set,
etc.). Specification
The integral room temperature sensor captures the actual room Power supply via KM BUS
temperature and effects any necessary correction of the flow tem- Power consumption 0.5 W
perature as well as a rapid heat-up at the start of the heating Protection class III
operation (if appropriately programmed). Protection level IP 30 to EN 60529;
Connection: safeguard through appro-
& 2-core lead, length max. 50 m (even if connecting several priate design and instal-
remote control units) lation
& Never route this lead immediately next to 230/400 V cables Permissible ambient temperature
& LV plug as standard delivery – during operation 0 to +40 °C
– during storage and transport −20 to +65 °C
Set room temperature range
– for standard mode 10 to 30 °C
adjustable from
3 to 23 °C or
17 to 37 °C
– for reduced mode 3 to 37 °C
Specification
(copper)
& Never route this lead immediately next to 230/400 V cables.
Function extension 0 to 10 V
Part no. 7174 718
KM BUS subscriber
Including cable (3.0 m long) and plugs fÖ and aVG.
& To default an additional set flow temperature via a 0 to 10 V
to a lower speed
Contactor relay
Part no. 7814 681 Specification
With 4 N/C and 4 N/O contacts.
Coil voltage 230 V~/50 Hz
Rated current (I th) 16 A
& Type FE1 – for type FA3 with TAE socket, code "6N"
Part no. 7143 430 – for type FI1 with RJ45 socket (ISDN)
& Type FI1 & LON communication module (accessories)
& For remote reporting, remote monitoring and scanning of faults between the Vitotronic and Vitocom 300 (7.0 m long)
and/or data points via the internet & Power supply unit * 1
& For remote switching, remote setting of parameters and codes & Power cable from the power supply unit to the standard module
for heating systems via the internet & Standard module * 1 (with 8 digital inputs, 2 digital outputs and 2
sensor inputs):
Configuration via: – Type FA1: with integral analog modem and connecting cable
& Vitosoft 200, type LNR via Optolink for telephone socket TAE 6N (2.0 m long)
& Vitodata 300 – Type FE1: with connecting cable with RJ45 plug and sub-D
Data points provided by the heating control unit are hooked up to plug (9 PIN) as a modem connecting cable (GSM modem
the Vitocom 300 via LON. Additional settings can be made during accessories) or a suitable external ISDN terminal adaptor
commissioning, if system-specific special functions, such as mon- – Type FI1: with integral ISDN modem and connecting cable
itoring limits, are required. with RJ45 plug for ISDN socket (2.0 m long)
Fault messages are reported to the Vitodata 300 server via the Accessories:
internet. These messages are then transferred by the
Vitodata 300 server to the following communication services: Accessories Part no.
& PC with internet access
Wall mounting enclosure for the installation of the
& Fax
Vitocom 300 module, if no control panel or electrical
& SMS to D1/D2/E-Plus/O [or other] mobile phones
2 distribution panel is available
& E-mail
2 rows 7143 434
& Voicemail
3 rows 7143 435
5822 223-6 GB
*1
Mounting rail installation TS35 to DIN EN 50 022, 35 x 15 and 35 x 7.5.
Tested quality