VIESMANN VITOTRONIC 300-K

Weather-compensated, digital cascade control unit

Datasheet
Part numbers and prices: see the respective boiler pricelist
Vitotec folder, register 18
File in:

VITOTRONIC 300-K Type MW1

For operation of multi-boiler systems with up to four boilers


with a Vitotronic 100, type GC1, with modulating boiler
water temperature.
For heating systems with one system circuit and up to 2
heating circuits with mixer (accessories).
With cylinder temperature control or control of a cylinder
primary system with mixer assembly.
With integral diagnostic system.
Programming unit with backlit plain text display.
External equipment is connected via system plugs.

5822 223-6 GB 4/2007


Benefits
& Standard easy operation: & Quick installation, commissioning and maintenance due to the
– Different control levels for system user and heating contractor Rast-5 plug-in system, modular function modules, easy access
– Easy to read through backlit, plain text displays and integral diagnostic system
– Backlit operating mode selector keys and heating circuit keys & Optolink laptop interface for scanning and setting of parameters
– Easy setting of switching times with a laptop
– Digital time switch for individual and 7-day programs. When & Standardised LON BUS for complete integration into building
time programs are changed, the set times for DHW heating management systems
and DHW circulation pump can be automatically matched & Remote monitoring in conjunction with Vitocom 300 TeleControl
– Plug & Work function for automatic recognition and adaptation & For all common hydraulic connections and systems
of sensors and system accessories & Special control strategies for condensing or low temperature
– Automatic summer/winter time changeover boilers
& Program selection for screed drying back-up

Application

Weather-compensated, digital cascade and heating circuit control & In conjunction with the Vitotronic 100, type GC1:
units: – For two-stage or modulating burners
& For multi-boiler systems with up to four boilers – For boilers with an integral Therm-Control start-up system,
& With sequential boiler strategy systems with a shunt pump or constant return temperature
& For one system circuit and up to two heating circuits with mixer control
(a maximum of 32 Vitotronic 200-H heating circuit control units & With capability to communicate via LON BUS (LON communica-
can be connected via the LON BUS) tion module and terminators are part of the standard delivery)
& With cylinder temperature control or control of a cylinder primary & With integral diagnostic system
system with a mixer assembly

5822 223-6 GB

2 VIESMANN VITOTRONIC 300-K


Specification

Construction and function


Modular construction – Max. limit: 20 to 130 °C
The control unit comprises a standard unit, electronic modules – Min. limit: 1 to 127 °C
and a programming unit. – Differential temperature for heating circuits with mixer: 0 to
Standard unit: 40 K
& ON/OFF switch & Set DHW temperature range:
& Emissions test switch 10 to 60 °C, may be changed to 10 to 95 °C
& Optolink laptop interface

& Operation and fault displays Time switch


& Wiring chamber Digital time switch
– Connection of external equipment via a system plug & Day and week program, annual calendar

– Plug the connectors directly into the front of the open control & Automatic summer/winter time changeover

unit & Automatic function for DHW heating and DHW circulation pump

– Connection of three-phase consumers via additional contac- & Time, day and standard switching times for central heating,

tors DHW heating and the DHW circulation pump are factory-set
Programming unit: & Switching times are individually programmable, i.e. up to four

& With digital time switch switching periods per day


& Backlit display with plain text support Shortest switching interval: 10 minutes
& Adjustment and display of temperatures and codes Power backup: 5 years
& Fault message display

& Rotary selector for the temperature in standard mode Setting heating programs
& Keys: The heating system frost protection (see frost protection function)
– Temperature for reduced mode applies to all heating programs.
– Program selection You can select the following heating programs with the program
– Holiday program keys:
– Party and economy mode & Heating and DHW

– DHW temperature & DHW only

– Heating curves for the system flow temperature and the flow & Standby mode

temperature of the heating circuits with mixer Optional external changeover of heating program for all heating
– Heating circuit selection circuits together or for selected heating circuits only.

Functions Frost protection


& Weather-compensated control of the system flow temperature & The frost protection function will be switched ON if the outside

of a multi-boiler system with up to four boilers with the temperature drops below approx. +1 °C, i.e. the heating circuit
Vitotronic 100, type GC1, (modulating) and the flow temperature pumps will be started and the flow temperature will be main-
of the heating circuits with mixer tained at a minimum temperature of 10 °C.
& Control of the Vitotronic 100, type GC1, to effect the control of & The frost protection function will be switched OFF, when the out-

the boiler in accordance with a boiler sequence strategy (freely side temperature exceeds approx.+3 °C, i.e. the heating circuit
selected) pumps will be switched OFF.
& Electronic maximum and minimum temperature limit

& Demand-dependent heating circuit pump stop Summer mode


& Adjustment of a variable heating limit ("DHW only")
& Anti-seizing pump protection One or several burner(s) start(s), if the DHW cylinder needs to be
& Central fault message heated up (regulated by the cylinder temperature controller).
& Integral diagnostic system The respective lower boiler water temperature of each boiler is
& Adaptive cylinder temperature control unit with priority control maintained.
(heating circuit pump OFF, mixer closed)
& Auxiliary function for DHW heating (short-term heating to a Adjusting the heating curves (slope and level)
higher temperature) The Vitotronic regulates (weather-compensated) the system flow
& Control unit of a cylinder primary system with a regulated three- temperature and the flow temperature of the heating circuits with
way mixing valve mixer. For this, the system flow temperature is automatically
& Screed drying, for underfloor heating systems boosted by between 0 and 40 K higher than the currently required
set flow temperature (delivered condition 8 K).
The requirements of DIN EN 12831 for the heating load calcula- The flow temperature required to reach a specific room tempera-
tion are met. To reduce the heat-up load, the reduced room tem- ture depends on the heating system and the thermal insulation of
perature will be raised in case of low outside temperatures. The the building to be heated.
flow temperature will be raised for a limited time to reduce the Adjusting the heating curves matches the system flow tempera-
heat-up time after a setback period. ture and the flow temperature of the heating circuits with mixer to
According to the Energy Savings Order [Germany], the tempera- these operating conditions.
ture in each room must be individually controlled, e.g. through The upper flow temperature of the heating circuits with mixer is
thermostatic radiator valves. limited by the thermostat "R" and the electronic maximum tem-
perature limit of the Vitotronic 100, type GC1.
Control characteristics
& PI characteristics with three-point output

& Setting range for heating curves:

– Slope: 0.2 to 3.5


5822 223-6 GB

– Level: −13 to 40 K

VITOTRONIC 300-K VIESMANN 3


Specification (cont.)

Contact temperature sensor


To measure the common flow temperature of the multi-boiler sys-
tem.
Secured with a tie.

Specification
Cable length 5.8 m, fully wired
Protection IP 32 to EN 60529;
safeguard through appro-
priate design and instal-
lation
Outside temperature sensor Permissible ambient temperature
Installation location: – during operation 0 to +120 °C
& North or north-western wall of the building – during storage and transport -20 to +70 °C
& 2 to 2.5 m above the ground, for multi-storey buildings in the

upper half of the second floor Cylinder temperature sensor


Connection:
& 2-core lead, length up to 35 m with a cross-section of 1.5 mm 2

(copper)
& Never route this lead immediately next to 230/400 V cables

Specification
Lead length 5.8 m, fully wired
Protection IP 32 to EN 60529; safe-
guard through appropriate
design and installation
Permissible ambient temperature
– during operation 0 to +90 °C
Specification – during storage and transport -20 to +70 °C
Protection IP 43 to EN 60529;
safeguard through appro-
priate design and instal- LON communication module
lation Integral PCB for data exchange with the Vitotronic 100, type GC1,
Permissible ambient temperature dur- Vitotronic 200-H, Vitocom 300 and for connection to a higher level
ing operation, storage and transport -40 to +70 °C building management system.

Terminator (2 pce.)
To terminate the LON BUS at the first and the last control unit.

Specification, Vitotronic 300-K


5822 223-6 GB

Rated voltage 230 V~


Rated frequency 50 Hz
Rated current 6A
Power consumption 10 W

4 VIESMANN VITOTRONIC 300-K


Specification (cont.)

Protection class I Rated capacity of the relay outputs


Protection IP 20 D to EN 60529; sÖ Heating circuit pumps
safeguard through or
appropriate design Heat exchanger set
and installation or
Function Type 1B to EN 60 730- Switching output 4(2) A 230 V~
1 sA Cylinder primary pump 4(2) A 230 V~
Permissible ambient temperature sK DHW circulation pump 4(2) A 230 V~
– during operation 0 to +40 °C sL Shunt pump 4(2) A 230 V~
Installation in living gÖ Central fault message 4(2) A 230 V~
spaces or boiler rooms gS Mixer motor
(standard ambient or
conditions) Mixer motor constant return tem-
– during storage and transport -20 to +65 °C perature control
or
Motor – three-way mixing valve,
cylinder primary system 0.2(0.1) A 230 V~
Total 6 A 230 V~

Dimensions

A Vitotronic 300-K
B Mounting panel

Delivered condition

Vitotronic 300-K
Type MW1 Heating system with heating circuit with mixer
Part no. 7248 233 An extension kit (accessories) is required for each heating circuit
& Programming unit with mixer.
& LON communication module with two terminators Because of the low return temperatures associated with conden-
& Outside temperature sensor sing boilers, install only three-way mixers in the heating circuits.
& Flow temperature sensor

& Cylinder temperature sensor Heating system with underfloor heating


& Mounting panel An extension kit for one heating circuit with mixer is required for
& Bag with technical documentation the underfloor heating circuit.
The control unit will be delivered with one of the boilers of the Install a temperature limiter into the flow of the underfloor heating
multi-boiler system (see pricelist) and is mounted with a mounting circuit to limit the maximum temperature. Observe DIN 18560-2.
bracket either on the wall or on the side of the boiler. The underfloor heating circuit should not be regulated by a remote
control with room temperature hook-up.
Heating system with DHW cylinder
Order separately: Plastic pipework for radiators
& Circulation pump with check valve for regulating the cylinder We also recommend the installation of a temperature limiter to
temperature limit the maximum temperature of plastic pipes in heating circuits
or with radiators.
5822 223-6 GB

& Vitotrans 222 cylinder primary system with mixer assembly

VITOTRONIC 300-K VIESMANN 5


Accessories

Extension kit for a heating circuit with mixer


Part no. 7450 650 Permissible ambient temperature
Components: – during operation 0 to +40 °C
& Mixer motor with connecting cable – during storage and transport -20 to +65 °C
& Plug for the heating circuit pump and flow temperature sensor Torque 3 Nm
(contact temperature sensor) Runtime for 90 °∢ 120 s
The mixer motor is mounted directly onto the Viessmann mixer
DN 20 to 50 and R ½" to 1¼".
Flow temperature sensor (contact temperature sensor)
Mixer motor

Specification
Cable length 5.8 m, fully wired
Specification Protection IP 32 to EN 60529; safe-
Cable length 4.2 m, fully wired guard through appropri-
Rated voltage 230 V~ ate design and
Rated frequency 50 Hz installation
Power consumption 4W Permissible ambient temperature
Protection class II – during operation 0 to +120 °C
Protection IP 42 to EN 60529; safe- – during storage and transport -20 to +70 °C
guard through appropri-
ate design and
installation

Mixer motor
Part no. 7450 657 Specification
The mixer motor is mounted directly onto the Viessmann mixer DN
20 to 50 and R ½" to 1¼". Rated voltage 230 V~
With system plug. Rated frequency 50 Hz
For wiring on site. Power consumption 4W
Protection class II
Protection IP 42 to EN 60529; safe-
guard through appropri-
ate design and
installation
Permissible ambient temperature
– during operation 0 to +40 °C
– during storage and transport -20 to +65 °C
Torque 3 Nm
Runtime for 90° ∢ 120 s

Mixer motor for flanged mixers


& Part no. 9522 487 For specification, see the "Mixer and mixer motors" datasheet in
5822 223-6 GB

DN 40 and 50, without system plug and connecting cable this folder.
& Part no. Z004344
DN 65 to 100, without system plug and connecting cable

6 VIESMANN VITOTRONIC 300-K


Accessories (cont.)

Plug sÖ
Part no. 7415 056
for heating circuit pump.

Plug gS
Part no. 7415 057
for mixer motors.

Plugs for sensors


Part no. 7415 058

Contact temperature sensor


Part no. 7183 288 Specification
For capturing the flow and return temperature.
Lead length 5.8 m, fully wired
Protection IP 32 to EN 60529; safe-
guard through appropri-
ate design and
installation
Permissible ambient temperature
– during operation 0 to +120 °C
– during storage and transport -20 to +70 °C

Sensor well
Part no. 7819 693
R ½" x 200 mm
For the cylinder temperature sensor, part of the standard delivery
of Viessmann DHW cylinders.

Immersion temperature sensor


& With sensor well R½" x 100 mm. Specification
Part no. 7450 641
& With sensor well R½" x 150 mm. Lead length 3.8 m, fully wired
Part no. 7173 188 Protection IP 32 to EN 60529; safe-
For capturing the flow and return temperature. guard through appropri-
ate design and
installation
Permissible ambient temperature
– during operation 0 to +90 °C
– during storage and transport -20 to +70 °C

Immersion thermostat
5822 223-6 GB

Part no. 7151 728


May be used as a maximum temperature limiter for underfloor
heating systems.
The temperature limiter is installed into the heating flow and
switches the heating circuit pump OFF in case of excessive flow
temperature.

VITOTRONIC 300-K VIESMANN 7


Accessories (cont.)

Specification

Cable length 4.2 m, fully wired


Setting range 30 to 80 °C
Switching differential max. 11 K
Breaking capacity 6(1.5) A 250 V~
Setting scale inside the casing
Stainless steel sensor well R ½" x 200 mm
DIN reg. no. DIN TR 77703
or
DIN TR 96803
or
DIN TR 110302

Contact thermostat
Part no. 7151 729 Specification
May be used as a maximum temperature limiter for underfloor
heating systems (only in conjunction with metallic pipes). Cable length 4.2 m, fully wired
The temperature limiter is installed into the heating flow and Setting range 30 to 80 °C
switches the heating circuit pump OFF in case of excessive flow Switching differential max. 14 K
temperature. Breaking capacity 6(1.5) A 250V~
Setting scale inside the casing
DIN reg. no. DIN TR 77703
or
DIN TR 96803
or
DIN TR 110302

Information regarding room temperature hook-up (RS function) for remote control units
Never activate the RS function for underfloor heating circuits
(inertia).

Information regarding the Vitotrol 200 and 300


For every heating circuit in a heating system, one Vitotrol 200 or
one Vitotrol 300 can be deployed.

Vitotrol 200
Part no. 7450 017 Installation in the main living room on an internal wall opposite
KM BUS subscriber radiators. Never install inside shelf units, recesses, immediately
The Vitotrol 200 remote control regulates the heating program for by a door or heat source (e.g. direct sunlight, fireplace, TV set,
one heating circuit and the required set room temperature in stan- etc.).
dard mode, from any room in the house. The integral room temperature sensor captures the actual room
The Vitotrol 200 is equipped with backlit heating program selec- temperature and effects any necessary correction of the flow tem-
5822 223-6 GB

tion keys as well as a party and economy key. perature as well as a rapid heat-up at the start of the heating
The fault display shows faults on the control unit. operation (if appropriately programmed).
WS function: Connection:
Installation anywhere in the building.
RS function:

8 VIESMANN VITOTRONIC 300-K


Accessories (cont.)
& 2-core lead, length max. 50 m (even if connecting several Specification
remote control units) Power supply via KM BUS
& Never route this lead immediately next to 230/400 V cables Power consumption 0.2 W
& LV plug part of the standard delivery Protection class III
Protection level IP 30 to EN 60529;
safeguard through appro-
priate design and instal-
lation
Permissible ambient temperature
– during operation 0 to +40 °C
– during storage and transport −20 to +65 °C
Set room temperature range 10 to 30 °C
adjustable from
3 to 23 °C or
17 to 37 °C
The set room temperature for reduced mode is adjusted at the
control unit.

Vitotrol 300
Part no. 7179 060
KM BUS subscriber
The Vitotrol 300 remote control regulates the required set room
temperature for one heating circuit in standard and reduced mode,
the heating program and the switching times for central heating,
DHW heating and the DHW circulation pump.
The Vitotrol 300 provides a backlit display as well as backlit heat-
ing program keys, a party and economy key, automatic summer/
winter time changeover, keys for holiday program, day and time.
WS function:
Installation anywhere in the building.
RS function:
Installation in the main living room on an internal wall opposite
radiators. Never install inside shelf units, recesses, immediately
by a door or heat source (e.g. direct sunlight, fireplace, TV set,
etc.). Specification
The integral room temperature sensor captures the actual room Power supply via KM BUS
temperature and effects any necessary correction of the flow tem- Power consumption 0.5 W
perature as well as a rapid heat-up at the start of the heating Protection class III
operation (if appropriately programmed). Protection level IP 30 to EN 60529;
Connection: safeguard through appro-
& 2-core lead, length max. 50 m (even if connecting several priate design and instal-
remote control units) lation
& Never route this lead immediately next to 230/400 V cables Permissible ambient temperature
& LV plug as standard delivery – during operation 0 to +40 °C
– during storage and transport −20 to +65 °C
Set room temperature range
– for standard mode 10 to 30 °C
adjustable from
3 to 23 °C or
17 to 37 °C
– for reduced mode 3 to 37 °C

Room temperature sensor


Part no. 7408 012 & 2-core lead with a cross-section of 1.5 mm 2 (copper)
Separate room temperature sensor as supplement to the Vitotrol & Lead length from the remote control up to 30 m
200 and 300; to be used if the Vitotrol 200 or 300 cannot be & Never route this lead immediately next to 230/400 V cables
installed inside the main living room or in a suitable position where
the unit can capture and adjust the temperature.
Installation in the main living room on an internal wall opposite
5822 223-6 GB

radiators. Never install inside shelf units, recesses, immediately


by a door or heat source (e.g. direct sunlight, fireplace, TV set,
etc.).
Connect the room temperature sensor to the Vitotrol 200 or 300.
Connection:

VITOTRONIC 300-K VIESMANN 9


Accessories (cont.)

Specification

Protection class III


Protection level IP 30 to EN 60529;
safeguard through appro-
priate design and instal-
lation
Permissible ambient temperature
– during operation 0 to +40 °C
– during storage and transport −20 to +65 °C

Casing for room temperature sensor


Part no. 7408 828 Specification
This casing is designed to protect room temperature sensors in
wet areas (e.g. swimming pools, commercial nurseries, etc.). Protection IP 43 to EN 60529; safe-
guard through appropri-
ate design and
installation

Radio clock receiver


Part no. 7450 563
For receiving the DCF 77 time signal (location: Mainflingen near
Frankfurt/Main).
Radio controlled setting of time and date.
Install on an outside wall, facing the transmitter. The reception
may be reduced by metallic elements in the building structure, e.g.
steel reinforced concrete, neighbouring buildings and sources of
electro-magnetic interference, e.g. HV and public transport lines.
Connection:
& 2-core lead, length up to 35 m with a cross-section of 1.5 mm 2

(copper)
& Never route this lead immediately next to 230/400 V cables.

Function extension 0 to 10 V
Part no. 7174 718
KM BUS subscriber
Including cable (3.0 m long) and plugs fÖ and aVG.
& To default an additional set flow temperature via a 0 to 10 V

input in the temperature range 10 to 100 °C or 30 to 120 °C


(0 to 1 V ≙ boiler "OFF" in multi-boiler systems)
& To signal reduced mode and to switch the heating circuit pump
5822 223-6 GB

to a lower speed

10 VIESMANN VITOTRONIC 300-K


Accessories (cont.)

Specification Protection IP 30 to EN 60529


safeguard through appro-
Rated voltage 230 V~ priate design and instal-
Rated frequency 50 Hz lation
Power consumption 1W Permissible ambient temperature
Rated breaking capacity of the relay 4(2) A 230 V~ – during operation 0 to +40 °C
output – during storage and transport -20 to +65 °C

Contactor relay
Part no. 7814 681 Specification
With 4 N/C and 4 N/O contacts.
Coil voltage 230 V~/50 Hz
Rated current (I th) 16 A

For LON connecting cables, see section "Vitocom"

Vitocom 300, type FA3, FE1 and FI1


& Type FA3 On-site requirements:
Part no. 7143 428 & Analog telephone connection

& Type FE1 – for type FA3 with TAE socket, code "6N"
Part no. 7143 430 – for type FI1 with RJ45 socket (ISDN)
& Type FI1 & LON communication module (accessories)

Part no. 7143 429


Standard delivery:
In conjunction with a Vitodata 300: & LON connecting cable RJ45 — RJ45 for data exchange

& For remote reporting, remote monitoring and scanning of faults between the Vitotronic and Vitocom 300 (7.0 m long)
and/or data points via the internet & Power supply unit * 1

& For remote switching, remote setting of parameters and codes & Power cable from the power supply unit to the standard module

for heating systems via the internet & Standard module * 1 (with 8 digital inputs, 2 digital outputs and 2

sensor inputs):
Configuration via: – Type FA1: with integral analog modem and connecting cable
& Vitosoft 200, type LNR via Optolink for telephone socket TAE 6N (2.0 m long)
& Vitodata 300 – Type FE1: with connecting cable with RJ45 plug and sub-D
Data points provided by the heating control unit are hooked up to plug (9 PIN) as a modem connecting cable (GSM modem
the Vitocom 300 via LON. Additional settings can be made during accessories) or a suitable external ISDN terminal adaptor
commissioning, if system-specific special functions, such as mon- – Type FI1: with integral ISDN modem and connecting cable
itoring limits, are required. with RJ45 plug for ISDN socket (2.0 m long)

Fault messages are reported to the Vitodata 300 server via the Accessories:
internet. These messages are then transferred by the
Vitodata 300 server to the following communication services: Accessories Part no.
& PC with internet access
Wall mounting enclosure for the installation of the
& Fax
Vitocom 300 module, if no control panel or electrical
& SMS to D1/D2/E-Plus/O [or other] mobile phones
2 distribution panel is available
& E-mail
2 rows 7143 434
& Voicemail
3 rows 7143 435
5822 223-6 GB

*1
Mounting rail installation TS35 to DIN EN 50 022, 35 x 15 and 35 x 7.5.

VITOTRONIC 300-K VIESMANN 11


Accessories (cont.)

Accessories Part no. Protection class II


Extension module * 1 Protection IP 20 to EN 60529;
– 10 digital inputs 7143 431 safeguard through appro-
– 7 analog inputs (2 may be configured as pulsed priate design and installa-
inputs) tion
– 2 digital outputs Potential separation
– see the standard module for dimensions primary/secondary SELV to EN 60 950
or Electrical safety EN 60 335
– 10 digital inputs 7159 767 Permissible ambient temperature
– 7 analog inputs (2 may be configured as pulsed – for operation with supply voltage −20 to +55 °C
inputs) UE 187 to 264 V Installation in living
– 2 digital outputs spaces or boiler rooms
– 1 M BUS interface with connection of up to, for (standard ambient condi-
example, 250 M BUS capable heat meters with M tions)
BUS slave interface to EN 1434-3 – for operation with supply voltage -5 to +55 °C
– see the standard module for dimensions UE 100 to 264 V Installation in living
Uninterruptible power supply unit * 1 (UPS) 7143 432 spaces or boiler rooms
Additional rechargeable battery pack* 1 for UPS (standard ambient condi-
– practical for: 1 standard module, 1 expansion 7143 436 tions)
module and allocation of all inputs – during storage and transport -25 to +85 °C
– required for: 1 standard module and 2 expansion
modules
Extension of the connecting cable Standard module (standard delivery, Vitocom 300):
Installation distance 7 to 14 m
– 1 connecting cable (7.0 m long) 7143 495
and and
1 LON coupling RJ45 7143 496
Installation distance 14 to 900 m
– 2 LON plug-in connectors RJ45 7199 251
and and
2-core cable, CAT5, screened or JY(St) on-site
Y 2 x 2 x 0.8
or
– 2 connecting cables (7.0 m long) 7143 495
and and
2 LON sockets RJ45, CAT6 7171 784
and and
2-core cable, CAT5, screened or JY(St) on-site
Y 2 x 2 x 0.8 Specification
Operating voltage 24 V –
Rated current
Power supply unit (standard delivery, Vitocom 300): – Type FA3 600 mA
– Type FE1 300 mA
– Type FI1 500 mA
Protection class II
Protection IP 20 to EN 60529;
safeguard through appro-
priate design and installa-
tion
Function Type 1B to EN 60730- 1
Permissible ambient temperature
– during operation 0 to +40 °C
Installation in living
spaces or boiler rooms
Specification (standard ambient condi-
Rated voltage 85 to 264 V ~ tions)
Rated frequency 50/60 Hz – during storage and transport −20 to +65 °C
Rated current 0.55 A
Output voltage 24 V – For further technical details, see the Viessmann technical guide
Output current 1.5 A "Communication systems".

Tested quality

VDE approval in conjunction with Viessmann boilers.


5822 223-6 GB

*1
Mounting rail installation TS35 to DIN EN 50 022, 35 x 15 and 35 x 7.5.

12 VIESMANN VITOTRONIC 300-K


5822 223-6 GB

VITOTRONIC 300-K VIESMANN 13


Printed on environmentally friendly,
chlorine-free bleached paper

Subject to technical modifications.