Professional Documents
Culture Documents
UniSCAN NX - H - V - Printer
UniSCAN NX - H - V - Printer
2. INSTALLATION / WIRING
3. OPERATION / PROGRAMMING
3.1.1. HMI Interface
3.2. Programming/Operation
3.2.1 Display Interval / Sl.No.& Auto/Manual Operation
3.2.2 Alarms Viewing / Programming
3.2.3 Calibration mode
3.2.4 Configuration / Setup mode
3.2.5 Auto Calibration Facility
APPENDIX A:
1. Wiring Diagram for Inputs (Extension Board)
2. Wiring Diagram for PS/Relays (Main Unit)
3. Back Connection for UniScan NX
4. Back Connection for UniScan H
5. Dimensions/Panel cutout details
1.1 INTORDUCTION
1.3 SPECIFICATIONS
1.3.1 Power Supply : 90-270 V AC, 50 Hz +/- 3 Hz
1.3.2 Input/Ranges : Site programmable as per following Input/range table:
Input Ranges (default) Resolution
LECTROTEK …..Your Process Control Instrument Systems Expert SINCE 1970 OPERATION MANUAL UniScan Series Page 2 of 6
Product LECTROTEK SYSTEMS
OPERATION MANUAL www.lectrtek.com
3.0 OPERATION / PROGRAMMING
3.1 HMI INTERFACE
The UNISCAN-NX/H/V has the following HMI-interface:
1. Top 4 digit 7-segment LED normally shows Process Value display of channel being shown (PV). This indicates the value of the channel’s
input being measured, in direct engineering units. The range can be programmed for mA/Sqrt inputs at site over any 4-digit range (-1999 to
9999 units).
2. Bottom 4 digit 7-segment LED normally shows Channel Number and Alarm Status of channel being shown.
3. 2 nos LEDs A & M for display of Auto-Manual status. The instrument can be operated in automatic mode, wherein the channel display
automatically scrolls through all channels as per user set display interval time. In Manual mode, user can select any channel and hold the
display to that channel.
4. 4 nos. keys for operating the instrument. Their normal functions are given below (keys from left to right)
1. S SCROLL: This key sequentially selects parameter being displayed or programmed.
2. Decrement: This key selects (decrements) channel numbers in Manual Mode
3. Increment: This key selects (increments) channel numbers in Manual Mode.
4. M Auto/Manual: This key toggles the instrument between Auto/Manual modes.
All keys are multi-function keys and used singly or in combination with other keys and this is described in the relevant sections.
Any unused channel should be terminated by minimum 100 Ω resistor
S Key DStn Auto mode display time selectable 1-99 seconds by or keys
S Key SLno Serial number 1-99 for addressing in network selectable by or keys
Alarm trip selected by or keys
S Key AtrP Continue pressing of or keys show yes or no If yes, trips at high Alarm and
keeps the relay in latched state until you ACKNOWLEDGE ( key)
Printer time interval selected by or keys
S Key Pntr Adjust the time interval for automatic printouts from 1-255 min. Assigning
‘Zero’ value to printer time interval will disable the automatic print facility.
S Key Exits to normal mode of display
M Key Toggles A or M LED Toggles instrument between Auto Scroll and Manual Mode of display
1. Press S + keys
Top display shows present alarm setting.
Enters into Alarm View /
Change Mode. 2 0 0.1 Change set value by using keys.
2. Alarms can be set or Bottom display shows the Channel No.(2 digits) and remaining two digits, it
programmed per channel. 1A01 sequentially shows: - 1A(Alarm 1), 1d (Relay Hysterisis of A1), 2A(Alarm 2)
and 2d (Relay Hysterisis of A2).
Press M key successively to Top display shows hysterisis value & polarity of 1st alarm of selected channel.
select on the Bottom Window: - 0 0. 8
Hysterisis: Respective alarm’s hysterisis can be adjusted for providing a dead-
1A(Alarm 1) band between alarm trip/reset, to avoid frequent trips/relay chattering. Relay
1d(Relay Hysterisis 1A) 1d01 state in alarm condition is set by polarity of the value.
2A(Alarm 2) and
The table below shows polarity settings:
2d(Relay Hysterisis 2A)
Hysterisis programmed Relay ON condition Relay OFF condition
This section describes the
relay hysterisis 1d and 2d,
used to select relay on-off Positive PV Alarm Set PV Alarm Set
differential and relay state in
alarm condition. Negative PV Alarm Set PV Alarm Set
Press S key to select Next
Channel, repeat procedure to 1 1 00
Repeat above steps to set alarms for channel selected.
set Alarms. Press S + keys to quit Alarm Mode
Press S + keys to quit
2A02
Important Note: Programming a negative or positive sign to the Hysterisis enables user to make relays OFF or ON in alarm
condition, as desired. User caution and care is to be taken while programming this feature in this extremely universal instrument.
LECTROTEK …..Your Process Control Instrument Systems Expert SINCE 1970 OPERATION MANUAL UniScan Series Page 3 of 6
Product LECTROTEK SYSTEMS
OPERATION MANUAL www.lectrtek.com
3.2.3 CALIBRATION MODE
The instrument can be calibrated from the front panel keyboard by adjusting the Slope/Intercept of each channel by connecting a calibrated
source/standard at the input terminals of channel to be calibrated.
Enter the calibration mode by pressing S + M key combination as per table below:
Important Note:
i) Whenever dual key press functions are discussed, the keys have to be pressed as follows: Press first key in the combination,
keeping it pressed, press second, release first and then release second. In above case, press S first, keep it pressed and press M, then
release S, then release M.
ii) After last channel, it shows Ambient. Adjust it by or keys. For thermocouple inputs apply absolute mV between terminal R AND
B and short terminals B and G and follow same procedure for calibration.
iii) If user will change any thing, he has to save the changes first.
LECTROTEK …..Your Process Control Instrument Systems Expert SINCE 1970 OPERATION MANUAL UniScan Series Page 4 of 6
Product LECTROTEK SYSTEMS
OPERATION MANUAL www.lectrtek.com
Press M key again Top display shows channel’s span side range value (Range High).
Enters Range High for the selected rH01 Use keys to change if required.
channel (e.g. 100.0 for 0-100.0 range)
Note: Ranges are limited by respective sensor types – see Section 1.2
Press M key again Top display shows channel’s zero side range value (Range Low).
Enters Range Low for the selected 0 0 0. 0
channel (e.g. 000.0 for 0-100.0 range) rL01 Use keys to change if required.
Press M key again
Enters Decimal Mode for the selected 0 0 0. 0 Top display shows channel’s Range Low with previous decimal point.
channel.
Use keys to change.
This selection is valid for mA dc inputs dP01 Note: Decimals are fixed as 0.1 for RTD and 1 digit for thermocouple inputs.
(linear and square root).
Press E key to select sequentially Top display shows relay number assignable to channel selected. Use
following conditions for channel: rL01 keys to assign relay number. If no relay is to be assigned to selected
channel, choose nORL by toggling beyond rL32
Alarm1 (1A). (using keys).
Alarm2 (2A).
Open Input (Pn) 1A0 1 Bottom display shows Channel Number and the Alarm type (changeable by
A/M key between A1, A2 and Pn conditions).
Press S + M keys Save and quits Configuration Mode, gets back to normal display mode.
I mportant Note 1: The UNISCAN’s standard software enables user to select up to 32 relays for assigning them for alarms of any desired channel.
The software allows selection of maximum number of relays (32), obviously, if lesser number of relays are ordered, user must select relay numbers
less than or equal to the relays ordered. (For example, if 8 relays are ordered, you can assign alarms of desired channels among these 8 relays only,
if an alarm is allocated to relay number higher than 8, it will not function).
Important Note 2: The user must satisfy himself that relays have been correctly assigned/grouped. This is especially important for critical
applications like alarm/trips of safety devices. Standard suggested method is to make a table of desired alarm assignments, so that alarm type
conflicts are avoided while programming the UNICSAN-NX. (For example, the same relay can be assigned for High or Low Alarm conditions to
different channels.
Important Note 3: When alarm condition ‘H’ (TRIP) for any channel occurs and if instrument is in auto mode then It stops scanning and holds
the temperature value of that channel. It will be remains in that state unless and until the condition get acknowledged. Press key to
acknowledge that condition, it will run in auto mode till next H alarm condition occurs.
LECTROTEK …..Your Process Control Instrument Systems Expert SINCE 1970 OPERATION MANUAL UniScan Series Page 5 of 6
Product LECTROTEK SYSTEMS
OPERATION MANUAL www.lectrtek.com
1-255 06 80xx Actual data for parameter to be
written
The Serial number represents the unique device id if it is connected on a network of many devices, the default serial number for the device
is ‘01’, Which can also be modified from option found by pressing ‘S’ key two times.
Function code ‘06’ is used in MODBUS protocol to write a single byte data.
To write the clock two byte address should start with ‘80’, the second byte of the address will specify what parameter is being written.
Please refer the table bellow to write relative parameter.
Important Note: The parameters should be written in the same sequence as mentioned in table above, to faithful data writing in clock.
APPENDIX
THERMOCOUPLE INPTS APPLY BETWEEN R&B AND SHORT B&G SHORTLINKS J19-J34
Pt100 APPLY BETWEEN R&B AND G SHORTLINKS J19-J34
mA INPUT APPLY BETWEEN R&B AND SHORT B&G SHORTLINKS J1-J34
Shortlinks are already placed on boards as per specification. If mixed inputs are to be used put only required shortlinks as per table.
1. WIRING DIAGRAM
For Inputs
CHANNEL 9 CHANNEL 16
F R C C A B LE
+- -
TC
CHANNEL 1 CHANNEL 8
LECTROTEK …..Your Process Control Instrument Systems Expert SINCE 1970 OPERATION MANUAL UniScan Series Page 6 of 6
Product LECTROTEK SYSTEMS
OPERATION MANUAL www.lectrtek.com
90V~
P N NC P5 N O NC P6 NO NC P7 NO NC P8 NO
to
264V ~
D1 CMN D2 D3 G B A
D IG ITA L RS
IN P U TS 485
P R IN TE R
IN P U T S
17-32
IN P U T S
1-16
+ -
NO P1 NC NO P2 NC NO P3 NC NO P4 NC 4-20 m A O P
U N IS C A N V
IN P U TS 49-64 IN P U TS 33-48
RS 485 PORT
B A G
4. BACK CONNECTION
For UniScan H
SU PPL Y N P N N P N N P N N P N N P N N P N N P N N P N
P N C 5 O C 6 O C 7 O O 8 O C 9 O C 10 O C 11 O C 12 C
Rs485
IN P U T S 17-32
N P N N P N N P N N P N
C O C O C O O
C C
O
IN P U T S 1-16
SN
U N ISC A N -H
IN P U T S 49-64
N P N N P N N P N N P N + -
O 1 C O 2 C O 3 C O 4 C 4-20 m A O P
IN P U T S 33-48
WARRANTY
18 Months after dispatch or 12 Months after commissioning, whichever is earlier, against manufacturing defects, ex-works / dealer. Refer to company for detailed warranty terms.
No implied warranty applicable other than company standard warranty
LECTROTEK …..Your Process Control Instrument Systems Expert SINCE 1970 OPERATION MANUAL UniScan Series Page 7 of 6