Taco Load Program Project Input Data 02/04/2012

Project: Heating/Cooling Load calculations

Project Information

Project Title: Heating/Cooling Load calculations


Address: 27 7th Avenue

City: Brooklyn State: ny Zip:


Comments:

Engineer:
Address:

City: State: Zip:


Comments:

Client:
Address:

City: State: Zip:


Comments:

Project Weather Information

Nearest Climatological Location:


State: New York City: NYC-La Guardia AP
Latitude: 40.77 Clearness Factor: 1.00
Elevation: 11

Outside Design Temp Cooling:


Dry Bulb°F 92.0 Wet Bulb°F 74.0
Daily Range°F 16.0 Winter Dry Bulb°F 20.0

Outside Design Temp Heating:


Dry Bulb°F .0
Taco Load Program Building Input Data 02/04/2012
Project: Heating/Cooling Load calculations

Design Conditions Cooling Design Conditions Heating

Inside Cooling Dry Bulb (°F) 72.0 Inside Heating Dry Bulb (°F) 75.0
Inside Cooling Rel. Hum.(%) 50 Heating Air Temperature Difference (°F) 50
Cooling Air Temperature Difference (°F) 20 Heating Hydronic Temperature Difference (°F) 10
Cooling Hydronic Temperature Difference (°F) 10

Building Data Design Loads

Wall Height (ft) 11.0 People Sensible (BtuH) 250


Hour Average (hr) 2 People Latent (BtuH) 200
Supply Air Min. (cfm/ft2) .00 People / Area (ft²) 100
Supply Air Min. (AC/hr) 6.00 Max. People 1000
Equipment / Area (W/ft²) 1.20
Lighting / Area (W/ft²) 1.50

Infiltration Ventilation

Summer AC (AC/hr) 1.00 % Fan 0


Summer Diversity 1 Flow / Person 20.00
Winter AC (AC/hr) 1.00 AC 1.00
Winter Diversity 1 Flow / Area .20

Diversity Factor

Lighting 1
Equipment 1
People 1
Taco Load Program Master Data Input 02/04/2012
Heating/Cooling Load calculations

Master Walls

Wall ID Description U Value Decrement Time Lag Color Below Grade


BtuH/ft²°F Heat LossBtuH/ft²

xterior wall .191 0.78 3.33 M

Master Roofs

Roof ID Description U Value Decrement Time Lag Color


BtuH/ft²°F

Roof 100 .064 0.13 11.22 L

Master Floors

Floor ID Description U Value Space Below Space Below Slab Below Grade Slab On Grade
BtuH/ft²°F Temp Summer°F Temp Winter°F LossBtuH/ft² LossBtuH/lf

Floor 100 -999999.000

Master Partitions

Partition ID Description U Value Uncond. Space Uncond. Space


Temp Summer Temp Winter

Master Windows

Window ID Description Height Width U Summer U Summer U Winter Shading Shading Shading ID
No Shading Shading Coeff. Glass Coeff. Glass
ft ft BtuH/ft²°F BtuH/ft²°F BtuH/ft²°F No Shading Inside Shade

4'window 5.00 4.00 .570 .570 .550 0.00 0.00


9.5' front window 7.00 10.00 .000 .000 .000 0.00 0.00
door 7.00 3.00 .240 .240 .240 0.00 0.00
front windows 7.00 7.00 .570 .570 .550 0.00 0.00
rear window 7.00 3.00 .570 .570 .550 0.00 0.00

Master Shadings

Shading ID Overhang Fin Left Fin Right


Above Beyond Beyond Depth Above Beyond Bottom Depth Above Beyond Bottom Depth
Top Left Right Top Left Top Right
Taco Load Program System Input Data 02/04/2012
Project: Heating/Cooling Load calculations

Basement

Design Conditions Cooling Design Conditions Heating

Inside Cooling Dry Bulb (°F) 72.0 Inside Heating Dry Bulb (°F) 75.0
Inside Cooling Rel. Hum.(%) 50 Heating Air Temperature Difference (°F) 50
Cooling Air Temperature Difference (°F) 20 Heating Hydronic Temperature Difference (°F) 10
Cooling Hydronic Temperature Difference (°F) 10

Building Data Design Loads

Wall Height (ft) 11.0 People Sensible (BtuH) 250


People Latent (BtuH) 200
Supply Air Min. (cfm/ft2) .00 People / Area (ft²) 100
Supply Air Min. (AC/hr) 6.00 Max. People 1000
Equipment / Area (W/ft²) 1.20
Lighting / Area (W/ft²) 1.50

Infiltration Ventilation

Summer AC (AC/hr) 1.00 % Fan 0


Summer Diversity 1 Flow / Person 20.00
Winter AC (AC/hr) 1.00 AC 1.00
Winter Diversity 1 Flow / Area .20

Diversity Factor

Lighting 1
Equipment 1
People 1
Taco Load Program System Input Data 02/04/2012
Project: Heating/Cooling Load calculations

First Floor

Design Conditions Cooling Design Conditions Heating

Inside Cooling Dry Bulb (°F) 72.0 Inside Heating Dry Bulb (°F) 75.0
Inside Cooling Rel. Hum.(%) 50 Heating Air Temperature Difference (°F) 50
Cooling Air Temperature Difference (°F) 20 Heating Hydronic Temperature Difference (°F) 10
Cooling Hydronic Temperature Difference (°F) 10

Building Data Design Loads

Wall Height (ft) 11.0 People Sensible (BtuH) 250


People Latent (BtuH) 200
Supply Air Min. (cfm/ft2) .00 People / Area (ft²) 100
Supply Air Min. (AC/hr) 6.00 Max. People 1000
Equipment / Area (W/ft²) 1.20
Lighting / Area (W/ft²) 1.50

Infiltration Ventilation

Summer AC (AC/hr) 1.00 % Fan 0


Summer Diversity 1 Flow / Person 20.00
Winter AC (AC/hr) 1.00 AC 1.00
Winter Diversity 1 Flow / Area .20

Diversity Factor

Lighting 1
Equipment 1
People 1
Taco Load Program System Input Data 02/04/2012
Project: Heating/Cooling Load calculations

Packaged Roof Unit

Design Conditions Cooling Design Conditions Heating

Inside Cooling Dry Bulb (°F) 72.0 Inside Heating Dry Bulb (°F) 75.0
Inside Cooling Rel. Hum.(%) 50 Heating Air Temperature Difference (°F) 50
Cooling Air Temperature Difference (°F) 20 Heating Hydronic Temperature Difference (°F) 10
Cooling Hydronic Temperature Difference (°F) 10

Building Data Design Loads

Wall Height (ft) 11.0 People Sensible (BtuH) 250


People Latent (BtuH) 200
Supply Air Min. (cfm/ft2) .00 People / Area (ft²) 100
Supply Air Min. (AC/hr) 6.00 Max. People 1000
Equipment / Area (W/ft²) 1.20
Lighting / Area (W/ft²) 1.50

Infiltration Ventilation

Summer AC (AC/hr) 1.00 % Fan 0


Summer Diversity 1 Flow / Person 20.00
Winter AC (AC/hr) 1.00 AC 1.00
Winter Diversity 1 Flow / Area .20

Diversity Factor

Lighting 1
Equipment 1
People 1
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 1st Floor - 1 SYSTEM First Floor TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
18.0 12.0 10.0 9.0 2 324 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 259 0 1.0 1.5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NW(15)/Vertical(90) 17.5 1 126.0 1 1

PEAK LOAD occurs at 9 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 307 0 2021
Window Solar 0
Wall Transmission 265 0 1805 0
Wall Solar 978 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 392 439 4005
Lights 1105 0 1105
People 500 400 500
Equipment 885 0 885
Sub Total 4431 839 0 7832 2489 0
Safety Factor 0 0 0 0 0

Total 4431 839 0 7832 2489 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 216 Total Load (BtuH) 5270 7832 Water (gpm) 1.1 .8
Volume (ft³) 1944 Total Load (BtuH/ft²) 24.4 36.3 Air Room Peak (cfm) 200 140
Sensible Heat Ratio .84 Total Load (Ton) .4 Air Room Peak (cfm/ft2) .9 .6
Total Load (ft²/Ton) 492 Air Room Peak (AC/hr) 6 4
Return Air (cfm) 200
Exhaust Airflow (cfm) 0
Infiltration (cfm) 32 49
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 1st Floor - 2 SYSTEM First Floor TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
11.5 12.0 10.0 9.0 1 207 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 166 0 1.0 1.5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
SE(-135)/Vertical(90) 11.5 1 94.0 2 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 239 0 866
Window Solar 0
Wall Transmission 359 0 1347 0
Wall Solar 513 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 455 540 2559
Lights 706 0 706
People 250 200 250
Equipment 565 0 565
Sub Total 3088 740 0 4772 1521 0
Safety Factor 0 0 0 0 0

Total 3088 740 0 4772 1521 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 138 Total Load (BtuH) 3828 4772 Water (gpm) .8 .5
Volume (ft³) 1242 Total Load (BtuH/ft²) 27.7 34.6 Air Room Peak (cfm) 140 90
Sensible Heat Ratio .81 Total Load (Ton) .3 Air Room Peak (cfm/ft2) 1.0 .7
Total Load (ft²/Ton) 433 Air Room Peak (AC/hr) 7 4
Return Air (cfm) 140
Exhaust Airflow (cfm) 0
Infiltration (cfm) 21 31
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 1st floor - 3 SYSTEM First Floor TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
14.5 13.0 9.0 9.0 2 283 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 226 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 9.5 1 64.5 2 1
ENE(-180)/Vertical(90) 6.5 1 38.5 3 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 467 0 1691
Window Solar 0
Wall Transmission 393 0 1475 0
Wall Solar 307 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 932 1107 4661
Lights 964 0 964
People 500 400 500
Equipment 772 0 772
Sub Total 4336 1507 0 7827 2236 0
Safety Factor 0 0 0 0 0

Total 4336 1507 0 7827 2236 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 189 Total Load (BtuH) 5843 7827 Water (gpm) 1.2 .8
Volume (ft³) 1696.5 Total Load (BtuH/ft²) 31.0 41.5 Air Room Peak (cfm) 200 140
Sensible Heat Ratio .74 Total Load (Ton) .5 Air Room Peak (cfm/ft2) 1.1 .7
Total Load (ft²/Ton) 387 Air Room Peak (AC/hr) 7 5
Return Air (cfm) 200
Exhaust Airflow (cfm) 0
Infiltration (cfm) 42 57
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 1st Floor - 5 SYSTEM First Floor TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
5.0 11.5 10.0 9.0 1 86 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 69 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 6.0 1 60.0
SW(75)/Vertical(90) 5.0 1 50.0
SE(-135)/Vertical(90) 11.5 1 94.0 2 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 239 0 866
Window Solar 0
Wall Transmission 779 0 2922 0
Wall Solar 654 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 284 338 1422
Lights 293 0 293
People 250 200 250
Equipment 235 0 235
Sub Total 2736 538 0 5210 779 0
Safety Factor 0 0 0 0 0

Total 2736 538 0 5210 779 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 58 Total Load (BtuH) 3274 5210 Water (gpm) .7 .5
Volume (ft³) 517.5 Total Load (BtuH/ft²) 56.9 90.6 Air Room Peak (cfm) 120 90
Sensible Heat Ratio .84 Total Load (Ton) .3 Air Room Peak (cfm/ft2) 2.1 1.6
Total Load (ft²/Ton) 211 Air Room Peak (AC/hr) 14 10
Return Air (cfm) 120
Exhaust Airflow (cfm) 0
Infiltration (cfm) 13 17
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 1st Floor -4- SYSTEM First Floor TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
6.0 8.5 10.0 9.0 1 77 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 61 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 6.0 1 60.0
SW(75)/Vertical(90) 6.0 1 60.0

PEAK LOAD occurs at 7 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 0 0 0
Window Solar 0
Wall Transmission 321 0 1719 0
Wall Solar 637 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 177 222 1261
Lights 261 0 261
People 250 200 250
Equipment 209 0 209
Sub Total 1854 422 0 2980 720 0
Safety Factor 0 0 0 0 0

Total 1854 422 0 2980 720 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 51 Total Load (BtuH) 2276 2980 Water (gpm) .5 .3
Volume (ft³) 459 Total Load (BtuH/ft²) 44.6 58.4 Air Room Peak (cfm) 80 50
Sensible Heat Ratio .81 Total Load (Ton) .2 Air Room Peak (cfm/ft2) 1.6 1.0
Total Load (ft²/Ton) 269 Air Room Peak (AC/hr) 10 7
Return Air (cfm) 80
Exhaust Airflow (cfm) 0
Infiltration (cfm) 11 15
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 1st Floor -5 SYSTEM First Floor TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
31.0 8.0 10.0 9.0 0 372 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 0 0 .5 .5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NW(15)/Vertical(90) 31.0 1 289.0 4 1

PEAK LOAD occurs at 9 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 55 0 378
Window Solar 0
Wall Transmission 607 0 4140 0
Wall Solar 2244 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 225 252 1533
Lights 1269 0 1269
People 0 0 0
Equipment 0 0 0
Sub Total 4400 252 0 6051 1269 0
Safety Factor 0 0 0 0 0

Total 4400 252 0 6051 1269 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 248 Total Load (BtuH) 4652 6051 Water (gpm) .9 .6
Volume (ft³) 2232 Total Load (BtuH/ft²) 18.8 24.4 Air Room Peak (cfm) 220 110
Sensible Heat Ratio .95 Total Load (Ton) .4 Air Room Peak (cfm/ft2) .9 .4
Total Load (ft²/Ton) 640 Air Room Peak (AC/hr) 6 3
Return Air (cfm) 220
Exhaust Airflow (cfm) 0
Infiltration (cfm) 19 19
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 2nd Floor - 2 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
16.0 12.0 10.0 9.0 2 288 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 230 0 1.0 1.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
SE(-135)/Vertical(90) 16.0 1 139.0 2 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 239 0 866
Window Solar 0
Wall Transmission 531 0 1991 0
Wall Solar 759 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 633 752 2374
Lights 982 0 982
People 500 400 500
Equipment 786 0 786
Sub Total 4431 1152 0 5231 2268 0
Safety Factor 0 0 0 0 0

Total 4431 1152 0 5231 2268 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 192 Total Load (BtuH) 5583 5231 Water (gpm) 1.1 .5
Volume (ft³) 1728 Total Load (BtuH/ft²) 29.1 27.2 Air Room Peak (cfm) 200 100
Sensible Heat Ratio .79 Total Load (Ton) .5 Air Room Peak (cfm/ft2) 1.0 .5
Total Load (ft²/Ton) 413 Air Room Peak (AC/hr) 7 3
Return Air (cfm) 200
Exhaust Airflow (cfm) 0
Infiltration (cfm) 29 29
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 2nd Floor - 3 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
16.0 9.0 10.0 9.0 1 216 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 173 0 1.0 1.5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 10.0 1 79.0 2 1
ESE(-150)/Vertical(90) 6.0 1 39.0 2 1

PEAK LOAD occurs at 1 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 431 0 1733
Window Solar 0
Wall Transmission 406 0 1690 0
Wall Solar 563 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 427 533 2670
Lights 737 0 737
People 250 200 250
Equipment 590 0 590
Sub Total 3403 733 0 6093 1576 0
Safety Factor 0 0 0 0 0

Total 3403 733 0 6093 1576 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 144 Total Load (BtuH) 4136 6093 Water (gpm) .8 .6
Volume (ft³) 1296 Total Load (BtuH/ft²) 28.7 42.3 Air Room Peak (cfm) 150 110
Sensible Heat Ratio .82 Total Load (Ton) .3 Air Room Peak (cfm/ft2) 1.0 .8
Total Load (ft²/Ton) 418 Air Room Peak (AC/hr) 7 5
Return Air (cfm) 150
Exhaust Airflow (cfm) 0
Infiltration (cfm) 22 32
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 2nd Floor - 4 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
10.0 11.5 10.0 9.0 1 173 1 115 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 138 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 10.0 1 100.0
SE(-135)/Vertical(90) 11.5 1 94.0 2 1
SW(75)/Vertical(90) 10.0 1 100.0

PEAK LOAD occurs at 6 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 203 0 866
Window Solar 0
Wall Transmission 955 0 4212 0
Wall Solar 1111 0
Roof Transmission 125 0 552
Roof Solar 3
Partition 0 0
Floor 0 0
Infiltration 483 550 2843
Lights 588 0 588
People 250 200 250
Equipment 471 0 471
Sub Total 4189 750 0 8473 1309 0
Safety Factor 0 0 0 0 0

Total 4189 750 0 8473 1309 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 115 Total Load (BtuH) 4940 8473 Water (gpm) 1.0 .8
Volume (ft³) 1035 Total Load (BtuH/ft²) 43.0 73.7 Air Room Peak (cfm) 190 150
Sensible Heat Ratio .85 Total Load (Ton) .4 Air Room Peak (cfm/ft2) 1.7 1.3
Total Load (ft²/Ton) 279 Air Room Peak (AC/hr) 11 9
Return Air (cfm) 190
Exhaust Airflow (cfm) 0
Infiltration (cfm) 26 35
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 2nd floor -1 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
14.0 20.5 10.0 9.0 2 431 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 344 0 1.0 1.5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NW(15)/Vertical(90) 14.0 1 70.0 5 1

PEAK LOAD occurs at 4 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 0 0 0
Window Solar 0
Wall Transmission 267 0 1003 0
Wall Solar 62 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 946 1124 5322
Lights 1468 0 1468
People 500 400 500
Equipment 1175 0 1175
Sub Total 4419 1524 0 6325 3143 0
Safety Factor 0 0 0 0 0

Total 4419 1524 0 6325 3143 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 287 Total Load (BtuH) 5943 6325 Water (gpm) 1.2 .6
Volume (ft³) 2583 Total Load (BtuH/ft²) 20.7 22.0 Air Room Peak (cfm) 260 120
Sensible Heat Ratio .74 Total Load (Ton) .5 Air Room Peak (cfm/ft2) .9 .4
Total Load (ft²/Ton) 579 Air Room Peak (AC/hr) 6 3
Return Air (cfm) 260
Exhaust Airflow (cfm) 0
Infiltration (cfm) 43 65
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 3rd Floor - 3 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
9.5 15.0 10.0 9.0 1 214 1 143 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 171 0 1.0 1.5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
SE(-135)/Vertical(90) 9.5 1 74.0 2 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 239 0 866
Window Solar 0
Wall Transmission 283 0 1060 0
Wall Solar 404 0
Roof Transmission 183 0 686
Roof Solar -28
Partition 0 0
Floor 0 0
Infiltration 470 558 2642
Lights 729 0 729
People 250 200 250
Equipment 584 0 584
Sub Total 3113 758 0 5255 1563 0
Safety Factor 0 0 0 0 0

Total 3113 758 0 5255 1563 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 143 Total Load (BtuH) 3872 5255 Water (gpm) .8 .5
Volume (ft³) 1282.5 Total Load (BtuH/ft²) 27.2 36.9 Air Room Peak (cfm) 140 100
Sensible Heat Ratio .80 Total Load (Ton) .3 Air Room Peak (cfm/ft2) 1.0 .7
Total Load (ft²/Ton) 442 Air Room Peak (AC/hr) 7 5
Return Air (cfm) 140
Exhaust Airflow (cfm) 0
Infiltration (cfm) 21 32
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 3rd Floor - 4 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
13.0 14.5 10.0 9.0 2 283 1 189 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 226 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
SE(-135)/Vertical(90) 10.0 1 79.0 2 1
ESE(-150)/Vertical(90) 6.0 1 39.0 2 1
NE(-195)/Vertical(90) 10.0 1 100.0

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 479 0 1733
Window Solar 0
Wall Transmission 833 0 3123 0
Wall Solar 888 0
Roof Transmission 242 0 907
Roof Solar -37
Partition 0 0
Floor 0 0
Infiltration 932 1107 4661
Lights 964 0 964
People 500 400 500
Equipment 772 0 772
Sub Total 5573 1507 0 10423 2236 0
Safety Factor 0 0 0 0 0

Total 5573 1507 0 10423 2236 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 189 Total Load (BtuH) 7080 10423 Water (gpm) 1.4 1.0
Volume (ft³) 1696.5 Total Load (BtuH/ft²) 37.6 55.3 Air Room Peak (cfm) 250 190
Sensible Heat Ratio .79 Total Load (Ton) .6 Air Room Peak (cfm/ft2) 1.3 1.0
Total Load (ft²/Ton) 319 Air Room Peak (AC/hr) 9 7
Return Air (cfm) 250
Exhaust Airflow (cfm) 0
Infiltration (cfm) 42 57
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 3rd Floor -1 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
20.5 13.0 10.0 9.0 3 400 1 267 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 320 0 1.0 1.5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NW(15)/Vertical(90) 20.5 1 135.0 5 1

PEAK LOAD occurs at 9 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 0 0 0
Window Solar 0
Wall Transmission 284 0 1934 0
Wall Solar 1048 0
Roof Transmission 188 0 1282
Roof Solar 176
Partition 0 0
Floor 0 0
Infiltration 483 541 4942
Lights 1363 0 1363
People 750 600 750
Equipment 1091 0 1091
Sub Total 5384 1141 0 8157 3205 0
Safety Factor 0 0 0 0 0

Total 5384 1141 0 8157 3205 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 267 Total Load (BtuH) 6525 8157 Water (gpm) 1.3 .8
Volume (ft³) 2398.5 Total Load (BtuH/ft²) 24.5 30.6 Air Room Peak (cfm) 240 150
Sensible Heat Ratio .83 Total Load (Ton) .5 Air Room Peak (cfm/ft2) .9 .6
Total Load (ft²/Ton) 490 Air Room Peak (AC/hr) 6 4
Return Air (cfm) 240
Exhaust Airflow (cfm) 0
Infiltration (cfm) 40 60
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM 3rd Floor -2 SYSTEM Packaged Roof Unit TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
8.0 6.5 10.0 9.0 1 78 1 52 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 62 0 .0 .0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA

PEAK LOAD occurs at 1 AM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 0 0 0
Window Solar 0
Wall Transmission 0 0 0 0
Wall Solar 0 0
Roof Transmission 20 0 250
Roof Solar 60
Partition 0 0
Floor 0 0
Infiltration 0 0 0
Lights 266 0 266
People 250 200 250
Equipment 213 0 213
Sub Total 809 200 0 250 729 0
Safety Factor 0 0 0 0 0

Total 809 200 0 250 729 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 52 Total Load (BtuH) 1009 250 Water (gpm) .2 .0
Volume (ft³) 468 Total Load (BtuH/ft²) 19.4 4.8 Air Room Peak (cfm) 50 0
Sensible Heat Ratio .80 Total Load (Ton) .1 Air Room Peak (cfm/ft2) 1.0 .0
Total Load (ft²/Ton) 618 Air Room Peak (AC/hr) 6 0
Return Air (cfm) 50
Exhaust Airflow (cfm) 0
Infiltration (cfm) 0 0
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM B-1 SYSTEM Basement TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
13.5 12.0 10.0 9.0 2 243 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 194 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NW(15)/Vertical(90) 13.5 1 86.0 1 1

PEAK LOAD occurs at 4 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 559 0 2021
Window Solar 0
Wall Transmission 329 0 1232 0
Wall Solar 77 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 801 952 4005
Lights 829 0 829
People 500 400 500
Equipment 663 0 663
Sub Total 3757 1352 0 7259 1992 0
Safety Factor 0 0 0 0 0

Total 3757 1352 0 7259 1992 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 162 Total Load (BtuH) 5109 7259 Water (gpm) 1.0 .7
Volume (ft³) 1458 Total Load (BtuH/ft²) 31.5 44.8 Air Room Peak (cfm) 170 130
Sensible Heat Ratio .74 Total Load (Ton) .4 Air Room Peak (cfm/ft2) 1.0 .8
Total Load (ft²/Ton) 381 Air Room Peak (AC/hr) 7 5
Return Air (cfm) 170
Exhaust Airflow (cfm) 0
Infiltration (cfm) 36 49
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM B-2 SYSTEM Basement TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
13.5 12.0 9.0 8.0 2 243 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 194 0 1.0 1.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
SE(-135)/Vertical(90) 13.5 1 100.5 2 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 239 0 866
Window Solar 0
Wall Transmission 384 0 1440 0
Wall Solar 549 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 475 564 1780
Lights 829 0 829
People 500 400 500
Equipment 663 0 663
Sub Total 3639 964 0 4086 1992 0
Safety Factor 0 0 0 0 0

Total 3639 964 0 4086 1992 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 162 Total Load (BtuH) 4603 4086 Water (gpm) .9 .4
Volume (ft³) 1296 Total Load (BtuH/ft²) 28.4 25.2 Air Room Peak (cfm) 170 70
Sensible Heat Ratio .79 Total Load (Ton) .4 Air Room Peak (cfm/ft2) 1.0 .4
Total Load (ft²/Ton) 422 Air Room Peak (AC/hr) 8 3
Return Air (cfm) 170
Exhaust Airflow (cfm) 0
Infiltration (cfm) 22 22
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM B-3 SYSTEM Basement TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
14.5 13.0 9.0 9.0 2 283 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 226 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 9.5 1 64.5 2 1
ENE(-180)/Vertical(90) 6.5 1 38.5 3 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 467 0 1691
Window Solar 0
Wall Transmission 393 0 1475 0
Wall Solar 307 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 932 1107 4661
Lights 964 0 964
People 500 400 500
Equipment 772 0 772
Sub Total 4336 1507 0 7827 2236 0
Safety Factor 0 0 0 0 0

Total 4336 1507 0 7827 2236 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 189 Total Load (BtuH) 5843 7827 Water (gpm) 1.2 .8
Volume (ft³) 1696.5 Total Load (BtuH/ft²) 31.0 41.5 Air Room Peak (cfm) 200 140
Sensible Heat Ratio .74 Total Load (Ton) .5 Air Room Peak (cfm/ft2) 1.1 .7
Total Load (ft²/Ton) 387 Air Room Peak (AC/hr) 7 5
Return Air (cfm) 200
Exhaust Airflow (cfm) 0
Infiltration (cfm) 42 57
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM B-4 SYSTEM Basement TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
6.0 8.5 9.0 9.0 1 77 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 61 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 6.0 1 54.0
SW(75)/Vertical(90) 6.0 1 54.0

PEAK LOAD occurs at 6 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 0 0 0
Window Solar 0
Wall Transmission 351 0 1547 0
Wall Solar 477 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 214 244 1261
Lights 261 0 261
People 250 200 250
Equipment 209 0 209
Sub Total 1762 444 0 2808 720 0
Safety Factor 0 0 0 0 0

Total 1762 444 0 2808 720 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 51 Total Load (BtuH) 2206 2808 Water (gpm) .4 .3
Volume (ft³) 459 Total Load (BtuH/ft²) 43.3 55.1 Air Room Peak (cfm) 80 50
Sensible Heat Ratio .80 Total Load (Ton) .2 Air Room Peak (cfm/ft2) 1.6 1.0
Total Load (ft²/Ton) 277 Air Room Peak (AC/hr) 10 7
Return Air (cfm) 80
Exhaust Airflow (cfm) 0
Infiltration (cfm) 11 15
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM B-5 SYSTEM Basement TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
5.0 11.5 9.0 9.0 1 86 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 69 0 1.5 2.0

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NE(-195)/Vertical(90) 6.0 1 54.0
SW(75)/Vertical(90) 5.0 1 45.0
SE(-135)/Vertical(90) 11.5 1 82.5 2 1

PEAK LOAD occurs at 2 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 239 0 866
Window Solar 0
Wall Transmission 693 0 2600 0
Wall Solar 577 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 284 338 1422
Lights 293 0 293
People 250 200 250
Equipment 235 0 235
Sub Total 2573 538 0 4888 779 0
Safety Factor 0 0 0 0 0

Total 2573 538 0 4888 779 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 58 Total Load (BtuH) 3111 4888 Water (gpm) .6 .5
Volume (ft³) 517.5 Total Load (BtuH/ft²) 54.1 85.0 Air Room Peak (cfm) 120 90
Sensible Heat Ratio .83 Total Load (Ton) .3 Air Room Peak (cfm/ft2) 2.1 1.6
Total Load (ft²/Ton) 222 Air Room Peak (AC/hr) 14 10
Return Air (cfm) 120
Exhaust Airflow (cfm) 0
Infiltration (cfm) 13 17
Taco Load Program Room Results 02/04/2012
Heating/Cooling Load calculations

ROOM B-6 SYSTEM Basement TERMINAL

Room Room Wall Clg Nr. Total Roof Flr Partition Hr. AC/Hr
Length Width Height Height People Watts ID Area RA ID ID Lgth Avg Min. OSA
31.0 8.0 9.0 9.0 0 372 0 0 0 0 .0 2.0

People Lights Equipment Infil. CFM


Sen. Lat. Pfl W/ft2 Pfl RA Inc Sensible Rad. Latent Pfl Summr Wintr
250 200 1.5 2 0 0 .5 .5

Exposure Exp Wall Window


Lgth ID Area Ra ID Nr. RA
NW(15)/Vertical(90) 31.0 1 258.0 4 1

PEAK LOAD occurs at 9 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 55 0 378
Window Solar 0
Wall Transmission 542 0 3696 0
Wall Solar 2003 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 225 252 1533
Lights 1269 0 1269
People 0 0 0
Equipment 0 0 0
Sub Total 4094 252 0 5607 1269 0
Safety Factor 0 0 0 0 0

Total 4094 252 0 5607 1269 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 248 Total Load (BtuH) 4346 5607 Water (gpm) .9 .6
Volume (ft³) 2232 Total Load (BtuH/ft²) 17.5 22.6 Air Room Peak (cfm) 220 100
Sensible Heat Ratio .94 Total Load (Ton) .4 Air Room Peak (cfm/ft2) .9 .4
Total Load (ft²/Ton) 685 Air Room Peak (AC/hr) 6 3
Return Air (cfm) 220
Exhaust Airflow (cfm) 0
Infiltration (cfm) 19 19
Taco Load Program System Results 02/04/2012
Heating/Cooling Load calculations

System Basement TYPE: Constant Vol

PEAK LOAD occurs at 3 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 1606 0 5823
Window Solar 0
Wall Transmission 3197 0 11990 0
Wall Solar 1493 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 3153 3885 14662
Lights 4444 0 4444
People 2000 1600 2000
Equipment 2543 0 2543
Sub Total 18437 5485 0 32475 8987 0
Safety Factor 0 0 0 0 0
Total 18437 5485 0 32475 8987 0
Ventilation 3736 4603 14011

Total 22173 10088 0 46486 8987 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 869 Total Load (BtuH) 32261 46486 Water (gpm) 6.5 4.6
Volume (ft³) 7659 Total Load (BtuH/ft²) 37.1 53.5 Air Sm Rm Peaks (cfm) 960 590
Sensible Heat Ratio .69 Total Load (Ton) 2.7 Air Room Peak (cfm) 840
Total Load (ft²/Ton) 323 Air Room Peak (cfm/ft2) 1.0 .7
Air Room Peak (AC/hr) 7 5
Return Air (cfm) 950
Exhaust Airflow (cfm) 0
Infiltration (cfm) 143 178
Ventilation (cfm) 170
Taco Load Program System Results 02/04/2012
Heating/Cooling Load calculations

System First Floor TYPE: Constant Vol

PEAK LOAD occurs at 3 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 1606 0 5823
Window Solar 0
Wall Transmission 3576 0 13408 0
Wall Solar 1578 0
Roof Transmission 0 0 0
Roof Solar 0
Partition 0 0
Floor 0 0
Infiltration 3044 3751 15441
Lights 4598 0 4598
People 1750 1400 1750
Equipment 2666 0 2666
Sub Total 18817 5151 0 34672 9014 0
Safety Factor 0 0 0 0 0
Total 18817 5151 0 34672 9014 0
Ventilation 3956 4874 14835

Total 22773 10025 0 49507 9014 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 899 Total Load (BtuH) 32798 49507 Water (gpm) 6.6 5.0
Volume (ft³) 8091 Total Load (BtuH/ft²) 36.5 55.1 Air Sm Rm Peaks (cfm) 960 630
Sensible Heat Ratio .69 Total Load (Ton) 2.7 Air Room Peak (cfm) 860
Total Load (ft²/Ton) 329 Air Room Peak (cfm/ft2) 1.0 .7
Air Room Peak (AC/hr) 6 5
Return Air (cfm) 970
Exhaust Airflow (cfm) 0
Infiltration (cfm) 139 187
Ventilation (cfm) 180
Taco Load Program System Results 02/04/2012
Heating/Cooling Load calculations

System Packaged Roof Unit TYPE: Constant Vol

PEAK LOAD occurs at 3 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 1676 0 6064
Window Solar 0
Wall Transmission 4003 0 15013 0
Wall Solar 2871 0
Roof Transmission 980 0 3677
Roof Solar -152
Partition 0 0
Floor 0 0
Infiltration 4903 6040 25454
Lights 7097 0 7097
People 3250 2600 3250
Equipment 5683 0 5683
Sub Total 30311 8640 0 50207 16030 0
Safety Factor 0 0 0 0 0
Total 30311 8640 0 50207 16030 0
Ventilation 6154 7581 23077

Total 36465 16222 0 73284 16030 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 1388 Total Load (BtuH) 52687 73284 Water (gpm) 10.5 7.3
Volume (ft³) 12487.5 Total Load (BtuH/ft²) 38.0 52.8 Air Sm Rm Peaks (cfm) 1480 910
Sensible Heat Ratio .69 Total Load (Ton) 4.4 Air Room Peak (cfm) 1380
Total Load (ft²/Ton) 316 Air Room Peak (cfm/ft2) 1.0 .7
Air Room Peak (AC/hr) 7 4
Return Air (cfm) 1490
Exhaust Airflow (cfm) 0
Infiltration (cfm) 223 309
Ventilation (cfm) 280
Taco Load Program Building Results 02/04/2012
Heating/Cooling Load calculations

PEAK LOAD occurs at 3 PM, July Heating for 0 DB and 0 WB OSA

COOLING LOAD HEATING LOAD


Sensible Latent To RA Losses Int. Gain To RA
Window Transmission 4887 0 17710
Window Solar 0
Wall Transmission 10776 0 40411 0
Wall Solar 5942 0
Roof Transmission 980 0 3677
Roof Solar -152
Partition 0 0
Floor 0 0
Infiltration 11101 13676 55557
Lights 16139 0 16139
People 7000 5600 7000
Equipment 10892 0 10892
Sub Total 67565 19276 0 117354 34031 0
Safety Factor 0 0 0 0 0
Total 67565 19276 0 117354 34031 0
Ventilation 13846 17058 51922

Total 81411 36334 0 169277 34031 0

General Loads Flows

Cooling Heating Cooling Heating


Area (ft²) 3156 Total Load (BtuH) 117746 169277 Water (gpm) 23.5 16.9
Volume (ft³) 28237.5 Total Load (BtuH/ft²) 37.3 53.6 Air Sm Rm Peaks (cfm) 3400 2140
Sensible Heat Ratio .69 Total Load (Ton) 9.8 Air Room Peak (cfm) 3070
Total Load (ft²/Ton) 322 Air Room Peak (cfm/ft2) 1.0 .7
Air Room Peak (AC/hr) 7 5
Return Air (cfm) 3400
Exhaust Airflow (cfm) 0
Infiltration (cfm) 505 674
Ventilation (cfm) 630