Supplementary conditions for STARTER V5.5 HF1

Supplementary conditions and function restrictions as well as notes on configuration and operation.
These notes take priority over statements made in other documents.

ID Title Description of the restriction Solution for the restriction


235653 Projects created with STEP 7 Opening projects that have been created in STEP 7 incl. Install the missing option packages. Projects that have
/ Drive ES cause problems in Drive ES results in errors in STARTER stand-alone. been created in higher-order engineering environments
STARTER stand-alone can only be processed further in these environments.

235501 Error message after going Simultaneous connection of two or more computers or ---
online with an already commissioning tools (AOP, STARTER) with a drive unit
opened project is not prevented. Parallel online operation with several
commissioning tools is not permitted.
236330 TM31 is green in the PN If the 24 V power supply is switched off for a The consistency display is automatically refreshed after
although it is no longer component, an error message is output in the drive, but going offline or online.
available STARTER remains consistent.

242231 BOP: Access level change Access level of the BOP and STARTER are coupled in None
between the BOP and parameter p0003. There is no separate setting option.
STARTER
229732 "Save data to memory card" When saving data to the memory card, an error This error message can be ignored as the data has
results in an error message message is output although the data has been written. been written to the memory card.

Supplementary conditions for STARTER V5.5 HF1 © SIEMENS 2023 Unrestricted 1/6
SIEMENS

ID Title Description of the restriction Solution for the restriction


229732 Selection of 1PH8 motors 1PH8 motors with brake are not offered for selection in You must always select the same motor without brake
with brake is not possible in the STARTER drive wizard. (8th position of the MLFB): On induction motors with
the STARTER wizard MLFB 1PH8xxx-3xxx, you must select 1PH8xxx-1xxx.
On induction motors with MLFB 1PH8xxx-4xxx, you
must select 1PH8xxx-2xxx. The following parameters
must also be adapted manually via the expert list: -
Permissible maximum motor speed with existing
holding brake (p1082) - opening and closing times of the
holding brake (p1216, p1217) - consider the moment of
inertia of the holding brake (additionally to p341 or
p1498). The corresponding values are stored for the
specific types in the Configuration Manual for 1PH8
motors (Chapter Holding brakes). Note: If the brake
moment of inertia should be considered via p341, the
motor must be subsequently registered as p300 = 1
("induction motor (rotary)").

262011 FM "Spindle diagnostics": With the selection of the "Spindle diagnostics" function First select the "Spindle diagnostics" function module
p322 = 0 is set on activation module, the maximum motor speed p322 = 0 is set. For and then run through the drive wizard. p322 then shows
listed motors this value cannot be changed manually the current maximum motor speed value.
due to write protection.
295224 Scrollbar is missing in the Without the horizontal scrollbar, you cannot view all If this problem occurs, it can be corrected by restarting
"Power unit supplementary information in the screen form. the wizard.
data" wizard for DCM
230518 Browsing in the online help to In the online help for drive parameters, the following Currently, a manual search is possible via the index or
the Parameter & fault list cross-references ('See also' or 'Further information') are search function.
available for a fault or alarm at 'Dependency'. Currently,
direct access to the specified alarm or parameter
number is not possible.
237771 DDS display in the expert list Drive data sets (DDS) can be activated online via P180, Change parameter P180 and then load the project to
and screen forms but they are not displayed in the screen forms or in the the PG. This refreshes the "Online view" and the indices
expert list. If DDS >1 is activated in the device (via of the drive data sets are displayed.
P180=3), then the indices are not displayed in the expert
list for DDS parameters in STARTER.

Supplementary conditions for STARTER V5.5 HF1 © SIEMENS 2023 Unrestricted 2/6
SIEMENS

ID Title Description of the restriction Solution for the restriction


238917 STARTER: General During a download, supplementary data (user data) is None
supplementary data is not not loaded to the target system. This also applies to the
stored on the CF card during storage of data on the CF card. This data is therefore
a download not stored on the CF card and is not displayed in
STARTER (e.g. in the Comparison dialog).

236198 Error during download with During a download, supplementary data (user data) is None
supplementary data not loaded to the target system. Accordingly, the
supplementary data is also not displayed in STARTER
(e.g. in the Comparison dialog).
230631 STARTER crash when When printing entire chapters with sections in the help, Only print individual topics and avoid printing large
printing a chapter of the OH STARTER cannot be operated for some time because chapters.
of the large data volume.
245325 After changing the units in After changing the units in the expert list (online), the The units must be changed offline. A download to the
the expert list, there is no display in the "Units" column is not updated target device is then required.
update of the units
236200 Problems with the unit The unit system cannot be changed via the expert list, The unit system can be changed offline for every drive
changeover P505 neither offline nor online. object on the Configuration -> Units page.

262994 Parallel connection can be The Motor Modules 6SL3320-1PG2x-xULx do not Do not select parallel connection in STARTER for the
selected for the new support a parallel connection. However, parallel Motor Modules 6SL3320-1PG2x-xULx.
blocksize Motor Modules connection can be selected in the STARTER wizard.
237069 STARTER cannot be After converting a project created with SIMOTION The message windows open after the conversion are
operated after converting a SCOUT, it may be that STARTER can no longer be not visible. They must be brought to the foreground with
project operated. During conversion, STEP 7 messages are ALT +TAB. STARTER can only be operated after these
output in the background that the user does not notice. messages have been acknowledged.

239102 STARTER: SlaveOM and Telegrams 700 (SIC) and 701 (SIC) cannot be Use PROFIBUS GSD or PROFINET GSD.
DeviceOM do not provide configured in the HW Config via SlaveOM and
telegrams 700 SIC / 701 DeviceOM.
SCC
244441 STARTER V4.3 - CU240E-2 If the G120 is connected via USB and a comparison is The G120 must then be restarted (Power off/on) in
V4.4 - USB connection hangs triggered, the connection is terminated. It may then no order to go online again.
up during a comparison longer be possible to go online with the G120 via USB.

Supplementary conditions for STARTER V5.5 HF1 © SIEMENS 2023 Unrestricted 3/6
SIEMENS

ID Title Description of the restriction Solution for the restriction


236251 No active node for After disconnecting and connecting USB-capable In the "Device Manager / Universal Serial Bus
Accessible nodes, USB, devices several times, it can occur that no node is Controllers", deactivate the appropriate "USB Enhanced
Windows XP detected. Host Controller" and then activate it shortly afterwards,
or restart the PC.
235312 You cannot go online via the No nodes are found with Accessible nodes if the device Do not use a USB hub, connect the device directly.
USB hub is connected via a USB hub.
234105 Automatic controller STARTER less than V4.1.2: The automatic controller If the automatic controller setting does not provide
optimization: Setting a setting for servo has not been released. STARTER as of satisfactory results, the controller and filters can be set
bandstop filter for resonance V4.1.2: The automatic controller setting for servo may manually.
not provide the best possible settings in all cases. This
applies especially to the placing of bandstop filters.
234707 Safety commissioning online: With a CUA31 HW version C or less, safety functions of Use a CUA31 with a HW version greater than C.
Change default setting p9601 the V4.5 firmware can be configured in STARTER, but
for CUA31 HW version C not used.
259259 DriveES: DeviceOM: No If an S120 configured on the PROFINET IO system is None
prompt that the program at deleted in the HW Config via DeviceOM, there is no
the drive will be deleted prompt whether the associated program should also be
deleted. The program can therefore be lost.
260535 Error message during the Error message during the automatic commissioning with It is not permitted to configure several separately
automatic commissioning of several ALMs on one CU. functioning ALMs on one infeed. Several ALMs can only
the project with four ALMs be configured in parallel connection on one CU.
and four MoMos
301059 Faulty text display with For the "Standard display setting = 125%" (Windows 7), With "Display setting = 100%", everything is correctly
Windows 7 "Display setting = texts are shifted or are incompletely displayed for some displayed.
125%" starter screens.
342571 Starter gets slower if more Starter gets slower if more communication masks are Keep the number of open communication masks as low
communication masks are opened in parallel. as possible.
opened in parallel. Error message about exhausted system resources may
appear.
267363 DCC: The basic sampling r21002 and r21003 are not updated offline (expert list). Parameters r21002 and r21003 can be determined in
time is not displayed offline the 'Set Execution Groups' dialog. The value of r21002
corresponds to p115[0], r21003 corresponds to
r7901[15]

Supplementary conditions for STARTER V5.5 HF1 © SIEMENS 2023 Unrestricted 4/6
SIEMENS

ID Title Description of the restriction Solution for the restriction


290731 DCC: RGJ: Overshoot for If the RGJ block is operated with RQN=1 (smoothing In order to prevent that the output value of the RGJ
YA, smoothing active, follow- on) and CF=1 (output follows input), jumps in the input ramps-up without any limits, ONLY the limited output YL
up inactive variable X can sporadically cause output Y to oscillate must be used to interconnect the setpoint. The limits LL
above the limits LL and LU until the input variable is and LU must be set to the mechanically permissible
changed again. values for the drive train.
Therefore, only output signal YL should be used to The speed limits in the drive must also be
interconnect the signal, and limits LL and LU must be parameterized so that the limits of the mechanical
set to the mechanical values permissible for the system can never be exceeded.
particular drive train.
The speed limits in the drive must also be
parameterized so that the limits of the mechanical
system can never be exceeded.
269509 DO renaming at XML import If a DCC license is not available, a changed DO name is Perform import with DCC license
not automatically adapted when importing a DCC chart.

269535 Upload after know-how After deactivating the device know-how protection on The project must be saved offline before activating the
protection activation is not the drive unit, an error occurs during the upload when device know-how protection on the drive unit.
possible the online project contains a DCC chart.
269565 Crash in connection with With a DCC chart under the CU, a sampling time of Use a different sampling time.
SAH_BY and factory 400x and around 100 blocks in the run sequence
settings, loading into target calculated prior to an SAH_BY block, the target device
device can crash when the factory settings are restored or the
project is loaded into a target device.
269564 Detail comparison doesn't If DCC charts cannot be compiled without errors offline, Correct the DCC compilation error before starting the
always work when DCC the DCC detail comparison may be completed with detail comparison function.
charts are faulty errors.
269534 DCC: Loading into the PG is After deactivating the device know-how protection on Save the project before activating the device know-how
not possible after the drive unit, an error occurs during the upload when protection on the drive unit or use the standard library
deactivating the device know- the online project contains a DCC. dcblib V4.8 in the project.
how protection

Supplementary conditions for STARTER V5.5 HF1 © SIEMENS 2023 Unrestricted 5/6
SIEMENS

ID Title Description of the restriction Solution for the restriction


267485 DCC: After converting and If a created project is converted to a higher STARTER version, In the event of an error, note the names of the DCCs that
reconverting the project, and the project is then compiled with "Save and recompile all", cannot be read and delete these subsequently. Then replace
problems occur in SINAMICS in and then reconverted again to the original STARTER version the noted names with the names of the readable DCCs and
conjunction with DCCs when via "Save in old project format", SINAMICS inconsistency is recompile. A download should then be performed.
uploading to the PG. displayed after connection to the target device. No errors
occur when loading to the PG, but a further DCC is added for
each DCC below the DO. The DCC can be read.
267319 DCC: Discrepancies occur when DCC lets you program new block types in the graphical Before a new download with a changed library type, restore
DCC projects are edited without programming language. These block types are managed in factory settings (SINAMICS) or delete user data on card
a CFC Editor license; DCC libraries. A block type is created from each DCC, and can (SIMOTION)
No new download when then be called in the DCC. Installable DCB libraries can be
changing the type of library created from the graphically created DCC libraries via the
context menu "Create DCB library". These can be transported
irrespective of a STEP 7 project, and can be used in the DCC
after installation in STARTER / SCOUT. Switching from the
graphically created DCC library to the installable library does
not require any further changes to the block calls in the DCC.
Only the library imported in the chart must be changed using
Options -> Block Types. If a project with DCC is loaded in the
target device, and only the library type is changed in the DCC,
the DCCs are not loaded to the target device again during
download. When loading to the PG into an empty project, an
error message appears: "Upgrading block types is not possible
due to missing libraries. Please install the libraries and re-open
the project."

269578 DCC: Blocks of a DCB lib are Between sinamics dcbib V4.7 and sinamics dcblib V5.1 Use the dcblib version with which the functionality was
no longer calculated after the sequence of execution of INIT methods changed: If tested
restarting the CU you use dcblib sinamics V4.7 or older then the block
instances in the chart are executed from the end to the
beginning. Using dcblib V5.1.1 or newer the block
instances are calculated from the start to the end.

Supplementary conditions for STARTER V5.5 HF1 © SIEMENS 2023 Unrestricted 6/6