Article 225 - Outside Branch Circuits and Feeders

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Copyright 2014 National Fire Protection Association (NFPA).

Licensed, by agreement, for individual use and single download on February 18, 2014 to Northern NY Chapter of NECA for designated user Martin
Sullivan. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact licensing@nfpa.org.

220.100 ARTICLE 225 — OUTSIDE BRANCH CIRCUITS AND FEEDERS

V. Farm Load Calculations Table 220.103 Method for Calculating Total Farm Load

220.100 General. Farm loads shall be calculated in accor- Individual Loads Calculated in Demand Factor
dance with Part V. Accordance with Table 220.102 (%)

220.102 Farm Loads — Buildings and Other Loads. Largest load 100
Second largest load 75
(A) Dwelling Unit. The feeder or service load of a farm Third largest load 65
dwelling unit shall be calculated in accordance with the Remaining loads 50
provisions for dwellings in Part III or IV of this article.
Note: To this total load, add the load of the farm dwelling unit calcu-
Where the dwelling has electric heat and the farm has elec-
lated in accordance with Part III or IV of this article. Where the
tric grain-drying systems, Part IV of this article shall not be dwelling has electric heat and the farm has electric grain-drying sys-
used to calculate the dwelling load where the dwelling and tems, Part IV of this article shall not be used to calculate the dwelling
farm loads are supplied by a common service. load.

(B) Other Than Dwelling Unit. Where a feeder or service


supplies a farm building or other load having two or more structures, or poles on the premises; and electrical equip-
separate branch circuits, the load for feeders, service con- ment and wiring for the supply of utilization equipment that
ductors, and service equipment shall be calculated in accor- is located on or attached to the outside of buildings, struc-
dance with demand factors not less than indicated in Table tures, or poles.
220.102. Informational Note: For additional information on wiring
over 1000 volts, see ANSI C2-2007, National Electrical
Safety Code.
Table 220.102 Method for Calculating Farm Loads for
Other Than Dwelling Unit •
225.3 Other Articles. Application of other articles, includ-
Demand Factor ing additional requirements to specific cases of equipment
Ampere Load at 240 Volts Maximum (%) and conductors, is shown in Table 225.3.
The greater of the following:
All loads that are expected to operate 100 I. General
simultaneously, or
125 percent of the full load current of 225.4 Conductor Covering. Where within 3.0 m (10 ft) of
the largest motor, or any building or structure other than supporting poles or
First 60 amperes of the load
Next 60 amperes of all other loads 50
towers, open individual (aerial) overhead conductors shall
Remainder of other loads 25 be insulated for the nominal voltage. Conductors in cables
or raceways, except Type MI cable, shall be of the rubber-
covered type or thermoplastic type and, in wet locations,
220.103 Farm Loads — Total. Where supplied by a com- shall comply with 310.10(C). Conductors for festoon light-
mon service, the total load of the farm for service conduc- ing shall be of the rubber-covered or thermoplastic type.
tors and service equipment shall be calculated in accor- Exception: Equipment grounding conductors and grounded
dance with the farm dwelling unit load and demand factors circuit conductors shall be permitted to be bare or covered as
specified in Table 220.103. Where there is equipment in specifically permitted elsewhere in this Code.
two or more farm equipment buildings or for loads having
the same function, such loads shall be calculated in accor- 225.5 Size of Conductors 600 Volts, Nominal, or Less.
dance with Table 220.102 and shall be permitted to be The ampacity of outdoor branch-circuit and feeder conduc-
combined as a single load in Table 220.103 for calculating tors shall be in accordance with 310.15 based on loads as
the total load. determined under 220.10 and Part III of Article 220.

225.6 Conductor Size and Support.

(A) Overhead Spans. Open individual conductors shall


ARTICLE 225
not be smaller than the following:
Outside Branch Circuits and Feeders
(1) For 1000 volts, nominal, or less, 10 AWG copper or
8 AWG aluminum for spans up to 15 m (50 ft) in
225.1 Scope. This article covers requirements for outside length, and 8 AWG copper or 6 AWG aluminum for a
branch circuits and feeders run on or between buildings, longer span unless supported by a messenger wire

70–76 NATIONAL ELECTRICAL CODE 2014 Edition

You might also like