MEW01215 Revision: 8 EBL512 G3 Table of Drawings 2014-05-14

A = Approved and valid drawing. Also available as a pdf file.


N = Not approved or not valid drawing.
DWG Sheet Rev. Date or Title
No. Rev.
512 G3 - Date EBL512 G3 ........
A 01 1/2 2 13-01-30 Control unit (C.i.e.) 5000 / 5001
Dimensions & overview
A 2/2 2 14-01-10 Control unit (C.i.e.) 5000 / 5001
Dimensions & overview
A 02 1/1 2 14-01-10 Control unit (C.i.e.) 5000 / 5001
Block diagram
A 03 1/1 1 12-02-01 Control unit (C.i.e.) 5000 / 5001
Internal connection diagram

A 11 1/1 2 14-01-16 Main board 5010


Dimensions & overview, P.c.b. no. 9290-4A
A 12 1/1 1 12-02-01 MMI board 5011
Dimensions & overview, P.c.b. no. 9291-4A
A 13 1/1 1 14-01-16 TLON connection board 1590
Dimensions & overview, P.c.b. no. 9302-3B
A 14 1/1 1 14-01-16 8 zones expansion board 4580
Dimensions & overview, P.c.b. no. 9287-3A
A 15 1/1 1 14-01-16 8 relays expansion board 4581
Dimensions & overview, P.c.b. no. 9286-2B
A 16 1/1 - 10-06-03 I/O Matrix board 4582
Dimensions & overview, P.c.b. no. 9292-1A
A 17 1/1 2 14-01-16 In & Outputs expansion board 4583
Dimensions & overview, P.c.b. no. 9215-1A

A 21 1/1 3 14-01-31 Main board 5010, T.B. J2


Connection diagram, Power supply 5037
A 22 1/1 2 13-01-30 Main board 5010, T.B. J3
Connection diagram, Web-server & Power supply outputs 0-4
A 23 1/2 3 13-12-30 Main board 5010, T.B. J4:1-20
Connection diagram, Out- & inputs S0-S3, R0-R1 & I0-I3
A 23 2/2 - 13-12-30 Main board 5010, T.B. J4:1-20
Connection diagram, Out- & inputs S0-S3, R0-R1 & I0-I3
A 24 1/1 3 13-01-30 Main board 5010, T.B. J4:21-40
Connection diagram, Fire & Fault tx, TLON Network, D.U.
A 25 1/1 2 14-01-27 Main board 5010, T.B. J5
Connection diagram, COM loops 0-3
A 26 1/1 3 14-01-30 Main board 5010, Connector J9
Connection diagram, Expansion boards 458x

A 31 1/1 4 14-05-07 Main board 5010, T.B. J5


Connection diagram, COM loop units
A 32 1/1 2 12-02-01 Main board 5010, T.B. J3:1-2 & J7
Connection diagram, Web-server II, 1598
A 33 1/1 1 14-02-05 8 zones expansion board 4580, J1 & J2
Connection diagram, Zone line inputs 0-7 / units
A 34 1/1 1 14-02-05 8 relays expansion board 4581, J1 & J2
Connection diagram
A 35 1/3 3 13-12-30 I/O expansion board 4583, J1 & J2
Connection diagram, Inputs & Outputs / units
A 2/3 1 13-12-30 I/O expansion board 4583, J1 & J2
Connection diagram, Supervised Inputs / units
A 3/3 - 13-12-30 I/O expansion board 4583, J1 & J2
Connection diagram, Supervised Inputs / units
A 36 1/1 2 14-02-05 Addressable Multipurpose I/O unit 3361
Connection diagram, COM loop / In- & outputs / Examples

L:\Drawings\CAD\EBL512 G3\MEW01215 (Rev 8).docx


MEW01215 Revision: 8 EBL512 G3 Table of Drawings 2014-05-14

A = Approved and valid drawing. Also available as a pdf file.


N = Not approved or not valid drawing.
DWG Sheet Rev. Date or Title
No. Rev.
512 G3 - Date EBL512 G3 ........
A 37 1/2 3 14-02-06 Hazardous (Ex) areas equipment
Connection diagram, Inputs / units
A 2/2 - 10-06-03 Hazardous (Ex) areas equipment
14-02-06 Connection diagram, Inputs / units
A 38 1/1 4 14-01-17 Addressable 2 voltage outputs unit 3364
Connection diagram, Ext. power supply 3366

A 41 1/1 1 14-02-06 COM loop cable


Cable length & specifications
A 42 1/1 1 14-02-06 TLON Network, Examples, 2-12 Control units
Connection diagram
A 43 1/1 1 14-02-06 TLON Network, Example, 30 Control units + 5 Routers
Connection diagram

L:\Drawings\CAD\EBL512 G3\MEW01215 (Rev 8).docx


Revision Revision date Revision note Signature Checked
Internal connection diagram, see drawing 512 G3 - 03. 1 2012-02-01 Info (article numbers) added. Some texts updated. JP MÖ

USB (B) Web-server II, 1598


connector See drawing 512 G3 - 32

5089

Door 3) 3)
switch LCD (5038) Front (5060 / 5061)
Expansion boards
no. 0 - 5
J9 J12 J7 J13

{
1

{
COM loops
2
3

458x
4
5
6
7
8
9
J5
J1 J1
See drawings 512 G3 - 25, - 31
10
11
12
13

1) J2
14
15
16

J1

{
1
2
3

J18 J2: 10 conductors ribbon cable


4
5
6
7
8

J3: 15 conductors ribbon cable


9

J9
10
11
12
13

External equipment 5010


14
15

J2
16
17

J3
18
19
20
21
J4
See drawings 512 G3 - 23, - 24 Main board 5011 MMI board
22
23
24

0
25
26
27
28
29
30

32

34
31

33

35
J4 J7 J6
36
37
38
39
40

0
24 V DC outputs
{ 1590 /
1
2
3
4

J3
5
6

See drawing 512 G3 - 22


8
7

9
0
5090
10
11
12

1
J4: 14 conductors ribbon cable
2
1
3
J2 1590 /
4
1
5
5090

{
J10 0 1 J11
458x Backside view
1)
Loudspeaker (5036)3)
J1

Not in 5001.
J2
5000 / 5001 Standard equipment:
5 5010 Main board
Power supply 5037
(Rectifier) 2) 5011 MMI board (not in 5001)
T6.3A H 250V 230 V AC, 1.6 A 5037 Power supply
(5x20mm ceramic) 24 V DC, 6.5 A 5038 Display - LCD (not in 5001)
3)
Printer (5058) 5060 / 5061 Front (not in 5001)
Not in 5001.
Options:
1590 / 5090 TLON Network connection board
1598 Web-server II
4580 8 zones exp. board
Battery Battery 4581 8 relays exp. board
12 V, 28 Ah 12 V, 28 Ah
4583 I/O exp. board
5089 Exp. boards connection cable
Battery temperature
sensor (5039) Spare parts:
3) 5036 Loudspeaker
E.g. Panasonic LC-P1228AP 5038 LCD

10 mm
5039 Battery temp. sensor
Mains 230 V AC 5058 Printer
(via a two-way circuit breaker) 5059 Printer paper roll

Original drawing A3L (420 x 297 mm)


5060 / 5061 Front
Designed by Checked by Approved by Filename Date Scale
1) Connection of external equipment, see drawings 512 G3 - 33 - - 35.
2) 5000 can be delivered with or without a printer depending on the article number (5000xxx). JP MÖ RP 512 G3-02_11.cdr 2010-06-03 --
3) Spare part number. Drawing title
EBL512 G3, Control unit (C.i.e.) 5000 / 5001
Block diagram
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 02 1/1 1
Revision Revision date Revision note Signature Checked
1)
C.i.e. skin C.i.e. metal housing 2 2013-01-30 Cable entry (Grommet): New type. Company name updated. JP MÖ
(to be mounted on the c.i.e. metal housing) (to be mounted on the wall mounting plate)
Wall mounting plate
The supplied Wall mounting plate is approved for
mounting on an inconbustable wall, e.g. concrete.
Options
Cable entry (Grommet) For mounting on an inflammable wall, e.g. wood, the
12 x Ø 12.6 mm Wall mounting plate 5021 can be used with cable glands.
C.i.e. skin top 5 x Ø 10.5 mm For mounting in a 19" mounting rack, the Wall mounting
C.i.e. earth point plate 5020 can be used.
2 x Hook for the C.i.e. metal housing 320 mm
Door switch USB port (type "B")
C.i.e. front with LCD
438 mm (418) behind plexiglass

Slit for the hook on the


wall mounting plate 52 mm
628 mm
(625)
Magnet
458x
Main board 5010
Cable
Symmetric 35 mm DIN rail entry
for Web-server 1598 opening.
TLON connection board 1590/5090, no. 0
458x (Plugged on the Main board 5010.) 100 x 320 600
mm mm
TLON connection board 1590/5090, no. 1
(Plugged on the Main board 5010.) 110 mm

2 x Cable entry opening.


37 x 128 mm 557
Power supply 5037
458x mm
(Rectifier)
230 V AC, 1.6 A
24 V DC, 6.5 A
C.i.e. door with plexiglass
Battery holder
ahead of the c.i.e. front

Space for batteries


2 x 12 V, 28 Ah

Battery temp. 2 x M6 Bolt


sensor (5039) For C.i.e. metal housing fixing
2)
2 x M6 Nut
For C.i.e. metal housing fixing
408 mm

Up to six Expansion boards 458x. 4 x M6 Nut


Extensible plate for information, labels etc. Mounted in two levels. For C.i.e. skin fixing 4 x Hole Ø 6 mm Cable entry
One board holder for level one Cable entry For wall mounting 40 x 40 mm
and one for level two. Knock-out Ø 23 mm

10 mm
Depth 187 mm (177)
C.i.e. skin bottom Mains cable clamp 1. Put up the wall mounting plate on the wall.
2. Hook the C.i.e. metal housing on the wall mounting plate and fix.

Original drawing A3L (420 x 297 mm)


3. Do all cable connections, C.i.e. commissioning, etc.
4. Put the C.i.e. skin on the metal housing and fix it.
Designed by Checked by Approved by Filename Date Scale
See also drawing 512 G3 - 01, sheet 2 / 2.
JP MÖ RP 512 G3-01_12.cdr 2010-06-03 Approx. 1:5
1) 5001 has no C.i.e. skin , i.e. no door with Plexiglass. Drawing title
EBL512 G3, Control unit (C.i.e.) 5000 / 5001
Instead it has a grey metal "hood", which dimensions are written within parentheses. Dimensions & overview
5001 has no front, no LCD and no printer. Drawing number Sheet Revision
2) Spare part number. Panasonic Eco Solutions Nordic AB
512 G3 - 01 1/2 2
Revision Revision date Revision note Signature Checked

1 2012-02-01 Some texts updated. Note 4 added. JP MÖ

C.i.e. front door with printer C.i.e. 5000 with printer


(the front door is hinged on the c.i.e. metal housing) (door open)

Frontside view Backside view

Door switch USB port (type "B")


C.i.e. front 5060/5061 with LCD (5038) Hinge with spring, for easy fixing / removal
4) of the front door on / from the c.i.e. metal housing
LCD (5038)
4)

MMI board 5011

C.i.e. skin with


the door opened

4) Key to unlock and


Release button Paper feed button Loudspeaker (5036), open the door
(green) for mounted on the backside
change of Mounting frame
paper roll for printer 2)
1)
3)
Printer Printer paper roll (58 mm) - inside. Printer 2 x M5
1) (5059) (backside) Bolt & Nut
4) 1)
Printer (5058)
4)
Holder on the inside of the
door for building drawings etc.

5001 has no C.i.e. skin , i.e. no door with Plexiglass.


Instead it has a grey metal "hood".
5001 has no front door, i.e. no front, no MMI board, no LCD and no printer.

Extensible plate for information, 4 x M6 Hexagon socket button head screw


labels etc. For C.i.e. skin fixing

10 mm
Original drawing A3L (420 x 297 mm)
Designed by Checked by Approved by Filename Date Scale
1) 5000 can be delivered with or without a printer depending on the article number (5000xxx). See also drawing 512 G3 - 01, sheet 1 / 2.
2) 5000 without a printer has no Mounting frame for printer. JP MÖ RP 512 G3-01_21.cdr 2010-06-03 Approx. 1:5
3) 5000 without a printer has no opening for printer in the plate below the c.i.e. front. Drawing title
4) Spare part number.
EBL512 G3, Control unit (C.i.e.) 5000 / 5001
Dimensions & overview
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 01 2/2 1
Revision Revision date Revision note Signature Checked
This drawing shall be read in conjunction with drawing 512 G3 - 02. 1 2012-02-01 Some texts updated. Note 5 added. JP MÖ

C.i.e. 5000 / 5001

Mains Battery Battery 5037 5010 Main board USB (B) Door Temp. 458x
230 V AC (Left) (Right) Power switch sensor (Expansion board)
supply
J1 J2 ETM 1 ETM 2 J10 J11 J4 J12 J13 J18 J9 (5039) J2 J2 J2 J2 J2 J2
1) 2) USB (B) 4) 4) 5) (no.0) (no.1) (no.2) (no.3) (no.4) (no.5)

L L F1 7 27 1 1

N N F2 8 28 2 2

? FG 29 3 3

V+ 1+ 30 4 4

V- 2- F1 7 31 1

+ 4+ F2 8 32 2

- + 33 1

- 5- 34 2

To be cont. below.
4) 4)
12

1 1 1 1 1 1 1

2 2 2 2 2 2 2

3 3 3 3 3 3 3

4 4 4 4 4 4 4

C.i.e. 5000

5011 MMI board 5060 / 5061 LCD (Display) Loud- Printer 3)


(Front) (5038) speaker (5058)
5) 5)
(5036)
J1 J2 J3 J4 J6 J7 J9 5)

1 1 1

2 2 2

To be cont. above.
12 10 10

1 1

2 2

15 15

1 1

2 2

14 14

1 1

4 2

1 +5 V

10 mm
2 TxD

3 RxD

4 RTS

5 GND

Original drawing A3L (420 x 297 mm)


Designed by Checked by Approved by Filename Date Scale
1) Connected to optional 1590 TLON connection board no. 0.
2) Connected to optional 1590 TLON connection board no. 1. JP MÖ RP 512 G3-03_11.cdr 2010-06-03 --
3) 5000 can be delivered with or without a printer depending on the article number (5000xxx). Drawing title
EBL512 G3, Control unit (C.i.e.) 5000 / 5001
4) Not in 5001. Internal connection diagram
5) Spare part number. Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 03 1/1 1
Revision Revision date Revision note Signature Checked
Connections to the Terminal Blocks J2-J5 and connectors J7 & J9 according to the drawing 512 G3 - nn respectively.
1 2012-02-01 Some texts updated. Note 3 added. JP MÖ
Other connections according to the drawings 512 G3 - 02 & - 03.
512 G3 - 22 512 G3 - 24 512 G3 - 23 512 G3 - 25 The p.c.b. is mounted in
the C.i.e. housing according to
260 mm 512 G3 - 21 drawing 512 G3 - 01.

12

10

16

14

12

10
40

38

36

34

32

30

28

26

24

22

20

18

16

14

12

10
8

2
8

2
T.B. J2
200 mm

15

13
11

11
39

37

35

33

31

29

27

25

23

21

19

17

15

13

11
9

1
9

1
J9
T.B. J3 T.B. J4 T.B. J5
NOTE! Most of the components are deleted on the p.c.b. to the right, for easier identification of connectors, etc.

For connection of

1
Expansion boards 512 G3 - 26
458x (J2)
F2 F1
J12
F12 F10 F8 F19 F7 F6 F5 F4 Internal connection
F11 F9 F13 to USB port (type "B") mounted
F18 in the metal housing frame,
intended for connection of
Not used a laptop PC (Win512 G3)

LED D11
Blinking: TLON board
no. 0 communicating. J7
Steady: TLON board For connection of
no. 1 (back-up board) F14 F17 F16 F15 Web-server 1598 512 G3 - 32
communicating. (RS232)

JP1
Service pins for
TLON board no. 0 SW2 1)
Main board (C.i.e.) boot
JP2
Service pins for P.c.b. label for
TLON board no. 1 identification

J10 (RJ-45) LED D24


For connection of a Steady: Normal condition.
laptop PC (TLON Off: Watchdog fault (C.i.e. dead)
Manager) to TLON or Main board in "Boot" mode.
board no. 0
F3: T3.15 A L 250V
(5x20mm glass)
J11 (RJ-45)
4A

2) 2)
For connection of a J13
laptop PC (TLON Internal connection
F3
Manager) to TLON to the C.i.e. door switch
board no. 1

10 mm
1)
SW1
Main board (i.e. C.i.e.) restart

Original drawing A3L (420 x 297 mm)


J1, Internal connection
Optional TLON board Optional TLON board J18, Internal connection to
to MMI board 5011, J1
1590 / 5090, no. 1 1590 / 5090, no. 0 battery temperature sensor (5039) 3)
Designed by Checked by Approved by Filename Date Scale
1) Used to set the Main board in "Boot" mode, e.g. in conjunction with new software download. F1-F2: See drawing 512 G3 - 21
2) If only one TLON board 1590 shall be used, it has to be position / no. 0. F3: 24 V for MMI board 5011 JP MÖ RP 512 G3-11_11.cdr 2010-06-03 Approx. 1:1
TLON board layout according to drawing 512 G3 - 13. F4-F7: See drawing 512 G3 - 23
Drawing title
3) Spare part number.
F8-F12: See drawing 512 G3 - 22 EBL512 G3, Main board 5010
F13: See drawing 512 G3 - 26 Dimensions & overview P.c.b. no. 9290-4A
F14-F17: See drawing 512 G3 - 25
F18: See drawing 512 G3 - 22 Drawing number Sheet Revision
F19: See drawing 512 G3 - 24
Panasonic Electric Works Nordic AB
512 G3 - 11 1/1 1
Revision Revision date Revision note Signature Checked
1) Mains 2 2013-01-30 F1 & F2: Info. updated. Company name updated. JP MÖ
230 V AC

C.i.e. 5000 / 5001 Internal connections on Main board 5010


7)
P.c.b. layout, see drawing 512 G3 - 11.
1 0
Terminal Block J2
T6.3A 250V (5x20mm ceramic)
Red 1 +
+24 V
Black 2 - F1
0V
3
T6.3A 250V (5x20mm ceramic)
Red 4 +
F2 Battery charger
Black 5 -

Power supply 5037


Recommendations
5) - First connect the batteries, then the mains (230 V AC).
4) - If the batteries are not connected, the fuse "F1" has
Brown
to be on place before connection of the mains.
L
2) (AC)
Blue
N
Yellow-Green
3) FG

-V
T6.3A H 250V (5x20mm ceramic)
4) Power supply mounted in the C.i.e.
CAUTION:
RISK OF EXPLOSION IF BATTERY -V according to drawing 512 G3 - 01.
IS REPLACED BY INCORRECT TYPE. F
DISPOSE USED BATTERIES +V
ACCORDING TO THE INSTRUCTIONS. NOTE!
+ - + - External batteries
The lid for the screw terminals shall after the
+V installation be correctly applied, i.e. protecting
Batteries > 28 Ah (but < 65 Ah) have to be the screw terminals.
placed outside the c.i.e.

The European Standard EN 60950-1:2006 and


National regulations have to be followed. 6) V ADJ. (SVR1)

10 mm
Due to the battery checking function, (LED1)
cables max. 3 m & min. 4 mm2 are recommended.
2 x 12 V, 28 Ah (placed inside the c.i.e.) Connections also according to

Original drawing A3L (420 x 297 mm)


Sealed Lead-Acid battery, shall fulfil UL94V-0. drawings 512 G3 - 02 & - 03.
E.g Panasonic LC-P1228AP
1) Connected to a household removable fuse intended for the fire alarm c.i.e. only. National regulations have to be followed. Designed by Checked by Approved by Filename Date Scale
2) The mains cable shall be securely clamped in the C.i.e. housing / chassis and the wires shall be as short as possible. JP MÖ RP 512 G3-21_12.cdr 2010-06-03 --
3) The mains safety earth (ground) wire shall be longer than the other wires to ensure that it is the last to be disconnected if the mains cable clamp should fail. Drawing title
EBL512 G3, Main board 5010, T.B. J2
4) Cable tie to keep the 24 V DC wiring well separated from the mains wires.
Connection diagram Power supply 5037
5) Switched power supply, Meanwell S-150-24. 230 V AC, 1.6 A / 24 V DC, 6.5 A.
Drawing number Sheet Revision
6) Voltage adj. range 21 - 28 V. Factory adjusted to 24 V and sealed. Panasonic Eco Solutions Nordic AB
7) A two-way circuit breaker, mounted outside and close to the c.i.e. To be used by service / maintenance personell. National regulations have to be followed. 512 G3 - 21 1/1 2
Revision Revision date Revision note Signature Checked

2 2013-01-30 F8-F12 & F18: Info. updated. Company name updated. JP MÖ

Internal connections on Main board 5010


P.c.b. layout, see drawing 512 G3 - 11.

T2A 250V (TR5)


Terminal block J3 T500mA 250V (TR5)
5)
1 F18 (2A)
1) +24 V +24 V
Web-server Power supply output 0V
2
0V
3 F8 (500mA)
2) +24 V
Power supply output 0 0V
4
5 F9 (4A)
+24 V
Power supply output 1 0V
6
7 F10 (4A)
+24 V
Power supply output 2 0V
8
9 F11 (4A)
+24 V
Power supply output 3 10
0V
11 F12 (4A)
+24 V
Power supply output 4 0V
12

4 x T4A 250V (TR5)

NOTE!
The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).
4)
3) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
In fire alarm condition < 6.0 A is available for the c.i.e. and all connected equipment.

10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale
1) See drawing 512 G3 - 32.
2) Normally used for routing equipment (fire brigade tx). JP MÖ RP 512 G3-22_12.cdr 2010-06-03 --
3) In quiescent condition the battery charging current can be up to 3A (6.3-3=3.3A). Drawing title
EBL512 G3, Main board 5010, T.B. J3
Battery charging will be turned off during fire alarm condition (6.0-0=6.0A).
Connection diagram, Web-server & Power supply outp. 0-4
4) Note that if 28 Ah batteries are used and 30 hours battery back-up time is required, max. 0.93 A can be used in quiescent condition (since 30 x 0.93 = 28).
Drawing number Sheet Revision
5) The fuse F18 is not supervised. Panasonic Eco Solutions Nordic AB
512 G3 - 22 1/1 2
Revision Revision date Revision note Signature Checked
Main board 5010
2 2012-02-01 Note 2: Info added. JP MÖ

INTERNAL
WIRING
3)
Web-server II, 1598 1. TX+
2. TX-
3. RX+
4.
PLC COM 5.
J7 (RS232C) ETHERNET COM 6. RX-
7.
8.
1 YELLOW YELLOW S (TXD) 8
RxD
GREEN RS232 SERIAL LINE FOR WEB-SERVER GREEN For connection to a 4)
2 R (RXD)
TxD Local Area Network.
3 BLACK BLACK G (GND)
(0V) GND 1

(MALE, MOLEX TYPE KK, 2.54) RJ-45


0.65 m CABLE, SUPPLIED WITH THE WEB-SERVER

0.65 m CABLE, SUPPLIED WITH THE WEB-SERVER MODEM COM


J3 POWER SUPPLY (RS232C)

2) 1 BROWN BROWN
+24 V + For connection to a separat
6 1
2 BLUE BLUE presentation system when
0V - 9 5 the Gateway function is used.
GREEN GREEN
EARTH 1)
EMI FILTER
1.
2. RxD
(MALE, MOLEX TYPE KK, 3.5) (SERIAL PORT, 3. TxD
J2 MALE 9-PIN CONN.) 4.
5. GND
1 6.
7. RTS
2 8. CTS
9.
3

P.C.B. LAYOUT ACCORDING TO


DRAWING EBL512 G3 - 11

10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale
1) Remove any factory mounted connector before connection to J3 and J2.
2) Web-server power supply fuse F18 (2A), see drawing 512 G3 - 22. Fuse F18 is not supervised.
JP MÖ RP 512 G3-32_12.cdr 2010-06-03 --
3) Web-server shall be mounted on the DIN rail inside the C.i.e. metal housing. See drawing 512 G3 - 01, sheet 1 / 2. Drawing title
EBL512 G3, Main board 5010, T.B. J3:1-2 & J7
4) Cable, e.g. CAT-5, CAT-5.1, CAT-6 etc. Connection diagram Web-server II, 1598
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 32 1/1 2
Revision Revision date Revision note Signature Checked
AD=Alarm Device (siren, etc.).
D1=Suppression Diode (e.g. 1N4004), when required. 3 2013-12-30 Sheet 2 added. Info. text added. JP MÖ
NOTE! D2=Series Diode (e.g. 1N4004). Required in all Alarm
Devices even if only one resistor is used.
R =Resistor 33K
This drawing 512 G3 - 23, sheet 1 of 2, No. 5 No. 1
is valid when the Voltage outputs S0 - S3 Internal connections on Main board 5010
have not to fulfil the EN54-13 regulation.
AD AD P.c.b. layout, see drawing 512 G3 - 11.
Else drawing 512 G3 - 23, sheet 2 of 2, - + - +

is valid.
D1
D2
D1
D2 Terminal Block J4 4 x T500mA 250 V (TR5)

2)
Programmable Voltage Outputs S0 - S3 R R 0V
1 F4 (500mA)
Each voltage output has to be programmed to be:
- Normally High or Normally Low
S0
Voltage output 5) 2 +24 V, Activated
+5 V, Supervised
3 F5 (500mA)
- Supervised or Not Supervised. 2)
Voltage output S1 5) 4
Each output has to have a control expression 5 F6 (500mA)
(i.e. one or more output trigger conditions). Voltage output S2 5) 6 S1-S3 are like S0.
7 F7 (500mA)
Voltage output S3 1) 5) 8
Programmable Relay Outputs R0 - R1 Relay contacts programmable to be
9
Each relay output has to be programmed to be: Normally Open (NO)
Normally Open (NO) or Normally Closed (NC).
Relay output R0 10 or
11 Normally Closed (NC)

Each output has to have a control expression Relay output R1 12 Contacts for max. 30 V, 1A.
(i.e. one or more output trigger conditions). 13
+ 24 V
Input I0 alt. 14
15
Programmable Inputs I0 - I3 Input I1 alt. 16
Each input has to be programmed to be: 17
Normally Open (NO) or Normally Closed (NC). Input I2 alt. 18
19
Each input has to have an input trigger
condition.
Input I3 alt. 20

An input has to be activated > 0.5 sec.


Open: R > 20K. Closed: R < 500 W .

Terminal Block J4 cont. on drawing 512 G3 - 24.

NOTE!
The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).
4)
3) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
In fire alarm condition < 6.3 A is available for the c.i.e. and all connected equipment.

10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) Voltage Output S3 will be low in case of watchdog fault, i.e. this output can be used as a supervised Fault condition output for routing equipment (fault tx). Designed by Checked by Approved by Filename Date Scale
2) Only a normally low Voltage Output can be supervised. One or up to five 33K resistors can be used. After connecting / changing equipment on a supervised output, a JP MÖ RP 512 G3-23_13.cdr 2010-06-03 --
calibration has to be done via menu H5 / A1. The calibrated value has to be in the range 4K7 - 50K, else a fault will be generated.
Drawing title
During the calibration and during restart of the C.i.e. a normally high output will be low for a few seconds. EBL512 G3, Main board 5010, T.B. J4:1-20
3) In quiescent condition the battery charging current can be up to 3A (6.3-3.0=3.3A). Connection diagram, Out- & inputs S0-S3, R0-R1 & I0-I3
Battery charging will be turned off during fire alarm condition (6.3-0=6.3A).
Drawing number Sheet Revision
4) Note that if 28 Ah batteries are used and 30 hours battery back-up time is required, max. 0.93 A can be used in quiescent condition (since 0.93A x 30h = 28Ah). Panasonic Eco Solutions Nordic AB
5) One 33K resistor is supplied per output. Can be dis-connected and used as end-of-line resistor. 512 G3 - 23 1/2 3
Revision Revision date Revision note Signature Checked

DA=Alarm Device (e.g. sounder) - - - - -


NOTE! NOTE! One AD, max. 15 mA.
(E.g. FulleonSymphoni Low Power.)
D =Series Diode ( 1N4007).
This drawing 512 G3 - 23, sheet 2 of 2, R =Resistor 1K / 1W

is valid when the Voltage outputs S0 - S3 Internal connections on Main board 5010
have to fulfil the EN54-13 regulation.
AD P.c.b. layout, see drawing 512 G3 - 11.
Else drawing 512 G3 - 23, sheet 1 of 2, - +

is valid.
R D
Terminal Block J4 4 x T500mA 250 V (TR5)

Programmable Voltage Outputs S0 - S3 0V


1 F4 (500mA)
Each voltage output has to be programmed to be:
- Normally Low
S0
Voltage output 1) 2 +24 V, Activated
+5 V, Supervised
3 F5 (500mA)
- Supervised
Voltage output S1 1) 4
Each output has to have a control expression 5 F6 (500mA)
(i.e. one or more output trigger conditions). Voltage output S2 1) 6 S1-S3 are like S0.
7 F7 (500mA)
Voltage output S3 1) 8
Programmable Relay Outputs R0 - R1 Relay contacts programmable to be
9
Each relay output has to be programmed to be: Normally Open (NO)
Normally Open (NO) or Normally Closed (NC).
Relay output R0 10 or
11 Normally Closed (NC)

Each output has to have a control expression Relay output R1 12 Contacts for max. 30 V, 1A.
(i.e. one or more output trigger conditions). 13
+ 24 V
Input I0 alt. 14
15
Programmable Inputs I0 - I3 Input I1 alt. 16
Each input has to be programmed to be: 17
Normally Open (NO) or Normally Closed (NC). Input I2 alt. 18
19
Each input has to have an input trigger
condition.
Input I3 alt. 20

An input has to be activated > 0.5 sec.


Open: R > 20K. Closed: R < 500 W .

Terminal Block J4 cont. on drawing 512 G3 - 24.

NOTE!
The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).
3)
2) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
In fire alarm condition < 6.3 A is available for the c.i.e. and all connected equipment.

10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) Cable resistance < 50 ohm. Designed by Checked by Approved by Filename Date Scale
2) In quiescent condition the battery charging current can be up to 3A (6.3-3.0=3.3A). JP MÖ RP 512 G3-23_2x.cdr 2013-12-30 --
Battery charging will be turned off during fire alarm condition (6.3-0=6.3A).
3) Note that if 28 Ah batteries are used and 30 hours battery back-up time is required, max. 0.93 A can be used in quiescent condition (since 0.93A x 30h = 28Ah). Drawing title
EBL512 G3, Main board 5010, T.B. J4:1-20
Connection diagram, Out- & inputs S0-S3, R0-R1 & I0-I3
Drawing number Sheet Revision
Panasonic Eco Solutions Nordic AB
512 G3 - 23 2/2 -
Revision Revision date Revision note Signature Checked
J4 J4
2 2013-01-30 F19: Info. updated. Company name updated. JP MÖ
35 35
FBF2003 36 FAT2002 36
RxD+ 37 RxD+ 37
38
Internal connections on Main board 5010
RxD- 38 RxD-
P.c.b. layout, see drawing 512 G3 - 11.

UB+ GND
0V UB+
Terminal Block J4
7) 3) 7) 3)
Terminal Block J4 cont. on drawing 512 G3 - 23

Display Unit types When Display Unit types 1826, 1828, 1735, 1736 and/or 1728 are
used, no German FBF2003 or FAT2002 can be used and vice versa.
1826 / 1828 External Fire Brigade Panel
1735 / 1736 Alert Annunciation Unit NOTE!
1728 External Presentation Unit The relay contacts are
Fire alarm 21
shown for a powerless C.i.e.
or
FBF2003

FAT2002
German Fire Brigade Panel
(Feuerwehr-Bedienfeld)
German Fire Brigade Indicator Panel
relay output for e.g. routing equipment
"Fire brigade tx"
6)
{ 22

24
23 Normally the fault relay is
activated, i.e. it will be
de-activated for a fault
Fault condition
(Feuerwehr-Anzeigetableau) relay output for e.g. routing equipment
"Fault tx"
{ 26
25

27
condition.
Contacts for max. 30 V, 1A.

"F1" (0)

1)
{ TLON Network (FTT-10) no. 0, in or termination resistor 105R, ± 1%, 1/8 W

TLON Network (FTT-10) no. 0, out or termination resistor 105R, ± 1%, 1/8 W
"F2" (0)
"F1" (0)
"F2" (0)
3)

3)
28

30
29

31
Connector "J10"
TLON connection
board 1590,
no. 0
1)

"F1" (1)

2)
{ TLON Network (FTT-10) no. 1, in or termination resistor 105R, ± 1%, 1/8 W

TLON Network (FTT-10) no. 1, out or termination resistor 105R, ± 1%, 1/8 W
"F2" (1)
"F1" (1)
"F2" (1)
3)

3) +24 V
32

34
33

35 F19
10)
(1.6A)
Connector "J11"
TLON connection
board 1590,
no. 1
2)

The TLON Network cable has to be screened, + 24 V


D.U. RS485 output 0V 36
e.g. Belden 7703 NH 1 pair 22 AWG or equivalent. 0V
T.B. J1 for Display Units B (-) "S0" 37 B (-)
D.U. 1 A (+) "S1" 38 RS485 A (+) IC56
T.B. J1 2 39
Terminals 39-40
1 3 40
are for future use
2 4 and must not be

{
+24 V 3 5 used.
0V 4 6 T1.6A 250 V (TR5)
To the next 5 7
Display Unit 6 8 NOTE!
B (-) "S0" 7 The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).9)
5) 4) 3)
A (+) "S1" 8
8) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
4) In fire alarm condition < 6.0 A is available for the c.i.e. and all connected equipment.
Max. 1200 m cable for Display Units,

10 mm
e.g. LIHCH-TP 2x2x0.75 mm2 or equivalent.
Max. 16 Display Units can be connected.

Original drawing A3L (420 x 297 mm)


NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) If only one TLON connection board 1590 is used, it has to be no. 0. 8) In quiescent condition the battery charging current can be up to 3A (6.0-3=3.3A). Designed by Checked by Approved by Filename Date Scale
2) If two TLON connection boards 1590 are used, board no. 1 is the back-up board. Battery charging will be turned off during fire alarm condition (6.0-0=6.0A). JP MÖ RP 512 G3-24_12.cdr 2010-06-03 --
3) Screen shall be connected to the C.i.e. earth point (see drawing 512 G3 - 01). 9) Note that if 28 Ah batteries are used and 30 hours battery back-up time is
Drawing title
4) Screen shall be connected to a cable fixing clamp screw in each Display Unit. required, max. 0.93 A can be used in quiescent condition (since 30 x 0.93 = 28). EBL512 G3, Main board 5010, T.B. J4:21-40
5) End-of-line (termination) resistor 120R shall be connected in the last Display Unit 10) Fuse F19 is not supervised. Connection diagram, Fire & Fault tx, TLON Network, D.U.
on the line, i.e. jumper "Jp8" shall be shunted in the Display Unit respectively. Drawing number Sheet Revision
6) Routing equipment has to fulfil the EN 60950-1 clause 6.2 requirements. Panasonic Eco Solutions Nordic AB
7) Panel earth point. 512 G3 - 24 1/1 2
Revision Revision date Revision note Signature Checked
MAIN BOARD 5010 A COM LOOP ADDRESS (001-255) SHALL BE SET IN EACH COM LOOP UNIT.
USE THE PROGRAMMING TOOL 3314 / 4414. 4 2014-05-07 Information revised and removed. EA2010N/G/Z-P added. JP MÖ
INTERNAL NOTE! IN TOTAL, ON ALL FOUR COM LOOPS TOGETHER, < 512 ADDRESSES (UNITS)
CAN BE ALARM POINTS (ACCORDING TO EN54-2). 11 4380
WIRING AE2010N/G/Z-P 2842
ASPIRATING ADDR. BEACON SA SB SA SB
4433 (4439 - ENCLOSED) WITH ISO IS BARRIER UNIT
3312 3309 11 3333 (3339 - ENCLOSED) SMOKE 3361 L C L C
J5 DETECTOR 24 V DC + 8
ANALOG BASE ENCLOSED ANALOG ADDRESSABLE ADDRESSABLE MULTI-
Aspect 12 1 2 3 4
HEAT DETECTOR MANUAL CALL POINT 0 V DC - PURPOSE I/O UNIT. 4
Nitro/Grizzle/Lazeer
L (SA)
1
A-DIRECTION
C (SB)
2
COM LOOP 0 L (SA)
3 OUT-/+ must
B-DIRECTION 2 not be used. 9 9
C (SB) SB SA
8 8 8
4 WHITE ORANGE P1 1 2 3 4
7 6 5 4 3 2 1
RED BLACK
L (SA) 1 4 4 - IN + - OUT +
4
5 SA SB SA SB SA1 SA2 CS1 I+1 I+2 PT1
LOOP 1 SB1 SB2 CS2 I-1 I-2 PT2 SB SA SB SA
CONNECTIONS,
C (SB) E- E+ IS-SA
6 8 IS-SB - + + SEE DRAWING
COM LOOP 1 L (SA) Z In0 512 G3 - 36.
7 4
In1 Re1 Re0

C (SB) SB SA E-/+ N.C.


8
IS COM Line 10
+ -
+ -
230 V AC 8 9 10 11 12 13 14 3312F / 3312FL
L (SA) CABLE LENGTH MAX. 30m
9 P1: 1 2 3 JP1: OUT ANALOG BASE
C (SB) P1: 1 2 3 JP1: OUT Hazardous (Ex) area
10 RED 2218 1
COM LOOP 2 WHITE EXTERNAL INDICATOR GREY BLUE
L (SA) 2218
11 (EXT. LED) E- SB
2218 EXTERNAL INDICATOR 2840 / 2841 + -
C (SB)
12 EXTERNAL INDICATOR (EXT. LED) 8 INTRINSICALLY SAFE E+ SA

L (SA) (EXT. LED) (IS) ANALOG P1: 1 2 3 JP1: OUT


13 4313 SMOKE / HEAT DETECTOR
C (SB) ANALOG BASE SA SB ONLY IN
14 4477 WITH ISO 3312FL
COM LOOP 3 3379 (3378) 11 3377 WITH ISOLATOR. 4620 5
L (SA) 6677 3364 3366
15 ADDRESSABLE ADDRESSABLE SEQUENCE (SERIAL) ADDRESSABLE BASE STATION
C (SB) UG-4 DUCT DETECTOR ADDR. 2 VOLTAGE EXTERNAL
SOUNDERBASE SIREN NUMBER REQUIRED FOR WIRELESS UNITS
16 CHAMBER OUTPUTS UNIT POWER SUPPLY

NOTE! Regarding communication P1: 2


direction, see drawing 512 G3 - 25. 2218 24VAC
8 8 P1: 3
2 EXT. LED FAN
COM LOOP FUSES F14 - F17 (1.6 A) SB SA 4 SAi SAo
4 8 J1 1 2 3 4 SB
8 8 J2 1 2 3 4
SEE DRAWING 512 G3 - 25. 1 2 3 4 5 6 7 8 9 10 7 6 5 4 3 2 1
CN1
1 4 SA SB SA SB 1 4 SA SB SA SB
SB SA
SB SA SB SA
4 J1
L C L C L C L C
E- E+ E- E+
6 DIL-SWITCH BLUE 3 3
SB SA
- + 3312FL J7 1 2 3 4
REGARDING 3379 (3378): REGARDING 4313: BASE & ISOLATOR IS ONE UNIT BUT CN2 and
THE ISOLATOR REQUIRE ONE ADDRESS AND THE 7
SOUNDER & BASE IS ONE UNIT BUT 4301
4 DETECTOR PLUGGED IN THE BASE REQUIRE ANOTHER E- E+
THE SOUNDER REQUIRE ONE ADDRESS ADDRESS. GREY 8 9 10 11 12 13 14 0V
AND THE DETECTOR PLUGGED IN THE BASE + - IT IS VERY IMPORTANT THAT THE "L" (SA) WIRES +24 V

REQUIRE ONE ADDRESS 1 ARE CONNECTED TO THE SAin & SAout TERMINALS IN /OK
P1: 1 2 3 JP1: OUT THE 4313 UNIT. DOUBLECHECK THE CONNECTIONS!! 0 V DC - + 24 V DC

10 mm
12 CONNECTIONS TO 3364 & 3366,
SEE ALSO DRAWING 512 G3 - 38
230 V AC
2218

Original drawing A3L (420 x 297 mm)


EXTERNAL INDICATOR 11) This product will soon be replaced. 4611 NOTE!
T.B. J5: SEE DRAWING EBL512 G3 - 25 (EXT. LED) WIRELESS SMOKE DETECTOR (1-16 PIECES) Max. 40 3364 units per C.i.e.
12) EXT. POWER SUPPLY, 3366 OR EBL512 G3
1) ANALOG SMOKE DETECTORS 430X AND 440X & ANALOG HEAT DETECTOR 3308 CAN BE PLUGGED IN THE BASE. 8) THE COM LOOP ADDRESS Designed by Checked by Approved by Filename Date Scale
2) IF SCREENED CABLE IS USED ONLY INCOMING (OR OUTGOING) SCREEN SHALL BE CONN. TO THE C.I.E. FUNCTIONAL AND MODE SETTINGS HAVE TO
EARTHING POINT. CONNECT THE SCREENS NEAR THE UNIT. KEEP COM LOOP WIRES AS SHORT AS POSSIBLE AND BE DONE BEFORE THE UNIT IS
JP MÖ RP 512 G3-31_14.cdr 2010-06-03 --
TWISTED >6 TURNS. CONNECTED TO THE COM Drawing title
3) THE UNIT HAS TO BE POWERED DURING ADDRESS SETTING, BUT NOT CONNECTED TO THE COM LOOP. LOOP.
EBL512 G3, Main board 5010, T.B. J5
4) PROGRAMMING TOOL (3314 / 4414) IS USED FOR COM LOOP ADDRESS & MODE SETTING. 9) CS1, CS2, PT1 and PT2 must Connection diagram COM loop units
5) THIS PRODUCT IS UNDER CONSTRUCTION. not be used. Drawing number Sheet Revision
6) COM LOOP ADDRESS IS SET ON A DIL-SWITCH. 10) No e-o-l device and no return Panasonic Eco Solutions Nordic AB
7) IF TERMINAL 8 IS NOT CONNECTED TO 3366 (J7:4) IT HAS TO BE CONNECTED TO TERMINAL 6. cable. Ended in the last detector. 512 G3 - 31 1/1 4
Revision Revision date Revision note Signature Checked

1 2013-01-30 F14-F17: Info. updated. Company name updated. JP MÖ

Internal connections on Main board 5010


P.c.b. layout, see drawing 512 G3 - 11.

4 x T1.6A 250 V (TR5)

Terminal block J5 2)

1 L (SA) F15 (1.6A)


A-direction 2 C (SB)
COM loop 0 3 L (SA) IC24
Address 1 - 255 B-direction 4 C (SB)
5 L (SA) F16 (1.6A)
A-direction 6 C (SB)
COM loop 1 7 L (SA) IC22
Address 1 - 255 B-direction 8 C (SB)
Connection of L (SA)
9 F17 (1.6A)
COM loop units A-direction 10 C (SB)
according to drawing COM loop 2 11 L (SA) IC25
512 G3 - 31 Address 1 - 255 B-direction 12 C (SB)
13 L (SA) F14 (1.6A)
A-direction 14 C (SB)
COM loop 3 15 L (SA) IC23
Address 1 - 255 B-direction 16 C (SB)

1)
In total 4 x 255 = 1020 addresses (units).

NOTE!
Max. 512 addresses (units) can be alarm points.
EBL512 G3 can have one of three basic configurations: Normally communication in the A-direction only.
1. Max. 128 alarm points In case of break (cut-off) or short-circuit on the loop, communication in both the A- and B-direction.
2. Max. 256 alarm points
3. Max. 512 alarm points NOTE!
Via menu H5 / A3, the communication can be turned off in order to check the COM loop voltage in the A- or B-direction or
in both directions.
Recommended COM loop cable: Via menu H8 / S1, the COM loop respectively can be (galvanicly) disconnected and Re-connected.
ELQYB 2 x 1 mm (=0.75 mm2); Twisted pair.
Wire resistance: 24.5 ohm per km.
Pair capacitance: 50 nF per km at 800 Hz.
Attenuation: 0.6 dB per km at 800 Hz.

Max. available COM loop current: 350 mA.

10 mm
Max. COM loop cable length is depending on the cable type and the COM loop units' current consumption.

Original drawing A3L (420 x 297 mm)


NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale
1) If screened COM loop cable is used, only incoming or outgoing screen shall be connected to a C.i.e. earth point.
In each loop unit, connect the screen so that the unscreened wires are as short as possible and twisted > six turns. JP MÖ RP 512 G3-25_11.cdr 2010-06-03 --
2) The fuses F14 - F17 must not be replaced. When a fuse is broken also other components are broken and the main board 5010 has to be replaced. Drawing title
EBL512 G3, Main board 5010, T.B. J5
Connection diagram COM loops 0 - 3
Drawing number Sheet Revision
Panasonic Eco Solutions Nordic AB
512 G3 - 25 1/1 1
Revision Revision date Revision note Signature Checked

Expansion boards 458x 2 2013-01-30 Fuse F13: T4A -> F4A. Company name updated. JP MÖ

4580 8 zones expansion board (See drawings 512 G3 - 14 & - 33.)


4581 8 relays expansion board (See drawings 512 G3 - 15 & - 34.) Internal connections on Main board 5010
4583 Inputs & Outputs expansion board (See drawings 512 G3 - 17 & - 35.) P.c.b. layout, see drawing 512 G3 - 11.

F4A 250 V (TR5)

J9 2)
Expansion boards 458x 5089 Ribbon cable with connectors
1) for J9 - J2(0) - - J2(5). F13 (4A)
Up to six boards can be + 24 V
0V
mounted in the C.i.e.
metal housing. IC24
Board no. 0 - 5.

Main board 5010

See drawing 512 G3 - 11.

J2 (1) J2 (0)

J2 (3) J2 (2)
The boards are mounted in the C.i.e. metal housing according to drawing 512 G3 - 01, sheet 1 / 2.

Connections also according to drawings EBL512 G3 - 02 & - 03.

The board no. (address) is not depending on the position of the board or which connector
on the connection cable it is connected to.

Each board has to have a unique board no. (0 - 5) in accordance with the WinG3 programming.

10 mm
Jumpers JP2, JP3 & JP4 on each expansion board are used for the board no. (0 - 5) setting.
Jumper positions according to drawings 512 G3 - 14, -15 & -17.
J2 (5) J2 (4)

Original drawing A3L (420 x 297 mm)


NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale
1) The I/O Matrix board 4582 is physically connected on a COM loop (via an application board) BUT if connected on COM loop 0 it has to be regarded as one expansion
board, i.e. one of the six expansion boards that can be used. JP MÖ RP 512 G3-26_12.cdr 2010-06-03 --
2) The fuse F13 is not supervised. Drawing title
EBL512 G3, Main board 5010, Connector J9
Connection diagram Expansion boards 458x
Drawing number Sheet Revision
Panasonic Eco Solutions Nordic AB
512 G3 - 26 1/1 2
Revision Revision date Revision note Signature Checked
Connections according to the drawings 512 G3 - 02 & - 03. 1 2012-02-01 Some texts updated. Note 2 added. JP MÖ

164 mm

9291-4A
140 mm

J1 1)
SW1
Internal connection
MMI board restart
to Main board 5010, J1
1)
9291-4A SW2
MMI board boot
P.c.b. label for
identification
J2 & J3
Internal connections

LEDs
to the Front 5060/5061
J9
(LEDs and Keyboard)
Internal connection
to LCD 5038

LED D18
Steady: Normal condition
VR1 Off: Restart or MMI board in "Boot" mode
Potentiometer for
LED D11
Loudspeaker
For future use
VR2
Potentiometer for
LCD contrast

Not used Not used

J7 J6
Internal connection Internal connection
to Loudspeaker (5036) to Printer (5058)
2) 2)
J4

10 mm
Internal connection
to LCD (5038)
2) The p.c.b. is mounted in

Original drawing A3L (420 x 297 mm)


the C.i.e. housing according to
NOTE! Most of the components are deleted on the p.c.b. above for easier identification of connectors, etc. drawing 512 G3 - 01.
Designed by Checked by Approved by Filename Date Scale
1) Used to set the MMI board in "Boot" mode, e.g. in conjunction with new software download.
2) Spare part number. JP MÖ RP 512 G3-12_11.cdr 2010-06-03 Approx. 1:1
Drawing title
EBL512 G3, MMI board 5011
Dimensions & overview P.c.b. no. 9291-4A
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 12 1/1 1
Revision Revision date Revision note Signature Checked

13 mm 88 mm 13 mm

JP1
8 zones exp. board restart
Not used
6 mm JP4 ("4")
JP3 ("2")
JP2 ("1")
Jumpers for board no. (address) setting (0-5)
(e.g. JP2 & JP3 shunted=no. "3")

J3
For production only
82 mm
JP6
For production only.
(Shall be normally shunted.)

P.c.b. label for identification

20 mm

J1 1)
8 zone line inputs (0-7)
Connections to J1
according to
J2 drawing 512 G3 - 33.
For connection to:
- The main board 5010 (J9) and the next expansion board 458x (J2)
- Other expansion boards 458x (J2)

10 mm
See drawings 512 G3 - 02, - 03 & - 26.

The p.c.b. is mounted in the

Original drawing A3L (420 x 297 mm)


C.i.e. housing according to
NOTE! Most of the components are deleted on the p.c.b. above for easier identification of connectors, etc. drawing 512 G3 - 01.
Designed by Checked by Approved by Filename Date Scale
1) End-of-line device depending on the mode programmed via WinG3.
- Capacity mode: Capacitor 470 nF. Cable data; Max. 50 ohm & max. 50 nF. JP MÖ RP 512 G3-14_1x.cdr 2010-06-03 Approx. 1:1
- Ex resistor mode: Resistor 10K. Cable data; Max. 40 ohm & max. 70 nF. See also drawing 512 G3 - 37.
Drawing title
- Resistor mode: Resistor 4K7. Cable data; Max. 50 ohm. EBL512 G3, 8 zones expansion board 4580
Conductor area max. 1.2 mm2 (Ø=1.2 mm).
Dimensions & overview P.c.b. no. 9287-3A
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 14 1/1 -
Revision Revision date Revision note Signature Checked
8 ZONES EXPANSION BOARD 4580 ("DET8")
-
P.C.B. LAYOUT ACCORDING TO 2324
INTERNAL DRAWING EBL512 G3 - 14 CONVENTIONAL
6295, -96, -97, -98
WIRING DETECTOR BASE FOR CONVENTIONAL ENCLOSED (CONVENTIONAL) 1
CONV. SMOKE OR HEAT MANUAL CALL POINT HEAT DETECTOR E-O-L DEVICE
DETECTOR
J1
2 470nF 4K7 10K
1 A+ A+
+
1
INPUT 0 - Zone line ALT. ALT.
2
470nF 1 B-
+ CAPACITY RESISTOR Ex-RESISTOR
3
B- L MODE MODE MODE
INPUT 1 -
4
+ 470nF 1 1 2 3 4 NOTE!
5
680 470 COMMON
In Ex-resistor
INPUT 2 -
6 mode a galvanic
1 680R isolator 2820
+ 470nF
7 WHITE ORANGE OR YELLOW
(MTL5061) is
INPUT 3 - RED BLACK
8 allways required,
+ 470nF 1 see drawing
9 512 G3 - 37.
+ -
INPUT 4 -
10
P1: 1 2 3 JP1: OUT
+ 470nF 1
11
INPUT 5 - E+ / E-
12 B A
2218 E+ TERMINALS
+ 470nF 1 E-
13 EXTERNAL INDICATOR FOR EXTERNAL
INPUT 6 - (EXT. LED) INDICATOR 2218
14
+ 470nF 1
15
INPUT 7
-
16

TO THE MAIN BOARD ("J9")


J2
OR VIA WinG3 CAN BE PROGRAMMED THAT
1 DETECTORS WITH A CLOSING CONTACT
+24 V TO ANOTHER EXP. BOARD ("J2")
2 SHALL BE CONNECTED (i.e. "ALARM AT SHORT CIRCUIT").
0V
3
SHORT CIRCUIT ON THE ZONE LINE WILL THEN ACTIVATE
L (SA) See also drawing 512 G3 - 26. A FIRE ALARM INSTEAD OF A FAULT.
4
C (SB)
NOTE!
TO ANOTHER EXP. BOARD ("J2")
MAX. 32 POINTS ON EACH ZONE LINE.

10 mm
J2: MALE, MOLEX OR
TYPE KK, 2.54 MAX. 40 POINTS ON EACH ZONE LINE IN AUS. / N.Z.
NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)
MAX. 512 ALARM POINTS IN ONE C.I.E. (EN54-2)

Original drawing A3L (420 x 297 mm)


NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale
1) EACH ZONE LINE INPUT (0-7) CAN VIA WinG3 BE PROGRAMMED FOR ONE OF TWO MODES (TYPES):
- CAPACITIVE, E-O-L CAPACITOR 470nF. MAX. 50ohm CABLE RESISTANCE. MAX. 50nF CABLE CAPACITANCE. JP MÖ RP 512 G3-33_1x.cdr 2010-06-03 --
- Ex-RESISTOR, E-O-L RESISTOR 10K. SEE DWG 512 G3 - 37. MAX. 40 ohm CABLE RESISTANCE. MAX. 70 nF CABLE CAPACITANCE.
Drawing title
- RESISTOR, E-O-L RESISTOR 4K7. MAX. 50ohm CABLE RESISTANCE. NOTE! 4580 P.C.B. NO. 9287-3A REQUIRED! EBL512 G3, 8 zones exp. board 4580, J1 & J2
2) ANY CONVENTIONAL MANUAL CALL POINT WITH AN ALARM RESISTOR 680R (±10%). Connection diagram Zone line inputs 0-7 / units
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 33 1/1 -
Revision Revision date Revision note Signature Checked

13 mm 88 mm 13 mm

JP1
8 relays exp. board restart
Not used
6 mm JP4 ("4")
JP3 ("2")
JP2 ("1")
Jumpers for board no. (address) setting (0-5)
(e.g. JP2 & JP3 shunted=no. "3")

J3
For production only
82 mm

P.c.b. label for identification

20 mm

J1 1)
8 relay outputs (0-7)
Connections to J1
according to
J2 drawing 512 G3 - 34.
For connection to:
- The main board 5010 (J9) and the next expansion board 458x (J2)
- Other expansion boards 458x (J2)

10 mm
See drawings 512 G3 - 02, - 03 & - 26.

The p.c.b. is mounted in the

Original drawing A3L (420 x 297 mm)


C.i.e. housing according to
NOTE! Most of the components are deleted on the p.c.b. above for easier identification of connectors, etc. drawing 512 G3 - 01.
Designed by Checked by Approved by Filename Date Scale
1) NO or NC relay contacts programmed via Win512 G3.
Conductor area max. 1.2 mm2 (Ø=1.2 mm). JP MÖ RP 512 G3-15_1x.cdr 2010-06-03 Approx. 1:1
Drawing title
EBL512 G3, 8 relays expansion board 4581
Dimensions & overview P.c.b. no. 9286-2B
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 15 1/1 -
Revision Revision date Revision note Signature Checked
8 RELAYS EXPANSION BOARD 4581 ("RE8")
-
P.C.B. LAYOUT ACCORDING TO
DRAWING EBL512 G3 - 15
INTERNAL
WIRING

J1
RELAY OUTPUT

1
0 0
2

3
1 1
4

5
2 2
6

7 EACH OUTPUT HAS TO BE PROGRAMMED


3 3 VIA WinG3.
8
EACH OUTPUT CAN BE PROGRAMMED
9
AS NORMALLY OPEN (NO)
4 4 OR NORMALLY CLOSED (NC).
10

11
5 5
12 RELAY CONTACT RATINGS:
MAX. 2 A @ 30 V DC.
13
6 6
14

15
7 7
16

TO THE MAIN BOARD ("J9")


J2
OR
1
+24 V TO ANOTHER EXP. BOARD ("J2")
2
0V
3
L (SA) See also drawing 512 G3 - 26.
4
C (SB)
TO ANOTHER EXP. BOARD ("J2")

10 mm
J2: MALE, MOLEX OR
TYPE KK, 2.54 NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)

Original drawing A3L (420 x 297 mm)


NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale

JP MÖ RP 512 G3-34_1x.cdr 2010-06-03 --


Drawing title
EBL512 G3, 8 relays exp. board 4581, J1 & J2
Connection diagram
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 34 1/1 -
Revision Revision date Revision note Signature Checked

P.c.b. labels for identification

63 mm
JP6 ("4")
JP5 ("2") 80 mm
JP4 ("1")
Jumpers for mode setting,
i.e. type of board (0-2) J3
0=Fan control For production only
1=Zone control
2=Generic
P.c.b. label for identification

JP1 ("1")
JP2 ("2") JP7
JP3 ("4") For production only.
Jumpers for board no. (address) setting (0-5) (Shall normally not be shunted.)
(e.g. JP1 & JP2 shunted=no. "3")

J1 (mounted on the reverse side of the p.c.b.)


Connector for an Application board.

The I/O Matrix board 4582 has 16 switch inputs and 48 LED outputs and has to be used in conjunction with an Application board.

10 mm
Original drawing A3L (420 x 297 mm)
NOTE! Most of the components are deleted on the p.c.b. above for easier identification of connectors, etc.
Designed by Checked by Approved by Filename Date Scale

JP MÖ RP 512 G3-16_1x.cdr 2010-06-03 Approx. 1:1


Drawing title
EBL512 G3, I/O Matrix board 4582
Dimensions & overview P.c.b. no. 9292-1A
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 16 1/1 -
Revision Revision date Revision note Signature Checked

13 mm 88 mm 13 mm

JP1
Inputs and outputs exp. board restart

6 mm

JP2 ("1")
JP3 ("2")
JP4 ("4")
Jumpers for board no. (address)
setting (0-5) J3
(e.g. JP2 & JP3 shunted=no. "3") For production only
82 mm
F1 F2 P.c.b. label for identification

20 mm

J1 1)
5 inputs (0-4) and 3 outputs (0-3)
Connections to J1
according to
J2 drawing 512 G3 - 35.
For connection to:
- The main board 5010 (J9) and the next expansion board 458x (J2)
- Other expansion boards 458x (J2)

10 mm
See drawings 512 G3 - 02, - 03 & - 26.

The p.c.b. is mounted in the

Original drawing A3L (420 x 297 mm)


C.i.e. housing according to
NOTE! Most of the components are deleted on the p.c.b. above for easier identification of connectors, etc. drawing 512 G3 - 01.
Designed by Checked by Approved by Filename Date Scale
1) All inputs & outputs are programmed via WinG3. F1-F2: 200 mA, see drawing 512 G3 - 35.
The inputs & outputs can be used for special German equipment, e.g. extinguishing equipment - "Löschanlage". JP MÖ RP 512 G3-17_1x.cdr 2010-06-03 Approx. 1:1
See drawing 512 G3 - 35.
Conductor area max. 1.2 mm2 (Ø=1.2 mm). Drawing title
EBL512 G3, In & Outputs expansion board 4583
Dimensions & overview P.c.b. no. 9215-1A
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 17 1/1 -
Revision Revision date Revision note Signature Checked
INPUTS & OUTPUTS EXPANSION BOARD 4583 ("GFBP")
3 2013-12-30 Sheet 3 added. NOTE! added. JP MÖ
NOTE!
INTERNAL AD=ALARM DEVICE (SIREN, ETC.) OUTPUT 0 CAN BE USED
24V DC IS THE NOMINAL VOLTAGE WHEN THE MAIN POWER SOURCE (RECTIFIER) IS
WIRING USED. WHEN THE SECOND POWER SOURCE (BACK-UP BATTERY) IS USED THE
D1=SUPPRESSION DIODE (e.g. 1N4004)
AD FOR GERMAN FIRE ALARM AD
WHEN REQUIRED
VOLTAGE CAN BE 20-28V DC. - + ROUTING EQUIPMENT, - +
FUSES F1-F2: D2=SERIES DIODE (1N4004). Required
FIRE ALARM.
SEE DRAWING in all Alarm Devices even if only one resistor
OUTPUT 2, INPUT 3 & 4 CAN BE USED AS A STANDARD is used. "E" "BRANDMELDUNG"
512 G3 -17 D1 D1
J1 GERMAN EXTINGUISHING INTERFACE R=Resistor 33K D2 (Trigger condition: Fire D2
(STANDARDSCHNITTSTELLE "LÖSCHEN"). R Brigade Tx) R
1-5 RESISTORS R=33K CAN BE USED.
F1 + +
2) 1
200mA - - OUTPUT 0, 24V DC, SUPERVISED, PROGRAMMABLE (CONTROL EXPRESSION & NORMALLY LOW OR HIGH) 3)
2
+ NO (>20K) NC (<500) INPUT 0 CAN BE USED FOR GERMAN FIRE ALARM
1) 3
- INPUT 0, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) ALT. 1) ROUTING EQUIPMENT, FAULT INPUT. "J" "MELDER
4 QUITTUNG". Trigger condition: Fault warning routing equipment fault.
F2 + + AN INPUT HAS TO BE ACTIVATED >0.5 SEC.
2) 5
OUTPUT 1, 24V DC, SUPERVISED, PROGRAMMABLE (CONTROL EXPRESSION & NORMALLY LOW OR HIGH) 3) OUTPUT 1 CAN BE USED FOR GERMAN KEY CABINET.
200mA - -
6 "FSK ÖFFNEN". Trigger condition: Key cabinet open.
+
7 INPUT 1 CAN BE USED FOR GERMAN KEY CABINET, FEEDBACK.
2 x T200mA 250 V - INPUT 1, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1)
8 "FSK RÜCKMELDUNG". Trigger condition: Activated Key cabinet.
(TR5)
+
9 INPUT 2 CAN BE USED FOR GERMAN KEY CABINET, SUPERVISION.
- INPUT 2, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1)
10 "FSK ÜBERWACHUNG".
3K3 680R +
11 SPECIAL OUTPUT FOR GERMAN EXTINGUISHING EQUIPMENT,
- OUTPUT 2, SUPERVISED, PROGRAMMABLE (CONTROL EXPRESSION & NORMALLY LOW OR HIGH RESISTANCE)
12 "G" "LÖSCHANLAGE". Trigger condition: Fire alarm.
LÖSCHANLAGE

NO / NC
+
13 INPUT 3 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, RELEASED.
P.C.B. LAYOUT ACCORDING TO

- INPUT 3, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1)


14 "G" "LÖSCHANLAGE AUSGELÖST" Trigger condition: Extinguishing system released.
DRAWING EBL512 G3 - 17.

+
15 INPUT 4 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, FAULT INPUT.
- INPUT 4, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1) "G" "LÖSCHANLAGE QUITTUNG" Trigger condition: Extinguishing system fault.
0V 16

TO THE MAIN BOARD ("J9")


J2
NOTE!
OR Output 0 & 1
1
+24 V TO ANOTHER EXP. BOARD ("J2") This drawing 512 G3 - 35, sheet 1 of Programmed Not activated Activated
2 3, is valid for board 4583. as: (Control expression not true.) (Control expression true.)
0V
3
Normally low Supervision voltage 1.5-3.6 V 24 V
L (SA) See also drawing 512 G3 - 26. a)
Drawing 512 G3 - 35, sheet 3 of 3, is
4 valid for board 4583GE. Normally high 24 V < 4.2 V
C (SB)
a)
Depending on the number of supervision resistors (1-5).

10 mm
TO ANOTHER EXP. BOARD ("J2")
J2: MALE, MOLEX OR
NOTE! THE SUPERVISON VOLTAGE HAS REVERSE POLARITY COMPARED TO 24V.
TYPE KK, 2.54 NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)

Original drawing A3L (420 x 297 mm)


NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) A PROGRAMMABLE INPUT CAN AS AN ALT. BE PROGRAMMED AS SUPERVISED. SEE DRW 512 G3 - 35, SHEET2/3. Designed by Checked by Approved by Filename Date Scale
2) VOLTAGE DEPENDING ON PROGRAMMING. SEE TABLE. JP MÖ RP 512 G3-35_13.cdr 2010-06-03 --
3) AFTER CONNECTION/COMMISSIONING, THE SUPERVISED OUTPUTS HAVE TO BE CALIBRATED VIA MENU H5/A1. THE CALIBRATED VALUE HAS TO BE IN THE RANGE 4K7-50K, Drawing title
ELSE A FAULT WILL BE GENERATED. ONLY A NORMALLY LOW OUTPUT CAN BE SUPERVISED, ALT. CAN BE PROGRAMMED AS NOT SUPERVISED. EBL512 G3, I/O expansion board 4583, J1 &J2
DURING RESTART OF EBL512 G3, A NORMALLY HIGH OUTPUT WILL BE LOW FOR A FEW SECONDS. Connection diagram Inputs & Outputs / units
Drawing number Sheet Revision
Panasonic Eco Solutions Nordic AB
512 G3 - 35 1/3 3
Revision Revision date Revision note Signature Checked

1 2013-12-30 Table revised. Table added. Info. revised. JP MÖ

NORMALLY HIGH RESISTANCE NORMALLY HIGH RESISTANCE NORMALLY LOW RESISTANCE

NO/NC ALT. ALT.


CONNECTION TO 4583 ("J1"),
SUPERVISED INPUTS 0-4,
EXAMPLES:
680R 3K3 680R 3K3 680R 3K3

1)
4583 INPUT 0-4, SUPERVISED, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY HIGH OR LOW RESISTANCE), SEE TABLES.

4583
Line resistance R Normally Normally
high resistance low resistance
R > 6K8 Fault Fault
6K8 > R > 2K Not activated Activated
(nom. 3K3)
2K > R > 70 Activated Not activated
(nom. 680)
R < 70 Fault Fault

4583GE
Line resistance R Normally Normally
high resistance low resistance
R > 4K Fault Fault
4K > R > 3K Not activated Activated
(nom. 3K3)
3K > R > 2K Fault Fault
2K > R > 70 Activated Not activated
(nom. 680)
R < 70 Fault Fault

10 mm
NOTE!
24 V DC IS THE NOMINAL VOLTAGE WHEN THE MAIN POWER SOURCE (RECTIFIER) IS USED.
WHEN THE SECOND POWER SOURCE (i.e. THE BACK-UP BATTERY) IS USED THE VOLTAGE CAN BE 20-28 V DC
ON BOARD 4583 AND 21.6-28 V ON BOARD 4583GE.

Original drawing A3L (420 x 297 mm)


1) THE PROGRAMMABLE INPUTS 0-4 CAN AS AN Designed by Checked by Approved by Filename Date Scale
ALTERNATIVE BE PROGRAMMED AS NOT SUPERVISED, i.e. AS NO / NC. JP MÖ RP 512 G3-35_21.cdr 2010-06-03 --
SEE DRAWING 512 G3 - 35, SHEET 1 / 3 and 3 / 3.
Drawing title
EBL512 G3, I/O expansion board 4583, J1 & J2
Connection diagram Supervised Inputs / units
Drawing number Sheet Revision
Panasonic Eco Solutions Nordic AB
512 G3 - 35 2/3 1
Revision Revision date Revision note Signature Checked
INPUTS & OUTPUTS EXPANSION BOARD 4583DE ("GFBP")
- - - - -
NOTE!
INTERNAL 24V DC IS THE NOMINAL VOLTAGE WHEN THE MAIN POWER SOURCE (RECTIFIER) IS
WIRING USED. WHEN THE SECOND POWER SOURCE (BACK-UP BATTERY) IS USED THE
VOLTAGE CAN BE 21.6-28V DC.
FUSES F1-F2:
SEE DRAWING OUTPUT 0 CAN BE USED
512 G3 -17 OUTPUT 2, INPUT 3 & 4 CAN BE USED AS A STANDARD FOR GERMAN FIRE ALARM
J1 GERMAN EXTINGUISHING INTERFACE ROUTING EQUIPMENT,
(STANDARDSCHNITTSTELLE "LÖSCHEN"). FIRE ALARM.
F1 + +
2) 1 "E" "BRANDMELDUNG"
200mA OUTPUT 0, 24V DC, SUPERVISED, NORMALLY LOW & PROGRAMMABLE (CONTROL EXPRESSION) 3) Trigger condition: Fire Brigade Tx.
- -
2
+ NO (>20K) NC (<500Ω) INPUT 0 CAN BE USED FOR GERMAN FIRE ALARM
1) 3
- INPUT 0, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) ALT. 1) ROUTING EQUIPMENT, FAULT INPUT. "J" "MELDER
4 QUITTUNG". Trigger condition: Fault warning routing equipment fault.
F2 + + AN INPUT HAS TO BE ACTIVATED >0.5 SEC.
2) 5
OUTPUT 1, 24V DC, SUPERVISED, NORMALLY LOW & PROGRAMMABLE (CONTROL EXPRESSION) 3)
OUTPUT 1 CAN BE USED FOR GERMAN KEY CABINET.
200mA - -
6 "FSK ÖFFNEN". Trigger condition: Key cabinet open.
+
7 INPUT 1 CAN BE USED FOR GERMAN KEY CABINET, FEEDBACK.
2 x T200mA 250 V - INPUT 1, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1)
8 "FSK RÜCKMELDUNG". Trigger condition: Activated Key cabinet.
(TR5)
+
9 INPUT 2 CAN BE USED FOR GERMAN KEY CABINET, SUPERVISION.
- INPUT 2, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1)
10 "FSK ÜBERWACHUNG".
3K3 680R +
11 SPECIAL OUTPUT FOR GERMAN EXTINGUISHING EQUIPMENT,
- OUTPUT 2, SUPERVISED, PROGRAMMABLE (CONTROL EXPRESSION & NORMALLY LOW OR HIGH RESISTANCE)
12 "G" "LÖSCHANLAGE". Trigger condition: Fire alarm.
LÖSCHANLAGE

NO / NC
+
13 INPUT 3 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, RELEASED.
P.C.B. LAYOUT ACCORDING TO

- INPUT 3, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1)


14 "G" "LÖSCHANLAGE AUSGELÖST" Trigger condition: Extinguishing system released.
DRAWING EBL512 G3 - 17.

+
15 INPUT 4 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, FAULT INPUT.
- INPUT 4, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1) "G" "LÖSCHANLAGE QUITTUNG" Trigger condition: Extinguishing system fault.
0V 16

J2
TO THE MAIN BOARD ("J9") Output 0 & 1
NOTE!
OR
1 Not activated (control expression not true): Supervision voltage 2.1 V DC
+24 V TO ANOTHER EXP. BOARD ("J2") This drawing 512 G3 - 35, sheet 3 of
2 3, is valid for board 4583DE. Activated (control expression true): 20.4 to 28 V DC
0V
3
L (SA) See also drawing 512 G3 - 26. Drawing 512 G3 - 35, sheet 1 of 3, is
4 NOTE! THE SUPERVISION VOLTAGE HAS THE SAME POLARITY AS THE 24V.
C (SB) valid for board 4583.

10 mm
TO ANOTHER EXP. BOARD ("J2")
J2: MALE, MOLEX OR
TYPE KK, 2.54 NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)

Original drawing A3L (420 x 297 mm)


NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) A PROGRAMMABLE INPUT CAN AS AN ALT. BE PROGRAMMED AS SUPERVISED. SEE DRW 512 G3 - 35, SHEET2/3. Designed by Checked by Approved by Filename Date Scale
2) VOLTAGE, SEE INFO. TO THE RIGHT. JP MÖ RP 512 G3-35_3x.cdr 2013-12-30 --
3) TERMINATION RESISTOR VALUE: 200 - 1000 OHM. (ACCORDING TO DIN 14675) Drawing title
EBL512 G3, I/O expansion board 4583, J1 &J2
Connection diagram Inputs & Outputs / units
Drawing number Sheet Revision
Panasonic Eco Solutions Nordic AB
512 G3 - 35 3/3 -
Revision Revision date Revision note Signature Checked

P.c.b. no. 9302-3B (on the reverse side of the p.c.b.)


59 mm
43 mm

S2 (mounted on the reverse side of the p.c.b.) S1 (mounted on the reverse side of the p.c.b.)
Connector for the Main board 5010 Connector for the Main board 5010

LED LD1
Flashing (1s/1s): Node not configured
Flashing a couple of times at startup then cont. off: Normal cond.
Cont. on: HW fault

1)
The TLON connection boards 1590 (no. 0 & no. 1) are plugged on the Main board 5010 (connectors S1 & S2). 2)
The TLON connection boards 1590 (no. 0 & no. 1) are internally connected to the Main board Terminal Block J4, to which the TLON Network cables are connected. 2)
The TLON connection boards 1590 (no. 0 & no. 1) are internally connected to the Main board RJ-45 connectors J10 & J11 resp. to which a laptop PC (TLON Manager) can be connected.

Connections also according to the drawings 512 G3 - 02 & - 03.

10 mm
The p.c.b. is mounted on the

Original drawing A3L (420 x 297 mm)


Main board 5010 according to
NOTE! Most of the components are deleted on the p.c.b. above for easier identification of connectors, etc. drawing 512 G3 - 11.
1) See drawing 512 G3 - 11. Designed by Checked by Approved by Filename Date Scale
2) See drawing 512 G3 - 24. JP MÖ RP 512 G3-13_1x.cdr 2010-06-03 Approx. 1:1
Drawing title
EBL512 G3, TLON connection board 1590
Dimensions & overview P.c.b. no. 9302-3B
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 13 1/1 -
Revision Revision date Revision note Signature Checked
Use cable ties to keep the
24 V DC wiring well separated 3 2013-01-30 F1-F5: Info. updated. JP MÖ
from the mains wires.
VO0 & VO1=PROGRAMMABLE & SUPERVISED OUTPUTS FOR e.g. ALARM DEVICES
The mains safety earth AD=ALARM DEVICE (SIREN, ETC.)
(ground) wire shall be longer D1=SUPPRESSION DIODE (e.g. 1N4004), WHEN REQUIRED.
than the other wires to ensure D2=SERIES DIODE (1N4004). Required in all Alarm Devices even if only one capacitor is used.
that it is the last to be dis- C=470nF, TEMP. STABLE <100PPM/°C. TO BE CONN. IN THE LAST UNIT
(END-OF-LINE CAPACITOR) OR CONN. INDIVIDUALLY IN UP TO FIVE
connected if the mains cable
DEVICES (i.e. UP TO FIVE 470nF CAPACITORS).
clamp should fail.
THE OUTPUT WILL BE ACTIVATED WHEN ITS PROGRAMMED CONTROL
EXPRESSION IS TRUE.

SEE DATA SHEET, TECHNICAL DESCRIPTION & PLANNING INSTRUCTIONS FOR


MORE INFORMATION.

BROWN AD AD
- + - +
BLUE

YELLOW-GREEN
D1 D1
4 D2 D2
C C

9. VO0+

10. VO0-
RED F1

11. VO1+
F1:T5A, glass BLACK VO1
LIKE
F2:T5A, CERAMIC 12. VO1- VO0
F3:T5A, CERAMIC GREEN VO2=SPECIAL OUTPUT FOR
F5:T4A, GLASS FIRE DOOR RELEASE MAGNET(S) ONLY
NOTE!
13. VO2+
M=FIRE DOOR RELEASE MAGNET
2 THE 3366 & 3364 UNITS HAVE D1=SUPPRESSION DIODE (e.g. 1N4004)
TO BE POWER SUPPLIED
BUT NOT CONNECTED TO THE COM LOOP
14. VO2-
DURING ADDRESS SETTING.
F2 F5 M
JP1: RESET
RED
- +
JP2 OPEN:
LOW CHARGINGMODE. BLACK
D1
1
JP2 SHUNTED: F3
RED
HIGH CHARGINGMODE. 5

BLACK 3

10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) THERE IS SPACE IN THE HOUSING FOR TWO MAINTENANCE-FREE SEALED LEAD-ACID Designed by Checked by Approved by Filename Date Scale
5) IF TERMINAL 8 IS NOT CONNECTED TO
BACKUP BATTERIES (2x12V, 7.5Ah). CONNECTION WIRES ARE SUPPLIED. 3366 (J7:4) IT HAS TO BE CONNECTED TO JP MÖ RP 512 G3-38_13.cdr 2010-06-03 --
TERMINAL 6 (0 V).
2) DASHED WIRING=FACTORY MADE CONNECTIONS. Drawing title
EBL512 G3, Addr. 2 voltage outputs unit 3364
3) ONLY REQUIRED WHEN THE "FIRE DOOR CLOSING" FUNCTION (ABDL) IS TO BE USED IN 3364. Connection diagram Ext. power supply 3366
NORMALLY LOW. HIGH=LOSS OF MAIN POWER SOURCE IN 3366=FIRE DOOR SHALL CLOSE (VIA 3364). Drawing number Sheet Revision
4) ONLY THE MAINS SAFETY EARTH (GROUND) WIRE MUST BE CONNECTED TO THIS TERMINAL.
Panasonic Eco Solutions Nordic AB
512 G3 - 38 1/1 3
Revision Revision date Revision note Signature Checked

L (SA) C (SB) 1 2012-02-01 Note 4 added. JP MÖ


CONVENTIONAL DETECTOR ZONE
3361 MULTIPURPOSE I/O UNIT MAX. 50 OHM CONDUCTOR RESISTANCE, i.e. MAX. 400m CABLE TYP EELQRB 2x0.6mm.
CONVENTIONAL DETECTORS / MANUAL CALL POINTS
MAX. 32 ALARM POINTS IN EACH ZONE (EN54-2) 4
SCREW TERMINALS
MAX. 40 ALARM POINTS IN EACH ZONE (AUS./N.Z.)
INTERNAL A+ A+
470nF
WIRING
END-OF-LINE
CAPACITOR
B- B-

SA 1
DETECTORS WITH A CLOSING CONTACT (SHORT-CIRCUIT) CAN BE
SB 2 CONNECTED. IN Win512 G3 HAS TO BE SET THAT SHORT-CIRCUIT
COM SHALL ACTIVATE FIRE ALARM (INSTEAD OF FAULT).
SA 3 LOOP
EXAMPLE 1a
DETECTORS WITH A CLOSING CONTACT AND AN ALARM RESISTOR (e.g. 435x + base 2324).
SB 4
EXAMPLE 2
5 L (SA) C (SB)
In0(+) THE INPUT HAS TO BE PROGRAMMED.
2

6 NORMALLY CLOSED (NC) OR NORMALLY OPEN (NO) CONTACT.


Z(+)

Z/In0(-) 7
ALT.

In1(-) 8
An input has to be
9 3
In1(+) activated > 0.5 sec.

Not used (N.C.) 10


0V 0V
11 EACH OUTPUT HAS TO BE PROGRAMMED. ALT.
+24V, 8mA +24V, 8mA
Re1 NORMALLY OPEN (NO) OR NORMALLY CLOSED (NC) CONTACTS.
RELAY CONTACTS FOR 12
1 CONNECTION OF e.g. A BEAM DETECTOR OR THE INPUT HAS TO BE PROGRAMMED.
30V DC, 2A. 13 AN HSSD VIA THE 3361 ZONE LINE INPUT (Z)
NORMALLY HIGH (+24V) OR NORMALLY LOW.
(MAX. 125V AC) 3361 DETECTOR / HSSD
Re0 14 6 NOTE! EXT. POWER SUPPLY IS REQUIRED.
EXAMPLE 1b
FAULT

470nF
END-OF-LINE 680R (ALARM RESISTOR) NOTE!
CAPACITOR THE RELAY CONTACTS ARE SHOWN IN NORMAL OPERATION STATE.

INPUT In1 CAN BE USED FOR PRE-WARNING.


OUTPUT Re0 / Re1 CAN BE USED FOR FIRE ALARM RESET.
FIRE ALARM
7

10 mm
11

RESET PULSE DETECTOR RESET


12

Original drawing A3L (420 x 297 mm)


1) TRIGGER CONDITION "FIRE DOOR CLOSING" SHOULD FOR SAFETY REASONS Designed by Checked by Approved by Filename Date Scale

NOT BE USED FOR THESE OUTPUTS. JP MÖ RP 512 G3-36_11.cdr 2010-06-03 --


2) MONITORED INPUT USED AS ZONE LINE INPUT Z (6 / 7) OR MONITORED INPUT USED AS GENERAL INPUT In0 (5 / 7) Drawing title
EBL512 G3, Addr. Multipurpose I/O unit 3361
3) In1 (8 / 9): ISOLATED INPUT (OPTOCOUPLER)
Connection diagram COM loop / In- & outputs / Examples
4) Max. 50nF conductor capacitance. Max. 1.0 mA detector current consumption. Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 36 1/1 1
Revision Revision date Revision note Signature Checked

NOTE! Alt. a)
EXP. BOARD 4580
2 2012-08-27 Info. added/revised. 2822 & 3361 added JP MÖ
INTERCONNECTING CABLE (SEE BELOW)
Analog Intrinsically Safe (IS) detectors EX ZONE LINE INPUT
2840 IS analog smoke detector. (EOL RESISTOR)
2841 IS analog heat detector. SEE ALSO DWG 512 G3 - 33
HAZARDOUZ (Ex) AREA
The analog IS detectors are connected
to a COM loop via an IS barrier unit 2842. MTL5061
Connections, see drawing 512 G3 - 31. INTRINSICALLY SAFE (IS) INTRINSICALLY SAFE (IS)
GALVANIC ISOLATOR (2820) MOUNTING BASE MANUAL CALL POINT
Conventional Intrinsically Safe (IS) detectors (IN A WATERPROOF BOX) YBN-R / 4 IS (2812) 1) MCP1A-R470FF-H029-01IS (2814)
I.e. the IS manual call point 2814 or smoke detector Alt. a)
2810 and heat detector 2811 plugged in base 2812. 1 (+) 12+ 1-
Alt. a) ZONE 8) ZONE 1 CHANNEL 1 5)
2 (-) 11- 2+
The conventional IS detectors are connected
via a galvanic isolator 2820 to an expansion board
4580 zone line input, according to this drawing. 3 5 6 1 2 3 4 Alt. a): 10K
The zone line input is via WinG3 programmed as: 3 470R Alt. b): 8K2
EX zone line input (EOL resistor). 4
Alt. b) 9+ 4- EXT. END-OF-LINE
E-O-L resistor 10K supplied with 2820. 2 1
4) ZONE 2 4) LED RESISTOR
CHANNEL 2 6)
Alt. b) 8- 5+ 7)
The conventional IS detectors are connected
via a galvanic isolator 2820 to an Addressable
Isolated zone interface 2822 that is connected
6
to an I/O unit 3361 zone line input, according
to this drawing.
E-O-L resistor 8K2 supplied with 2822.
Alt. b)
Addressable Isolated
I/O unit (3361) zone interface (2822) EARTH CONDUCTOR TERMINAL
IN THE BOX
J1 J2
1 SA 1 OPTIONAL
CABLE SCREEN Alarm state current max. 50 mA @ 24 V
2 SB 2
CABLE:
2
COM loop 3) FKAR-PG 2x0.5 mm , BLUE
3 SA
(WITH ALUMINIUM POLYESTER FOIL SHEELD+TINNED COPPER
2
DRAIN WIRE 1 mm . NORMALLY NOT USED / CONNECTED.)
4 SB

5
THE INTERCONNECTING CABLE SHOULD HAVE THE FOLLOWING MAX. PARAMETERS:
6 In0 (Z) 3
GROUP CAPACITANCE (C) INDUCTANCE (L) INDUCTANCE TO RESISTANCE RATIO
7 In0 (Z) 4
µF mH OR µH / ohm

1+ IIC 0.13 4.2 55


24 V DC IIB 0.39 12.6 165

10 mm
2-
IIA 1.04 33.6 440

Original drawing A3L (420 x 297 mm)


1) IN THE BASE CAN BE PLUGGED A SMOKE DETECTOR SLR-E-IS (2810) OR A HEAT DETECTOR DCD-1E-IS (2811). NOTE! MAX. TOTAL CABLE RESISTANCE IS 40 ohm, i.e. THE ZONE LINE CABLE
2) - IN THE Ex AREA+THE ZONE LINE CABLE IN THE SAFE AREA <40ohm.
3) IF CABLE SCREEN IS USED IT SHOULD BE CONNECTED TO THE CLOSEST EARTH POINT (PROTECTIVE EARTH) OUTSIDE THE
Designed by Checked by Approved by Filename Date Scale
HAZARDOUZ AREA AND SHOULD BE CAPABLE OF WITHSTANDING A TEST VOLTAGE (500V AC) FOR ONE MINUTE.
4) ZONE 2 (CHANNEL 2) TO BE CONNECTED LIKE ZONE 1 (CHANNEL 1). JP MÖ RP 512 G3-37_12.cdr 2010-06-03 --
5) MAX. 5 UNITS ON THE ZONE LINE (CHANNEL). CABLE: FKAR-PG 2x0.5 mm2, BLUE.
Drawing title
6) BODY SURFACE AREA MIN.230 mm2. EBL512 G3, Hazardous (Ex) areas equipment
7) LED SURFACE AREA MIN. 230 mm2. MAX. 20 mA. MUST CONSIST OF A LIGHT EMITTING DIOD ONLY. Connection diagram Inputs / units
THE LED's CONNECTION CABLE IS CONSIDERED AS A PART OF THE INTERCONNECTING CABLE.
Drawing number Sheet Revision
8) EKKR / ELQRB 2x0.6 mm (0.3mm2). CONNECTION OF ALARM POINTS IS NOT ALLOWED ON THIS LINE. Panasonic Eco Solutions Nordic AB
512 G3 - 37 1/1 2
Revision Revision date Revision note Signature Checked
EXPLANATIONS
1. COM LOOP, -
NO FEEDER LINE A) LAST UNIT WHEN COMM. IN A-DIRECTION CABLE TYPE EXAMPLES
2
A-DIRECTION
B) LAST UNIT WHEN COMM. IN B-DIRECTION COM LOOP: ELKY 2x1mm (0.75mm) (TWISTED PAIR)
L A CABLE LENGTH WHEN COMM. IN A-DIRECTION FEEDER LINE: ELKY10x2x1mm (TWISTED PAIRS)
L B CABLE LENGTH WHEN COMM. IN B-DIRECTION OR THE HALOGEN-FREE & FLAME-PROOF TYPES:
B) COM LOOP: ELQYB 2x1mm (TWISTED PAIRS)
EBL
The A-direction cable length (LA) is most important since communication in the FEEDER LINE: ELQYB 10x2x1mm (TWISTED PAIRS)
B-direction is valid only in case of short-circuit or a break (cut-off) on the COM loop.
B-DIRECTION If so, the communication is in both directions (A & B) at the same time until the fault ALL TYPES HAVE THE PAIR CAPACITANCE 50nF/km AT 800Hz,
A) is corrected, which is checked every 10th minutes.
THE CONDUCTOR RESISTANCE 24.5 ohm/km
EQUIVALENT DIAGRAM
AND THE ATTENUATION 0.6dB/km AT 800Hz.
EBL EBL
THE NUMBER OF UNITS ON THE COM LOOP
L (SA) L (SA)
A-DIRECTION B-DIRECTION
C (SB) C (SB) THE UNITS ARE TO BE DISTRIBUTED AS EVEN AS POSSIBLE
B) A) ON THE COM LOOP

L A THE MAXIMUM NUMBER OF ADDRESSES (255) ON EACH COM LOOP


ONLY SHOWS THE ADDRESSES POSSIBLE TO USE.
LB
THE CURRENT CONSUMPTION ON THE COM LOOP IS
DEPENDING ON THE NUMBER & TYPE OF THE CONNECTED UNITS.

2. COM LOOP EACH UNIT'S CURRENT CONSUMPTION IS FOUND IN


INCL. FEEDER LINE = DETECTOR / ALARM POINT
PLANNING INSTRUCTIONS, CHAPTER "CURRENT CONSUMPTION".
A-DIRECTION 1)
DB=DISTRIBUTION BOX MAXIMUM CABLE LENGTH (L), i.e. THE CONDUCTOR RESISTANCE
IN RELATION TO THE CURRENT CONSUMPTION AND AVAILABLE
FEEDER- DB
LINE B) EBL=EBL512 G3 CURRENT ON THE COM LOOP: SEE PLANNING INSTRUCTIONS,
EBL CHAPTER "COM LOOP CABLE LENGTH".

B-DIRECTION
A)
NOTE! THE NUMBER AND TYPE
EQUIVALENT DIAGRAM OF UNITS, CABLE INSTALLA-
EBL DB DB EBL TION, EXT. DISTURBANCES,
L (SA) L (SA) ETC. MIGHT AFFECT THE CABLE
A-DIRECTION B-DIRECTION
RESISTANCE AND CAPA-
C (SB) C (SB)
B) A) CITANCE AND ALSO THE
COMMUNICATION.
L A

ALL CALCULATED VALUES

10 mm
LB
ARE CONSEQUENTLY
APPROXIMATE VALUES.

Original drawing A3L (420 x 297 mm)


1) THE TOTAL CONDUCTOR RESISTANCE R (=r ohm in CONDUCTOR L + r ohm in CONDUCTOR C) AND THE CABLE LENGTH Designed by Checked by Approved by Filename Date Scale
MUST NOT EXCEED THE VALUES FOUND IN PLANNING INSTRUCTIONS, CHAPTER "COM LOOP CABLE LENGTH". JP MÖ RP 512 G3-41_1x.cdr 2010-06-03 --
L (SA) Drawing title
The total conductor resistance will be EBL512 G3, COM loop cable
C (SB) R = two times rC-C (=2 x rC-C). Cable length & specifications
Ohm
meter r C-C L (SA) R must be < 42.3 ohm. Drawing number Sheet Revision
C (SB)
Panasonic Electric Works Nordic AB
512 G3 - 41 1/1 -
Revision Revision date Revision note Signature Checked
R = Termination resistor. 105R ±1%, 1/8 W. One termination resistor is required at the end points of each Channel. -
L = Cable length < 900 m. The cable has to be sheelded, e.g. Belden 7703 NH 1 pair 22 AWG or equivalent.

Two Control Units (00 & 01). No Router Up to six Control Units (00 - 05). No Router
C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001
no. 00 no. 01 no. 00 no. 01 no. 04 no. 05

5010 5010 5010 5010 5010 5010


Main board Main board Main board Main board Main board Main board

J4 J4 J4 J4 J4 J4

27 (F1)
2) 27 (F1) 27/31 (F1)
2) 27/31 (F1)
2) 27/31 (F1)
2) 27/31 (F1)

R 28 (F2) 28 (F2) R 28/32 (F2) 28/32 (F2) 28/32 (F2) 28/32 (F2)

29 (F1) 29 (F1) 29/33 (F1) 29/33 (F1) 29/33 (F1) 29/33 (F1)

30 (F2) R 30 (F2) 30/34 (F2) 30/34 (F2) 30/34 (F2) R 30/34 (F2)

2) Channel 1 2) 2) Channel 1 2)
L L

TLON Network no. 0 TLON Network no. 0 / 1

2) NOTE!
31 (F1) 31 (F1) When a redundant network is required both TLON Network no. 0 and
R 32 (F2) 32 (F2) TLON Network no. 1 have to be used.
33 (F1) 33 (F1)
Each TLON Network require one TLON Connection board 1590 to be plugged on
34 (F2) R 34 (F2) the Main board 5010, see drawing EBL512 G3 - 11.
2) Channel 1
L

TLON Network no. 1

Two Control Units (00 & 01). One Router Up to twelve Control Units (00 - 05) and (06 - 11). One Router

C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001
no. 00 TP/FT10 - TP/FT10 no. 01 no. 00 TP/FT10 - TP/FT10 no. 11

5010 5010 5010 5010


Main board Main board Main board Main board

J4 J4 J4 J4

27/31 (F1) A1 27/31 (F1) A1


2) 2)
R 28/32 (F2) A2 R 1) 27/31 (F1) R 28/32 (F2) A2 R 1) 27/31 (F1)

29/33 (F1) SHA 28/32 (F2) 29/33 (F1) 28/32 (F2)


SHA
30/34 (F2) B1 29/33 (F1) 30/34 (F2) B1 29/33 (F1)
1) R B2 R 30/34 (F2) 1) R B2 R 30/34 (F2)
2) SHB
2)
SHB
Va
Channel 1 Channel 2 Channel 1
Va
Channel 2
24V DC/AC Vb
24V DC/AC Vb
L L L L

TLON Network no. 0 / 1 TLON Network no. 0 / 1

10 mm
Original drawing A3L (420 x 297 mm)
Designed by Checked by Approved by Filename Date Scale
1) The SysMik SmartRouter TP/FT10 - TP/FT10 has built-in termination resistors, which can be connected va DIP switches.
2) Screen shall be connected to the C.i.e. earth point (see drawing 512 G3 - 01). JP MÖ RP 512 G3-42_1x.cdr 2010-06-03 --
Drawing title
EBL512 G3, TLON Network. Examples,
Connection diagram 2-12 Control units
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 42 1/1 -
Revision Revision date Revision note Signature Checked
R = Termination resistor. 105R ±1%, 1/8 W. One termination resistor is required at the end points of each Channel. -
L = Cable length < 900 m. The cable has to be sheelded, e.g. Belden 7703 NH 1 pair 22 AWG or equivalent.

Up to six Control Units (00 - 05). One Router (no. 1) Up to six Control Units (06 - 11). One Router (no. 2) Up to six Control Units (12 - 17). One Router (no. 3)

C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 SysMik SmartRouter
no. 00 TP/FT10 - TP/FT10 no. 06 TP/FT10 - TP/FT10 no. 12 TP/FT10 - TP/FT10

5010 5010 5010


Main board Main board Main board

J4 J4 J4

27 (F1) A1 27 (F1) A1 27 (F1) A1

R 28 (F2) A2 R 1) R 28 (F2) A2 R 1) R 28 (F2) A2 R 1)


29 (F1) SHA 29 (F1) SHA 29 (F1) SHA
30 (F2) 30 (F2) 30 (F2)

2) Channel 1 2) Channel 2 2) Channel 3


L L L

TLON Network no. 0 TLON Network no. 0 TLON Network no. 0

B1 B1 B1

1) R B2 B2 B2 To be cont. below.
SHB SHB SHB

Va Va Va

24V DC/AC Vb 24V DC/AC Vb 24V DC/AC Vb


Backbone, Channel 6
L

Up to six Control Units (18 - 23). One Router (no. 4) Up to six Control Units (24 - 29). One Router (no. 5)

C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 SysMik SmartRouter
no. 18 TP/FT10 - TP/FT10 no. 24 TP/FT10 - TP/FT10

5010 5010
Main board Main board

J4 J4

27 (F1) A1 27 (F1) A1

R 28 (F2) A2 R 1) R 28 (F2) A2 R 1)
29 (F1) SHA 29 (F1) SHA
30 (F2) 30 (F2)

2) Channel 4 2) Channel 5
L L

TLON Network no. 0 TLON Network no. 0

B1 B1

To be cont. above. B2 B2 R 1)
SHB SHB
Va Va

24V DC/AC Vb 24V DC/AC Vb

Backbone, Channel 6
L NOTE!
When a redundant network is required both TLON Network no. 0 and
TLON Network no. 1 have to be used.

10 mm
For the TLON Network no. 1, J4 terminal numbers, see drawing 512 G3 - 42.

Each TLON Network require one TLON Connection board 1590 to be plugged on
the Main board 5010, see drawing EBL512 G3 - 11.

Original drawing A3L (420 x 297 mm)


Designed by Checked by Approved by Filename Date Scale
1) The SysMik SmartRouter TP/FT10 - TP/FT10 has built-in termination resistors, which can be connected va DIP switches.
JP MÖ RP 512 G3-43_1x.cdr 2010-06-03 --
Drawing title
EBL512 G3, TLON Network. Example,
Connection diagram 30 Control units + 5 Routers
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 43 1/1 -