Professional Documents
Culture Documents
EBL512 G3 Drawings
EBL512 G3 Drawings
5089
Door 3) 3)
switch LCD (5038) Front (5060 / 5061)
Expansion boards
no. 0 - 5
J9 J12 J7 J13
{
1
{
COM loops
2
3
458x
4
5
6
7
8
9
J5
J1 J1
See drawings 512 G3 - 25, - 31
10
11
12
13
1) J2
14
15
16
J1
{
1
2
3
J9
10
11
12
13
J2
16
17
J3
18
19
20
21
J4
See drawings 512 G3 - 23, - 24 Main board 5011 MMI board
22
23
24
0
25
26
27
28
29
30
32
34
31
33
35
J4 J7 J6
36
37
38
39
40
0
24 V DC outputs
{ 1590 /
1
2
3
4
J3
5
6
9
0
5090
10
11
12
1
J4: 14 conductors ribbon cable
2
1
3
J2 1590 /
4
1
5
5090
{
J10 0 1 J11
458x Backside view
1)
Loudspeaker (5036)3)
J1
Not in 5001.
J2
5000 / 5001 Standard equipment:
5 5010 Main board
Power supply 5037
(Rectifier) 2) 5011 MMI board (not in 5001)
T6.3A H 250V 230 V AC, 1.6 A 5037 Power supply
(5x20mm ceramic) 24 V DC, 6.5 A 5038 Display - LCD (not in 5001)
3)
Printer (5058) 5060 / 5061 Front (not in 5001)
Not in 5001.
Options:
1590 / 5090 TLON Network connection board
1598 Web-server II
4580 8 zones exp. board
Battery Battery 4581 8 relays exp. board
12 V, 28 Ah 12 V, 28 Ah
4583 I/O exp. board
5089 Exp. boards connection cable
Battery temperature
sensor (5039) Spare parts:
3) 5036 Loudspeaker
E.g. Panasonic LC-P1228AP 5038 LCD
10 mm
5039 Battery temp. sensor
Mains 230 V AC 5058 Printer
(via a two-way circuit breaker) 5059 Printer paper roll
10 mm
Depth 187 mm (177)
C.i.e. skin bottom Mains cable clamp 1. Put up the wall mounting plate on the wall.
2. Hook the C.i.e. metal housing on the wall mounting plate and fix.
10 mm
Original drawing A3L (420 x 297 mm)
Designed by Checked by Approved by Filename Date Scale
1) 5000 can be delivered with or without a printer depending on the article number (5000xxx). See also drawing 512 G3 - 01, sheet 1 / 2.
2) 5000 without a printer has no Mounting frame for printer. JP MÖ RP 512 G3-01_21.cdr 2010-06-03 Approx. 1:5
3) 5000 without a printer has no opening for printer in the plate below the c.i.e. front. Drawing title
4) Spare part number.
EBL512 G3, Control unit (C.i.e.) 5000 / 5001
Dimensions & overview
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 01 2/2 1
Revision Revision date Revision note Signature Checked
This drawing shall be read in conjunction with drawing 512 G3 - 02. 1 2012-02-01 Some texts updated. Note 5 added. JP MÖ
Mains Battery Battery 5037 5010 Main board USB (B) Door Temp. 458x
230 V AC (Left) (Right) Power switch sensor (Expansion board)
supply
J1 J2 ETM 1 ETM 2 J10 J11 J4 J12 J13 J18 J9 (5039) J2 J2 J2 J2 J2 J2
1) 2) USB (B) 4) 4) 5) (no.0) (no.1) (no.2) (no.3) (no.4) (no.5)
L L F1 7 27 1 1
N N F2 8 28 2 2
? FG 29 3 3
V+ 1+ 30 4 4
V- 2- F1 7 31 1
+ 4+ F2 8 32 2
- + 33 1
- 5- 34 2
To be cont. below.
4) 4)
12
1 1 1 1 1 1 1
2 2 2 2 2 2 2
3 3 3 3 3 3 3
4 4 4 4 4 4 4
C.i.e. 5000
1 1 1
2 2 2
To be cont. above.
12 10 10
1 1
2 2
15 15
1 1
2 2
14 14
1 1
4 2
1 +5 V
10 mm
2 TxD
3 RxD
4 RTS
5 GND
12
10
16
14
12
10
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
2
8
2
T.B. J2
200 mm
15
13
11
11
39
37
35
33
31
29
27
25
23
21
19
17
15
13
11
9
1
9
1
J9
T.B. J3 T.B. J4 T.B. J5
NOTE! Most of the components are deleted on the p.c.b. to the right, for easier identification of connectors, etc.
For connection of
1
Expansion boards 512 G3 - 26
458x (J2)
F2 F1
J12
F12 F10 F8 F19 F7 F6 F5 F4 Internal connection
F11 F9 F13 to USB port (type "B") mounted
F18 in the metal housing frame,
intended for connection of
Not used a laptop PC (Win512 G3)
LED D11
Blinking: TLON board
no. 0 communicating. J7
Steady: TLON board For connection of
no. 1 (back-up board) F14 F17 F16 F15 Web-server 1598 512 G3 - 32
communicating. (RS232)
JP1
Service pins for
TLON board no. 0 SW2 1)
Main board (C.i.e.) boot
JP2
Service pins for P.c.b. label for
TLON board no. 1 identification
2) 2)
For connection of a J13
laptop PC (TLON Internal connection
F3
Manager) to TLON to the C.i.e. door switch
board no. 1
10 mm
1)
SW1
Main board (i.e. C.i.e.) restart
-V
T6.3A H 250V (5x20mm ceramic)
4) Power supply mounted in the C.i.e.
CAUTION:
RISK OF EXPLOSION IF BATTERY -V according to drawing 512 G3 - 01.
IS REPLACED BY INCORRECT TYPE. F
DISPOSE USED BATTERIES +V
ACCORDING TO THE INSTRUCTIONS. NOTE!
+ - + - External batteries
The lid for the screw terminals shall after the
+V installation be correctly applied, i.e. protecting
Batteries > 28 Ah (but < 65 Ah) have to be the screw terminals.
placed outside the c.i.e.
10 mm
Due to the battery checking function, (LED1)
cables max. 3 m & min. 4 mm2 are recommended.
2 x 12 V, 28 Ah (placed inside the c.i.e.) Connections also according to
NOTE!
The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).
4)
3) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
In fire alarm condition < 6.0 A is available for the c.i.e. and all connected equipment.
10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale
1) See drawing 512 G3 - 32.
2) Normally used for routing equipment (fire brigade tx). JP MÖ RP 512 G3-22_12.cdr 2010-06-03 --
3) In quiescent condition the battery charging current can be up to 3A (6.3-3=3.3A). Drawing title
EBL512 G3, Main board 5010, T.B. J3
Battery charging will be turned off during fire alarm condition (6.0-0=6.0A).
Connection diagram, Web-server & Power supply outp. 0-4
4) Note that if 28 Ah batteries are used and 30 hours battery back-up time is required, max. 0.93 A can be used in quiescent condition (since 30 x 0.93 = 28).
Drawing number Sheet Revision
5) The fuse F18 is not supervised. Panasonic Eco Solutions Nordic AB
512 G3 - 22 1/1 2
Revision Revision date Revision note Signature Checked
Main board 5010
2 2012-02-01 Note 2: Info added. JP MÖ
INTERNAL
WIRING
3)
Web-server II, 1598 1. TX+
2. TX-
3. RX+
4.
PLC COM 5.
J7 (RS232C) ETHERNET COM 6. RX-
7.
8.
1 YELLOW YELLOW S (TXD) 8
RxD
GREEN RS232 SERIAL LINE FOR WEB-SERVER GREEN For connection to a 4)
2 R (RXD)
TxD Local Area Network.
3 BLACK BLACK G (GND)
(0V) GND 1
2) 1 BROWN BROWN
+24 V + For connection to a separat
6 1
2 BLUE BLUE presentation system when
0V - 9 5 the Gateway function is used.
GREEN GREEN
EARTH 1)
EMI FILTER
1.
2. RxD
(MALE, MOLEX TYPE KK, 3.5) (SERIAL PORT, 3. TxD
J2 MALE 9-PIN CONN.) 4.
5. GND
1 6.
7. RTS
2 8. CTS
9.
3
10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
Designed by Checked by Approved by Filename Date Scale
1) Remove any factory mounted connector before connection to J3 and J2.
2) Web-server power supply fuse F18 (2A), see drawing 512 G3 - 22. Fuse F18 is not supervised.
JP MÖ RP 512 G3-32_12.cdr 2010-06-03 --
3) Web-server shall be mounted on the DIN rail inside the C.i.e. metal housing. See drawing 512 G3 - 01, sheet 1 / 2. Drawing title
EBL512 G3, Main board 5010, T.B. J3:1-2 & J7
4) Cable, e.g. CAT-5, CAT-5.1, CAT-6 etc. Connection diagram Web-server II, 1598
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 32 1/1 2
Revision Revision date Revision note Signature Checked
AD=Alarm Device (siren, etc.).
D1=Suppression Diode (e.g. 1N4004), when required. 3 2013-12-30 Sheet 2 added. Info. text added. JP MÖ
NOTE! D2=Series Diode (e.g. 1N4004). Required in all Alarm
Devices even if only one resistor is used.
R =Resistor 33K
This drawing 512 G3 - 23, sheet 1 of 2, No. 5 No. 1
is valid when the Voltage outputs S0 - S3 Internal connections on Main board 5010
have not to fulfil the EN54-13 regulation.
AD AD P.c.b. layout, see drawing 512 G3 - 11.
Else drawing 512 G3 - 23, sheet 2 of 2, - + - +
is valid.
D1
D2
D1
D2 Terminal Block J4 4 x T500mA 250 V (TR5)
2)
Programmable Voltage Outputs S0 - S3 R R 0V
1 F4 (500mA)
Each voltage output has to be programmed to be:
- Normally High or Normally Low
S0
Voltage output 5) 2 +24 V, Activated
+5 V, Supervised
3 F5 (500mA)
- Supervised or Not Supervised. 2)
Voltage output S1 5) 4
Each output has to have a control expression 5 F6 (500mA)
(i.e. one or more output trigger conditions). Voltage output S2 5) 6 S1-S3 are like S0.
7 F7 (500mA)
Voltage output S3 1) 5) 8
Programmable Relay Outputs R0 - R1 Relay contacts programmable to be
9
Each relay output has to be programmed to be: Normally Open (NO)
Normally Open (NO) or Normally Closed (NC).
Relay output R0 10 or
11 Normally Closed (NC)
Each output has to have a control expression Relay output R1 12 Contacts for max. 30 V, 1A.
(i.e. one or more output trigger conditions). 13
+ 24 V
Input I0 alt. 14
15
Programmable Inputs I0 - I3 Input I1 alt. 16
Each input has to be programmed to be: 17
Normally Open (NO) or Normally Closed (NC). Input I2 alt. 18
19
Each input has to have an input trigger
condition.
Input I3 alt. 20
NOTE!
The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).
4)
3) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
In fire alarm condition < 6.3 A is available for the c.i.e. and all connected equipment.
10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) Voltage Output S3 will be low in case of watchdog fault, i.e. this output can be used as a supervised Fault condition output for routing equipment (fault tx). Designed by Checked by Approved by Filename Date Scale
2) Only a normally low Voltage Output can be supervised. One or up to five 33K resistors can be used. After connecting / changing equipment on a supervised output, a JP MÖ RP 512 G3-23_13.cdr 2010-06-03 --
calibration has to be done via menu H5 / A1. The calibrated value has to be in the range 4K7 - 50K, else a fault will be generated.
Drawing title
During the calibration and during restart of the C.i.e. a normally high output will be low for a few seconds. EBL512 G3, Main board 5010, T.B. J4:1-20
3) In quiescent condition the battery charging current can be up to 3A (6.3-3.0=3.3A). Connection diagram, Out- & inputs S0-S3, R0-R1 & I0-I3
Battery charging will be turned off during fire alarm condition (6.3-0=6.3A).
Drawing number Sheet Revision
4) Note that if 28 Ah batteries are used and 30 hours battery back-up time is required, max. 0.93 A can be used in quiescent condition (since 0.93A x 30h = 28Ah). Panasonic Eco Solutions Nordic AB
5) One 33K resistor is supplied per output. Can be dis-connected and used as end-of-line resistor. 512 G3 - 23 1/2 3
Revision Revision date Revision note Signature Checked
is valid when the Voltage outputs S0 - S3 Internal connections on Main board 5010
have to fulfil the EN54-13 regulation.
AD P.c.b. layout, see drawing 512 G3 - 11.
Else drawing 512 G3 - 23, sheet 1 of 2, - +
is valid.
R D
Terminal Block J4 4 x T500mA 250 V (TR5)
Each output has to have a control expression Relay output R1 12 Contacts for max. 30 V, 1A.
(i.e. one or more output trigger conditions). 13
+ 24 V
Input I0 alt. 14
15
Programmable Inputs I0 - I3 Input I1 alt. 16
Each input has to be programmed to be: 17
Normally Open (NO) or Normally Closed (NC). Input I2 alt. 18
19
Each input has to have an input trigger
condition.
Input I3 alt. 20
NOTE!
The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).
3)
2) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
In fire alarm condition < 6.3 A is available for the c.i.e. and all connected equipment.
10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) Cable resistance < 50 ohm. Designed by Checked by Approved by Filename Date Scale
2) In quiescent condition the battery charging current can be up to 3A (6.3-3.0=3.3A). JP MÖ RP 512 G3-23_2x.cdr 2013-12-30 --
Battery charging will be turned off during fire alarm condition (6.3-0=6.3A).
3) Note that if 28 Ah batteries are used and 30 hours battery back-up time is required, max. 0.93 A can be used in quiescent condition (since 0.93A x 30h = 28Ah). Drawing title
EBL512 G3, Main board 5010, T.B. J4:1-20
Connection diagram, Out- & inputs S0-S3, R0-R1 & I0-I3
Drawing number Sheet Revision
Panasonic Eco Solutions Nordic AB
512 G3 - 23 2/2 -
Revision Revision date Revision note Signature Checked
J4 J4
2 2013-01-30 F19: Info. updated. Company name updated. JP MÖ
35 35
FBF2003 36 FAT2002 36
RxD+ 37 RxD+ 37
38
Internal connections on Main board 5010
RxD- 38 RxD-
P.c.b. layout, see drawing 512 G3 - 11.
UB+ GND
0V UB+
Terminal Block J4
7) 3) 7) 3)
Terminal Block J4 cont. on drawing 512 G3 - 23
Display Unit types When Display Unit types 1826, 1828, 1735, 1736 and/or 1728 are
used, no German FBF2003 or FAT2002 can be used and vice versa.
1826 / 1828 External Fire Brigade Panel
1735 / 1736 Alert Annunciation Unit NOTE!
1728 External Presentation Unit The relay contacts are
Fire alarm 21
shown for a powerless C.i.e.
or
FBF2003
FAT2002
German Fire Brigade Panel
(Feuerwehr-Bedienfeld)
German Fire Brigade Indicator Panel
relay output for e.g. routing equipment
"Fire brigade tx"
6)
{ 22
24
23 Normally the fault relay is
activated, i.e. it will be
de-activated for a fault
Fault condition
(Feuerwehr-Anzeigetableau) relay output for e.g. routing equipment
"Fault tx"
{ 26
25
27
condition.
Contacts for max. 30 V, 1A.
"F1" (0)
1)
{ TLON Network (FTT-10) no. 0, in or termination resistor 105R, ± 1%, 1/8 W
TLON Network (FTT-10) no. 0, out or termination resistor 105R, ± 1%, 1/8 W
"F2" (0)
"F1" (0)
"F2" (0)
3)
3)
28
30
29
31
Connector "J10"
TLON connection
board 1590,
no. 0
1)
"F1" (1)
2)
{ TLON Network (FTT-10) no. 1, in or termination resistor 105R, ± 1%, 1/8 W
TLON Network (FTT-10) no. 1, out or termination resistor 105R, ± 1%, 1/8 W
"F2" (1)
"F1" (1)
"F2" (1)
3)
3) +24 V
32
34
33
35 F19
10)
(1.6A)
Connector "J11"
TLON connection
board 1590,
no. 1
2)
{
+24 V 3 5 used.
0V 4 6 T1.6A 250 V (TR5)
To the next 5 7
Display Unit 6 8 NOTE!
B (-) "S0" 7 The Power supply 5037 rated output current is < 6.5 A but is limited to 6.3 A (by F1).9)
5) 4) 3)
A (+) "S1" 8
8) In quiescent condition < 3.3 A is available for the c.i.e. and all connected equipment.
4) In fire alarm condition < 6.0 A is available for the c.i.e. and all connected equipment.
Max. 1200 m cable for Display Units,
10 mm
e.g. LIHCH-TP 2x2x0.75 mm2 or equivalent.
Max. 16 Display Units can be connected.
REQUIRE ONE ADDRESS 1 ARE CONNECTED TO THE SAin & SAout TERMINALS IN /OK
P1: 1 2 3 JP1: OUT THE 4313 UNIT. DOUBLECHECK THE CONNECTIONS!! 0 V DC - + 24 V DC
10 mm
12 CONNECTIONS TO 3364 & 3366,
SEE ALSO DRAWING 512 G3 - 38
230 V AC
2218
Terminal block J5 2)
1)
In total 4 x 255 = 1020 addresses (units).
NOTE!
Max. 512 addresses (units) can be alarm points.
EBL512 G3 can have one of three basic configurations: Normally communication in the A-direction only.
1. Max. 128 alarm points In case of break (cut-off) or short-circuit on the loop, communication in both the A- and B-direction.
2. Max. 256 alarm points
3. Max. 512 alarm points NOTE!
Via menu H5 / A3, the communication can be turned off in order to check the COM loop voltage in the A- or B-direction or
in both directions.
Recommended COM loop cable: Via menu H8 / S1, the COM loop respectively can be (galvanicly) disconnected and Re-connected.
ELQYB 2 x 1 mm (=0.75 mm2); Twisted pair.
Wire resistance: 24.5 ohm per km.
Pair capacitance: 50 nF per km at 800 Hz.
Attenuation: 0.6 dB per km at 800 Hz.
10 mm
Max. COM loop cable length is depending on the cable type and the COM loop units' current consumption.
Expansion boards 458x 2 2013-01-30 Fuse F13: T4A -> F4A. Company name updated. JP MÖ
J9 2)
Expansion boards 458x 5089 Ribbon cable with connectors
1) for J9 - J2(0) - - J2(5). F13 (4A)
Up to six boards can be + 24 V
0V
mounted in the C.i.e.
metal housing. IC24
Board no. 0 - 5.
J2 (1) J2 (0)
J2 (3) J2 (2)
The boards are mounted in the C.i.e. metal housing according to drawing 512 G3 - 01, sheet 1 / 2.
The board no. (address) is not depending on the position of the board or which connector
on the connection cable it is connected to.
Each board has to have a unique board no. (0 - 5) in accordance with the WinG3 programming.
10 mm
Jumpers JP2, JP3 & JP4 on each expansion board are used for the board no. (0 - 5) setting.
Jumper positions according to drawings 512 G3 - 14, -15 & -17.
J2 (5) J2 (4)
164 mm
9291-4A
140 mm
J1 1)
SW1
Internal connection
MMI board restart
to Main board 5010, J1
1)
9291-4A SW2
MMI board boot
P.c.b. label for
identification
J2 & J3
Internal connections
LEDs
to the Front 5060/5061
J9
(LEDs and Keyboard)
Internal connection
to LCD 5038
LED D18
Steady: Normal condition
VR1 Off: Restart or MMI board in "Boot" mode
Potentiometer for
LED D11
Loudspeaker
For future use
VR2
Potentiometer for
LCD contrast
J7 J6
Internal connection Internal connection
to Loudspeaker (5036) to Printer (5058)
2) 2)
J4
10 mm
Internal connection
to LCD (5038)
2) The p.c.b. is mounted in
13 mm 88 mm 13 mm
JP1
8 zones exp. board restart
Not used
6 mm JP4 ("4")
JP3 ("2")
JP2 ("1")
Jumpers for board no. (address) setting (0-5)
(e.g. JP2 & JP3 shunted=no. "3")
J3
For production only
82 mm
JP6
For production only.
(Shall be normally shunted.)
20 mm
J1 1)
8 zone line inputs (0-7)
Connections to J1
according to
J2 drawing 512 G3 - 33.
For connection to:
- The main board 5010 (J9) and the next expansion board 458x (J2)
- Other expansion boards 458x (J2)
10 mm
See drawings 512 G3 - 02, - 03 & - 26.
10 mm
J2: MALE, MOLEX OR
TYPE KK, 2.54 MAX. 40 POINTS ON EACH ZONE LINE IN AUS. / N.Z.
NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)
MAX. 512 ALARM POINTS IN ONE C.I.E. (EN54-2)
13 mm 88 mm 13 mm
JP1
8 relays exp. board restart
Not used
6 mm JP4 ("4")
JP3 ("2")
JP2 ("1")
Jumpers for board no. (address) setting (0-5)
(e.g. JP2 & JP3 shunted=no. "3")
J3
For production only
82 mm
20 mm
J1 1)
8 relay outputs (0-7)
Connections to J1
according to
J2 drawing 512 G3 - 34.
For connection to:
- The main board 5010 (J9) and the next expansion board 458x (J2)
- Other expansion boards 458x (J2)
10 mm
See drawings 512 G3 - 02, - 03 & - 26.
J1
RELAY OUTPUT
1
0 0
2
3
1 1
4
5
2 2
6
11
5 5
12 RELAY CONTACT RATINGS:
MAX. 2 A @ 30 V DC.
13
6 6
14
15
7 7
16
10 mm
J2: MALE, MOLEX OR
TYPE KK, 2.54 NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)
63 mm
JP6 ("4")
JP5 ("2") 80 mm
JP4 ("1")
Jumpers for mode setting,
i.e. type of board (0-2) J3
0=Fan control For production only
1=Zone control
2=Generic
P.c.b. label for identification
JP1 ("1")
JP2 ("2") JP7
JP3 ("4") For production only.
Jumpers for board no. (address) setting (0-5) (Shall normally not be shunted.)
(e.g. JP1 & JP2 shunted=no. "3")
The I/O Matrix board 4582 has 16 switch inputs and 48 LED outputs and has to be used in conjunction with an Application board.
10 mm
Original drawing A3L (420 x 297 mm)
NOTE! Most of the components are deleted on the p.c.b. above for easier identification of connectors, etc.
Designed by Checked by Approved by Filename Date Scale
13 mm 88 mm 13 mm
JP1
Inputs and outputs exp. board restart
6 mm
JP2 ("1")
JP3 ("2")
JP4 ("4")
Jumpers for board no. (address)
setting (0-5) J3
(e.g. JP2 & JP3 shunted=no. "3") For production only
82 mm
F1 F2 P.c.b. label for identification
20 mm
J1 1)
5 inputs (0-4) and 3 outputs (0-3)
Connections to J1
according to
J2 drawing 512 G3 - 35.
For connection to:
- The main board 5010 (J9) and the next expansion board 458x (J2)
- Other expansion boards 458x (J2)
10 mm
See drawings 512 G3 - 02, - 03 & - 26.
NO / NC
+
13 INPUT 3 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, RELEASED.
P.C.B. LAYOUT ACCORDING TO
+
15 INPUT 4 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, FAULT INPUT.
- INPUT 4, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1) "G" "LÖSCHANLAGE QUITTUNG" Trigger condition: Extinguishing system fault.
0V 16
10 mm
TO ANOTHER EXP. BOARD ("J2")
J2: MALE, MOLEX OR
NOTE! THE SUPERVISON VOLTAGE HAS REVERSE POLARITY COMPARED TO 24V.
TYPE KK, 2.54 NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)
1)
4583 INPUT 0-4, SUPERVISED, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY HIGH OR LOW RESISTANCE), SEE TABLES.
4583
Line resistance R Normally Normally
high resistance low resistance
R > 6K8 Fault Fault
6K8 > R > 2K Not activated Activated
(nom. 3K3)
2K > R > 70 Activated Not activated
(nom. 680)
R < 70 Fault Fault
4583GE
Line resistance R Normally Normally
high resistance low resistance
R > 4K Fault Fault
4K > R > 3K Not activated Activated
(nom. 3K3)
3K > R > 2K Fault Fault
2K > R > 70 Activated Not activated
(nom. 680)
R < 70 Fault Fault
10 mm
NOTE!
24 V DC IS THE NOMINAL VOLTAGE WHEN THE MAIN POWER SOURCE (RECTIFIER) IS USED.
WHEN THE SECOND POWER SOURCE (i.e. THE BACK-UP BATTERY) IS USED THE VOLTAGE CAN BE 20-28 V DC
ON BOARD 4583 AND 21.6-28 V ON BOARD 4583GE.
NO / NC
+
13 INPUT 3 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, RELEASED.
P.C.B. LAYOUT ACCORDING TO
+
15 INPUT 4 CAN BE USED FOR GERMAN EXTINGUISHING EQUIPMENT, FAULT INPUT.
- INPUT 4, PROGRAMMABLE (TRIGGER CONDITION & NORMALLY OPEN OR CLOSED) 1) "G" "LÖSCHANLAGE QUITTUNG" Trigger condition: Extinguishing system fault.
0V 16
J2
TO THE MAIN BOARD ("J9") Output 0 & 1
NOTE!
OR
1 Not activated (control expression not true): Supervision voltage 2.1 V DC
+24 V TO ANOTHER EXP. BOARD ("J2") This drawing 512 G3 - 35, sheet 3 of
2 3, is valid for board 4583DE. Activated (control expression true): 20.4 to 28 V DC
0V
3
L (SA) See also drawing 512 G3 - 26. Drawing 512 G3 - 35, sheet 1 of 3, is
4 NOTE! THE SUPERVISION VOLTAGE HAS THE SAME POLARITY AS THE 24V.
C (SB) valid for board 4583.
10 mm
TO ANOTHER EXP. BOARD ("J2")
J2: MALE, MOLEX OR
TYPE KK, 2.54 NOT CONNECTED (ON THE LAST / SIXth EXP. BOARD)
S2 (mounted on the reverse side of the p.c.b.) S1 (mounted on the reverse side of the p.c.b.)
Connector for the Main board 5010 Connector for the Main board 5010
LED LD1
Flashing (1s/1s): Node not configured
Flashing a couple of times at startup then cont. off: Normal cond.
Cont. on: HW fault
1)
The TLON connection boards 1590 (no. 0 & no. 1) are plugged on the Main board 5010 (connectors S1 & S2). 2)
The TLON connection boards 1590 (no. 0 & no. 1) are internally connected to the Main board Terminal Block J4, to which the TLON Network cables are connected. 2)
The TLON connection boards 1590 (no. 0 & no. 1) are internally connected to the Main board RJ-45 connectors J10 & J11 resp. to which a laptop PC (TLON Manager) can be connected.
10 mm
The p.c.b. is mounted on the
BROWN AD AD
- + - +
BLUE
YELLOW-GREEN
D1 D1
4 D2 D2
C C
9. VO0+
10. VO0-
RED F1
11. VO1+
F1:T5A, glass BLACK VO1
LIKE
F2:T5A, CERAMIC 12. VO1- VO0
F3:T5A, CERAMIC GREEN VO2=SPECIAL OUTPUT FOR
F5:T4A, GLASS FIRE DOOR RELEASE MAGNET(S) ONLY
NOTE!
13. VO2+
M=FIRE DOOR RELEASE MAGNET
2 THE 3366 & 3364 UNITS HAVE D1=SUPPRESSION DIODE (e.g. 1N4004)
TO BE POWER SUPPLIED
BUT NOT CONNECTED TO THE COM LOOP
14. VO2-
DURING ADDRESS SETTING.
F2 F5 M
JP1: RESET
RED
- +
JP2 OPEN:
LOW CHARGINGMODE. BLACK
D1
1
JP2 SHUNTED: F3
RED
HIGH CHARGINGMODE. 5
BLACK 3
10 mm
Original drawing A3L (420 x 297 mm)
NOTE!
User installed cables shall be tied together, i.e. safely away from mains terminals.
1) THERE IS SPACE IN THE HOUSING FOR TWO MAINTENANCE-FREE SEALED LEAD-ACID Designed by Checked by Approved by Filename Date Scale
5) IF TERMINAL 8 IS NOT CONNECTED TO
BACKUP BATTERIES (2x12V, 7.5Ah). CONNECTION WIRES ARE SUPPLIED. 3366 (J7:4) IT HAS TO BE CONNECTED TO JP MÖ RP 512 G3-38_13.cdr 2010-06-03 --
TERMINAL 6 (0 V).
2) DASHED WIRING=FACTORY MADE CONNECTIONS. Drawing title
EBL512 G3, Addr. 2 voltage outputs unit 3364
3) ONLY REQUIRED WHEN THE "FIRE DOOR CLOSING" FUNCTION (ABDL) IS TO BE USED IN 3364. Connection diagram Ext. power supply 3366
NORMALLY LOW. HIGH=LOSS OF MAIN POWER SOURCE IN 3366=FIRE DOOR SHALL CLOSE (VIA 3364). Drawing number Sheet Revision
4) ONLY THE MAINS SAFETY EARTH (GROUND) WIRE MUST BE CONNECTED TO THIS TERMINAL.
Panasonic Eco Solutions Nordic AB
512 G3 - 38 1/1 3
Revision Revision date Revision note Signature Checked
SA 1
DETECTORS WITH A CLOSING CONTACT (SHORT-CIRCUIT) CAN BE
SB 2 CONNECTED. IN Win512 G3 HAS TO BE SET THAT SHORT-CIRCUIT
COM SHALL ACTIVATE FIRE ALARM (INSTEAD OF FAULT).
SA 3 LOOP
EXAMPLE 1a
DETECTORS WITH A CLOSING CONTACT AND AN ALARM RESISTOR (e.g. 435x + base 2324).
SB 4
EXAMPLE 2
5 L (SA) C (SB)
In0(+) THE INPUT HAS TO BE PROGRAMMED.
2
Z/In0(-) 7
ALT.
In1(-) 8
An input has to be
9 3
In1(+) activated > 0.5 sec.
470nF
END-OF-LINE 680R (ALARM RESISTOR) NOTE!
CAPACITOR THE RELAY CONTACTS ARE SHOWN IN NORMAL OPERATION STATE.
10 mm
11
NOTE! Alt. a)
EXP. BOARD 4580
2 2012-08-27 Info. added/revised. 2822 & 3361 added JP MÖ
INTERCONNECTING CABLE (SEE BELOW)
Analog Intrinsically Safe (IS) detectors EX ZONE LINE INPUT
2840 IS analog smoke detector. (EOL RESISTOR)
2841 IS analog heat detector. SEE ALSO DWG 512 G3 - 33
HAZARDOUZ (Ex) AREA
The analog IS detectors are connected
to a COM loop via an IS barrier unit 2842. MTL5061
Connections, see drawing 512 G3 - 31. INTRINSICALLY SAFE (IS) INTRINSICALLY SAFE (IS)
GALVANIC ISOLATOR (2820) MOUNTING BASE MANUAL CALL POINT
Conventional Intrinsically Safe (IS) detectors (IN A WATERPROOF BOX) YBN-R / 4 IS (2812) 1) MCP1A-R470FF-H029-01IS (2814)
I.e. the IS manual call point 2814 or smoke detector Alt. a)
2810 and heat detector 2811 plugged in base 2812. 1 (+) 12+ 1-
Alt. a) ZONE 8) ZONE 1 CHANNEL 1 5)
2 (-) 11- 2+
The conventional IS detectors are connected
via a galvanic isolator 2820 to an expansion board
4580 zone line input, according to this drawing. 3 5 6 1 2 3 4 Alt. a): 10K
The zone line input is via WinG3 programmed as: 3 470R Alt. b): 8K2
EX zone line input (EOL resistor). 4
Alt. b) 9+ 4- EXT. END-OF-LINE
E-O-L resistor 10K supplied with 2820. 2 1
4) ZONE 2 4) LED RESISTOR
CHANNEL 2 6)
Alt. b) 8- 5+ 7)
The conventional IS detectors are connected
via a galvanic isolator 2820 to an Addressable
Isolated zone interface 2822 that is connected
6
to an I/O unit 3361 zone line input, according
to this drawing.
E-O-L resistor 8K2 supplied with 2822.
Alt. b)
Addressable Isolated
I/O unit (3361) zone interface (2822) EARTH CONDUCTOR TERMINAL
IN THE BOX
J1 J2
1 SA 1 OPTIONAL
CABLE SCREEN Alarm state current max. 50 mA @ 24 V
2 SB 2
CABLE:
2
COM loop 3) FKAR-PG 2x0.5 mm , BLUE
3 SA
(WITH ALUMINIUM POLYESTER FOIL SHEELD+TINNED COPPER
2
DRAIN WIRE 1 mm . NORMALLY NOT USED / CONNECTED.)
4 SB
5
THE INTERCONNECTING CABLE SHOULD HAVE THE FOLLOWING MAX. PARAMETERS:
6 In0 (Z) 3
GROUP CAPACITANCE (C) INDUCTANCE (L) INDUCTANCE TO RESISTANCE RATIO
7 In0 (Z) 4
µF mH OR µH / ohm
10 mm
2-
IIA 1.04 33.6 440
B-DIRECTION
A)
NOTE! THE NUMBER AND TYPE
EQUIVALENT DIAGRAM OF UNITS, CABLE INSTALLA-
EBL DB DB EBL TION, EXT. DISTURBANCES,
L (SA) L (SA) ETC. MIGHT AFFECT THE CABLE
A-DIRECTION B-DIRECTION
RESISTANCE AND CAPA-
C (SB) C (SB)
B) A) CITANCE AND ALSO THE
COMMUNICATION.
L A
10 mm
LB
ARE CONSEQUENTLY
APPROXIMATE VALUES.
Two Control Units (00 & 01). No Router Up to six Control Units (00 - 05). No Router
C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 C.i.e. 5000 / 5001
no. 00 no. 01 no. 00 no. 01 no. 04 no. 05
J4 J4 J4 J4 J4 J4
27 (F1)
2) 27 (F1) 27/31 (F1)
2) 27/31 (F1)
2) 27/31 (F1)
2) 27/31 (F1)
R 28 (F2) 28 (F2) R 28/32 (F2) 28/32 (F2) 28/32 (F2) 28/32 (F2)
29 (F1) 29 (F1) 29/33 (F1) 29/33 (F1) 29/33 (F1) 29/33 (F1)
30 (F2) R 30 (F2) 30/34 (F2) 30/34 (F2) 30/34 (F2) R 30/34 (F2)
2) Channel 1 2) 2) Channel 1 2)
L L
2) NOTE!
31 (F1) 31 (F1) When a redundant network is required both TLON Network no. 0 and
R 32 (F2) 32 (F2) TLON Network no. 1 have to be used.
33 (F1) 33 (F1)
Each TLON Network require one TLON Connection board 1590 to be plugged on
34 (F2) R 34 (F2) the Main board 5010, see drawing EBL512 G3 - 11.
2) Channel 1
L
Two Control Units (00 & 01). One Router Up to twelve Control Units (00 - 05) and (06 - 11). One Router
C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001
no. 00 TP/FT10 - TP/FT10 no. 01 no. 00 TP/FT10 - TP/FT10 no. 11
J4 J4 J4 J4
10 mm
Original drawing A3L (420 x 297 mm)
Designed by Checked by Approved by Filename Date Scale
1) The SysMik SmartRouter TP/FT10 - TP/FT10 has built-in termination resistors, which can be connected va DIP switches.
2) Screen shall be connected to the C.i.e. earth point (see drawing 512 G3 - 01). JP MÖ RP 512 G3-42_1x.cdr 2010-06-03 --
Drawing title
EBL512 G3, TLON Network. Examples,
Connection diagram 2-12 Control units
Drawing number Sheet Revision
Panasonic Electric Works Nordic AB
512 G3 - 42 1/1 -
Revision Revision date Revision note Signature Checked
R = Termination resistor. 105R ±1%, 1/8 W. One termination resistor is required at the end points of each Channel. -
L = Cable length < 900 m. The cable has to be sheelded, e.g. Belden 7703 NH 1 pair 22 AWG or equivalent.
Up to six Control Units (00 - 05). One Router (no. 1) Up to six Control Units (06 - 11). One Router (no. 2) Up to six Control Units (12 - 17). One Router (no. 3)
C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 SysMik SmartRouter
no. 00 TP/FT10 - TP/FT10 no. 06 TP/FT10 - TP/FT10 no. 12 TP/FT10 - TP/FT10
J4 J4 J4
B1 B1 B1
1) R B2 B2 B2 To be cont. below.
SHB SHB SHB
Va Va Va
Up to six Control Units (18 - 23). One Router (no. 4) Up to six Control Units (24 - 29). One Router (no. 5)
C.i.e. 5000 / 5001 SysMik SmartRouter C.i.e. 5000 / 5001 SysMik SmartRouter
no. 18 TP/FT10 - TP/FT10 no. 24 TP/FT10 - TP/FT10
5010 5010
Main board Main board
J4 J4
27 (F1) A1 27 (F1) A1
R 28 (F2) A2 R 1) R 28 (F2) A2 R 1)
29 (F1) SHA 29 (F1) SHA
30 (F2) 30 (F2)
2) Channel 4 2) Channel 5
L L
B1 B1
To be cont. above. B2 B2 R 1)
SHB SHB
Va Va
Backbone, Channel 6
L NOTE!
When a redundant network is required both TLON Network no. 0 and
TLON Network no. 1 have to be used.
10 mm
For the TLON Network no. 1, J4 terminal numbers, see drawing 512 G3 - 42.
Each TLON Network require one TLON Connection board 1590 to be plugged on
the Main board 5010, see drawing EBL512 G3 - 11.