Service FM-300 FM-480 FM600 FM750 FM1000
Service FM-300 FM-480 FM600 FM750 FM1000
FM-170AKE-N
FM-300AKE
FM-300AKE-N
FM-480AKE
FM-480AKE-N
SERVICE MANUAL FM-480AWKE
FM-480AWKE-N
FM-600AKE
FM-600AKE-N
FM-600AWKE
FM-600AWKE-N
FM-750AKE
FM-750AKE-N
FM-1000AKE
FM-1000AKE-N
FM-1200ALKE
FM-1200ALKE-N
FM-1800ALKE
FM-1800ALKE-N
FM-480AWKE-R452-SB
FM-480AWKE-R452N-SB
FM-600AKE-R452-SB
FM-600AKE-R452N-SB
FM-600AWKE-R452-SB
FM-600AWKE-R452N-SB
FM-750AKE-R452-SB
FM-750AKE-R452N-SB
FM-1000AKE-R452-SB
FM-1000AKE-R452N-SB
FM-1200AKE-R452-SB
FM-1200AKE-R452N-SB
FM-1800AKE-R452-SB
FM-1800AKE-R452N-SB
F054-812 (011520)
CONTENTS PAGE
I. SPECIFICATIONS------------------------------------------------------------------------------------------ 1
1. DIMENSIONS/SPECIFICATIONS---------------------------------------------------------------------- 1
FM-170AKE--------------------------------------------------------------------------------------------------- 1
FM-170AKE-N----------------------------------------------------------------------------------------------- 2
FM-300AKE--------------------------------------------------------------------------------------------------- 3
FM-300AKE-N----------------------------------------------------------------------------------------------- 5
FM-480AKE--------------------------------------------------------------------------------------------------- 7
FM-480AKE-N----------------------------------------------------------------------------------------------- 9
FM-480AWKE-----------------------------------------------------------------------------------------------11
FM-480AWKE-N------------------------------------------------------------------------------------------- 13
FM-600AKE------------------------------------------------------------------------------------------------- 15
FM-600AKE-N--------------------------------------------------------------------------------------------- 17
FM-600AWKE---------------------------------------------------------------------------------------------- 19
FM-600AWKE-N------------------------------------------------------------------------------------------- 21
FM-750AKE------------------------------------------------------------------------------------------------- 23
FM-750AKE-N --------------------------------------------------------------------------------------------- 25
FM-1000AKE ---------------------------------------------------------------------------------------------- 27
FM-1000AKE-N ------------------------------------------------------------------------------------------- 29
FM-1200ALKE -------------------------------------------------------------------------------------------- 31
FM-1200ALKE-N ----------------------------------------------------------------------------------------- 33
FM-1800ALKE -------------------------------------------------------------------------------------------- 35
FM-1800ALKE-N ----------------------------------------------------------------------------------------- 37
FM-480AWKE-R452-SB--------------------------------------------------------------------------------- 39
FM-480AWKE-R452N-SB ------------------------------------------------------------------------------ 40
FM-600AKE-R452-SB----------------------------------------------------------------------------------- 41
FM-600AKE-R452N-SB--------------------------------------------------------------------------------- 42
FM-600AWKE-R452-SB--------------------------------------------------------------------------------- 43
FM-600AWKE-R452N-SB------------------------------------------------------------------------------- 44
FM-750AKE-R452-SB----------------------------------------------------------------------------------- 45
FM-750AKE-R452N-SB -------------------------------------------------------------------------------- 46
FM-1000AKE-R452-SB --------------------------------------------------------------------------------- 47
FM-1000AKE-R452N-SB ------------------------------------------------------------------------------- 48
FM-1200AKE-R452-SB --------------------------------------------------------------------------------- 49
FM-1200AKE-R452N-SB ------------------------------------------------------------------------------- 50
FM-1800ALKE-R452-SB ------------------------------------------------------------------------------- 51
FM-1800ALKE-N-R452N-SB -------------------------------------------------------------------------- 52
2. CONSTRUCTION----------------------------------------------------------------------------------------- 53
[a] FM-170AKE(-N)--------------------------------------------------------------------------------------- 53
[b] FM-300AKE(-N), FM-480AKE(-N), FM-600AKE(-N), FM-600AKE-R452(N)-SB----- 54
[c] FM-480AWKE(-N), FM-600AWKE(-N), FM-480AWKE-R452(N)-SB,
FM-600AWKE-R452(N)-SB------------------------------------------------------------------------ 55
[d] FM-750AKE(-N), FM-1000AKE(-N), FM-750AKE-R452(N)-SB,
FM-1000AKE-R452(N)-SB------------------------------------------------------------------------- 56
[e] FM-1200ALKE(-N), FM-1200ALKE-R452(N)-SB--------------------------------------------- 57
[f] FM-1800ALKE(-N), FM-1800ALKE-R452(N)-SB--------------------------------------------- 58
[g] BIN CONTROL SWITCH AND SPOUT -------------------------------------------------------- 59
i
II. MAINTENANCE AND CLEANING INSTRUCTIONS--------------------------------------------- 60
1. PERIODIC PARTS REPLACEMENT----------------------------------------------------------------- 60
2. EXTRUDING HEAD (UPPER BEARING), HOUSING (LOWER BEARING)--------------- 61
3. MECHANICAL SEAL------------------------------------------------------------------------------------- 61
4. GEAR MOTOR-------------------------------------------------------------------------------------------- 62
5. CONDENSER (AIR-COOLED MODEL ONLY)---------------------------------------------------- 62
6. AIR FILTER (AIR-COOLED MODEL ONLY)------------------------------------------------------- 62
7. CONTROL WATER VALVE----------------------------------------------------------------------------- 63
8. CLEANING OF WATER SYSTEM-------------------------------------------------------------------- 64
ii
[d] DISPLAYING ERROR LOG-----------------------------------------------------------------------121
[e] RESETTING ERROR LOG-----------------------------------------------------------------------122
[f] RESETTING COMPRESSOR OPERATING HOURS--------------------------------------122
[g] REDUCING COMPRESSOR STARTING TIME---------------------------------------------123
6. PROTECTORS-------------------------------------------------------------------------------------------123
[a] INDICATION------------------------------------------------------------------------------------------123
7. ERROR CODES------------------------------------------------------------------------------------------124
8. PERFORMANCE DATA--------------------------------------------------------------------------------126
[a] FM-170AKE-------------------------------------------------------------------------------------------126
[b] FM-170AKE-N----------------------------------------------------------------------------------------127
[c] FM-300AKE-------------------------------------------------------------------------------------------128
[d] FM-300AKE-N----------------------------------------------------------------------------------------129
[e] FM-480AKE-------------------------------------------------------------------------------------------130
[f] FM-480AKE-N----------------------------------------------------------------------------------------131
[g] FM-480AWKE, FM-480AWKE-R452-SB -----------------------------------------------------132
[h] FM-480AWKE-N, FM-480AWKE-R452N-SB-------------------------------------------------133
[i] FM-600AKE, FM-600AKE-R452-SB------------------------------------------------------------134
[j] FM-600AKE-N, FM-600AKE-R452N-SB------------------------------------------------------135
[k] FM-600AWKE, FM-600AWKE-R452-SB------------------------------------------------------136
[l] FM-600AWKE-N, FM-600AWKE-R452N-SB-------------------------------------------------137
[m] FM-750AKE, FM-750AKE-R452-SB------------------------------------------------------------138
[n] FM-750AKE-N, FM-750AKE-R452N-SB------------------------------------------------------139
[o] FM-1000AKE, FM-1000AKE-R452-SB--------------------------------------------------------140
[p] FM-1000AKE-N, FM-1000AKE-R452N-SB---------------------------------------------------141
[q] FM-1200ALKE, FM-1200ALKE-R452-SB-----------------------------------------------------142
[r] FM-1200ALKE-N, FM-1200ALKE-R452N-SB------------------------------------------------142
[s] FM-1800ALKE, FM-1800ALKE-R452-SB-----------------------------------------------------143
[t] FM-1800ALKE-N, FM-1800ALKE-R452N-SB------------------------------------------------143
iii
ITEM HOSHIZAKI FLAKE ICE MAKER FM-170AKE
MODEL FM-170AKE
1 Phase 220-240/220-230V 50/60Hz
POWER SUPPLY
Capacity: 1.62/1.19kVA (6.8/5.2A)
AMPERAGE 3.9/3.5A Starting: 19A
ELECTRIC CONSUMPTION 600/675W (Power Factor: 66/83%)
Approx. 170kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
ICE PRODUCTION
Approx. 145kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 120kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
I. SPECIFICATIONS
368
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
HEAT REJECTION 1350W (Ambient temp. 32 °C, Water temp. 21 °C)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4
1. DIMENSIONS/SPECIFICATIONS
COMPRESSOR Hermetic
AIR Fin and Tube Type, Air-cooled
CONDENSER
259
1
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
560
REFRIGERANT R134a
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Water Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
91 REFRIGERANT Compressor Internal Thermostat (Auto-reset), Pressure
47 CIRCUIT PROTECTION Switch (Auto-reset)
MALE CONNECTOR WATER SUPPLY INLET G3/4 MECHANISM PROTECTION Micro Switch (Manual-reset)
(ICE MAKING WATER) INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 68kg (Gross: 75kg)
PACKAGE Carton 671(W)×820(D)×971mm(H)
(19)
ACCESSORIES Mounting Bracket, Installation Kit
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
769
736
CONDITIONS
Voltage Range: Rated Voltage ±10%
579
565
*We reserve the right to make changes in specifications and design without prior
(29) notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
DRAIN OUTLET R3/4 2. The ice production depends on the ambient and water temperatures. Refer to the
49
50 instruction manual.
3. Product Code: F084
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-170AKE-N
FM-170AKE-N
368
HEAT REJECTION 1350W (Ambient temp. 32 °C, Water temp. 21 °C)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4
COMPRESSOR Hermetic
AIR CONDENSER Fin and Tube Type, Air-cooled
2
259 Tube coiled around Cylinder (Solder Plated)
EVAPORATOR
560 REFRIGERANT R134a
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Water Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
780
CONDITIONS
736
769
565
*We reserve the right to make changes in specifications and design without prior
(29) notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
DRAIN OUTLET R3/4 2. The ice production depends on the ambient and water temperatures. Refer to the
49
50 instruction manual.
3. Product Code: F084-C106
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-300AKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 1.66kVA (7.2A)
AMPERAGE 5.8A Starting: 19A
ELECTRIC CONSUMPTION 1000W (Power Factor: 77%)
Approx. 320kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
ICE PRODUCTION
Approx. 260kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 200kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Flake
AIR
MAX. STORAGE CAPACITY Not Applicable
Approx. 0.350m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 0.290m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
ICE DISCHARGE HOLE PER 24h
Approx. 0.230m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
(BOTTOM)
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
HEAT REJECTION 2200W (Ambient temp. 32 °C, Water temp. 21 °C)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
AIR CONDENSER Fin and Tube Type, Air-cooled
FM-300AKE (Auxiliary code: D-0 or earlier)
3
278 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
560 REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
780
CONDITIONS
769
736
565
*We reserve the right to make changes in specifications and design without prior
(29) notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
49
instruction manual.
DRAIN OUTLET R3/4
3. Product Code: F081
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-300AKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 1.66kVA (7.2A)
AMPERAGE 5.8A Starting: 19A
ELECTRIC 1000W (Power Factor: 77%)
CONSUMPTION
Approx.320kg (Ambient Temp. 10°C, Water Temp. 10°C)
ICE PRODUCTION Approx.260kg (Ambient Temp. 21°C, Water Temp. 15°C)
AIR
PER 24h Approx.200kg (Ambient Temp. 32°C, Water Temp. 21°C)
SHAPE OF ICE Flake
ICE DISCHARGE HOLE 15° 2
2 (BOTTOM)(154×79) MAX. STORAGE Not Applicable
330
CAPACITY
WATER Approx.0.350m³ (Ambient Temp. 10°C, Water Temp. 10°C)
700
CONSUMPTION Approx.0.290m³ (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.0.230m³ (Ambient Temp. 32°C, Water Temp. 21°C)
OUTSIDE 560(W) x 700(D) x 780mm(H)
DIMENSIONS
HEAT REJECTION 2200W(Ambient temp.32°C,Water temp.21°C)
AIR CABINET Stainless Steel, Galvanized Steel (Rear)
2 281
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
560
WATER SUPPLY Direct Connection to Water Main, Inlet:
SYSTEM G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
FM-300AKE (Auxiliary code: D-1 or later)
92
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
4
47 REFRIGERANT R404A
MALE CONNECTOR WATER SUPPLY INLET G3/4
35
(ICE MAKING WATER) BIN CONTROL Actuator and Reed Switch
(Time delay controlled)
ICEMAKING WATER
(19) CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT Circuit Breaker, Earth Wire
PROTECTION
780
769
736
682
REFRIGERANT
565
Compressor Internal Thermostat
CIRCUIT (Auto-reset), Pressure Switch (Auto-reset)
(29)
PROTECTION
MECHANISM
Micro Switch (Manual-reset)
PROTECTION
49
ICE PRODUCTION PER 24h Approx. 270kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
Approx. 225kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
Approx. 180kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Nugget
AIR
MAX. STORAGE CAPACITY Not Applicable
Approx. 0.300m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION PER
Approx. 0.255m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
ICE DISCHARGE HOLE 24h
Approx. 0.210m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
(BOTTOM)
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
HEAT REJECTION 2200W (Ambient temp. 32 °C, Water temp. 21 °C)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
AIR CONDENSER Fin and Tube Type, Air-cooled
5
278 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
R404A
FM-300AKE-N (Auxiliary code: D-0 or earlier)
560 REFRIGERANT
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
780
769
736
565
*We reserve the right to make changes in specifications and design without prior
(29) notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
49
instruction manual.
DRAIN OUTLET R3/4 3. Product Code: F081-C106
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-300AKE-N
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 1.64kVA (7.1A)
AMPERAGE 5.7A Starting: 19A
ELECTRIC
1000W (Power Factor: 77%)
CONSUMPTION
Approx.270kg (Ambient Temp. 10°C, Water Temp. 10°C)
AIR ICE PRODUCTION Approx.225kg (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.180kg (Ambient Temp. 32°C, Water Temp. 21°C)
ICE DISCHARGE HOLE 15° 2
SHAPE OF ICE Nugget
2 (BOTTOM)(154×79) MAX. STORAGE Not Applicable
330
CAPACITY
WATER Approx.0.300m (Ambient Temp. 10°C, Water Temp. 10°C)
700
CONSUMPTION Approx.0.255m (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.0.210m (Ambient Temp. 32°C, Water Temp. 21°C)
OUTSIDE
560(W) x 700(D) x 780mm(H)
DIMENSIONS
HEAT REJECTION 2200W(Ambient temp.32°C,Water temp.21°C)
AIR CABINET Stainless Steel, Galvanized Steel (Rear)
2 281
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
560
WATER SUPPLY
SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
CONDENSER Fin and Tube Type, Air-cooled
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
92 REFRIGERANT R404A
FM-300AKE-N (Auxiliary code: D-1 or later)
6
47
MALE CONNECTOR BIN CONTROL Actuator and Reed Switch (Time delay controlled)
35 WATER SUPPLY INLET G3/4
(ICE MAKING WATER) ICEMAKING WATER
CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT
(19) PROTECTION Circuit Breaker, Earth Wire
REFRIGERANT
Compressor Internal Thermostat (Auto-reset), Pressure
CIRCUIT
780
Switch (Auto-reset)
769
736 PROTECTION
682
565
MECHANISM
(29) PROTECTION Micro Switch (Manual-reset)
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 80kg(Gross: 87kg)
49
2
PACKAGE Carton 665(W)×820(D)×950mm(H)
DRAIN OUTLET R3/4
ACCESSORIES Mounting Bracket, Installation Kit
Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
OPERATING Water Supply Pressure: 0.05-0.8MPa(0.5-8bar)
CONDITIONS Voltage Range: Rated Voltage±10%
*We reserve the right to make changes in specifications and design without prior
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F081-C106
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-480AKE
POWER SUPPLY 1 Phase 230V 50Hz Capacity: 2.7kVA (11.7A)
AMPERAGE 8.4A Starting: 43A
ELECTRIC CONSUMPTION 1650W (Power Factor: 87.5%)
Approx. 500kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
ICE PRODUCTION
Approx. 425kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 325kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Flake
AIR MAX. STORAGE CAPACITY Not Applicable
Approx. 0.530m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 0.455m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
ICE DISCHARGE HOLE PER 24h
Approx. 0.355m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
(BOTTOM)
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
1
HEAT REJECTION 3320W (Ambient temp. 32 °C, Water temp. 21 °C)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
AIR
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
AIR CONDENSER Fin and Tube Type, Air-cooled
FM-480AKE (Auxiliary code: D-0 or earlier)
7
278 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
560 (17) REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
96
REFRIGERANT Compressor Internal Thermostat (Auto-reset), Pressure
47 CIRCUIT PROTECTION Switch (Auto-reset)
328
(19) Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
682
565
*We reserve the right to make changes in specifications and design without prior
(29)
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
49
instruction manual.
DRAIN OUTLET R3/4 3. Product Code: F082
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-480AKE
POWER SUPPLY 1 Phase 230V 50Hz Capacity: 2.7kVA (11.7A)
AMPERAGE 8.4A Starting: 43A
ELECTRIC 1650W (Power Factor: 87.5%)
AIR CONSUMPTION
ICE PRODUCTION Approx.500kg (Ambient Temp. 10°C, Water Temp. 10°C)
PER 24h Approx.425kg (Ambient Temp. 21°C, Water Temp. 15°C)
ICE DISCHARGE HOLE 15° 2 Approx.325kg (Ambient Temp. 32°C, Water Temp. 21°C)
2 (BOTTOM)(154×79)
266
330
SHAPE OF ICE Flake
700
MAX. STORAGE
AIR CAPACITY Not Applicable
340
WATER Approx.0.530m (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.0.455m (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.0.355m (Ambient Temp. 32°C, Water Temp. 21°C)
AIR OUTSIDE
560(W) x 700(D) x 780mm(H)
2 281 DIMENSIONS
560 (17) HEAT REJECTION 3320W (Ambient temp.32°C,Water temp.21°C)
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING Thin ice forming inside Cylinder (Flake Ice)
SYSTEM
WATER SUPPLY
Direct Connection to Water Main, Inlet: G1/2 (Rear)
SYSTEM
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
FM-480AKE (Auxiliary code: D-1 or later)
COMPRESSOR Hermetic
96 CONDENSER Fin and Tube Type, Air-cooled
8
47 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
MALE CONNECTOR 35
WATER SUPPLY INLET G3/4 REFRIGERANT R404A
(ICE MAKING WATER)
Actuator and Reed Switch
BIN CONTROL
(Time delay controlled)
ICEMAKING
Float Switch and Solenoid Valve
328
(19) WATER CONTROL
780
769
682
PROTECTION
565
(29) REFRIGERANT Compressor Internal Thermostat (Auto-reset),
380
CIRCUIT PROTECTION Pressure Switch (Auto-reset)
MECHANISM
Micro Switch (Manual-reset)
PROTECTION
49
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
HEAT REJECTION 3320W (Ambient temp. 32 °C, Water temp. 21 °C)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
AIR
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
AIR CONDENSER Fin and Tube Type, Air-cooled
278
9
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
FM-480AKE-N (Auxiliary code: D-0 or earlier)
328
(19) Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
682
565
*We reserve the right to make changes in specifications and design without prior
(29)
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
49
instruction manual.
DRAIN OUTLET R3/4 3. Product Code: F082-C106
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-480AKE-N
POWER SUPPLY 1 Phase 230V 50Hz Capacity: 2.7kVA (11.7A)
AMPERAGE 8.6A Starting: 43A
ELECTRIC
CONSUMPTION 1650W (Power Factor: 88%)
AIR
Approx.430kg (Ambient Temp. 10°C, Water Temp. 10°C)
ICE PRODUCTION Approx.360kg (Ambient Temp. 21°C, Water Temp. 15°C)
ICE DISCHARGE HOLE
PER 24h Approx.290kg (Ambient Temp. 32°C, Water Temp. 21°C)
15° 2
2 (BOTTOM)(154×79)
266
330
SHAPE OF ICE Nugget
MAX. STORAGE
Not Applicable
700
CAPACITY
AIR
340
WATER Approx.0.460m³ (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.0.390m³ (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.0.320m³ (Ambient Temp. 32°C, Water Temp. 21°C)
OUTSIDE
560(W) x 700(D) x 780mm(H)
AIR DIMENSIONS
2 281 HEAT REJECTION 3320W (Ambient temp. 32°C, Water temp. 21°C)
560 (17)
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY
Direct Connection to Water Main, Inlet: G3/4 (Rear)
SYSTEM
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
CONDENSER Fin and Tube Type, Air-cooled
FM-480AKE-N (Auxiliary code: D-1 or later)
10
REFRIGERANT R404A
96
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
47
ICEMAKING WATER
MALE CONNECTOR 35 CONTROL Float Switch and Solenoid Valve
WATER SUPPLY INLET G3/4
(ICE MAKING WATER) ELECTRICAL
CIRCUIT Circuit Breaker, Earth Wire
PROTECTION
REFRIGERANT
Compressor Internal Thermostat (Auto-reset),
328
(19) CIRCUIT
Pressure Switch (Auto-reset)
PROTECTION
780
769
716
682
MECHANISM
565
Microswitch (Manual-reset)
(29) PROTECTION
380
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 95kg (Gross: 102kg)
2 PACKAGE Carton 665(W)×820(D)×950mm(H)
49
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
CABINET Stainless Steel, Galvanized Steel (Rear)
700
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
340
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4, Cond.Inlet: Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4, Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
CONDENSER Tube in Tube Type, Water-cooled
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
278
11
REFRIGERANT R404A
FM-480AWKE (Auxiliary code: D-0 or earlier)
560 (17) BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
197
REFRIGERANT Compressor Internal Thermostat (Auto-reset), Pressure
96 CIRCUIT PROTECTION Switch (Auto-reset)
MALE CONNECTOR
47 MECHANISM PROTECTION Micro Switch (Manual-reset)
DRAIN OUTLET Rc3/8 35 INTERLOCK Shutdown by Microprocessor (Manual-reset)
WATER SUPPLY INLET G3/4
(COND.) WEIGHT Net: 95kg (Gross: 102kg)
(ICE MAKING WATER)
PACKAGE Carton 671(W)×820(D)×971mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
328
(19) Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
CONDITIONS
Voltage Range: Rated Voltage ±10%
780
769
716
*We reserve the right to make changes in specifications and design without prior
682
612
notice.
565
(29)
380
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
174
266
330
SHAPE OF ICE Flake
MAX. STORAGE
Not Applicable
700
CAPACITY
AIR
340
1 WATER Approx.1.627m³ (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.2.002m³ (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.2.75m³ (Ambient Temp. 32°C, Water Temp. 21°C)
1
OUTSIDE 560(W) x 700(D) x 780mm(H)
AIR DIMENSIONS
1 281
CABINET Stainless Steel, Galvanized Steel (Rear)
560 (17)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY Direct Connection to Water Main, Inlet: G3/4, Cond.Inlet:
SYSTEM Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4 , Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
CONDENSER Tube in Tube Type, Water-cooled
FM-480AWKE (Auxiliary code: D-1 or later)
12
92
REFRIGERANT R404A
MALE CONNECTOR BIN CONTROL Actuator and Reed Switch (Time delay controlled)
47
DRAIN OUTLET Rc3/8 35 ICEMAKING WATER
WATER SUPPLY INLET G3/4 Float Switch and Solenoid Valve
(COND.) CONTROL
(ICE MAKING WATER)
ELECTRICAL CIRCUIT
Circuit Breaker, Earth Wire
PROTECTION
REFRIGERANT
CIRCUIT Compressor Internal Thermostat (Auto-reset), Pressure
(19)
328
PROTECTION Switch (Auto-reset)
780
769
MECHANISM
716
682
PROTECTION
565
(29)
380
INTERLOCK Shutdown by Microprocessor (Manual-reset)
174
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
700
340
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4, Cond.Inlet: Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4 , Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
CONDENSER Tube in Tube Type, Water-cooled
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
278
13
REFRIGERANT R404A
560 (17) BIN CONTROL Actuator and Reed Switch (Time delay controlled)
FM-480AWKE-N (Auxiliary code: D-0 or earlier)
328
(19) Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
CONDITIONS
Voltage Range: Rated Voltage ±10%
780
769
716
*We reserve the right to make changes in specifications and design without prior
682
612
565
notice.
(29)
380
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
174
266
1
330
SHAPE OF ICE Nugget
MAX. STORAGE Not Applicable
700
CAPACITY
AIR
340
1
WATER Approx.1.56m³ (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.2.002m³ (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.2.76m³ (Ambient Temp. 32°C, Water Temp. 21°C)
1
OUTSIDE 560(W) x 700(D) x 780mm(H)
AIR DIMENSIONS
1
281
CABINET Stainless Steel, Galvanized Steel (Rear)
560 (17)
ICE MAKING
Thin ice forming inside Cylinder (Nugget Ice)
SYSTEM
WATER SUPPLY Direct Connection to Water Main, Inlet: G3/4,
SYSTEM Cond.Inlet: Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4 , Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
CONDENSER Tube in Tube Type, Water-cooled
197 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
14
92 REFRIGERANT R404A
FM-480AWKE-N (Auxiliary code: D-1 or later)
MALE CONNECTOR 47 BIN CONTROL Actuator and Reed Switch (Time delay controlled)
DRAIN OUTLET Rc3/8 35 ICEMAKING
WATER SUPPLY INLET G3/4 Float Switch and Solenoid Valve
(COND.) (ICE MAKING WATER) WATER CONTROL
ELECTRICAL
CIRCUIT Circuit Breaker, Earth Wire
PROTECTION
328
(19) REFRIGERANT
Compressor Internal Thermostat (Auto-reset), Pressure
CIRCUIT
Switch (Auto-reset)
780
769
716
PROTECTION
682
612
565
(29)
MECHANISM Microswitch (Manual-reset)
380
PROTECTION
174
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
HEAT REJECTION 3950W (Ambient temp. 32 °C, Water temp. 21 °C)
675
700
AIR AIR CABINET Stainless Steel, Galvanized Steel (Rear)
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
AIR CONDENSER Fin and Tube Type, Air-cooled
FM-600AKE (Auxiliary code: D-0 or earlier)
15
(17) 560 (17) REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Water Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
REFRIGERANT Compressor Internal Motor Protector, Internal Pressure
675 47 CIRCUIT PROTECTION Relief Valve (Auto-reset) Pressure Switch (Auto-reset)
35 MECHANISM PROTECTION Micro Switch (Manual-reset)
WATER SUPPLY INLET G3/4
(ICE MAKING WATER) INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 107kg (Gross: 114kg)
PACKAGE Carton 671(W)×820(D)×971mm(H)
(19)
ACCESSORIES Mounting Bracket, Installation Kit
328
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
751
565
*We reserve the right to make changes in specifications and design without prior
(29)
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
49
instruction manual.
DRAIN OUTLET R3/4 3. Product Code: F083
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-600AKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 4.76kVA (20.7A)
AMPERAGE 10.5A Starting: 76A
ELECTRIC 1900W (Power Factor: 85%)
CONSUMPTION
ICE Approx.600kg (Ambient Temp. 10°C, Water Temp. 10°C)
AIR PRODUCTION Approx.540kg (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.445kg (Ambient Temp. 32°C, Water Temp. 21°C)
SHAPE OF ICE Flake
ICE DISCHARGE HOLE 15° 2
2 (BOTTOM)(154×79) MAX. STORAGE
266
Not Applicable
330
CAPACITY
Approx.0.630m³ (Ambient Temp. 10°C, Water Temp. 10°C)
675
WATER
700
AIR AIR Approx.0.570m³ (Ambient Temp. 21°C, Water Temp. 15°C)
CONSUMPTION
340
PER 24h Approx.0.480m³ (Ambient Temp. 32°C, Water Temp. 21°C)
OUTSIDE
560(W) x 700(D) x 780mm(H)
DIMENSIONS
AIR HEAT REJECTION 3950W (Ambient temp.32°C, Water temp.21°C)
2 281 CABINET Stainless Steel, Galvanized Steel (Rear)
(17) 560 (17)
ICE MAKING Thin ice forming inside Cylinder (Flake Ice)
SYSTEM
WATER SUPPLY Direct Connection to Water Main, Inlet: G3/4 (Rear)
SYSTEM
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
FM-600AKE (Auxiliary code: D-1 or later)
16
(ICE MAKING WATER) EVAPORATOR Tube coiled around Cylinder (Solder Plated)
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
(19)
ICEMAKING WATER Float Switch and Water Valve
328
CONTROL
780
769
ELECTRICAL CIRCUIT
751
682
Circuit Breaker, Earth Wire
PROTECTION
565
(29)
380
REFRIGERANT Compressor Internal Motor Protector,Internal Pressure
CIRCUIT Relief Valve(Auto-reset)
PROTECTION Pressure Switch(Auto-reset)
MECHANISM
49
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
HEAT REJECTION 3700W (Ambient temp. 32 °C, Water temp. 21 °C)
700
AIR AIR CABINET Stainless Steel, Galvanized Steel (Rear)
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
AIR CONDENSER Fin and Tube Type, Air-cooled
278 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
17
(17) 560 (17)
FM-600AKE-N (Auxiliary code: D-0 or earlier)
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Water Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
REFRIGERANT Compressor Internal Motor Protector, Internal Pressure
47 CIRCUIT PROTECTION Relief Valve (Auto-reset) Pressure Switch (Auto-reset)
35 MECHANISM PROTECTION Micro Switch (Manual-reset)
WATER SUPPLY INLET G3/4
(ICE MAKING WATER) INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 107kg (Gross: 114kg)
PACKAGE Carton 671(W)×820(D)×971mm(H)
(19)
ACCESSORIES Mounting Bracket, Installation Kit
328
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
682
565
*We reserve the right to make changes in specifications and design without prior
(29)
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
49
instruction manual.
DRAIN OUTLET R3/4 3. Product Code: F083-C106
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-600AKE-N
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 4.76kVA (20.7A)
AMPERAGE 10.8A Starting: 76A
ELECTRIC 1950W (Power Factor: 82%)
CONSUMPTION
Approx.530kg (Ambient Temp. 10°C, Water Temp. 10°C)
ICE PRODUCTION
AIR Approx.460kg (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h
Approx.400kg (Ambient Temp. 32°C, Water Temp. 21°C)
ICE DISCHARGE HOLE 15° 2
SHAPE OF ICE Nugget
2 (BOTTOM)(154×79) MAX. STORAGE
266
Not Applicable
330
CAPACITY
WATER Approx.0.560m³ (Ambient Temp. 10°C, Water Temp. 10°C)
700
AIR AIR
CONSUMPTION Approx.0.490m³ (Ambient Temp. 21°C, Water Temp. 15°C)
340
PER 24h Approx.0.430m³ (Ambient Temp. 32°C, Water Temp. 21°C)
OUTSIDE 560(W) x 700(D) x 780mm(H)
DIMENSIONS
AIR HEAT REJECTION 3700W (Ambient temp. 32°C, Water temp. 21°C)
2 281 CABINET Stainless Steel, Galvanized Steel (Rear)
(17) 560 (17)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY
SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
COMPRESSOR Hermetic
47 CONDENSER Fin and Tube Type, Air-cooled
FM-600AKE-N (Auxiliary code: D-1 or later)
18
(ICE MAKING WATER)
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
(19)
ICEMAKING
Float Switch and Water Valve
328
WATER CONTROL
ELECTRICAL CIRCUIT
780
769
751
565
(29) REFRIGERANT Compressor Internal Motor Protector, Internal Pressure
380
CIRCUIT Relief Valve (Auto-reset)
PROTECTION Pressure Switch (Auto-reset)
MECHANISM Micro Switch (Manual-reset)
49
PROTECTION
DRAIN OUTLET R3/4 INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 107kg (Gross: 114kg)
2
PACKAGE Carton 665(W)×820(D)×950mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
OPERATING Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
CONDITIONS Voltage Range: Rated Voltage±10%
*We reserve the right to make changes in specifications and design without prior
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F083-C106
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-600AWKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 4.76kVA (20.7A)
AMPERAGE 9.6A Starting: 76A
ELECTRIC CONSUMPTION 1705W (Power Factor: 77%)
Approx. 600kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
ICE PRODUCTION
Approx. 560kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 520kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Flake
MAX. STORAGE CAPACITY Not Applicable
Approx. 1.685m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 2.333m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
ICE DISCHARGE HOLE PER 24h
Approx. 3.125m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
(BOTTOM)
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
CABINET Stainless Steel, Galvanized Steel (Rear)
675
700
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
340
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4, Cond.Inlet: Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4 , Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
CONDENSER Tube in Tube Type, Water-cooled
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
278
19
REFRIGERANT R404A
FM-600AWKE (Auxiliary code: D-0 or earlier)
560 (17) BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Water Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
160
REFRIGERANT Compressor Internal Motor Protector, Internal Pressure
CIRCUIT PROTECTION Relief Valve (Auto-reset) Pressure Switch (Auto-reset)
WATER SUPPLY INLET Rc1/2 47
675 MECHANISM PROTECTION Micro Switch (Manual-reset)
(Cond.) 35
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WATER SUPPLY INLET G3/4
(ICE MAKING WATER) WEIGHT Net: 107kg (Gross: 114kg)
PACKAGE Carton 671(W)×820(D)×971mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
(19)
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
328
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
CONDITIONS
Voltage Range: Rated Voltage ±10%
780
770
751
*We reserve the right to make changes in specifications and design without prior
682
622
129
565
notice.
(29)
380
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
DRAIN OUTLET Rc3/8 instruction manual.
49
266
CAPACITY
330
WATER Approx.1.685m³ (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.2.333m³ (Ambient Temp. 21°C, Water Temp. 15°C)
675
700
AIR PER 24h Approx.3.125m³ (Ambient Temp. 32°C, Water Temp. 21°C)
340
1 OUTSIDE
560(W) x 700(D) x 780mm(H)
DIMENSIONS
CABINET Stainless Steel, Galvanized Steel (Rear)
1
AIR ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
1 281 WATER SUPPLY Direct Connection to Water Main, Inlet:
560 (17) SYSTEM G3/4, Cond.Inlet: Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4 , Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
160 CONDENSER Tube in Tube Type, Water-cooled
FM-600AWKE (Auxiliary code: D-1 or later)
20
675 REFRIGERANT R404A
(Cond.) 35
WATER SUPPLY INLET G3/4
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
(ICE MAKING WATER) ICEMAKING WATER Float Switch and Water Valve
CONTROL
(19)
ELECTRICAL CIRCUIT Circuit Breaker, Earth Wire
PROTECTION
328
REFRIGERANT Compressor Internal Motor Protector,
CIRCUIT Internal Pressure Relief Valve(Auto-reset)
780
770
751
565
(29) MECHANISM
380
Micro Switch(Manual-reset)
PROTECTION
INTERLOCK Shutdown by Microprocessor (Manual-reset)
DRAIN OUTLET Rc3/8 WEIGHT Net: 107kg(Gross: 114kg)
(Cond.)
49
266
OUTSIDE DIMENSIONS 560(W)×700(D)×780mm(H)
329
CABINET Stainless Steel, Galvanized Steel (Rear)
Thin ice forming inside Cylinder (Nugget Ice)
700
ICE MAKING SYSTEM
340
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4, Cond.Inlet: Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4, Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
CONDENSER Tube in Tube Type, Water-cooled
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
278 R404A
21
REFRIGERANT
560 (17) BIN CONTROL Actuator and Reed Switch (Time delay controlled)
FM-600AWKE-N (Auxiliary code: D-0 or earlier)
328
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
CONDITIONS
Voltage Range: Rated Voltage ±10%
780
770
751
*We reserve the right to make changes in specifications and design without prior
682
622
129
565
notice.
(29)
380
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
DRAIN OUTLET Rc3/8 instruction manual.
(Cond.)
49
266
330
CAPACITY
WATER Approx.1.685m³ (Ambient Temp. 10°C, Water Temp. 10°C)
Approx.2.318m³ (Ambient Temp. 21°C, Water Temp. 15°C)
700
CONSUMPTION
AIR PER 24h Approx.3.067m³ (Ambient Temp. 32°C, Water Temp. 21°C)
340
1
OUTSIDE
560(W) x 700(D) x 780mm(H)
DIMENSIONS
CABINET Stainless Steel, Galvanized Steel (Rear)
1
AIR ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
1 281
(17)
WATER SUPPLY Direct Connection to Water Main, Inlet: G3/4,
560 SYSTEM Cond.Inlet: Rc1/2 (Rear)
DRAIN SYSTEM Outlet: R3/4 , Cond.Outlet Rc3/8 (Rear)
COMPRESSOR Hermetic
160 CONDENSER Tube in Tube Type, Water-cooled
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
WATER SUPPLY INLET Rc1/2 47
22
(Cond.) REFRIGERANT R404A
35
FM-600AWKE-N (Auxiliary code: D-1 or later)
WATER SUPPLY INLET G3/4 BIN CONTROL Actuator and Reed Switch (Time delay controlled)
(ICE MAKING WATER) ICEMAKING WATER
Float Switch and Water Valve
CONTROL
(19)
ELECTRICAL CIRCUIT
Circuit Breaker, Earth Wire
PROTECTION
328
REFRIGERANT Compressor Internal Motor Protector,
CIRCUIT Internal Pressure Relief Valve(Auto-reset)
780
770
751
565
(29) MECHANISM
Micro Switch(Manual-reset)
380
PROTECTION
INTERLOCK Shutdown by Microprocessor (Manual-reset)
DRAIN OUTLET Rc3/8 WEIGHT Net: 107kg(Gross: 114kg)
(Cond.)
49
216
266
(BOTTOM) OUTSIDE DIMENSIONS 762(W)×700(D)×780mm(H)
469
HEAT REJECTION 3650W (Ambient temp. 32 °C, Water temp. 21 °C)
AIR AIR
700
CABINET Stainless Steel, Galvanized Steel (Rear)
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 (Rear)
285 COMPRESSOR Hermetic
428 AIR CONDENSER Fin and Tube Type, Air-cooled
FM-750AKE (Auxiliary code: D-0 or earlier)
(17) 762 (17) EVAPORATOR Tube coiled around Cylinder (Solder Plated)
23
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
WATER SUPPLY INLET G3/4
REFRIGERANT Compressor Internal Thermostat (Auto-reset), Pressure
(ICE MAKING WATER) 157 CIRCUIT PROTECTION Switch (Auto-reset)
MALE CONNECTOR 53
MECHANISM PROTECTION Micro Switch (Manual-reset)
47
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 133kg (Gross: 143kg)
PACKAGE Carton 895(W)×875(D)×965mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
(19)
328
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
682
565
(29) *We reserve the right to make changes in specifications and design without prior
49
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
DRAIN OUTLET R3/4 2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F054
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-750AKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 2.7kVA (11.7A)
AMPERAGE 9.2A Starting: 43A
ELECTRIC 1880W (Power Factor: 89%)
CONSUMPTION
Approx.750kg (Ambient Temp. 10°C, Water Temp. 10°C)
ICE PRODUCTION Approx.650kg (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.530kg (Ambient Temp. 32°C, Water Temp. 21°C)
AIR SHAPE OF ICE Flake
15° MAX. STORAGE Not Applicable
CAPACITY
ICE DISCHARGE HOLE 3 WATER Approx.0.77m³ (Ambient Temp. 10°C, Water Temp. 10°C)
219
(BOTTOM)(154×79)
266
3 CONSUMPTION Approx.0.68m³ (Ambient Temp. 21°C, Water Temp. 15°C)
3
486
PER 24h Approx.0.56m³ (Ambient Temp. 32°C, Water Temp. 21°C)
AIR AIR
700
OUTSIDE
762(W) x 700(D) x 780mm(H)
340
DIMENSIONS
5° HEAT REJECTION 3650W(Ambient temp.32°C,Water temp.21°C)
CABINET Stainless Steel, Galvanized Steel (Rear)
3 270 ICE MAKING Thin ice forming inside Cylinder (Flake Ice)
3 444 AIR SYSTEM
(17) 762 (17)
WATER SUPPLY Direct Connection to Water Main, Inlet: G3/4 (Rear)
SYSTEM
DRAIN SYSTEM Outlet: R3/4 (Rear)
FM-750AKE (Auxiliary code: D-1 or later)
COMPRESSOR Hermetic
WATER SUPPLY INLET G3/4
CONDENSER Fin and Tube Type, Air-cooled
(ICE MAKING WATER) EVAPORATOR Tube coiled around Cylinder (Solder Plated)
24
157
MALE CONNECTOR 53 REFRIGERANT R404A
47 BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING Float Switch and Solenoid Valve
WATER CONTROL
ELECTRICAL CIRCUIT Circuit Breaker, Earth Wire
(19)
PROTECTION
328
REFRIGERANT Compressor Internal Thermostat
CIRCUIT
780
769
PROTECTION
565
(29)
49
MECHANISM
380
Micro Switch (Manual-reset)
PROTECTION
INTERLOCK Shutdown by Microprocessor (Manual-reset)
DRAIN OUTLET R3/4 WEIGHT Net: 133kg(Gross: 143kg)
3
PACKAGE Carton 873(W)×820(D)×947mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
OPERATING Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
CONDITIONS Water Supply Pressure: 0.05-0.8MPa(0.5-8bar)
Voltage Range: Rated Voltage±10%
*We reserve the right to make changes in specifications and design without
prior notice.
1. Install the ice maker properly in accordance with the instructions on location,
water supply/drain connections and electrical connections stated in the
instruction and installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to
the instruction manual.
3. Product Code: F054
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-750AKE-N
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 2.7kVA (11.7A)
AMPERAGE 9.7A Starting: 43A
ELECTRIC CONSUMPTION 2010W (Power Factor: 90%)
Approx. 590kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
ICE PRODUCTION
Approx. 500kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 390kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Nugget
AIR MAX. STORAGE CAPACITY Not Applicable
Approx. 0.60m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 0.51m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
ICE DISCHARGE HOLE Approx. 0.40m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
216
266
(BOTTOM) OUTSIDE DIMENSIONS 762(W)×700(D)×780mm(H)
469
HEAT REJECTION 3650W (Ambient temp. 32 °C, Water temp. 21 °C)
AIR AIR
700
CABINET Stainless Steel, Galvanized Steel (Rear)
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 (Rear)
285 COMPRESSOR Hermetic
428 AIR CONDENSER Fin and Tube Type, Air-cooled
(17) 762 (17) EVAPORATOR Tube coiled around Cylinder (Solder Plated)
25
FM-750AKE-N (Auxiliary code: D-0 or earlier)
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
WATER SUPPLY INLET G3/4
REFRIGERANT Compressor Internal Thermostat (Auto-reset), Pressure
(ICE MAKING WATER) 157 CIRCUIT PROTECTION Switch (Auto-reset)
MALE CONNECTOR 53
MECHANISM PROTECTION Micro Switch (Manual-reset)
47
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 133kg (Gross: 143kg)
PACKAGE Carton 895(W)×875(D)×965mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
(19)
328
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
682
565
(29) *We reserve the right to make changes in specifications and design without prior
49
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
DRAIN OUTLET R3/4 2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F054-C106
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-750AKE-N
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 2.7kVA (11.7A)
AMPERAGE 9.7A Starting: 43A
ELECTRIC 2010W (Power Factor: 90%)
CONSUMPTION
Approx.590kg (Ambient Temp. 10°C, Water Temp. 10°C)
ICE PRODUCTION
PER 24h Approx.500kg (Ambient Temp. 21°C, Water Temp. 15°C)
Approx.390kg (Ambient Temp. 32°C, Water Temp. 21°C)
AIR SHAPE OF ICE Nugget
15°
MAX. STORAGE
Not Applicable
CAPACITY
ICE DISCHARGE HOLE 3 WATER Approx.0.60m³ (Ambient Temp. 10°C, Water Temp. 10°C)
219
CONSUMPTION Approx.0.51m³ (Ambient Temp. 21°C, Water Temp. 15°C)
266
(BOTTOM)(154×79) 3
3
486
PER 24h Approx.0.40m³ (Ambient Temp. 32°C, Water Temp. 21°C)
AIR AIR OUTSIDE
700
762(W) x 700(D) x 780mm(H)
DIMENSIONS
340
HEAT REJECTION 3650W(Ambient temp.32°C,Water temp.21°C)
5°
CABINET Stainless Steel, Galvanized Steel (Rear)
3
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
270
WATER SUPPLY Direct Connection to Water Main, Inlet: G3/4 (Rear)
3 444 AIR SYSTEM
(17) 762 (17) DRAIN SYSTEM Outlet: R3/4 (Rear)
COMPRESSOR Hermetic
CONDENSER Fin and Tube Type, Air-cooled
FM-750AKE-N (Auxiliary code: D-1 or later)
26
REFRIGERANT R404A
WATER SUPPLY INLET G3/4
(ICE MAKING WATER) BIN CONTROL Actuator and Reed Switch (Time delay controlled)
157
MALE CONNECTOR 53 ICEMAKING WATER Float Switch and Solenoid Valve
CONTROL
47
ELECTRICAL CIRCUIT Circuit Breaker, Earth Wire
PROTECTION
REFRIGERANT Compressor Internal Thermostat (Auto-reset),
CIRCUIT Pressure Switch (Auto-reset)
(19) PROTECTION
328
MECHANISM Micro Switch (Manual-reset)
PROTECTION
780
769
715
682
565
(29)
49
380
WEIGHT Net: 133kg(Gross: 143kg)
3 PACKAGE Carton 873(W)×820(D)×947mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
DRAIN OUTLET R3/4 Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
OPERATING
CONDITIONS Water Supply Pressure: 0.05-0.8MPa(0.5-8bar)
Voltage Range: Rated Voltage±10%
*We reserve the right to make changes in specifications and design without
prior notice.
1. Install the ice maker properly in accordance with the instructions on
location, water supply/drain connections and electrical connections stated
in the instruction and installation manuals provided.
2. The ice production depends on the ambient and water temperatures.
Refer to the instruction manual.
3. Product Code: F054-C106
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-1000AKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 3.9kVA (16.3A)
AMPERAGE 12.3A Starting: 76A
ELECTRIC CONSUMPTION 2490W (Power Factor: 86%)
Approx. 1030kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
ICE PRODUCTION
Approx. 890kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
POWER CORD 2800mm LONG OUTSIDE PER 24h
Approx. 740kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Flake
AIR MAX. STORAGE CAPACITY Not Applicable
Approx. 1.04m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 0.90m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
ICE DISCHARGE HOLE Approx. 0.75m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
216
266
(BOTTOM) OUTSIDE DIMENSIONS 762(W)×700(D)×780mm(H)
469
HEAT REJECTION 4470W (Ambient temp. 32 °C, Water temp. 21 °C)
AIR AIR
700
CABINET Stainless Steel, Galvanized Steel (Rear)
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 (Rear)
285 COMPRESSOR Hermetic
428 AIR CONDENSER Fin and Tube Type, Air-cooled
(17) 762 (17) EVAPORATOR Tube coiled around Cylinder (Solder Plated)
27
FM-1000AKE (Auxiliary code: D-0 or earlier)
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
ELECTRICAL CIRCUIT PROTECTION Circuit Breaker, Earth Wire
REFRIGERANT Compressor Internal Thermostat (Auto-reset), Pressure
117 CIRCUIT PROTECTION Switch (Auto-reset)
WATER SUPPLY INLET G3/4
53
(ICE MAKING WATER) MECHANISM PROTECTION Micro Switch (Manual-reset)
47
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 146kg (Gross: 156kg)
PACKAGE Carton 895(W)×875(D)×965mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
(19)
328
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
2 Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
747
565
(29) *We reserve the right to make changes in specifications and design without prior
49
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
DRAIN OUTLET R3/4 2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F055
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-1000AKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 3.9kVA (16.3A)
AMPERAGE 12.3A Starting: 76A
ELECTRIC 2490W (Power Factor: 86%)
CONSUMPTION
ICE PRODUCTION Approx.1030kg (Ambient Temp. 10°C, Water Temp. 10°C)
POWER CORD 2800mm LONG OUTSIDE Approx.890kg (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h
Approx.740kg (Ambient Temp. 32°C, Water Temp. 21°C)
AIR SHAPE OF ICE Flake
15° MAX. STORAGE Not Applicable
CAPACITY
ICE DISCHARGE HOLE 3 WATER Approx.1.04m³ (Ambient Temp. 10°C, Water Temp. 10°C)
219
266
(BOTTOM)(154×79) 3 CONSUMPTION Approx.0.90m³ (Ambient Temp. 21°C, Water Temp. 15°C)
3
486
PER 24h Approx.0.75m³ (Ambient Temp. 32°C, Water Temp. 21°C)
AIR AIR OUTSIDE
700
762(W) x 700(D) x 780mm(H)
DIMENSIONS
340
5° HEAT REJECTION 4470W(Ambient temp.32°C,Water temp.21°C)
CABINET Stainless Steel, Galvanized Steel (Rear)
3 270 ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
3 444 AIR WATER SUPPLY
(17) (17) SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
762
DRAIN SYSTEM Outlet: R3/4 (Rear)
COMPRESSOR Hermetic
FM-1000AKE (Auxiliary code: D-1 or later)
28
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
REFRIGERANT R404A
117 BIN CONTROL Actuator and Reed Switch (Time delay controlled)
WATER SUPPLY INLET G3/4
53
(ICE MAKING WATER) ICEMAKING
47 Float Switch and Solenoid Valve
WATER CONTROL
ELECTRICAL CIRCUIT
Circuit Breaker, Earth Wire
PROTECTION
REFRIGERANT Compressor Internal Thermostat (Auto-reset),
(19) CIRCUIT PROTECTION Pressure Switch (Auto-reset)
328
MECHANISM Micro Switch (Manual-reset)
PROTECTION
780
769
747
682
565
(29)
49
380
3 PACKAGE Carton 873(W)×820(D)×947mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
DRAIN OUTLET R3/4 Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
OPERATING Water Supply Pressure: 0.05-0.8MPa(0.5-8bar)
CONDITIONS Voltage Range: Rated Voltage±10%
*We reserve the right to make changes in specifications and design without prior
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F055
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-1000AKE-N
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 3.9kVA (16.3A)
AMPERAGE 12.5A Starting: 76A
ELECTRIC CONSUMPTION 2550W (Power Factor: 88%)
Approx. 860kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
ICE PRODUCTION
Approx. 730kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
POWER CORD 2800mm LONG OUTSIDE PER 24h
Approx. 590kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Nugget
AIR MAX. STORAGE CAPACITY Not Applicable
Approx. 0.87m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 0.74m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
ICE DISCHARGE HOLE Approx. 0.60m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
216
266
(BOTTOM) OUTSIDE DIMENSIONS 762(W)×700(D)×780mm(H)
469
HEAT REJECTION 4470W (Ambient temp. 32 °C, Water temp. 21 °C)
AIR AIR
700
CABINET Stainless Steel, Galvanized Steel (Rear)
340
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 (Rear)
285 COMPRESSOR Hermetic
428 AIR CONDENSER Fin and Tube Type, Air-cooled
(17) 762 (17) EVAPORATOR Tube coiled around Cylinder (Solder Plated)
29
REFRIGERANT R404A
FM-1000AKE-N (Auxiliary code: D-0 or earlier)
328
Ambient Temp.: 5-40 °C, Water Supply Temp.: 5-35 °C
OPERATING
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
780
CONDITIONS
769
747
565
(29) *We reserve the right to make changes in specifications and design without prior
49
380
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
DRAIN OUTLET R3/4 2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F055-C106
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-1000AKE-N
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 3.9kVA (16.3A)
AMPERAGE 12.5A Starting: 76A
ELECTRIC 2550W (Power Factor: 88%)
CONSUMPTION
Approx.860kg (Ambient Temp. 10°C, Water Temp. 10°C)
POWER CORD 2800mm LONG OUTSIDE
ICE PRODUCTION Approx.730kg (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h
Approx.590kg (Ambient Temp. 32°C, Water Temp. 21°C)
AIR
SHAPE OF ICE Nugget
15°
MAX. STORAGE
Not Applicable
ICE DISCHARGE HOLE
CAPACITY
3
219
(BOTTOM)(154×79) 3 Approx.0.87m³ (Ambient Temp. 10°C, Water Temp. 10°C)
266
3
WATER
486
CONSUMPTION Approx.0.74m³ (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.0.60m³ (Ambient Temp. 32°C, Water Temp. 21°C)
AIR AIR
700
OUTSIDE
340
762(W) x 700(D) x 780mm(H)
DIMENSIONS
5°
HEAT REJECTION 4470W(Ambient temp.32°C, Water temp.21°C)
3
CABINET Stainless Steel, Galvanized Steel (Rear)
270
3 AIR ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
444
(17) 762 (17) WATER SUPPLY Direct Connection to Water Main, Inlet: G3/4 (Rear)
SYSTEM
DRAIN SYSTEM Outlet: R3/4 (Rear)
COMPRESSOR Hermetic
CONDENSER Fin and Tube Type, Air-cooled
30
FM-1000AKE-N (Auxiliary code: D-1 or later)
328
Compressor Internal Thermostat (Auto-reset),
CIRCUIT
Pressure Switch (Auto-reset)
PROTECTION
780
769
747
682
MECHANISM
565
(29) PROTECTION Micro Switch (Manual-reset)
49
380
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 146kg(Gross: 156kg)
3 PACKAGE Carton 873(W)×820(D)×947mm(H)
DRAIN OUTLET R3/4
ACCESSORIES Mounting Bracket, Installation Kit
OPERATING Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
CONDITIONS Water Supply Pressure: 0.05-0.8MPa(0.5-8bar)
Voltage Range: Rated Voltage±10%
*We reserve the right to make changes in specifications and design without
prior notice.
1. Install the ice maker properly in accordance with the instructions on
location, water supply/drain connections and electrical connections stated
in the instruction and installation manuals provided.
2. The ice production depends on the ambient and water temperatures.
Refer to the instruction manual.
3. Product Code: F055-C106
ITEM HOSHIZAKI FLAKE ICE MAKER
MODEL FM-1200ALKE
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 0.74kVa (3.2A)
AMPERAGE 2.5A Starting: 11A
ELECTRIC CONSUMPTION 470W (Power Factor: 81%)
In the case of Specification sheet Ps 1.05bar Evaporator
temp -25 °C 2830W
ICE PRODUCTION
Approx. 1200kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
PER 24h
Approx. 1040kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
Approx. 890kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
SHAPE OF ICE Flake
MAX. STORAGE CAPACITY Not Applicable
ICE DISCHARGE HOLE Approx. 1.21m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
216
(BOTTOM) Approx. 1.05m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
469
Approx. 0.90m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
OUTSIDE DIMENSIONS 762(W)×700(D)×780mm(H)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 (Rear)
285
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
428
REFRIGERANT R404A
762
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
31
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
FM-1200ALKE (Auxiliary code: D-0 or earlier)
780
770
747
682
*We reserve the right to make changes in specifications and design without prior
(29)
565
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
60
49
219
(BOTTOM)(154×79) 3
3 3
WATER Approx.1.21m³ (Ambient Temp. 10°C, Water Temp. 10°C)
486
CONSUMPTION Approx.1.05m³ (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.0.90m³ (Ambient Temp. 32°C, Water Temp. 21°C)
700
OUTSIDE
DIMENSIONS 762(W) x 700(D) x 780mm(H)
5°
CABINET Stainless Steel, Galvanized Steel (Rear)
3 270 ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
3 444 WATER SUPPLY
Direct Connection to Water Main, inlet: G3/4 (Rear)
SYSTEM
762
DRAIN SYSTEM Outlet: R3/4 (Rear)
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
WATER SUPPLY INLET G3/4
REFRIGERANT R404A
(ICE MAKING WATER)
FM-1200ALKE (Auxiliary code: D-1 or later)
32
MALE CONNECTOR
ICEMAKING Float Switch and Solenoid Valve
LIQUID LINE WATER CONTROL
CONNECTION 3/8" 167
53 ELECTRICAL
Circuit Breaker, Earth Wire
SUCTION LINE 47 PROTECTION
CONNECTION 5/8" Thermal Protector(Auto-reset)
GEAR MOTOR
PROTECTION Motor Rotation Protection, Current
Protection (Manual-reset)
LOW WATER
(19) Float Switch and Microprocessor
PROTECTION
MECHANISM
PROTECTION Micro Switch (Manual-reset)
780
770
747
682
565
WEIGHT Net: 98kg(Gross: 108kg)
3
PACKAGE Carton 873(W)×820(D)×947mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
49
OPERATING
60
216
(BOTTOM) Approx. 0.93m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 0.81m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
469
OUTSIDE DIMENSIONS 762(W)×700(D)×780mm(H)
700
CABINET Stainless Steel, Galvanized Steel (Rear)
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
WATER SUPPLY SYSTEM Direct Connection to Water Main, Inlet: G3/4 (Rear)
DRAIN SYSTEM Outlet: R3/4 (Rear)
285
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
428
REFRIGERANT R404A
762
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
33
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
WATER SUPPLY INLET G3/4
ELECTRICAL PROTECTION Circuit Breaker, Earth Wire
(ICE MAKING WATER)
GEAR MOTOR Thermal Protector (Auto-reset) Motor Rotation Protection,
FM-1200ALKE-N (Auxiliary code: D-0 or earlier)
780
770
747
682
*We reserve the right to make changes in specifications and design without prior
(29)
565
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
supply/drain connections and electrical connections stated in the instruction and
installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
60
49
219
(BOTTOM)(154×79) CAPACITY Not Applicable
3 3
486
WATER Approx.1.07m³ (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.0.93m³ (Ambient Temp. 21°C, Water Temp. 15°C)
700
PER 24h Approx.0.81m³ (Ambient Temp. 32°C, Water Temp. 21°C)
OUTSIDE
5° DIMENSIONS 762(W) x 700(D) x 780mm(H)
34
MALE CONNECTOR REFRIGERANT R404A
FM-1200ALKE-N (Auxiliary code: D-1 or later)
LIQUID LINE BIN CONTROL Actuator and Reed Switch (Time delay controlled)
167
CONNECTION 3/8" ICEMAKING WATER
53 Float Switch and Solenoid Valve
SUCTION LINE 47 CONTROL
CONNECTION 5/8" ELECTRICAL
Circuit Breaker, Earth Wire
PROTECTION
GEAR MOTOR Thermal Protector(Auto-reset)
PROTECTION Motor Rotation Protection, Current
(19) Protection(Manual-reset)
LOW WATER Float Switch and Microprocessor
PROTECTION
780
770
747
682
(29) MECHANISM
565
PROTECTION Micro Switch (Manual-reset)
60
216
235
Flake
469
SHAPE OF ICE
MAX. STORAGE CAPACITY Not Applicable
700
Approx. 1.81m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 1.57m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 1.35m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
OUTSIDE DIMENSIONS 1080(W)×700(D)×780mm(H)
CABINET Stainless Steel, Galvanized Steel (Rear)
285
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
428
WATER SUPPLY SYSTEM Direct Connection to Water Main, inlet: G3/4 x 2 (Rear)
821 DRAIN SYSTEM Outlet: R3/4 x 2 (Rear)
1080 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
35
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
FM-1800ALKE (Auxiliary code: D-0 or earlier)
WATER SUPPLY INLET G3/4 ELECTRICAL PROTECTION Circuit Breaker, Earth Wire
(ICE MAKING WATER) 200 47
GEAR MOTOR Thermal Protector (Auto-reset) Motor Rotation Protection,
MALE CONNECTOR 153 PROTECTION Current Protection (Manual-reset)
LOW WATER PROTECTION Float Switch and Microprocessor
MECHANISM PROTECTION Micro Switch (Manual-reset)
INTERLOCK Shutdown by Microprocessor (Manual-reset)
(19) WEIGHT Net: 140kg (Gross: 155kg)
PACKAGE Carton 1215(W)×875(D)×965mm(H)
ACCESSORIES Mounting Bracket, Installation Kit
780
770
747
OPERATING
565
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
CONDITIONS
(29) Voltage Range: Rated Voltage ±10%
*We reserve the right to make changes in specifications and design without prior
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
83 65
60
supply/drain connections and electrical connections stated in the instruction and
49
219
3 Approx.1560kg(Ambient Temp. 21°C,Water Temp. 15°C)
262
Approx.1335kg(Ambient Temp. 32°C,Water Temp. 21°C)
486
15°
SHAPE OF ICE Flake
700
MAX. STORAGE
Not Applicable
CAPACITY
WATER Approx.1.81m³ (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.1.57m³ (Ambient Temp. 21°C, Water Temp. 15°C)
3 5° PER 24h Approx.1.35m³ (Ambient Temp. 32°C, Water Temp. 21°C)
272
OUTSIDE
3
1080(W) x 700(D) x 780mm(H)
446 DIMENSIONS
3 826 CABINET Stainless Steel, Galvanized Steel (Rear)
1080 ICE MAKING SYSTEM Thin ice forming inside Cylinder (Flake Ice)
WATER SUPPLY
SYSTEM Direct Connection to Water Main, inlet: G3/4 x 2 (Rear)
DRAIN SYSTEM Outlet: R3/4 x 2 (Rear)
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
REFRIGERANT R404A
FM-1800ALKE (Auxiliary code: D-1 or later)
36
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
(ICE MAKING WATER) 200 47
ICEMAKING
MALE CONNECTOR 153 Float Switch and Solenoid Valve
WATER CONTROL
ELECTRICAL
PROTECTION Circuit Breaker, Earth Wire
780
682
MECHANISM
565
PROTECTION Micro Switch (Manual-reset)
(29)
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 140kg(Gross: 155kg)
83 65 3
PACKAGE Carton 1191(W)×820(D)×947mm(H)
60 49
ACCESSORIES Mounting Bracket, Installation Kit
310 53
SUCTION LINE Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
CONNECTION 5/8" OPERATING Water Supply Pressure: 0.05-0.8MPa(0.5-8bar)
LIQUID LINE
CONDITIONS Voltage Range: Rated Voltage±10%
CONNECTION 3/8" *We reserve the right to make changes in specifications and design without prior
notice.
DRAIN OUTLET R3/4 1. Install the ice maker properly in accordance with the instructions on location,
water supply/drain connections and electrical connections stated in the instruction
and installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to the
instruction manual.
3. Product Code: F074
ITEM HOSHIZAKI NUGGET ICE MAKER
MODEL FM-1800ALKE-N
POWER SUPPLY 1 Phase 220-240V 50Hz Capacity: 1.08kVa (4.74A)
AMPERAGE 3.9A Starting: 16.5A
ICE DISCHARGE HOLE
ELECTRIC CONSUMPTION 770W (Power Factor: 85%)
(BOTTOM)
In the case of Specification sheet Ps 1.05bar
Evaporator temp -25 °C 4300W
ICE PRODUCTION
Approx. 1590kg (Ambient Temp. 10 °C, Water Temp. 10 °C)
PER 24h
Approx. 1380kg (Ambient Temp. 21 °C, Water Temp. 15 °C)
Approx. 1200kg (Ambient Temp. 32 °C, Water Temp. 21 °C)
216
235
SHAPE OF ICE Nugget
469
MAX. STORAGE CAPACITY Not Applicable
700
Approx. 1.60m3 (Ambient Temp. 10 °C, Water Temp. 10 °C)
WATER CONSUMPTION
Approx. 1.39m3 (Ambient Temp. 21 °C, Water Temp. 15 °C)
PER 24h
Approx. 1.21m3 (Ambient Temp. 32 °C, Water Temp. 21 °C)
OUTSIDE DIMENSIONS 1080(W)×700(D)×780mm(H)
CABINET Stainless Steel, Galvanized Steel (Rear)
285
ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
428
WATER SUPPLY SYSTEM Direct Connection to Water Main, inlet: G3/4 x 2 (Rear)
821 DRAIN SYSTEM Outlet: R3/4 × 2 (Rear)
1080 EVAPORATOR Tube coiled around Cylinder (Solder Plated)
REFRIGERANT R404A
BIN CONTROL Actuator and Reed Switch (Time delay controlled)
37
ICEMAKING WATER CONTROL Float Switch and Solenoid Valve
WATER SUPPLY INLET G3/4 ELECTRICAL PROTECTION Circuit Breaker, Earth Wire
(ICE MAKING WATER) 200 47
GEAR MOTOR Thermal Protector (Auto-reset) Motor Rotation Protection,
FM-1800ALKE-N (Auxiliary code: D-0 or earlier)
780
747
OPERATING
565
Water Supply Pressure: 0.05-0.8MPa (0.5-8bar)
CONDITIONS
(29) Voltage Range: Rated Voltage ±10%
*We reserve the right to make changes in specifications and design without prior
notice.
1. Install the ice maker properly in accordance with the instructions on location, water
83 65
60
supply/drain connections and electrical connections stated in the instruction and
49
219
Approx.1200kg (Ambient Temp. 32°C, Water Temp. 21°C)
262
SHAPE OF ICE Nugget
486
15
° MAX. STORAGE
700
Not Applicable
CAPACITY
WATER Approx.1.60m³ (Ambient Temp. 10°C, Water Temp. 10°C)
CONSUMPTION Approx.1.39m³ (Ambient Temp. 21°C, Water Temp. 15°C)
PER 24h Approx.1.21m³ (Ambient Temp. 32°C, Water Temp. 21°C)
3 5° OUTSIDE
272 1080(W) x 700(D) x 780mm(H)
DIMENSIONS
3 446 CABINET Stainless Steel, Galvanized Steel (Rear)
3 826 ICE MAKING SYSTEM Thin ice forming inside Cylinder (Nugget Ice)
1080
WATER SUPPLY Direct Connection to Water Main, inlet: G3/4 x 2 (Rear)
SYSTEM
DRAIN SYSTEM Outlet: R3/4 x 2 (Rear)
EVAPORATOR Tube coiled around Cylinder (Solder Plated)
REFRIGERANT R404A
38
WATER SUPPLY INLET G3/4 BIN CONTROL Actuator and Reed Switch (Time delay controlled)
(ICE MAKING WATER) 200 47
ICEMAKING WATER
FM-1800ALKE-N (Auxiliary code: D-1 or later)
780
770
747
MECHANISM
682
565
(29)
INTERLOCK Shutdown by Microprocessor (Manual-reset)
WEIGHT Net: 140kg(Gross: 155kg)
3 PACKAGE Carton 1191(W)×820(D)×947mm(H)
83 65
49
60
ACCESSORIES Mounting Bracket, Installation Kit
310 53 Ambient Temp.: 5 - 40°C, Water Supply Temp.: 5-35°C
SUCTION LINE
CONNECTION 5/8" OPERATING Water Supply Pressure: 0.05-0.8MPa(0.5-8bar)
CONDITIONS Voltage Range: Rated Voltage±10%
LIQUID LINE
CONNECTION 3/8" *We reserve the right to make changes in specifications and design without
prior notice.
DRAIN OUTLET R3/4 1. Install the ice maker properly in accordance with the instructions on location,
water supply/drain connections and electrical connections stated in the
instruction and installation manuals provided.
2. The ice production depends on the ambient and water temperatures. Refer to
the instruction manual.
3. Product Code: F074-C106
FM-480AWKE-R452-SB
39
FM-480AWKE-R452N-SB
40
FM-600AKE-R452-SB
41
FM-600AKE-R452N-SB
42
FM-600AWKE-R452-SB
43
FM-600AWKE-R452N-SB
44
FM-750AKE-R452-SB
45
FM-750AKE-R452N-SB
46
FM-1000AKE-R452-SB
47
FM-1000AKE-R452N-SB
48
FM-1200ALKE-R452-SB
49
FM-1200ALKE-R452N-SB
50
FM-1800ALKE-R452-SB
51
FM-1800ALKE-R452N-SB
52
2. CONSTRUCTION
[a] FM-170AKE(-N)
Reservoir
Control Box
Evaporator
Air-Cooled
Condenser
Flush Water Valve
Gear Motor
Fan Motor
Compressor
53
[b] FM-300AKE(-N), FM-480AKE(-N), FM-600AKE(-N), FM-600AKE-R452(N)-SB
Fan Motor
Reservoir
Control Box
Evaporator
Air-Cooled
Condenser
Flush Water Valve
Gear Motor
Compressor
The bin control switch and spout have been changed from D-1. See “[g] BIN CONTROL
SWITCH AND SPOUT” for reference.
54
[c] FM-480AWKE(-N), FM-600AWKE(-N), FM-480AWKE-R452(N)-SB, FM-600AWKE-
R452(N)-SB
Reservoir
Evaporator
Water-Cooled
Condenser
Flush Water Valve
Control Box
Gear Motor
Fan Motor
Compressor
* FM-600AWKE(-N) only
The bin control switch and spout have been changed from D-1. See “[g] BIN CONTROL
SWITCH AND SPOUT” for reference.
55
[d] FM-750AKE(-N), FM-1000AKE(-N), FM-750AKE-R452(N)-SB, FM-1000AKE-R452(N)-
SB
Evaporator
Gear Motor
Control Box
Reservoir
* The bin control switch and spout shown here are for the auxiliary code A-2 or
earlier. For the auxiliary codes from A-3 to D-0, they are the same as those for
FM-170/300/480/600.
The bin control switch and spout have been changed from D-1. See “[g] BIN CONTROL
SWITCH AND SPOUT” for reference.
56
[e] FM-1200ALKE(-N), FM-1200ALKE-R452(N)-SB
Spout *
Control Water Valve
Evaporator Pressure
Evaporator Regulator
Expansion Valve
Solenoid Valve
Gear Motor
The bin control switch and spout have been changed from D-1. See “[g] BIN CONTROL
SWITCH AND SPOUT” for reference.
57
[f] FM-1800ALKE(-N), FM-1800ALKE-R452(N)-SB
Evaporator
Expansion Valve
Solenoid Valve
Bin Control Switch *
Spout Cover
Reed Switch
Spring (Bin Control)
Actuator
Spout
Reed Switch
(Spout Switch)
Chute
59
II. MAINTENANCE AND CLEANING INSTRUCTIONS
IMPORTANT
Operation Panel
When the total operating time reaches 20,000 hours, the display flashes “PC”. Then, after
500 hours, the unit shuts down to ensure safety. The operation can be resumed by turning
off the operation switch and turning it back on. But the unit shuts down again after 500
hours and cannot be restarted.
This information is provided on the label attached to the front panel and in the instruction
manual. But instruct the user to contact a Hoshizaki service agent for replacement as soon
as the display starts flashing “PC”.
60
After replacing the extruding head and mechanical seal:
1) Reset the compressor operating hours in accordance with “III. 5. [f] RESETTING
COMPRESSOR OPERATING HOURS”. The “PC” indication on the display goes off.
2) Record the date of replacement on the label attached to the front panel.
3. MECHANICAL SEAL
The mechanical seal prevents water leaks from between the auger and the housing
bearing and gradually wears out to reduce its watertightness. Check the amount of water
leakage from the drain pipe located at the side of the gear case to determine the necessity
of replacement.
Attach the mechanical seal with its floating sheet facing the housing. After replacement,
there should be no water leakage from the mating surface.
61
Note: The water leakage will exceed the above amount with scale/dirt build up or damage
on the mating surface. Replace the mechanical seal when the water leakage exceeds
0.5 mL/h.
4. GEAR MOTOR
After the following hours of operation, check the gear motor for excessive noise caused by
increased torque or deterioration of mechanical parts.
Note: When the output shaft oil seal is exposed to a large amount of water at one time,
water may enter the gear case. Always drain the water circuit before removing the
auger for service.
2) Clean the air filter by using a vacuum cleaner. When severely clogged, use warm water
and a neutral cleaner to wash the air filter.
3) Rinse and dry the air filter thoroughly, and place it in position.
Air Filter
Louver
62
7. CONTROL WATER VALVE
1) Disconnect the power source.
5) Replace the filter packing and inlet hose in their correct positions.
Filter Packing
63
8. CLEANING OF WATER SYSTEM
WARNING
1. HOSHIZAKI recommends cleaning this unit at least twice a year. More frequent
cleaning, however, may be required in some existing water conditions.
3. Always wear rubber gloves, eye protectors, apron, etc. for safe handling of the
cleaner and sanitiser.
4. Use the cleaners and sanitisers recommended by Hoshizaki. Contact your local
Hoshizaki office for further details. (The instructions below give an example of
those recommended cleaners and sanitisers.)
7. Do not use any ammonia type cleaners on any part of the icemaker.
CAUTION
Do not use ice produced with cleaning and sanitizing solutions. Be sure none
remains in the storage bin on completion of cleaning.
<STEP 1>
IMPORTANT
For safety and maximum effectiveness, use the solutions immediately after dilution.
<STEP 2>
Use the cleaning solution to remove lime deposits in the water system.
2) Press the stop button to activate the flush cycle (approx. 10 minutes).
64
3) Remove all ice from the storage bin to avoid contamination by the cleaner.
5) Remove the cover of the reservoir. Remove any loose debris or scale.
6) Carefully fill the reservoir with the solution to the overflow point. If necessary, use a
small brush to clean the inside of the reservoir.
10) Allow the icemaker to stand for about 10 minutes, then plug in the icemaker to make
ice with the solution.
11) With the water supply tap open, allow the machine to continue icemaking for a further
20 minutes. Open the access flap and press the stop button.
12) Allow time for the gear motor to stop and the water system to drain.
14) Pour warm water into the storage bin to melt any ice down the drain.
Note: 1. If the machine has heavy deposits of scale, repeat the complete cleaning
procedure.
2. Do not increase the proportion of cleaning solution to shorten cleaning times, as
this may lock the auger when completing item 10).
<STEP 3>
65
III. TECHNICAL INFORMATION
CONDENSER
ACCESS VALVE
HEAT EXCHANGER
* FM-480AKE(-N), FM-600AKE(-N) only
350 mm 800 mm
WATER INLET
DRIER RESERVOIR
EVAPORATOR
EXP.V
WATER OUTLET
FLUSH WATER VALVE
Pressure Switch
[FM-170AKE(-N)]
Cut-out 1.57 + 0.15/0 MPa
Cut-in 0.98 ± 0.15 MPa
[FM-300AKE(-N)]
Cut-out 2.85 + 0.15/0 MPa
Cut-in 2.30 ± 0.15 MPa
[FM-480AKE(-N)]
Cut-out 3.14 + 0.15/0 MPa
Cut-in 2.26 ± 0.15 MPa
[FM-600AKE(-N), FM-600AKE-R452(N)-SB]
Cut-out 2.65 + 0.15/0 MPa
Cut-in 2.20 ± 0.15 MPa
66
[b] FM-750AKE(-N), FM-1000AKE(-N), FM-750AKE-R452(N)-SB, FM-1000AKE-R452(N)-
SB
CONDENSER
ACCESS VALVE
HEAT EXCHANGER
350 mm
EVAPORATOR
WATER INLET
DRIER RESERVOIR
EVAPORATOR
EXP.V
EXP.V
WATER OUTLET
FLUSH WATER VALVE
Pressure Switch
Cut-out 3.14 + 0.15/0 MPa
Cut-in 2.26 ± 0.15 MPa
67
[c] FM-1200ALKE(-N), FM-1200ALKE-R452(N)-SB
E.P REGULATOR
CONTROL WATER VALVE
FLOAT SWITCH
SOLENOID VALVE
EVAPORATOR
WATER INLET
RESERVOIR
EXP.V
EVAPORATOR
EXP.V
WATER OUTLET
FLUSH WATER VALVE
68
[d] FM-1800ALKE(-N), FM-1800ALKE-R452(N)-SB
E.P REGULATOR
RESERVOIR
EXP.V EVAPORATOR
FLUSH WATER VALVE
FLOAT SWITCH
CONTROL WATER VALVE
EXP.V
EVAPORATOR
WATER OUTLET
WATER INLET
RESERVOIR
EXP.V
WATER OUTLET
69
[e] FM-480AWKE(-N), FM-600AWKE(-N), FM-480AWKE-R452(N)-SB, FM-600AWKE-
R452(N)-SB
HEAT EXCHANGER
* FM-480AWKE(-N): 400 mm
FM-600AWKE(-N): 800 mm
WATER INLET
DRIER RESERVOIR
EVAPORATOR
EXP.V
WATER OUTLET
FLUSH WATER VALVE
Pressure Switch
[FM-480AWKE(-N), FM-480AWKE-R452(N)-SB]
Cut-out 3.14 + 0.15/0 MPa
Cut-in 2.26 ± 0.15 MPa
[FM-600AWKE(-N), FM-600AWKE-R452(N)-SB]
Cut-out 2.65 + 0.15/0 MPa
Cut-in 2.20 ± 0.15 MPa
70
2. WIRING DIAGRAM
[a] WIRING DIAGRAM
SET No.
L N GR/Y
PROTECTION
BR
20
-LINE 10A
BR LBU
SURGE ABSORBER (VARISTOR)
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
BK W
START CAP.
60MFD
SURGE (BK) (BK)
ABSORBER
(LIGHTNING COMP.
ARRESTER) 11 13
CN7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
V 10 12
14
CN5
STARTER [{XA}]
BR X4 1 BIN CONTROL SWITCH
2
V DBU
3
DBU
4
BR PROTECTION SWITCH
X3 5
FAN MOTOR 6 V PRESSURE
O SWITCH
7 V
(BR) THERMAL (LBU) 8 Y
PROTECTOR 9 Y
GEAR MOTOR 10
THERMAL
PROTECTOR CAP. 5µF
(Y)
CB 11
12
BR
BR
O
13
(Y) CN4
[{XA}] LBU
FLOAT SWITCH
TRANSFORMER 1
220V 2 P (R) (BU)
OPERATION SWITCH (BR) 3
1 2 230V GY (BK)
BU 240V (BU) 1V CN3
CONNECT (O) (BK) [{XA}]
CORRESPONDING FUSE CN1 11
INPUT LINE (W) 3.15A [{VH}]
(R) (GY)
1V 10
14V 11V
P 1 9
W
2 8
CN9 7
[{VH}] 6
8 6 4 2
LBU CONTROL WATER VALVE 1 X1 5
RELAY-X5 4
R BR 2
7 5 3 1 3 3
GY SPARK KILLER 2
BR BR 4 X2 1
5 WIRE COLOR CODE
O ORANGE
R RED
FLASH WATER VALVE BU BLUE
CN10 DBU DARK BLUE
O [{XA}] BR BROWN
8 GY GRAY
SPARK KILLER
7 LBU LIGHT BLUE
6 P PINK
5 Y YELLOW
4 V VIOLET
3 BK BLACK
2 W WHITE
1 GR/Y GREEN/YELLOW
71
FM-170AKE(-N) (Auxiliary code: C-1 or later)
SET No.
L N GR/Y
PROTECTION
BR
20
-LINE 10A
BR LBU
SURGE ABSORBER (VARISTOR)
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
BK W
START CAP.
60MFD
SURGE (BK) (BK)
ABSORBER
(LIGHTNING COMP.
ARRESTER) 11 13
CN7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
V 10 12
14
CN5
STARTER [{XA}]
BR X4 1 BIN CONTROL SWITCH
2
V DBU
3
DBU
4
BR PROTECTION SWITCH
X3 5
FAN MOTOR 6 V PRESSURE
O SWITCH
7 V
(BR) THERMAL (LBU) 8 Y
PROTECTOR 9 Y
GEAR MOTOR 10
THERMAL
PROTECTOR CAP. 5µF
(Y)
CB 11
12
BR
BR
O
13
(Y) CN4
[{XA}] LBU
FLOAT SWITCH
TRANSFORMER 1
220V 2 P (R) (BU)
OPERATION SWITCH (BR) 3
1 2 230V GY (BK)
BU 240V (BU) 1V CN3
CONNECT (O) (BK) [{XA}]
CORRESPONDING FUSE CN1 11
INPUT LINE (W) 3.15A [{VH}]
(R) (GY)
1V 10
14V 11V
P 1 9
W
2 8
CN9 7
[{VH}] 6
8 6 4 2
LBU CONTROL WATER VALVE 1 X1 5
RELAY-X5 4
R BR 2
7 5 3 1 3 3
GY 2
BR BR 4 X2 1
5 WIRE COLOR CODE
O ORANGE
R RED
FLASH WATER VALVE BU BLUE
CN10 DBU DARK BLUE
O [{XA}] BR BROWN
8 GY GRAY
7 LBU LIGHT BLUE
6 P PINK
5 Y YELLOW
4 V VIOLET
3 BK BLACK
2 W WHITE
1 GR/Y GREEN/YELLOW
72
FM-300AKE(-N) (Auxiliary code: D-0 or earlier)
SET No.
17
L N GR/Y
BR
PROTECTION
-LINE 10A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
BR LBU
CAPACITOR
(BU) (BR)
STARTING COMPRESSOR
RELAY 11 13
R 10 12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 CN7
[{XA}]
14
CN5
[{XA}]
1 BIN CONTROL SWITCH1
BR
2 (BK)
X3 DBU
O 3
DBU
4
GEAR MOTOR 1 P CAP. 6µF 5 PROTECTION SWITCH1
C
P W 6 V
O THERMAL
D
(BK)
W 7 V
PROTECTOR 8 Y PRESSURE
BR 9 Y
SWITCH
X4 10
11
R
12
13
CN4
[{XA}] LBU FLOAT SWITCH
FAN MOTOR 1 1
2 P (R) (BU)
Y (BR) THERMAL (BU) 3
BR Y GY (BK)
CB
PROTECTOR
7 5 3 1 CN3
LBU [{XA}]
220V 11
OPERATION SWITCH (BR) 10
8 6 4 2 1 2 230V BK
O
RELAY-X5 BU 240V (BU)
9 W
0V
(O) (BR) 8 V
CN1 7 O
TRANSFORMER-1 FUSE 3.15A [{VH}] 6 RS1
0V (W)
1 5
24(Y) P
(R) 12V (GY) W 2 4
3
CN9
[{VH}] 2
CONTROL WATER VALVE 1 X1 1
R LBU/W 2 CN10
SPARK KILLER 3 [{XA}]
4 8 WIRE COLOR CODE
X2
5 7 O ORANGE
FLASH WATER VALVE 6 R RED
5 BU BLUE
DBU/Y 4 DBU DARK BLUE
SPARK KILLER 3 BR BROWN
2 DBU GY GRAY
1 LBU LIGHT BLUE
DBU EVAPORATOR
P PINK
OUTLET
Y YELLOW
THERMISTOR
V VIOLET
BK BLACK
W WHITE
73
FM-300AKE(-N) (Auxiliary code: D-1 or later)
SET No.
17
L N GR/Y
BR
PROTECTION
-LINE 10A
OB K1
[{XA}]
BR LBU
CAPACITOR
(BU) (BR) COMPRESSOR
STARTING 11 13
RELAY
R 10 12 CN7
[{XA}]
14
CN5
[{XA}]
BIN CONTROL SWITCH1
BR
X3 DBU (BK)
O DBU
GEAR MOTOR 1 T2
CAP. 6µF PROTECTION SWITCH1
C
P T1
P W
O C V (BK)
THERMAL W
PROTECTOR V
Y
PRESSURE
BR SWITCH
X4 Y
CN4
[{XA}] LBU FLOAT SWITCH
FAN MOTOR 1
P (R) (BU)
Y (BR) THERMAL (BU) GY (BK)
CB
BR Y
PROTECTOR
3 CN3
LBU [{XA}]
220V
OPERATION SWITCH
O 230V (BR) BK
RELAY-X5 BU 240V (BU) 0V W
(O) (BR) V
CN1 O
TRANSFORMER-1 FUSE 3.15A [{VH}] RS1
0V (W)
24(Y) P
(R) 12V (GY) W
CN9
[{VH}]
CONTROL WATER VALVE X1
R LBU/W CN10
[{XA}]
X2 WIRE COLOR CODE
O ORANGE
FLASH WATER VALVE R RED
BU BLUE
DBU/Y DBU DARK BLUE
BR BROWN
DBU EVAPORATOR GY GRAY
DBU OUTLET LBU LIGHT BLUE
P PINK
THERMISTOR
Y YELLOW
V VIOLET
BK BLACK
W WHITE
74
FM-480AKE(-N) (Auxiliary code: D-0 or earlier)
SET No.
18
L N GR/Y
BR
PROTECTION
-LINE 20A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
BR LBU
75
FM-480AKE(-N) (Auxiliary code: D-1 or later)
SET No.
18
L N GR/Y
BR
PROTECTION
-LINE 20A
OB K1
[{XA}]
BR LBU
CN4
[{XA}] LBU FLOAT SWITCH
FAN MOTOR1
P (R) (BU)
Y (BR) THERMAL (BU) GY (BK)
BR Y
CB
PROTECTOR CN3
LBU FAN MOTOR2 [{XA}]
76
FM-480AWKE(-N) (Auxiliary code: D-0 or earlier)
SET No.
18
L N GR/Y
BR
PROTECTION
-LINE 20A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
BR LBU
77
FM-480AWKE(-N) (Auxiliary code: D-1 or later), FM-480AWKE-R452(N)-SB
SET No.
18
L N GR/Y
BR
PROTECTION
-LINE 20A
OB K1
[{XA}]
BR LBU
1 2 R C CN7
THERMAL [{XA}]
O GY S PROTECTOR
4 5 CN5
R START CAP. STARTER [{XA}]
BIN CONTROL SWITCH1
BR
X3 DBU (BK)
O DBU
GEAR MOTOR 1 T2 C CAP. 6µF PROTECTION SWITCH1
P P T1 W
THERMAL D V (BK)
O W
PROTECTOR V
Y PRESSURE
BR
Y
SWITCH
X4
R
CN4
[{XA}] LBU
FM-480AKE-N FLOAT SWITCH
HEATER1 P (R) (BU)
(W) (W)
BR Y Y GY (BK)
LBU CB CN3
[{XA}]
O BK
RELAY-X5 W
V
O
RS1
220V
OPERATION SWITCH (BR)
230V
BU 240V (BU) 0V
(O) (BR)
CN1
FUSE 3.15A [{VH}]
TRANSFORMER-1 0V (W)
24(Y) P
(R) 12V (GY) W
CN9 CN10 WIRE COLOR CODE
[{VH}] [{XA}] O ORANGE
CONTROL WATER VALVE X1 R RED
BU BLUE
R LBU/W DBU DARK BLUE
BR BROWN
X2 GY GRAY
LBU LIGHT BLUE
FLASH WATER VALVE DBU P PINK
DBU EVAPORATOR Y YELLOW
DBU/Y OUTLET V VIOLET
THERMISTOR BK BLACK
W WHITE
78
FM-600AKE(-N) (Auxiliary code: D-0 or earlier)
SET No.
18
L N GR/Y
BR
PROTECTION
-LINE 25A
BR LBU
OB K1
CRANKCASE HEATER 1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
V
NOISE SUPPRESSION
CAPACITOR
(W) (W)
RUN CAP. COMPRESSOR
R R C CN7
START CAP. 1 2 3 4 5 6 7 8 9 10 11 12 13 14
1 2 THERMAL [{XA}]
O GY S PROTECTOR
STARTER 5 CN5
[{XA}]
1 BIN CONTROL SWITCH1
BR
2
X3 DBU (BK)
O 3
DBU
4
GEAR MOTOR 1 P CAP. 6µF 5 PROTECTION SWITCH1
C
P
W 6
O THERMAL
D V (BK)
W 7 V
PROTECTOR 8 PRESSURE
Y
BR 9 SWITCH
Y
RELAY-X6 X4 10
R
6 0 11
DBU DBU 12
13
1 1
LBU
CN4
BR [{XA}] LBU FLOAT SWITCH
1
RUN CAP. 2 P (R) (BU)
FAN MOTOR1 (BOTTOM)
(BR) 3 GY (BK)
BR Y V
7 5 3 1
Y (BU)
(GR/Y)
THERMAL (BR)
PROTECTOR
CB CN3
[{XA}]
LBU FAN MOTOR2 (TOP) 11
10
BK
(BR) THERMAL (BU) 9 W
O 8 6 4 2 PROTECTOR FM-600AKE-N 8
RELAY-X5 V
HEATER1 7
O
(W) (W) 6 RS1
5
220V
4
OPERATION SWITCH (BR) 3
1 2 230V 2
BU 240V (BU) 0V 1
(O) (BR)
CN1
TRANSFORMER-1 FUSE 3.15A [{VH}]
0V (W)
1
24(Y) P
2 CN10 WIRE COLOR CODE
(R) 12V (GY) W O ORANGE
[{XA}]
CN9 R RED
[{VH}] 8
BU BLUE
CONTROL WATER VALVE 1 X1 7 DBU DARK BLUE
6
R 2 5 BR BROWN
LBU/W
SPARK KILLER 3 4 GY GRAY
LBU LIGHT BLUE
4 X2 3 P PINK
5 2
DBU Y YELLOW
1
FLASH WATER VALVE DBU EVAPORATOR V VIOLET
OUTLET BK BLACK
DBU/Y THERMISTOR W WHITE
SPARK KILLER
79
FM-600AKE(-N) (Auxiliary code: D-1 or later), FM-600AKE-R452(N)-SB
SET No.
18
LBR N GR/Y
PROTECTION
-LINE 25A
BR LBU OB K1
CRANKCASE HEATER [{XA}]
v NOISE SUPPRESSION
CAPACITOR
(w) (w)
RUN CAP. COMPRESSOR
R START CAP. R C CN7
3 2 THERMAL
O [{XA}]
GY S PROTECTOR
STARTER 1 CN5
[{XA}]
BIN CONTROL SWITCH1
BR
O
X3 DBU (BK)
DBU
GEAR MOTOR 1 T2 C CAP. 6µF PROTECTION SWITCH1
P P T1 W
O THERMAL D V (BK)
W V
PROTECTOR PRESSURE
Y SWITCH
BR
Y
RELAY-X6 X4
R
DBU DBU
LBU CN4
BR [{XA}] LBU FLOAT SWITCH
FAN MOTOR1 (BOTTOM)(BR)RUN CAP. P (R) (BU)
GY (BK)
BR Y V Y (BU)
THERMAL (BK)
GB/F
PROTECTOR
CB CN3
[{XA}]
LBU FAN MOTOR2 (TOP)
BK
(BR) THERMAL (BU)
O W
PROTECTOR FN-610AKE-N
RELAY-X5 V
HEATER1 O
(W) (W)
RS1
220V
OPERATION SWITCH
230V (BR)
BU 240V (BU) 0V
(O) (BR)
CN1
FUSE 3.15A [{VH}]
TRANSFORMER-1 0V (W) 1
24(Y) P
2 CN10 WIRE COLOR CODE
(R) 12V (GY) W
[{XA}] O ORANGE
CN9 R
[{VH}] RED
CONTROL WATER VALVE BU BLUE
X1
DBU DARK BLUE
R LBU/W BR BROWN
GY GRAY
X2 LBU LIGHT BLUE
DBU P PINK
FLASH WATER VALVE DBU EVAPORATOR Y YELLOW
OUTLET V VIOLET
DBU/Y THERMISTOR BK BLACK
W WHITE
80
FM-600AWKE(-N) (Auxiliary code: D-0 or earlier)
SET No.
18
L N GR/Y
BR
PROTECTION
-LINE 25A
BR LBU OB K1
CRANKCASE HEATER 1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
V
NOISE SUPPRESSION
CAPACITOR
(W) (W)
RUN CAP. COMPRESSOR
R START CAP. R C 1 2 3 4 5 6 7 8 9 10 11 12 13 14
CN7
1 2 THERMAL [{XA}]
O GY S PROTECTOR
STARTER 5 CN5
[{XA}]
1 BIN CONTROL SWITCH1
BR
2
X3 DBU (BK)
O 3
4 DBU
GEAR MOTOR 1 P
C CAP. 6µF 5 PROTECTION SWITCH1
P P W 6
O THERMAL
D V (BK)
W 7 V
PROTECTOR 8 Y PRESSURE
BR 9 SWITCH
Y
RELAY-X6 X4 10
R
6 0 11
DBU DBU 12
13
1 1
LBU
CN4
BR [{XA}] LBU FLOAT SWITCH
1
FAN MOTOR (TOP) 2 P (R) (BU)
3
GY (BK)
BR Y V
7 5 3 1
Y (BK) THERMAL
PROTECTOR
(BK)
FM-600AWKE-N
CB CN3
[{XA}]
LBU 11
HEATER1
(W) (W) 10 BK
8 6 4 2 9 W
O 8
RELAY-X5 V
7
6 O
RS1
5
220V 4
OPERATION SWITCH (BR) 3
1 2 230V 2
BU 240V (BU) 0V 1
(O) (BR)
CN1
FUSE 3.15A [{VH}]
TRANSFORMER-1 0V (W)
1
24(Y) P
2 CN10 WIRE COLOR CODE
(R) 12V (GY) W
[{XA}] O ORANGE
CN9 R RED
[{VH}] 8
BU BLUE
CONTROL WATER VALVE 1 X1 7 DBU DARK BLUE
6
R LBU/W 2 5 BR BROWN
SPARK KILLER 3 4 GY GRAY
LBU LIGHT BLUE
4 X2 3 P PINK
5 2
DBU Y YELLOW
1
FLASH WATER VALVE DBU EVAPORATOR V VIOLET
OUTLET BK BLACK
DBU/Y THERMISTOR W WHITE
SPARK KILLER
81
FM-600AWKE(-N) (Auxiliary code: D-1 or later), FM-600AWKE-R452(N)-SB
SET No.
18
LBR N
GR/Y
PROTECTION
-LINE 25A
BR LBU OB K1
CRANKCASE HEATER
[{XA}]
V NOISE SUPPRESSION
CAPACITOR
(W) (W)
RUN CAP. COMPRESSOR
R START CAP. R C CN7
1 2 THERMAL [{XA}]
O GY S PROTECTOR
STARTER 6 CN5
[{XA}]
BIN CONTROL SWITCH1
BR
X3 DBU (BK)
O DBU
GEAR MOTOR 1T2 PROTECTION SWITCH1
P
C CAP. 6µF
P T1
C W (BK)
O THERMAL
W
PROTECTOR
PRESSURE
BR SWITCH
R
RELAY-X6 X4
5 3
DBU DBU
4 1
LBU CN4
BR [{XA}] LBU FLOAT SWITCH
FM-600AWKE-N
CB CN3
[{XA}]
LBU
HEATER1
(W) (W) BK
O W
RELAY-X5 V
O
220V
OPERATION SWITCH
230V (BR)
BU 240V (BU) 0V
(O) (BR)
CN1
FUSE 3.15A [{VH}]
TRANSFORMER-1 0V (W)
24(Y)
P
CN10 WIRE COLOR CODE
(R) 12V (GY) W [{XA}] O ORANGE
CN9 R RED
[{VH}] BU
CONTROL WATER VALVE BLUE
X1 DBU DARK BLUE
LBU/W BR BROWN
GY GRAY
X2 LBU LIGHT BLUE
DBU P PINK
FLASH WATER VALVE Y YELLOW
DBU EVAPORATOR
V VIOLET
OUTLET
DBU/Y BK BLACK
THERMISTOR
W WHITE
82
FM-750AKE(-N) [Auxiliary code: A-2 or earlier]
L N GR/Y
BR
PROTECTION
-LINE 20A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
BR LBU
RUN CAP. COMPRESSOR
R C
START CAP.
1 2 THERMAL
R O GY S PROTECTOR
STARTER 5 CN7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}] BIN CONTROL SWITCH1
BR X4 (BK)
CN5
R [{XA}] BIN CONTROL SWITCH2
1
BR R
2
X3 3 DBU (DBU)
FUSE 3.15A BK
BR/W
4
GEAR MOTOR 1 P
C CAP. 6µF 5 PROTECTION SWITCH1 PROTECTION SWITCH2
P P U W/R
C 6
BR/W THERMAL V (BK)
PROTECTOR
W/R 7
V
8 PRESSURE
Y
GEAR MOTOR 2 P
CAP. 6µF 9 SWITCH
C Y
P P U 10
CB
C P/W
THERMAL W/R 11
PROTECTOR 12
13
TRANSFORMER-1
220V CN4
OPERATION SWITCH (BR) [{XA}] LBU
1 2 230V FLOAT SWITCH
1
BK/R 240V (BU) 0V 2 P (R) (BU)
(O) (BR)
(W)
CN1 3 GY (BK)
100V
(R) (GY) [{VH}] CN3
W/BK
P/BK 1 [{XA}]
24(Y) 2
(R) 12V (GY) W/Y 11
CN9 10
BK
WATER SOLENOID [{VH}] 9
7 5 3 1 R/Y
VALVE-CONTROL W
LBU 1 X1 8 V
RELAY-X5 7
LBU/W 2 O (O)
6 RS1
8 6 4 2 3 P (V) RS2
BR/W 5 Y
W/BK Y/BK DBU/Y 4 X2 4
5 3
WATER SOLENOID WIRE COLOR CODE
VALVE-FLASH 2
1 O ORANGE
R RED
BU BLUE
DBU DARK BLUE
BR BROWN
CN10 GY GRAY
[{XA}] LBU LIGHT BLUE
8 P PINK
7 Y YELLOW
6 V VIOLET
FAN MOTOR1 RUN CAP. 5 BK BLACK
(R)
(W) 4 W WHITE
(BK) 3 LBU/W LIGHT BLUEw/WHITE
THERMAL (BU)
(BR) PROTECTOR 2 P/BK PINKw/BLACK
DBU
FAN MOTOR2 1 W/BK WHITEw/BLACK
DBU EVAPORATOR
OUTLET Y/BK YELLOWw/BLACK
(BR) THERMAL (BU) THERMISTOR W/Y WHITEw/YELLOW
PROTECTOR O/BK ORANGEw/BLACK
BR/W BROWNw/WHITE
W/R WHITEw/RED
HEATER1 BK/W BLACKw/WHITE
(W) (W)
DBU/Y DARK BLUEw/YELLOW
V/BK VIOLETw/BLACK
(W)
HEATER2(W) BK/R BLACKw/RED
DBU/W DARK BLUEw/WHITE
R/Y REDw/YELLOW
P/W PINKw/WHITE
83
FM-750AKE(-N) [Auxiliary code: A-3 and B-0]
BR X4
CN5
R [{XA}]
1 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
BR 2
X3 DBU (BK)
FUSE 3.15A 3
DBU
BR/W
4
GEAR MOTOR 1 P
CAP. 6µF PROTECTION SWITCH1 PROTECTION SWITCH2
C 5
P U
P
C W/R 6
BR/W THERMAL V (BK)
PROTECTOR
W/R 7 V
8 Y PRESSURE
GEAR MOTOR 2 P CAP. 6µF 9 SWITCH
C Y
P P U
P/W 10
CB
C
THERMAL P/W 11
PROTECTOR 12
13
TRANSFORMER-1
220V CN4
OPERATION SWITCH (BR) [{XA}] LBU FLOAT SWITCH
1 2 230V
1
BK/R 240V (BU) 0V 2 P (R) (BU)
(O) (BR)
(W)
CN1 3
100V GY (BK)
(R) (GY) [{VH}] CN3
W/BK
P/BK
1 [{XA}]
24(Y)
12V (GY) W/Y
2 11
(R)
CN9 10 BK
[{VH}] 9
7 5 3 1 W
LBU CONTROL WATER VALVE 1 X1 8 V
RELAY-X5 2 7
LBU/W O (O)
R/Y 6 P RS1 (V) RS2
8 6 4 2 3
BR/W SPARK KILLER 5 Y
W/BK
4 X2 4
Y/BK
5 3
2
WIRE COLOR CODE
1
O ORANGE
FLUSH WATER VALVE R RED
BU BLUE
DBU/Y DBU DARK BLUE
SPARK KILLER
BR BROWN
CN10 GY GRAY
[{XA}] LBU LIGHT BLUE
8 P PINK
7 Y YELLOW
6 V VIOLET
FAN MOTOR1 RUN CAP. 5 BK BLACK
(R)
(W) 4 W WHITE
(BK)
(BU)
3 LBU/W LIGHT BLUEw/WHITE
THERMAL
(BR)
PROTECTOR 2 P/BK PINKw/BLACK
DBU
1 EVAPORATOR W/BK WHITEw/BLACK
FAN MOTOR2 DBU
OUTLET Y/BK YELLOWw/BLACK
(BR) THERMAL (BU) THERMISTOR W/Y WHITEw/YELLOW
PROTECTOR O/BK ORANGEw/BLACK
BR/W BROWNw/WHITE
W/R WHITEw/RED
HEATER1 BK/W BLACKw/WHITE
(W) (W)
DBU/Y DARK BLUEw/YELLOW
V/BK VIOLETw/BLACK
(W)
HEATER2(W) BK/R BLACKw/RED
DBU/W DARK BLUEw/WHITE
R/Y REDw/YELLOW
P/W PINKw/WHITE
84
FM-750AKE(-N) [Auxiliary code: B-1 to D-0]
SET No.
05
L N GR/Y
BR
PROTECTION
-LINE 20A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
BR LBU
85
FM-750AKE(-N) [Auxiliary code: D-1 or later], FM-750AKE-R452(N)-SB
OB K1
[{XA}]
BR LBU
86
FM-1000AKE(-N) [Auxiliary code: A-2 or earlier]
L N
GR/Y
BR
PROTECTION
-LINE 25A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
BR LBU
CRANKCASE HEATER
V/BK
87
FM-1000AKE(-N) [Auxiliary code: A-3 and B-0]
88
FM-1000AKE(-N) [Auxiliary code: B-1 to D-0]
SET No.
05
L N GR/Y
BR
PROTECTION
-LINE 25A
BR LBU OB K1
CRANKCASE HEATER 1 2 3 4 5 6 7 8 9 10 1112 13 14
[{XA}]
V
NOISE SUPPRESSION
CAPACITOR
(W) (W)
RUN CAP. COMPRESSOR
R R C 1 2 3 4 5 6 7 8 9 10 1112 13 14 CN7
START CAP. [{XA}]
1 2 THERMAL
0 GY S PROTECTOR
STARTER 5 CN5
[{XA}]
1 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
BR
2 DBU (BK)
X3
0 3
DBU
4
GEAR MOTOR 1 CAP. 6µF 5 PROTECTION SWITCH1 PROTECTION SWITCH2
T1
C
P P U
C
W 6
BR/W THERMAL W
V (BK)
PROTECTOR 7
V
8 PRESSURE
Y
GEAR MOTOR 2 T2
CAP. 6µF 9 SWITCH
C Y
P P U
C
P 10
THERMAL P 11
PROTECTOR 12
BR
13
RELAY-X6 X4 CN4
R LBU
O [{XA}] FLOAT SWITCH
DBU R
1
2 P (R) (BU)
4 1
LBU 3
GY (BK)
CB
BR
CN3
FAN MOTOR1 [{XA}]
11
Y (BR) THERMAL (BU)
10
BR Y V PROTECTOR BK
9
LBU
7 5 3 1 W
FAN MOTOR2 8
V
7 (O)
O
(BR) THERMAL (BU) 6 RS1 (V) RS2
O
8 6 4 2 PROTECTOR P
5
RELAY-X5 Y
HEATER1 (W) 4
(W)
3
(W)
HEATER2 (W) 2
1
220V
OPERATION SWITCH (BR)
1 2 230V
BU (BU)
240V 0V
(O) (BR)
CN1 CN10
FUSE 3.15A [{VH}] [{XA}]
TRANSFORMER-1 BR (W)
P 1 8 WIRE COLOR CODE
24(Y)
2 7 O ORANGE
(R) 12V (GY) W R RED
CN9 6
5 BU BLUE
[{VH}]
DBU DARK BLUE
CONTROL WATER VALVE 1 X1 4 BR BROWN
3
2 GY GRAY
R LBU 2
3 DBU LBU LIGHT BLUE
SPARK KILLER 1 DBU P
4 EVAPORATOR PINK
X2 OUTLET Y YELLOW
5 VIOLET
THERMISTOR V
FLUSH WATER VALVE BK BLACK
W WHITE
DBU
SPARK KILLER
89
FM-1000AKE(-N) [Auxiliary code: D-1 or later], FM-1000AKE-R452(N)-SB
SET No.
05
L N GR/Y
BR
PROTECTION
-LINE 25A
BR LBU OB K1
CRANKCASE HEATER 1 2 3 4 5 6 7 8 9 10 1112 13 14
[{XA}]
V
NOISE SUPPRESSION
CAPACITOR
(W) (W)
RUN CAP. COMPRESSOR
R R C 1 2 3 4 5 6 7 8 9 10 1112 13 14 CN7
START CAP. [{XA}]
1 2 THERMAL
0 GY S PROTECTOR
STARTER 5 CN5
[{XA}]
1 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
BR
2 DBU (BK)
X3
0 3
DBU
4
GEAR MOTOR 1 CAP. 6µF 5 PROTECTION SWITCH1 PROTECTION SWITCH2
T1
C
P P U
C
W 6
BR/W THERMAL W
V (BK)
PROTECTOR 7
V
8 PRESSURE
Y
GEAR MOTOR 2 T2
CAP. 6µF 9 SWITCH
C Y
P P U
C
P 10
THERMAL P 11
PROTECTOR 12
BR
13
RELAY-X6 X4 CN4
R LBU
O [{XA}] FLOAT SWITCH
DBU R
1
2 P (R) (BU)
4 1
LBU 3
GY (BK)
CB
BK
CN3
FAN MOTOR1 [{XA}]
11
Y (BR) THERMAL (BU)
10
BR Y V PROTECTOR BK
9
LBU
7 5 3 1 W
FAN MOTOR2 8
V
7 (O)
O
(BR) THERMAL (BU) 6 RS1 (V) RS2
O
8 6 4 2 PROTECTOR P
5
RELAY-X5 Y
HEATER1 (W) 4
(W)
3
(W)
HEATER2 (W) 2
1
220V
OPERATION SWITCH (BR)
1 2 230V
BU (BU)
240V 0V
(O) (BR)
CN1 CN10
FUSE 3.15A [{VH}] [{XA}]
TRANSFORMER-1 BR (W)
P 1 8 WIRE COLOR CODE
24(Y)
2 7 O ORANGE
(R) 12V (GY) W R RED
CN9 6
5 BU BLUE
[{VH}]
DBU DARK BLUE
CONTROL WATER VALVE 1 X1 4 BR BROWN
3
2 GY GRAY
R LBU 2
3 DBU LBU LIGHT BLUE
1 DBU P
4 EVAPORATOR PINK
X2 OUTLET Y YELLOW
5 VIOLET
THERMISTOR V
FLUSH WATER VALVE BK BLACK
W WHITE
DBU
90
FM-1200ALKE(-N) [Auxiliary code: A-3 or earlier]
L N GR/Y
BR
PROTECTION
-LINE 10A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
BR LBU
SOLENOID VALVE
CN7
(BR) (BU) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}] BIN CONTROL SWITCH1
R
BR X4 (BK)
CN5
R [{XA}] BIN CONTROL SWITCH2
1 R
BR
2
X3 DBU (DBU)
FUSE 3.15A 3
BK
BR/W
4
GEAR MOTOR 1 T2
CAP. 6µF PROTECTION SWITCH1 PROTECTION SWITCH2
C 5
P P T1 P
W/R 6
BR/W THERMAL C V (BK)
W/R 7
PROTECTOR V
8
GEAR MOTOR 2 T2 CAP. 6µF 9
C
P P T1 P/W 10
CB
C
THERMAL 11
P/W
PROTECTOR
12
13
TRANSFORMER
220V CN4
OPERATION SWITCH (BR) [{XA}] LBU
FLOAT SWITCH
1 2 230V
(BU) 1
BK/R BU 240V 0V P (R) (BU)
2
(O) (BK)
(W)
CN1 3 GY (BK)
100V
(R) (GY) [{VH}] CN3
W/BK
P/BK 1 [{XA}]
24(V)
(R) 12V (GY) W/Y 2 11
10 BK
CN9
WATER SOLENOID [{VH}] 9
7 5 3 1 R/Y W
LBU VALVE-CONTROL 1 X1 8 V
RELAY-X5 7 O (O)
LBU/W
2
6 (V) RS2
8 6 4 2 3 P RS1
BR/W 5
4 Y
W/BK Y/BK DBU/Y X2 4
WATER SOLENOID W/BK 5 3
VALVE-FLASH 2 WIRE COLOR CODE
1 O ORANGE
DBU/Y
R RED
BU BLUE
DBU DARK BLUE
BR BROWN
CN10 GY GRAY
[{XA}] LBU LIGHT BLUE
8 P PINK
7 Y YELLOW
6 V VIOLET
5 BK BLACK
HEATER1 4 W WHITE
(W) (W)
3 LBU/W LIGHT BLUEw/WHITE
2 DBU P/BK PINKw/BLACK
HEATER2 1 DBU W/BK WHITEw/BLACK
(W) (W) EVAPORATOR
OUTLET Y/BK YELLOWw/BLACK
THERMISTOR W/Y WHITEw/YELLOW
O/BK ORANGEw/BLACK
BR/W BROWNw/WHITE
W/R WHITEw/RED
BK/W BLACKw/WHITE
DBU/Y DARK BLUEw/YELLOW
V/BK VIOLETw/BLACK
BK/R BLACKw/RED
DBU/W DARK BLUEw/WHITE
R/Y REDw/YELLOW
P/W PINKw/WHITE
91
FM-1200ALKE(-N) [Auxiliary code: A-4 and B-0]
L N
GR/Y SET No.
BR
PROTECTION 13
-LINE 10A
OB
K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
BR LBU
SOLENOID VALVE
CN7
(BR) (BU) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
R
BR X4
CN5
R [{XA}]
1 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
BR
2 DBU
X3 (BK)
FUSE 3.15A 3
DBU
4
GEAR MOTOR 1 T2
CAP. 6µF
BR/W
PROTECTION SWITCH1 PROTECTION SWITCH2
C 5
P P T1
C
W/R 6
BR/W THERMAL V (BK)
PROTECTOR
W/R 7
V
8
GEAR MOTOR 2 T2 CAP. 6µF 9
C
P P T1 10
CB
C P/W
THERMAL P/W 11
PROTECTOR 12
13
TRANSFORMER
220V CN4
OPERATION SWITCH (BR) [{XA}] LBU FLOAT SWITCH
1 2 230V
BK/R BU (BU) 1
240V 0V 2 P (R) (BU)
(O) (BK)
(W)
CN1 3
100V GY (BK)
(R) (GY)
[{VH}] CN3
W/BK
P/BK
1 [{XA}]
24(V) 2
(R) 12V (GY) W/Y 11
10
CN9 BK
[{VH}] 9 W
7 5 3 1
LBU CONTROL WATER VALVE 1 X1 8 V
RELAY-X5 7
R/Y LBU/W 2 O (O)
6 RS1
8 6 4 2 3 P (V) RS2
BR/W SPARK KILLER 5
4 Y
W/BK Y/BK X2 4
5 3
2
WIRE COLOR CODE
1
O ORANGE
FLUSH WATER VALVE R RED
BU BLUE
DBU/Y DBU DARK BLUE
SPARK KILLER BR BROWN
CN10 GY GRAY
[{XA}] LBU LIGHT BLUE
8 P PINK
7 Y YELLOW
6 V VIOLET
5 BK BLACK
HEATER1 4
(W) (W) W WHITE
3 LBU/W LIGHT BLUEw/WHITE
2 P/BK PINKw/BLACK
HEATER2 DBU
(W) 1 W/BK WHITEw/BLACK
(W) DBU EVAPORATOR
OUTLET Y/BK YELLOWw/BLACK
THERMISTOR W/Y WHITEw/YELLOW
O/BK ORANGEw/BLACK
BR/W BROWNw/WHITE
W/R WHITEw/RED
BK/W BLACKw/WHITE
DBU/Y DARK BLUEw/YELLOW
V/BK VIOLETw/BLACK
BK/R BLACKw/RED
DBU/W DARK BLUEw/WHITE
R/Y REDw/YELLOW
P/W PINKw/WHITE
92
FM-1200ALKE(-N) [Auxiliary code: B-1 to D-0]
SET No.
13
L N GR/Y
BR
PROTECTION
-LINE 10A
OB K1
1 2 3 4 5 6 7 8 9 10 1112 13 14
[{XA}]
BR LBU
SOLENOID VALVE
(BR) (BU)
R
1 2 3 4 5 6 7 8 9 10 1112 13 14 CN7
[{XA}]
CN5
BR [{XA}]
X3 1 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
0
2
GEAR MOTOR 1 DBU (BK)
T2
C CAP. 6µF 3
P T1 DBU
P
C W 4
O THERMAL W 5 PROTECTION SWITCH1 PROTECTION SWITCH2
PROTECTOR
6 V (BK)
GEAR MOTOR 2 T2
CAP. 6µF 7
C V
P P T1
P 8 PRESSURE
Y
THERMAL
C
9 SWITCH
P Y
PROTECTOR 10
11
BR 12
X4 13
R
CN4
[{XA}] LBU FLOAT SWITCH
1
(W)
HEATER1 (W) 2 P (R) (BU)
Y 3 GY (BK)
BR Y
LBU
7 5 3 1
HEATER2 (W)
CB CN3
[{XA}]
(W) 11
8 6 4 2 10
O BK
RELAY-X5 9
W
8
V
7
O (O)
6 RS1 (V) RS2
P
220V 5 Y
OPERATION SWITCH (BR) 4
1 2 230V 3
BU (BU)
240V 0V 2
(O) (BR)
CN1 1
FUSE 3.15A [{VH}]
TRANSFORMER-1 BR (W)
P 1
24(Y)
(R) 12V (GY) W
2
CN9 CN10
[{VH}] [{XA}]
CONTROL WATER VALVE 1 X1 8
7 WIRE COLOR CODE
LBU 2
R 6 O ORANGE
SPARK KILLER 3 5
4 R RED
X2 4 BU BLUE
5 3 DBU DARK BLUE
FLUSH WATER VALVE 2 DBU BR BROWN
1 DBU EVAPORATOR GY GRAY
DBU OUTLET LBU LIGHT BLUE
SPARK KILLER THERMISTOR P PINK
Y YELLOW
V VIOLET
BK BLACK
W WHITE
93
93
FM-1200ALKE(-N) [Auxiliary code: D-1 or later], FM-1200ALKE-R452(N)-SB
OB K1
[{XA}]
BR LBU
SOLENOID VALVE
(BR) (BU)
R CN7
[{XA}]
CN5
BR [{XA}]
0 X3 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
GEAR MOTOR 1 DBU (BK)
T2
C CAP. 6µF DBU
P T1
P W
O THERMAL C
PROTECTION SWITCH1 PROTECTION SWITCH2
W
PROTECTOR
V (BK)
GEAR MOTOR 2 T2 C CAP. 6µF V
P P T1
C P Y PRESSURE
THERMAL Y SWITCH
P
PROTECTOR
BR
R
X4
CN4
[{XA}] LBU FLOAT SWITCH
(W)
HEATER1(W) P (R) (BU)
Y
BR Y GY (BK)
LBU
HEATER2
CB CN3
[{XA}]
(W) (W)
O BK
RELAY-X5 W
V
O
P RS1 RS2
220V Y
OPERATION SWITCH (BR)
1 2 230V
BU (BU)
240V 0V
(O) (BR)
CN1
FUSE 3.15A [{VH}]
TRANSFORMER-1 BR (W)
P WIRE COLOR CODE
24(Y)
(R) 12V (GY) W CN10 O ORANGE
CN9 R RED
[{VH}] [{XA}]
BU BLUE
CONTROL WATER VALVE X1 D DARK BLUE
LBU BR BROWN
GY GRAY
X2 LBU LIGHT BLUE
P PINK
FLUSH WATER VALVE DBU Y YELLOW
DBU
DBU EVAPORATOR V VIOLET
OUTLET BK BLACK
THERMISTOR WHITE
W
94
FM-1800ALKE(-N) [Auxiliary code: A-3 or earlier]
L N
GR/Y
BR
PROTECTION
-LINE 10A
OB K1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}]
BR LBU
BIN CONTROL SWITCH1
(R)
(DBU)
SOLENOID VALVE (BK)
CN7
(BR) (BU) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 [{XA}] BIN CONTROL SWITCH2
R (R)
(DBU)
BR X4 (BK)
CN5
R [{XA}] BIN CONTROL SWITCH3
1 R (R)
BR 2
X3 DBU (DBU)
FUSE 3.15A 3 BK (BK)
BR/W 4
GEAR MOTOR 1 CAP. 6µF
T2
C 5 PROTECTION SWITCH1 PROTECTION SWITCH2
P P T1 W/R
BR/W C 6 V (BK) (BK)
THERMAL W/R
PROTECTOR 7 V
8 PROTECTION SWITCH3
GEAR MOTOR 2 T2 CAP. 6µF 9
C Y
P P T1 P/W 10 FLOAT SWITCH2
THERMAL
PROTECTOR
C
P/W CB 11
12 O (R) (BU)
GEAR MOTOR 3 13
T2
C CAP. 6µF BR (BK)
P P T1
C
P/W CN4
THERMAL
P/W [{XA}] LBU
PROTECTOR FLOAT SWITCH1
1
2 P (R) (BU)
TRANSFORMER
3 (BK)
220V GY
OPERATION SWITCH (BR) CN3
1 2 230V
(BU)
[{XA}]
BK/R BU 240V 0V
(O) (BK)
11
(W)
100V CN1 10 BK
(GY) [{VH}] 9 W
(R)
W/BK
1 8 V
P/BK
24(V) 2 7 O (O) (O)
(R) 12V (GY) W/Y
6 (V) RS1 (V) RS2
CN9 P
5 Y
7 5 3 1 R/Y WATER SOLENOID [{VH}] 4
LBU VALVE-CONTROL 1 1 X1 3 GY
RELAY-X5
2
R WIRE COLOR CODE
LBU/W 2 DBU O ORANGE
8 6 4 2 3 1 LBU (O)
BR/W R RED
W/BK Y/BK O/W 4 X2 (V) RS3 BU BLUE
WATER SOLENOID 5 DBU DARK BLUE
VALVE-CONTROL 2 BR BROWN
CN10 GY GRAY
[{XA}] LBU LIGHT BLUE
CN8
[{XA}] 8 LBU P PINK
RELAY-X7 1 7 Y YELLOW
LBU EVAPORATOR
7 5 3 1 2 6 OUTLET V VIOLET
5 THERMISTOR2 BK BLACK
3
4 W WHITE
4
DBU/Y
8 6 4 2 3 LBU/W LIGHT BLUEw/WHITE
5 2
O/BK P/BK
DBU P/BK PINKw/BLACK
6 1 W/BK WHITEw/BLACK
WATER SOLENOID DBU EVAPORATOR
VALVE-FLASH1 OUTLET Y/BK YELLOWw/BLACK
THERMISTOR1 W/Y WHITEw/YELLOW
O/BK ORANGEw/BLACK
7 5 3 1
BR/W BROWNw/WHITE
GY W/R WHITEw/RED
WATER SOLENOID RELAY-X6 BK/W BLACKw/WHITE
HEATER1 VALVE-FLASH2
(W) (W) GY DBU/Y DARK BLUEw/YELLOW
8 6 4 2
V/BK VIOLETw/BLACK
HEATER2 O/W P/BK
BK/R BLACKw/RED
(W) (W)
DBU/W DARK BLUEw/WHITE
HEATER3 R/Y REDw/YELLOW
(W) (W)
P/W PINKw/WHITE
95
FM-1800ALKE(-N) [Auxiliary code: A-4 and B-0]
SOLENOID VALVE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 CN7
(BR) (BU) [{XA}]
R
BR X4
CN5
R [{XA}]
1 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
BR 2
X3 DBU (BK) (BK)
FUSE 3.15A 3 DBU
4 BIN CONTROL SWITCH3
GEAR MOTOR 1 T2 BR/W
P P T1
C CAP. 6µF 5 PROTECTION SWITCH1 PROTECTION SWITCH2
W/R 6
BR/W THERMAL C
V (BK) (BK)
PROTECTOR
W/R 7
8
V PROTECTION SWITCH3
GEAR MOTOR 2 T2 C CAP. 6µF 9
P P T1 10 Y FLOAT SWITCH2
CB
C P/W
THERMAL P/W 11
PROTECTOR 12 O (R) (BU)
GEAR MOTOR 3 T2 13
C CAP. 6µF BR (BK)
P T1
P
C P/W CN4
THERMAL P/W [{XA}] LBU FLOAT SWITCH1
PROTECTOR 1
2 P (R) (BU)
TRANSFORMER
3
220V GY (BK)
OPERATION SWITCH (BR) CN3
1 2 230V
BK/R BU
[{XA}]
240V (BU) 0V 11
(O) (W) (BK)
CN1 10 BK
100V
(R) (GY) [{VH}] 9 W
W/BK 8
P/BK
1 V
24(V) 2 7 (O) (O)
(R) 12V (GY) W/Y O
6
CN9 P (V) RS1 (V) RS2
5 Y
[{VH}]
7 5 3 1 R/Y
CONTROL WATER VALVE-1 4 GY
LBU 1 X1 3
RELAY-X5
2 2
R WIRE COLOR CODE
LBU/W DBU O
3 ORANGE
8 6 4 2 SPARK KILLER 1 (O)
BR/W LBU R RED
W/BK Y/BK 4 X2 (V) RS3 BU BLUE
CONTROL WATER VALVE-2 5 DBU DARK BLUE
BR BROWN
O/W CN10 GY GRAY
SPARK KILLER CN8 [{XA}] LBU LIGHT BLUE
[{XA}] 8 P PINK
LBU
1 7 Y YELLOW
LBU EVAPORATOR
2 6 V VIOLET
OUTLET
7 5 3 1 5 BK BLACK
3 THERMISTOR2
RELAY-X7 4 W WHITE
4 3 LBU/W LIGHT BLUEw/WHITE
8 6 4 2 5 2 P/BK PINKw/BLACK
DBU/Y DBU
P/BK 6 1 EVAPORATOR W/BK WHITEw/BLACK
FLUSH WATER VALVE-1 DBU
OUTLET Y/BK YELLOWw/BLACK
O/BK THERMISTOR1 W/Y WHITEw/YELLOW
SPARK KILLER O/BK ORANGEw/BLACK
BR/W BROWNw/WHITE
7 5 3 1
GY W/R WHITEw/RED
FLUSH WATER VALVE-2 RELAY-X6 BK/W BLACKw/WHITE
GY DBU/Y DARK BLUEw/YELLOW
8 6 4 2
SPARK KILLER V/BK VIOLETw/BLACK
O/W P/BK
HEATER1 BK/R BLACKw/RED
(W) (W) DBU/W DARK BLUEw/WHITE
HEATER2 R/Y REDw/YELLOW
(W) (W) P/W PINKw/WHITE
HEATER3
(W) (W)
96
FM-1800ALKE(-N) [Auxiliary code: B-1 and D-0]
SOLENOID VALVE
CN7
(BR) (BU) 1 2 3 4 5 6 7 8 9 10 11 12 13 14
[{XA}]
R
BR X4
R
CN5
BR [{XA}]
X3 1 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
2
GEAR MOTOR 1 O DBU (BK) (BK)
T2 CAP. 6µF 3
C
4
DBU BIN CONTROL SWITCH3
P P T1
C
W
O THERMAL 5 PROTECTION SWITCH1 PROTECTION SWITCH2
W
PROTECTOR 6 V (BK) (BK)
GEAR MOTOR 2 7 V
T2 CAP. 6µF PROTECTION SWITCH3
P P T1
C
8
P
O THERMAL
C 9
P Y
10 FLOAT SWITCH2
CB
PROTECTOR
11
GEAR MOTOR 3 T2
CAP. 6µF 12 O (R) (BU)
C
P T1
O
P
C
P 13
THERMAL P BR (BK)
PROTECTOR CN4
[{XA}] LBU FLOAT SWITCH1
HEATER1 1
(W) (W)
2 P (R) (BU)
HEATER2 3
(W) (W)
GY (BK)
HEATER3 CN3
(W) (W)
[{XA}]
11
220V 10
OPERATION SWITCH BK
(BR) 9
1 2 230V W
8
BU 240V (BU) 0V 7
V
(O) (BK) O (O) (O)
CN1 6 (V) RS2
P (V) RS1
FUSE 3.15A [{VH}] 5
TRANSFORMER-1 Y
GY (W)
1 4
P GY
BR Y
24(V)
2 3
(R) 12V (GY) W R
2
1 CN9 DBU
7 5 3 1 (O)
LBU [{VH}] LBU
RELAY-X5 CONTROL WATER VALVE-1 (V) RS3
1 X1
8 6 4 2 2
0 R LBU
SPARK KILLER 3 CN10
4 X2 [{XA}]
5 8
CONTROL WATER VALVE-2 LBU
7 LBU EVAPORATOR
W 6 OUTLET
SPARK KILLER CN8 5 THERMISTOR2
[{XA}] 4
1 3 WIRE COLOR CODE
2 2 DBU O ORANGE
7 5 3 1 1 R RED
3 DBU EVAPORATOR
RELAY-X7
OUTLET BU BLUE
4
THERMISTOR1 DBU DARK BLUE
DBU
8 6 4 2 5 BR BROWN
P 6 GY GRAY
FLUSH WATER VALVE-1
LBU LIGHT BLUE
BK P PINK
7 5 3 1
SPARK KILLER GY Y YELLOW
RELAY-X6 V VIOLET
GY BK BLACK
FLUSH WATER VALVE-2 8 6 4 2
P
W WHITE
W
SPARK KILLER
97
FM-1800ALKE(-N) [Auxiliary code: D-1 or later], FM-1800ALKE-R452(N)-SB
SOLENOID VALVE
CN7
(BR) (BU) [{XA}]
R
BR X4
R
CN5
BR [{XA}]
X3 BIN CONTROL SWITCH1 BIN CONTROL SWITCH2
O DBU (BK) (BK)
GEAR MOTOR 1 T2
CAP. 6µF DBU
P P T1
C
W
BIN CONTROL SWITCH3
C
O THERMAL PROTECTION SWITCH1 PROTECTION SWITCH2
W
PROTECTOR
V (BK) (BK)
GEAR MOTOR 2 T2
C CAP. 6µF V PROTECTION SWITCH3
P P T1
C P
O THERMAL P
CB
PROTECTOR FLOAT SWITCH2
GEAR MOTOR 3 T2
C CAP. 6µF (R) (BU)
P P T1
R Y
O THERMAL
C
R
BR (BK)
PROTECTOR CN4
[{XA}] LBU O FLOAT SWITCH1
(W) HEATER1 (W)
P (R) (BU)
(W)
HEATER2
(W)
GY (BK)
(W)
HEATER3 CN3
(W)
[{XA}]
220V BK
OPERATION SWITCH
1 2 230V W
BU 240V 0V
V
(BK) O (O) (O)
CN1 P (V) RS1 (V) RS2
TRANSFORMER-1 GY (W)
FUSE 3.15A [{VH}] Y
P GY
24(V)
BR Y (R) 12V (GY) W
R
7 5 3 1 CN9 DBU
LBU [{VH}] LBU (O)
RELAY-X5 CONTROL WATER VALVE-1 X1 (V) RS3
8 6 4 2
R LBU
CN10
X2 [{XA}]
CONTROL WATER VALVE-2 LBU
LBU EVAPORATOR
W
OUTLET
CN8
[{XA}] THERMISTOR2
DBU
DBU EVAPORATOR WIRE COLOR CODE
RELAY-X1
OUTLET O ORANGE
DBU
THERMISTOR1 R RED
P BU BLUE
FLUSH WATER VALVE-1
DBU DARK BLUE
BK BR BROWN
1 GY
GY GRAY
RELAY-X6 LBU LIGHT BLUE
GY P PINK
FLUSH WATER VALVE-2 Y YELLOW
W P V VIOLET
BK BLACK
W WHITE
98
[b] CONTROL BOX LAYOUT
FM-170AKE(-N)
CB CONTROLLER BOARD-MAIN
OB CONTROLLER BOARD-OPERATION
X1 POWER RELAY (CONTROL WATER VALVE, ON BOARD)
X2 POWER RELAY (FLUSH WATER VALVE, ON BOARD)
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
X5 POWER RELAY (GM DRIVE)
S3 OPERATION SWITCH
OL CIRCUIT PROTECTOR (10A)
SA2 SURGE ABSORBER (LIGHTENING ARRESTER)
F FUSE 3.15A
99
FM-300AKE(-N), FM-480AKE(-N)
CB CONTROLLER BOARD-MAIN
OB CONTROLLER BOARD-OPERATION
X1 POWER RELAY (CONTROL WATER VALVE, ON BOARD)
X2 POWER RELAY (FLUSH WATER VALVE, ON BOARD)
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
X5 POWER RELAY (GM DRIVE)
S3 OPERATION SWITCH
OL CIRCUIT PROTECTOR (10A: 300AKE / 20A: 480AKE)
C1 CAPACITOR (GM1)
F FUSE 3.15A
TR TRANSFORMER
100
FM-480AWKE(-N), FM-480AWKE-R452(N)-SB
CB CONTROLLER BOARD-MAIN
OB CONTROLLER BOARD-OPERATION
X1 POWER RELAY (CONTROL WATER VALVE, ON BOARD)
X2 POWER RELAY (FLUSH WATER VALVE, ON BOARD)
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
X5 POWER RELAY (GM DRIVE)
S3 OPERATION SWITCH
OL CIRCUIT PROTECTOR (20A)
C1 CAPACITOR (GM1)
F FUSE 3.15A
TR TRANSFORMER
101
FM-600AKE(-N), FM-600AWKE(-N), FM-600AKE-R452(N)-SB, FM-600AWKE-R452(N)-
SB
CB CONTROLLER BOARD-MAIN
OB CONTROLLER BOARD-OPERATION
X1 POWER RELAY (CONTROL WATER VALVE, ON BOARD)
X2 POWER RELAY (FLUSH WATER VALVE, ON BOARD)
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
X5 POWER RELAY (GM DRIVE)
X6 POWER RELAY (COMPRESSOR)
SR STARTER (COMPRESSOR)
SC START CAPACITOR (COMPRESSOR)
RC RUN CAPACITOR (COMPRESSOR)
S3 OPERATION SWITCH
OL CIRCUIT PROTECTOR (25A)
C1 CAPACITOR (GM1)
F FUSE 3.15A
TR TRANSFORMER
102
FM-750AKE(-N), FM-1000AKE(-N) [Auxiliary code: B0 or earlier]
X4
X3
OB
CB S5
X6
OL
C1 C2
RC SC SR
X5
F
CB CONTROLLER BOARD-MAIN
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
OB CONTROLLER BOARD-OPERATION
C1 CAPACITOR (GM1)
C2 CAPACITOR (GM2)
SR STARTER
SC START CAPACITOR
RC RUN CAPACITOR
F FUSE
OL CIRCUIT PROTECTOR
X5 POWER RELAY
X6 POWER RELAY (FM-1000AKE FM-1000AKE-N ONLY)
S5 OPERATION SWITCH
103
FM-1200ALKE(-N) [Auxiliary code: B0 or earlier]
CB CONTROLLER BOARD-MAIN
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (SOLENOID VALVE, ON BOARD)
OB CONTROLLER BOARD-OPERATION
C1 CAPACITOR (GM1)
C2 CAPACITOR (GM2)
X5 POWER RELAY
OL CIRCUIT PROTECTOR
F FUSE
S5 OPERATION SWITCH
104
FM-1800ALKE(-N) [Auxiliary code: B0 or earlier]
CB CONTROLLER BOARD-MAIN
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (SOLENOID VALVE, ON BOARD)
OB CONTROLLER BOARD-OPERATION
C1 CAPACITOR (GM1)
C2 CAPACITOR (GM2)
C3 CAPACITOR (GM3)
X5 POWER RELAY
X6 POWER RELAY
X7 POWER RELAY
OL CIRCUIT PROTECTOR
F FUSE
S7 OPERATION SWITCH
105
FM-750AKE(-N), FM-1200ALKE(-N) [Auxiliary code: B1 or later], FM-750AKE-R452(N)-
SB, FM-1200ALKE-R452(N)-SB
CB CONTROLLER BOARD-MAIN
OB CONTROLLER BOARD-OPERATION
X1 POWER RELAY (CONTROL WATER VALVE, ON BOARD)
X2 POWER RELAY (FLUSH WATER VALVE, ON BOARD)
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
X5 POWER RELAY (GM DRIVE)
S5 OPERATION SWITCH
OL CIRCUIT PROTECTOR (20A: 750AKE/10A: 1200ALKE)
C1 CAPACITOR (GM1)
C2 CAPACITOR (GM2)
F FUSE 3.15A
TR TRANSFORMER
106
FM-1000AKE(-N) [Auxiliary code: B1 or later], FM-1000AKE-R452(N)-SB
CB CONTROLLER BOARD-MAIN
OB CONTROLLER BOARD-OPERATION
X1 POWER RELAY (CONTROL WATER VALVE, ON BOARD)
X2 POWER RELAY (FLUSH WATER VALVE, ON BOARD)
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
X5 POWER RELAY (GM DRIVE)
X6 POWER RELAY (COMPRESSOR)
SR STARTER (COMPRESSOR)
SC START CAPACITOR (COMPRESSOR)
RC RUN CAPACITOR (COMPRESSOR)
S5 OPERATION SWITCH
OL CIRCUIT PROTECTOR (25A)
C1 CAPACITOR (GM1)
C2 CAPACITOR (GM2)
F FUSE 3.15A
TR TRANSFORMER
107
FM-1800ALKE(-N) [Auxiliary code: B1 or later], FM-1800ALKE-R452(N)-SB
CB CONTROLLER BOARD-MAIN
OB CONTROLLER BOARD-OPERATION
X1 POWER RELAY (CONTROL WATER VALVE, ON BOARD)
X2 POWER RELAY (FLUSH WATER VALVE, ON BOARD)
X3 POWER RELAY (GEAR MOTOR, ON BOARD)
X4 POWER RELAY (COMPRESSOR, ON BOARD)
X5 POWER RELAY (GM DRIVE)
X6 POWER RELAY (CONTROL WATER VALVE-2)
X7 POWER RELAY (FLUSH WATER VALVE)
S7 OPERATION SWITCH
OL CIRCUIT PROTECTOR (10A)
C1 CAPACITOR (GM1)
C2 CAPACITOR (GM2)
C3 CAPACITOR (GM3)
F FUSE 3.15A
TR TRANSFORMER
108
3. ICEMAKING MECHANISM
Flake Type Nugget Type
Pin
Screw
Bolt
Spring
Washer
Cutter
Auger
Extruding
Head Packing - Spout
Flange
Mechanical Seal
Housing
Coupling
Evaporator
Screw
Gear Motor
109
[a] EVAPORATOR (CASING)
The evaporator consists of a stainless steel icemaking cylinder coiled with a refrigeration
pipe and wrapped together with a polyurethane foam insulation material. Water coming
from the inlet into the evaporator will be frozen into ice. The ice spout is located on top of
the evaporator.
[b] AUGER
The stainless steel auger is supported by the upper and lower bearings of the evaporator
and slowly rotated by the gear motor, while scraping off the ice forming on the inner wall of
the cylinder and pushing up to the ice spout.
The stainless steel extruding head is provided with a press-fit plastic bearing inside and
fixed on top of the evaporator. The extruding head functions as the auger bearing and
compresses the sherbet ice carried up by the auger into a column shape with the path
resistance.
[d] HOUSING
The cast bronze housing is provided with a press-fit plastic bearing inside and fixed on the
bottom of the evaporator for connection with the gear motor.
The mechanical seal on the lower auger bearing prevents icemaking water leaks into the
evaporator. The mating surfaces are made of ceramic and carbon.
The auger bottom and gear motor output shaft are splined and connected with the spline
joint.
The gear motor consists of a 200W 1 phase 240V or 80W 1 phase 220 - 240 / 220V
drive motor integrated with a decelerator and provided with a built-in auto-reset thermal
protector. When the thermal protector trips, the controller board will stop the gear motor.
The thermal protector trips when the gear motor mechanism is overloaded or when
excessively high or low voltage is applied on the gear motor. The electrical capacity must
be increased if a large current flows through the surrounding equipment.
110
[h] BELT HEATER (provided on some models)
The belt heater is provided to reduce the load of ice passing the extruding head during a
freeze cycle and to prevent vapor lock during a flush cycle.
The flange used to be welded on the evaporator to fix the spout. But sometimes the
extruding head applies excessive load on the evaporator to compress ice, resulting in
breaking the welded joints. To avoid the load, the flange has been changed to a separate
part to be secured together with the extruding head by using sealing bolts.
Sometimes the icemaking operation may produce white solids on the drip pan. They are
deposits of silica and calcium contents in the icemaking water leaking from the sealing
bolt. The bolt is provided with retaining and sealing functions, which may be reduced by
the load and vibration during a freeze cycle. Do not reuse a removed sealing bolt.
111
[k] CHUTE, BIN CONTROL SWITCH
[FM-750/1000 (Auxiliary code: A-2 or earlier), FM-1200/1800 (Auxiliary code: A-3
or earlier)]
The chute and bin control switch are caulked and combined.
Ice formed in the evaporator casing passes through the spout, chute, and bin control switch
and drops out of the unit bottom. The chute is made of integrally molded hard PVC and soft
PVC. Ice sliding down on the spout hits the soft material, resulting in lower hitting sounds.
The bin control switch is an infrared photo sensor built in a plastic bracket. The infrared
photo sensor has a light emitting element and a light receiving element. The sensor
detects there is no ice when infrared rays from the light emitting element come into the
light receiving element. When ice comes between the two elements, the sensor detects the
bin is full and stops icemaking operation. The unit resumes operation automatically when
ice disappears from between the two elements.
If the plastic part of the bin control switch or the infrared sensor lens is not clean and blocks
infrared rays, the sensor falsely detects the bin is full and stops the unit. When making
periodic inspections or replacing periodic replacement parts, check that the infrared ray
passages and infrared sensor lenses in the plastic part of the bin control switch are clean.
If not, wipe them clean with a soft cloth.
Soft PVC
Soft PVC
Chute
112
[l] BIN CONTROL SWITCH
[FM-170/300/480/600 (Auxiliary code: D0 or earlier), FM-750/1000 (Auxiliary code:
A-3 to D0), FM-1200/1800 (Auxiliary code: A-4 to D0)]
13
original position to switch on the proximity
º
switch. The gear motor will restart in 7
61
seconds, and the compressor in 5 minutes.
The bin control switch is composed of a reed switch attached to the spout and an actuator
(ice detector) provided inside the spout and chute. The bin control switch operates as
follows:
1. Ice reaches up to the ice detector.
2. Ice pushes and moves the ice detector.
3. The actuator magnet shifts and departs from the reed switch
4. The reed switch turns off.
113
5. The icemaking operation stops.
Heavy soil inside the spout or chute may cause ice to get stuck. Dirty actuator hinge may
disturb the movement of actuator. Check the cleanness of spout, chute, and actuator at
periodic inspection or periodic part replacement. Wipe clean any notably dirty part.
The ice detector is different for flake icemaker and nugget icemaker. If incorrect detector
is attached, the bin control function will not work. If the icemaking operation continues, the
abnormal stop switch trips and the unit stops with an error. Be sure to attach the proper
ice detector. The actuator is composed of two components bonded. The letters “C” and “F”
are stamped on the fitting part. The type of icemaker can be distinguished by boss fitting
position.
Magnet
Actuator Hinge
Spout
Actuator
Ice Detector
Actuator
Ice Detector Ice
Flake
C Boss fitting position
F C: Nugget
Nugget F: Flake
The chute switch consists of a microswitch and a band securing the spout and chute.
When the bin control switch breaks down, the band opens and presses the button on the
microswitch (contacts open) to stop the icemaker (error code: EL).
To restart the icemaker, remove ice from the spout and chute, and move the operation
switch to the “STOP” position, then to the “RUN” position. Normal Condition
Normal Condition
114
Band
Microswitch
Chute
Spout
Abnormal Condition
(Band moves and presses microswitch)
Band
Microswitch
Chute
Spout
Reed Switch
Equipments employing a large amount of refrigerant are provided with the crankcase
Heater to prevent refrigerant migration to the compressor during off-cycles resulting in oil
shortage at startup. The crankcase heater will be energized also when the user turns off
the operation switch on the operation board.
115
4. ELECTRIC CIRCUIT
CAUTION
Reassemble all the components as they were after servicing the unit according to a
service call.
The icemaker starts water supply when the operation switch is moved to the “ON” position.
On completion of water supply, the gear motor starts immediately. After 5 minutes the
compressor starts to begin icemaking operation.
In normal operation, the icemaker shuts down when the storage bin fills up to trip the bin
control switch or the stop button is pressed. When the compressor operates for 6 hours
in total and continuously for more than 10 minutes, the icemaker supplies water until the
reservoir fills up and starts a drain cycle. After 10 minutes the icemaker automatically starts
water supply and resumes icemaking operation.
Operation switch ON
After 10 min
Low ice bin level Water supply starts Drain
After 5 min
After 5 min
116
Restart
Bin Control Automatic icemaking
Bin Control STOP Button ICE Button (more than 1hr) Drain process
Trip Reset ON ON Trip Reset
7sec 7sec 6hrs
ON
ICE Button
OFF
Control Water ON
[b] TIMING CHART
Valve OFF
High
Water Level Middle
Low
Float Switch ON
(Upper) OFF
Float Switch ON
(Lower) OFF
Fan Motor ON
Gear Motor OFF
117
5min 5min 5min 5min 5min 5min 5min 5min
ON
Compressor
OFF
Bin Control ON
Switch OFF
Drain Water ON
Valve OFF
“ICE” ON
Indication OFF
“STOP” ON
Indication OFF
“BIN FULL” ON
Indication OFF
“DRAIN” ON
Indication OFF
5. OPERATION BOARD
ICE = When pressed in the STOP mode, the unit is supplied with water and starts
icemaking operation.
STOP = When pressed in the ICE mode, the unit stops icemaking operation and drains.
MAINTENANCE A = Used for various maintenance operations.
MAINTENANCE B = Used for model code setting.
OPERATION SWITCH = Power supply for the icemaker. Move it to the “OFF” position to
shut down the unit for a long time.
The model number must be set at the time of replacement of the controller board. Check
the model number specified on the wiring label. Improper setting may result in failure or
inoperability.
1) Press and hold the maintenance B button, and move the operation switch to the “ON”
position.
2) When the display shows “99”, release the maintenance B button.
3) Press the stop button to increase the number, or press the ice button to decrease the
number until it matches the model number on the wiring label.
4) Press the maintenance B button to complete the setting and start icemaking operation
in the ice mode.
5) To check the model number, see next page.
118
3)
2) 4)
1)
Press and hold the maintenance A button, and press the ice button. The display shows the
following items one by one every time the ice button is pressed.
This function is available in the ice or stop mode.
119
Note:
1. The display shows the next item if the ice button is pressed before one item appears
in the display.
2. The display mode is cancelled if the maintenance A button is released.
3. The software version is displayed repeatedly while the maintenance A button is
pressed. Release the maintenance A button to cancel the display mode.
a) Compressor Operating Hours
The display shows the compressor operating hours in six digits divided into three parts
(2 digits for 2 seconds each time).
Then, “- -” appears in the display (to show the end of the compressor operating hours
display mode).
e.g. 3527 hours = “00”, “35”, “27”, “- -”
b) Cycle Time
The display shows the cycle time in four digits divided into two parts (first minutes then
seconds, for 2 seconds each time) from the latest record (5 records at maximum).
Then, “- -” appears in the display (to show the end of the cycle time display mode).
If no cycle time is recorded, the display shows “- -” only.
Minutes are indicated as follows:
o 0 to 9 = 0 to 9 minutes
A 0 to 9 = 10 to 19 minutes
b 0 to 9 = 20 to 29 minutes
C 0 to 9 = 30 to 39 minutes
d 0 to 9 = 40 to 49 minutes
E 0 to 9 = 50 to 59 minutes
Seconds are indicated as 0 to 5 0 to 9.
This is just an approximate capacity. The actual capacity depends on ambient temperature,
water temperature, voltage and frequency.
120
For accurate measurement, use a container to receive ice actually produced for 10 minutes,
measure its weight, and calculate ice production per day. Repeat this three times to figure
out the average.
c) Model Number
The display shows two digits.
e.g. FM-750AKE(-N), FM-1000AKE(-N) = “05”
d) Software Version
The display shows the software version in six digits/symbols divided into three parts.
e.g. Ver. 9-3-6 = “09”, “-3”, “-6”
The indication is repeated until the maintenance A button is released.
Press and hold the maintenance A button, and press the stop button. The display shows
the following items one by one every time the stop button is pressed.
This function is available in the ice or stop mode.
Note:
1. The display does not show the ongoing error even if the stop button is pressed while the
error log is in the display. To display the ongoing error, press the stop button while “- -”
is in the display to show the end of the error log display mode.
121
[e] RESETTING ERROR LOG
With the operation switch in the “OFF” position, press and hold the stop and maintenance
A buttons. Move the operation switch to the “ON” position. Release the buttons when the
display shows the ice mode. Now the error log is reset. Do not reset more than necessary.
Note: This operation should be performed only when the display shows “PC”.
With the power switch turned off, press and hold the ice, stop and maintenance A buttons.
Move the operation switch to the “ON” position. Release the buttons when the display
shows the ice mode. Now the compressor operating hours are reset.
When the compressor starts in 15 seconds after the water supply cycle ends, the error
log is not set to be updated. After resetting the compressor operating hours, move the
operation switch to the “OFF” position, turn off the power switch, and turn it back on.
122
[g] REDUCING COMPRESSOR STARTING TIME
With the power switch turned off, press and hold the maintenance A button. Move the
operation switch to the “ON” position. Release the button when the display shows the ice
mode.
The compressor starts in 30 seconds after the water supply cycle ends.
6. PROTECTORS
[a] INDICATION
When an operational error occurs, “E_” will appear and blink in the display on the operation
board, and the icemaker will stop. When a service call is received, ask the user to check
which error code is in the display. Then, see the error code table in “7. ERROR CODES” to
locate the cause.
123
7. ERROR CODES
Interlock Errors
Code Error Condition Operation Reset Check/Repair
Water leak from water circuit
(reservoir, inlet hose, outlet
Icemaking Water c0 error occurs 2 times in Whole Power supply, Turn
E0 hose, hose joint, mechanical
Leak a row. unit stops. OFF - Turn ON
seal, flush water valve), float
switch
Gas leak, control water valve
Icemaking cycle takes too Whole Power supply, Turn
E1 Low Ice Production not closing, vapor lock, freeze,
long. unit stops. OFF - Turn ON
float switch
With flush water valve
OFF, float switch trips at Whole Power supply, Turn
E2 Float Switch Error Float switch
both upper and lower float unit stops. OFF - Turn ON
levels for 2 seconds.
Gear motor is ON with
Rotation sensor, current
rotation sensor or current
Gear Motor Error or sensor circuit open. Power supply, Turn sensor
Whole
E3 Gear Motor Sensor OFF -
Gear motor relay is ON unit stops. Gear motor protective circuit
Circuit Open Turn ON
with gear motor protective (TPO, overload, etc.), gear
circuit detector OFF. motor relay
Fan motor, cooling water
c2 error occurs 5 times
Abnormal High Side circuit, refrigeration circuit,
E4 in 1 hour of compressor E4 blinks. N/A
Pressure condenser clogged, water
operation.
supply, installation conditions
Gear motor is OFF on
controller board while
rotation sensor signals
gear motor rotation or Miswiring, gear motor magnet
Gear Motor Drive Whole Power supply, Turn
E5 current flows. switch or relay Replace
Element Error unit stops. OFF - Turn ON
controller board.
Gear motor relay is OFF
with gear motor protective
circuit detector ON.
Discharge Pipe Discharge pipe thermostat Whole Power supply, Turn Gas leak, compressor cooling
E8
Temperature Error is OFF. unit stops. OFF - Turn ON fan failure
Water Thermistor Water thermistor circuit is
EA EA blinks. N/A Water thermistor
Circuit Open open.
Condenser
Condenser thermistor Whole Power supply, Turn
Eb Thermistor Circuit Condenser thermistor
circuit is open. unit stops. OFF - Turn ON
Open
Evaporator Outlet
Evaporator outlet Whole Power supply, Turn
EC Thermistor Circuit Evaporator outlet thermistor
thermistor circuit is open. unit stops. OFF - Turn ON
Open
Rotation sensor detects Gear motor locked, hunting or
reversing. Whole Power supply, Turn
EE Gear Motor Error overloaded, supply voltage,
unit stops. OFF - Turn ON
c5 error occurs 5 times. high ambient temperature
Abnormal Low c3 error occurs 3 times in Whole Power supply, Turn
EF Supply voltage
Voltage 24 hours. unit stops. OFF - Turn ON
Discharge Pipe
Discharge pipe thermistor
EH Thermistor Circuit EH blinks. N/A Discharge pipe thermistor
circuit is open.
Open
Bin Control Switch Bin control protective Whole Power supply, Turn
EL Bin control switch
Error switch trips. unit stops. OFF - Turn ON
Low Voltage Sensing Low voltage sensing
Whole Power supply, Turn Low voltage sensing
En Transformer Circuit transformer circuit is
unit stops. OFF - Turn ON Transformer
Open open.
Controller Board Whole Power supply, Turn
EU Controller board IC fails. Replace controller board.
Error unit stops. OFF - Turn ON
Power supply, Turn
Electric Leak Short Electric leak or Whole
None OFF - Turn ON Electric leak, fuse
Circuit overcurrent. unit stops.
Replace fuse
124
Non-Interlock Errors
Code Error Condition Operation Reset Check/Repair
Error records
CM Microcomputer and compressor
Microcomputer fails to Memory circuit not Replace controller
Time Read/Write operating hours
read/write properly. available. board.
“- -” Error not available on
display
Water leak from
After initial water supply,
Whole unit stops. Flush water circuit
float switch trips at lower
Icemaking water valve turns ON (reservoir, hoses,
c0 float level within 5 minutes Error record only.
Water Leak for 1 second, then turns mechanical seal,
after gear motor starts and
OFF. Unit restarts. flush water valve),
before compressor starts.
float switch
Water supply continues Water supply
for more than 90 seconds, Whole unit stops until interruption, control
or float switch trips at reservoir fills up. Only Automatically resets water valve not
c1 Low Water lower float level and does control water valve after reservoir fills opening, flush
not reset for more than operates intermittently for up. water valve not
60 seconds after water 5 minutes. closing, float
supply. switch, water leak
Automatically resets
Pressure switch stays
after pressure Condenser
OFF for 5 seconds or
Abnormal High switch turns ON clogged, cooling
c2 condenser thermistor Whole unit stops.
Side Pressure or condenser water circuit,
reads higher than set point
thermistor reads refrigeration circuit
for 5 seconds.
lower than set point.
Voltage stays below setting Automatically resets
Abnormal Low for more than 1 second after voltage stays
c3 Whole unit stops. Supply voltage
Voltage with compressor ON and above reset setting
control water valve OFF. for 2 minutes.
Float switch trips at upper Flush water valve
float level in 10 minutes not opening,
c4 Drain Error N/A Error record only.
after flush water valve control water valve
turns ON. not closing
Rotation rate reduces.
Gear Motor While gear motor is running, Whole unit stops. Automatically resets Gear motor
c5
Error voltage detection signal is after 30 minutes. overloaded
not input to controller board.
Evaporator Evaporator inside
Outlet Evaporator outlet Automatically not clean, extruding
c7 Indication only.
Temperature temperature decreases. resets. head not clean,
Decrease heater circuit open
[20,000 hours] “PC” starts
flashing.
[20,500 hours] Whole
After replacing Replace extruding
unit stops but can be
Periodic Parts Compressor operating parts, reset head (upper
PC restarted by turning OFF
Replacement hours reach 20,000 hours. compressor bearing) and
and ON power supply.
operating hours. mechanical seal.
[21,000 hours] Whole unit
stops again and cannot
be restarted.
125
8. PERFORMANCE DATA
[a] FM-170AKE
0.18
190
170 0.16
150
0.14
130
0.12
110
90 0.1
0 10 20 30 40 0 10 20 30 40
3.9 15
3.85
Wattage [kWh/day]
14.5
Amperage [A]
3.8
3.75 14
3.7
13.5
3.65
3.6 13
0 10 20 30 40 0 10 20 30 40
1200 80
70
Head Pressure [kPa]
1000
60
800 50
40
600
30
400 20
0 10 20 30 40 0 10 20 30 40
126
[b] FM-170AKE-N
0.18
190
170 0.16
150
0.14
130
0.12
110
90 0.1
0 10 20 30 40 0 10 20 30 40
3.9 15
3.85
Wattage [kWh/day]
14.5
Amperage [A]
3.8
3.75 14
3.7
13.5
3.65
3.6 13
0 10 20 30 40 0 10 20 30 40
1200 80
Suction Pressure [kPa]
Head Pressure [kPa]
70
1000
60
800 50
40
600
30
400 20
0 10 20 30 40 0 10 20 30 40
127
[c] FM-300AKE
350 0.35
300 0.3
250 0.25
200 0.2
150 0.15
0 10 20 30 40 0 10 20 30 40
6 26
Wattage [kWh/day]
5.8
Amperage [A]
24
5.6
22
5.4
5.2 20
0 10 20 30 40 0 10 20 30 40
2200 340
2000
Head Pressure [kPa]
128
[d] FM-300AKE-N
350 0.35
300 0.3
250 0.25
200 0.2
150 0.15
0 10 20 30 40 0 10 20 30 40
6 26
Wattage [kWh/day]
5.8
Amperage [A]
24
5.6
22
5.4
5.2 20
0 10 20 30 40 0 10 20 30 40
2200 340
2000
Head Pressure [kPa]
320
1800
300
1600
280
1400
1200 260
1000 240
0 10 20 30 40 0 10 20 30 40
129
[e] FM-480AKE
600 0.6
550 0.55
500 0.5
0.45
450
0.4
400
0.35
350
0.3
300 0.25
250 0.2
0 10 20 30 40 0 10 20 30 40
9 42
Wattage [kWh/day]
40
8.5
Amperage [A]
38
8
36
7.5 34
7 32
0 10 20 30 40 0 10 20 30 40
2000 250
Suction Pressure [kPa]
Head Pressure [kPa]
1800 230
1600 210
1400 190
1200 170
1000 150
0 10 20 30 40 0 10 20 30 40
130
[f] FM-480AKE-N
600 0.6
Ice Production Capacity [kg/day]
9 42
Wattage [kWh/day]
40
8.5
Amperage [A]
38
8
36
7.5 34
7 32
0 10 20 30 40 0 10 20 30 40
2000 250
Suction Pressure [kPa]
Head Pressure [kPa]
1800 230
1600 210
1400 190
1200 170
1000 150
0 10 20 30 40 0 10 20 30 40
131
[g] FM-480AWKE, FM-480AWKE-R452-SB
500 0.5
Ice Production Capacity [kg/day]
400 0.4
350 0.35
300 0.3
0 10 20 30 40 0 10 20 30 40
7.5 36
Wattage [kWh/day]
7.3
35
Amperage [A]
7.1
34
6.9
6.7 33
6.5 32
0 10 20 30 40 0 10 20 30 40
1750 220
Head Pressure [kPa]
1725 210
1700 200
1675 190
1650 180
0 10 20 30 40 0 10 20 30 40
132
[h] FM-480AWKE-N, FM-480AWKE-R452N-SB
500 0.5
450 0.45
400 0.4
350 0.35
300 0.3
0 10 20 30 40 0 10 20 30 40
7.5 36
Wattage [kWh/day]
7.3
35
Amperage [A]
7.1
34
6.9
6.7 33
6.5 32
0 10 20 30 40 0 10 20 30 40
1750 220
Head Pressure [kPa]
1725 210
1700 200
1675 190
1650 180
0 10 20 30 40 0 10 20 30 40
133
[i] FM-600AKE, FM-600AKE-R452-SB
700 0.65
650
Ice Production Capacity [kg/day]
11 50
Wattage [kWh/day]
48
Amperage [A]
10.5
46
44
10
42
9.5 40
0 10 20 30 40 0 10 20 30 40
2000 160
Head Pressure [kPa]
1000 80
0 10 20 30 40 50 0 10 20 30 40 50
134
[j] FM-600AKE-N, FM-600AKE-R452N-SB
700 0.65
650
0.6
600
550 0.55
500
450 0.5
400
0.45
350
300 0.4
0 10 20 30 40 0 10 20 30 40
11 50
Wattage [kWh/day]
48
Amperage [A]
10.5
46
44
10
42
9.5 40
0 10 20 30 40 0 10 20 30 40
2000 160
Head Pressure [kPa]
1000 80
0 10 20 30 40 50 0 10 20 30 40 50
135
[k] FM-600AWKE, FM-600AWKE-R452-SB
650 0.6
600
0.55
550
500 0.5
450
0.45
400
350 0.4
0 10 20 30 40 0 10 20 30 40
10 43
9.8 42.5
Wattage [kWh/day]
Amperage [A]
42
9.6
41.5
9.4
41
9.2 40.5
9 40
0 10 20 30 40 0 10 20 30 40
1750 130
Suction Pressure [kPa]
Head Pressure [kPa]
125
1700
120
1650
115
1600 110
0 10 20 30 40 0 10 20 30 40
136
[l] FM-600AWKE-N, FM-600AWKE-R452N-SB
650 0.6
600
0.55
550
500 0.5
450
0.45
400
350 0.4
0 10 20 30 40 0 10 20 30 40
10 43
Wattage [kWh/day]
9.8 42.5
Amperage [A]
42
9.6
41.5
9.4
41
9.2 40.5
9 40
0 10 20 30 40 0 10 20 30 40
1750 130
Head Pressure [kPa]
1600 110
0 10 20 30 40 0 10 20 30 40
137
[m] FM-750AKE, FM-750AKE-R452-SB
900 0.8
850
800 0.7
750
700 0.6
650
600 0.5
550
500 0.4
450
400 0.3
350
300 0.2
0 10 20 30 40 50 0 10 20 30 40 50
9 44
43
Wattage [kWh/day]
Amperage [A]
8.5 42
41
8 40
39
7.5 38
0 10 20 30 40 50 0 10 20 30 40 50
2200 340
320
Suction Pressure [kPa]
Head Pressure [kPa]
2000
300
1800
280
1600
260
1400
240
1200 220
1000 200
0 10 20 30 40 50 0 10 20 30 40 50
138
[n] FM-750AKE-N, FM-750AKE-R452N-SB
700 0.6
650
Ice Production Capacity [kg/day]
10 46
45
9.5
Wattage [kWh/day]
44
Amperage [A]
9 43
8.5 42
41
8
40
7.5 39
7 38
0 10 20 30 40 50 0 10 20 30 40 50
2400 340
2200 320
Head Pressure [kPa]
2000 300
1800 280
1600 260
1400 240
1200 220
1000 200
0 10 20 30 40 50 0 10 20 30 40 50
The horizontal axis shows the ambient temperature.
It refers to the data of at/wt=10/10, 21/15, 32/21, 40/35.
139
[o] FM-1000AKE, FM-1000AKE-R452-SB
1200 1.1
1150
1100
1.0
1050
1000
950 0.9
900
850 0.8
800
750
0.7
700
650
600 0.6
550
500 0.5
0 10 20 30 40 50 0 10 20 30 40 50
13 62
61
Wattage [kWh/day]
60
12.5
Amperage [A]
59
58
12
57
56
11.5 55
0 10 20 30 40 50 0 10 20 30 40 50
2200 300
2000
280
Suction Pressure [kPa]
Head Pressure [kPa]
1800
1600 260
1400 240
1200
220
1000
800 200
0 10 20 30 40 50 0 10 20 30 40 50
The horizontal axis shows the ambient temperature.
It refers to the data of at/wt=10/10, 21/15, 32/21, 40/35.
140
[p] FM-1000AKE-N, FM-1000AKE-R452N-SB
1000 0.9
Ice Production Capacity [kg/day]
400 0.4
0 10 20 30 40 50 0 10 20 30 40 50
13 63
62
Wattage [kWh/day]
61
Amperage [A]
12.5
60
59
12
58
57
11.5 56
0 10 20 30 40 50 0 10 20 30 40 50
2200 300
2000
280
Suction Pressure [kPa]
Head Pressure [kPa]
1800
1600 260
1400 240
1200
220
1000
800 200
0 10 20 30 40 50 0 10 20 30 40 50
The horizontal axis shows the ambient temperature.
It refers to the data of at/wt=10/10, 21/15, 32/21, 40/35.
141
[q] FM-1200ALKE, FM-1200ALKE-R452-SB
1400 1.3
Ice Production Capacity [kg/day]
1300 1.2
700 0.7
0 10 20 30 40 0 10 20 30 40
1400 1.3
Ice Production Capacity [kg/day]
700 0.7
0 10 20 30 40 0 10 20 30 40
142
[s] FM-1800ALKE, FM-1800ALKE-R452-SB
2000 1.9
1900 1.8
Ice Production Capacity [kg/day]
2000 1.9
Ice Production Capacity [kg/day]
1900 1.8
143
IV. SERVICE DIAGNOSIS
Display error records by operating the operation board (see “III. 5. [d] DISPLAYING
ERROR LOG”). Check for a possible cause and service the unit.
1. NO ICE PRODUCTION
PROBLEM POSSIBLE CAUSE REMEDY
[1] The icemaker will a) Power supply 1. OFF position. 1. Move to ON position.
not start.
2. Loose connections. 2. Tighten.
3. Bad contacts. 3. Check for continuity and
replace.
4. Blown fuse. 4. Replace.
5. Voltage too low. 5. Get recommended voltage.
b) Fuse 1. Blown out. No 1. Locate and resolve the cause
indication on operation of short circuit (ex. control
board. water valve, flush water
valve), and replace.
c) Transformer 1. Disconnected. 1. Connect.
receptacle
d) Operation switch 1. OFF position. 1. Move to ON position.
2. Bad contacts. 2. Check for continuity and
replace.
e) Transformer 1. Coil winding opened. 1. Replace.
f) Water valve 1. Coil winding opened. 1. Replace.
g) Water supply tap 1. Closed. 1. Open.
2. Water failure. 2. Wait till water is supplied.
h) Plug and receptacle 1. Disconnected. 1. Connect.
(control box)
2. Terminal out of plug or 2. Insert terminal back in
receptacle. position.
i) Reed switch (spout) 1. Tripped. 1. See 1 - [3] - a).
j) Overload protector 1. Tripped. 1. Reset.
k) Model number 1. Incorrect. 1. Set correct number. See
“III. 5. [b] SETTING MODEL
NUMBER”.
[2] Water does not a) Water control relay 1. Contacts fused. 1. Replace controller board.
stop, and the (controller board)
2. Coil winding opened. 2. Replace controller board.
icemaker will not
start. b) Float switch 1. Bad contacts. 1. Check for continuity and
replace.
2. Float does not move 2. Clean or replace.
freely.
c) Flush water valve 1. Valve seat clogged 1. Clean or replace.
and water leaking.
d) Hoses 1. Disconnected. 1. Connect.
e) Mechanical seal 1. Water leaks. 1. Replace.
f) Reservoir 1. Cracked. 1. Replace.
[3] Water has been a) Bin control 1. Bad contacts. 1. Check for continuity and
supplied, but the replace.
icemaker will not
b) Gear motor 1. Tripped. 1. Find out the cause, resolve
start.
protector (thermal it, and press reset button on
breaker) motor protector.
c) Controller board 1. Defective. 1. Replace.
144
PROBLEM POSSIBLE CAUSE REMEDY
[3] (Continued) d) Pressure switch, 1. Dirty condenser fins. 1. Clean.
condenser 2. Ambient temperature 2. Check for recommended
thermistor too warm. temperature.
3. Fan not rotating. 3. Replace.
4. Condenser water 4. Check and get recommended
pressure too low or pressure.
off.
5. Water regulating valve 5. Clean.
clogged.
6. Refrigerant 6. Recharge.
overcharged.
7. Refrigerant line or 7. Clean and replace drier.
components plugged.
8. Bad contacts. 8. Check for continuity and
replace.
9. Loose connections. 9. Tighten.
e) Thermostat 1. Ambient temperature 1. Check for recommended
(water-cooled too warm. temperature.
model) 2. Compressor cooling 2. Replace.
fan motor defective.
3. Bad contacts. 3. Check for continuity and
replace.
4. Loose connections. 4. Tighten.
f) Gear motor protect 1. Coil winding opened. 1. Replace.
relay 2. Bad contacts. 2. Check for continuity and
replace.
[4] Gear motor a) X4 relay (controller 1. Bad contacts. 1. Check for continuity and
starts, but board) replace controller board.
compressor 2. Coil winding opened. 2. Replace controller board.
will not start
or operates b) X6 relay 1. Bad contacts. 1. Check for continuity and
intermittently. replace X6 relay.
2. Coil winding opened. 2. Replace X6 relay.
c) Compressor 1. Loose connections. 1. Tighten.
2. Motor winding opened 2. Replace.
or earthed.
3. Motor protector 3. Find out the cause of
tripped. overheat or overcurrent.
d) Power supply 1. Circuit ampacity too 1. Install a larger-sized
low. conductor.
e) Controller board 1. Defective. 1. Replace.
f) Start capacitor or 1. Defective. 1. Replace.
run capacitor
[5] Gear motor and a) Refrigerant line 1. Gas leaks. 1. Check for leaks with a leak
compressor start, detector. Reweld leak,
but no ice is replace drier and charge
produced. with refrigerant. The amount
of refrigerant is marked on
nameplate or label.
2. Refrigerant line 2. Replace the clogged
clogged. component.
145
2. LOW ICE PRODUCTION
PROBLEM POSSIBLE CAUSE REMEDY
[1] Low ice a) Refrigerant line 1. Gas leaks. 1. See 1 - [5] - a).
production 2. Refrigerant line 2. Replace the clogged
clogged. component.
3. Overcharged. 3. Recharge.
b) High-side pressure 1. Dirty air filter or 1. Clean.
too high condenser.
2. Ambient or condenser 2. Check for recommended
water temperature too temperature.
warm.
3. Condenser water 3. Check and get recommended
pressure too low or pressure.
off.
4. Fan rotating too slow. 4. Replace.
5. Water regulating valve 5. Clean.
clogged.
6. Bad ventilation. 6. Remove anything blocking
vents.
7. Less than specified 7. Allow proper clearance for
clearance at rear, ventilation.
sides and top.
c) Expansion valve 1. Low-side pressure 1. Replace.
(not adjustable) exceeding the limit.
d) Evaporator 1. Evaporator pipe 1. Replace.
crushed.
3. OTHERS
PROBLEM POSSIBLE CAUSE REMEDY
[1] Abnormal noise a) Fan motor 1. Bearing worn out. 1. Replace.
(condenser unit) 2. Fan blade deformed. 2. Replace fan blade.
3. Fan blade does not 3. Replace.
move freely.
b) Compressor 1. Bearings worn out, 1. Replace.
or cylinder valve
defective.
2. Mounting pad out of 2. Reinstall.
position.
c) Refrigerant lines 1. Rub or touch lines or 1. Replace.
other surfaces.
d) Gear motor (ice 1. Bearing or gear wear/ 1. Replace.
making) damage.
e) Evaporator 1. Low-side pressure too 1. See if expansion valve
low. bulb is mounted properly,
and replace the valve if
necessary.
2. Scale on inside wall of 2. Remove auger. Use a
freezing cylinder. solution of lime removing
cleaner to clean periodically.
If water is found to surpass
the following levels, install a
conditioner.
Hardness 50 ppm
Silica 30 ppm
146
PROBLEM POSSIBLE CAUSE REMEDY
[1] (Continued) f) Heater 1. Defective. 1. Replace.
g) CPR (condenser 1. Internal leaks. 1. Replace.
unit)
[2] Overflow from a) Water supply 1. Water pressure too 1. Install a pressure reducing
reservoir (Water high. valve.
does not stop.) b) Water valve 1. Diaphragm does not 1. Clean or replace.
close.
c) Float switch 1. Bad contacts. 1. Check for continuity and
replace.
[3] Gear motor a) Power supply 1. Too high or too low. 1. Connect the unit to a power
protector voltage supply of proper voltage.
operates b) Evaporator assy 1. Bearings or auger 1. Replace bearing or auger.
frequently. worn out.
147
V. REMOVAL AND REPLACEMENT
The compressor must not be opened more than 15 minutes in replacement or service.
Do not mix lubricants of different compressors even if both are charged with the same
refrigerant, except when they use the same lubricant.
If a refrigerant leak occurs in the low side of an ice maker, air may be drawn in. Even
if the low side pressure is higher than the atmospheric pressure in normal operation,
a continuous refrigerant leak will eventually lower the low side pressure below the
atmospheric pressure and will cause air suction. Air contains a large amount of moisture,
and ester oil easily absorbs a lot of moisture. If an ice maker charged with R452A/R404A/
R134A has possibly drawn in air, the drier must be replaced. Be sure to use a drier
designed for R452A/R404A/R134A.
Repair of the refrigerant circuit requires brazing. It is no problem to use the same handy
flux that has been used for the current refrigerants. However, its entrance into the
refrigerant circuit should be avoided as much as possible.
When processing the copper tubing for service, wipe off oil, if any used, by using alcohol or
the like. Do not use too much oil or let it into the tubing, as wax contained in the oil will clog
the capillary tubing.
Some parts used for refrigerants other than R452A/R404A/R134A are similar to those for
R404A/R134A. But never use any parts unless they are specified for R452A/R404A/R134A
because their endurance against the refrigerant has not been evaluated. Also, for R452A/
R404A/R134A, do not use any parts that have been used for other refrigerants. Otherwise,
wax and chlorine remaining on the parts may adversely affect R452A/R404A/R134A.
The copper tubes currently in use are suitable for R452A/R404A/R134A. But do not use
them if oily inside. The residual oil in copper tubes should be as little as possible. (Low
residual oil type copper tubes are used in the shipped units.)
148
7) Evacuation, Vacuum Pump and Refrigerant Charge [R452A/R404A/R134A]
Never allow the oil in the vacuum pump to flow backward. The vacuum level and vacuum
pump may be the same as those for the current refrigerants. However, the rubber hose
and gauge manifold to be used for evacuation and refrigerant charge should be exclusively
for R452A/R404A/R134A.
Refrigerant leaks can be detected by charging the unit with a little refrigerant, raising the
pressure with nitrogen and using an electronic detector. Do not use air or oxygen instead
of nitrogen for this purpose, or rise in pressure as well as in temperature may cause
R452A/R404A/R134A to suddenly react with oxygen and explode. Be sure to use nitrogen
to prevent explosion.
The refrigerant must be recovered if required by an applicable law. A low-side access valve
is provided in the unit (modular type only). Recover the refrigerant from the access valve,
and store it in a proper container. Do not discharge the refrigerant into the atmosphere.
When replacing the drier, take the opportunity to also fit a low-side access valve (self-
contained type only) and a high-side access valve for ease of charging liquid refrigerant.
R134a models
1) Attach a charging hose of a gauge manifold to a vacuum pump and the low-side access
valve (to be fitted by service personnel for self-contained type).
2) Open the low-side valve on the gauge manifold, and turn on the vacuum pump.
3) Allow the vacuum pump to pull down to a 760 mmHg vacuum. Evacuating period
depends on the pump capacity.
5) Disconnect the vacuum pump, and attach a refrigerant charging cylinder to accurately
weigh in the liquid charge. Remember to purge any air from the charging hose. See the
nameplate for the required refrigerant charge.
6) Open the low-side valve on the gauge manifold and the valve on the charging cylinder.
7) When no more refrigerant is drawn in, turn on the icemaker. When the required amount
of refrigerant has been charged, close the valve on the charging cylinder and turn off
the icemaker.
149
9) Disconnect the charging hose from the access valve. Always cap the access valve to
prevent a refrigerant leak.
10) Always thoroughly leak test all joints and valve caps.
11) Avoid charging large quantities of liquid into the low side in case of damage to the
compressor.
R452A/R404A models
1) Attach charging hoses of a gauge manifold to a vacuum pump, the low-side access
valve and the high-side access valve (to be fitted by service personnel).
2) Open the low-side and high-side valves on the gauge manifold, and turn on the vacuum
pump.
3) Allow the vacuum pump to pull down to a 760 mmHg vacuum. Evacuating period
depends on the pump capacity.
5) Disconnect the vacuum pump, and attach a refrigerant charging cylinder to accurately
weigh in the liquid charge. Remember to purge any air from the charging hose. See the
nameplate for the required refrigerant charge.
6) Open the high-side valve on the gauge manifold and the valve on the charging cylinder.
Note: Always charge in the liquid stage, as many refrigerants are blends and vapour
charging will affect the blend consistency.
7) When no more refrigerant is drawn in, turn on the icemaker. When the required amount
of refrigerant has been charged, close the valve on the charging cylinder and turn off
the icemaker.
9) Disconnect the charging hoses from the access valves. Always cap the access valves
to prevent a refrigerant leak.
10) Always thoroughly leak test all joints and valve caps.
11) Avoid charging large quantities of liquid into the low side in case of damage to the
compressor.
150
2. BRAZING
DANGER
4. In its liquid state, the refrigerant can cause frostbite because of the low temperature.
3. COMPRESSOR
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do
not replace the drier until after all other repair or replacement has been made.
3) Remove the terminal cover on the compressor, and disconnect the compressor wiring.
4) Recover the refrigerant and store it in a proper container, if required by an applicable law
(See “1. [b] REFRIGERANT RECOVERY”).
5) Remove the discharge, suction and access pipes from the compressor using brazing
equipment.
WARNING
When repairing a refrigerant system, be careful not to let the burner flame contact
any electrical wires or insulation.
7) Slide and remove the compressor. Unpack the new compressor package. Install the new
compressor.
151
10) Place the compressor in position, and secure it using the bolts and washers.
11) Remove plugs from the discharge, suction and access pipes.
12) Braze the access, suction and discharge pipes (Do not change this order) with nitrogen
gas flowing at the pressure of 0.2 - 0.3 bar.
14) Check for leaks using nitrogen gas (10 bar) and soap bubbles.
15) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge (See “1. [c] EVACUATION AND RECHARGE”).
16) Connect the terminals to the compressor, and replace the terminal cover in its correct
position.
4. DRIER
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do
not replace the drier until after all other repair or replacement has been made.
3) Recover the refrigerant and store it in a proper container, if required by an applicable law
(See “1. [b] REFRIGERANT RECOVERY”).
5) Install the new drier with the arrow on the drier in the direction of the refrigerant flow. Use
nitrogen gas at the pressure of 0.2 - 0.3 bar when brazing the tubings.
6) Check for leaks using nitrogen gas (10 bar) and soap bubbles.
7) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge (See “1. [c] EVACUATION AND RECHARGE”).
152
5. EXPANSION VALVE
IMPORTANT
Sometimes moisture in the refrigerant circuit exceeds the drier capacity and
freezes up at the expansion valve. Always install a new drier every time the sealed
refrigeration system is opened. Do not replace the drier until after all other repair or
replacement has been made.
3) Recover the refrigerant and store it in a proper container, if required by an applicable law
(See “1. [b] REFRIGERANT RECOVERY”).
5) Remove the expansion valve cover, and disconnect the expansion valve using brazing
equipment.
6) Braze the new expansion valve with nitrogen gas flowing at the pressure of 0.2 - 0.3 bar.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve from
overheating. Do not braze with the valve body exceeding 120°C.
8) Check for leaks using nitrogen gas (10 bar) and soap bubbles.
9) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge (See “1. [c] EVACUATION AND RECHARGE”).
10) Attach the bulb to the suction line. Be sure to secure the bulb using a wire or clamp and
replace the insulation.
153
6. WATER REGULATING VALVE - WATER-COOLED MODEL ONLY
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do
not replace the drier until after all other repair or replacement has been made.
10) Check for leaks using nitrogen gas (10 bar) and soap bubbles.
12) Evacuate the system, and charge it with refrigerant. See the nameplate for the required
refrigerant charge.
154
7. EVAPORATOR ASSEMBLY
See the exploded view under “III. 3. ICEMAKING MECHANISM”.
4) Remove the three thumbscrews, and take off the spout from the evaporator.
CUTTER
BELT HEATER
EXTRUDING HEAD
9) Remove the sealing bolts, and lift off the extruding head.
10) Check the bearing inside the extruding head. If it is worn out or scratched, replace the
bearing.
Note: Replacing the bearing needs a fitting tool. If it is not available, replace the whole
extruding head.
AUGER
11) Lift out the auger. Check the top and bottom areas in contact with the bearings. If the
surface is scratched or pitted, replace the auger. Check the blade edge of the auger. If
it is scratched or worn where it has contacted the evaporator, replace it.
EVAPORATOR
Note: Skip the following steps 12) through 18) when the evaporator does not need
replacement.
12) Recover the refrigerant and store it in a proper container, if required by an applicable
law.
155
IMPORTANT
Always install a new drier every time the sealed refrigeration system is opened. Do
not replace the drier until after all other repair or replacement has been made.
14) Disconnect the brazing connections of the expansion valve and the copper tube - low
side from the evaporator, using brazing equipment.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve from
overheating. Do not braze with the valve body exceeding 120°C.
15) Remove the two truss head machine screws and the strap securing the evaporator.
17) Remove the four socket head cap screws securing the evaporator with the housing.
19) The mechanical seal consists of two parts. One part rotates with the auger, the other is
static and is fitted into a top recess in the housing. If the contact surfaces of these two
parts become worn or scratched, the mechanical seal may leak water and should be
replaced.
20) Remove the O-ring on the top outer edge of the housing.
21) Remove the four bolts and lift the housing clear of the gear motor. Check the bearing
inside the housing. If it is worn or scratched, replace it using a fitting tool. Carefully
ease out the lower part of the mechanical seal before replacing the bearing.
Note: If a fitting tool is not available, replace the whole lower housing complete with
bearing.
GEAR MOTOR
23) Remove the three socket head cap screws securing the gear motor.
24) Assemble the removed parts in the reverse order of which they were removed.
156
WARNING
Be careful not to scratch the surface of the O-ring, or it may cause water leaks.
Handle the mechanical seal with care not to scratch nor to contaminate its contact
surface.
(a) Braze the new evaporator with nitrogen gas flowing at the pressure of 0.2 - 0.3 bar.
(b) Replace the drier.
(c) Check for leaks using nitrogen gas (10 bar) and soap bubbles.
(d) Evacuate the system, and charge it with refrigerant. See the nameplate for the
required refrigerant charge.
26) Refit the panels in their correct position.
157
8. CONTROL WATER VALVE
1) Disconnect the power source.
5) Remove the cover - reservoir Inlet from the control water valve.
6) Loosen the fitting nut on the control water valve Inlets, and remove the control water
valve. Do not lose the packings inside the fitting nut.
8) Assemble the removed parts in the reverse order of which they were removed.
4) Remove the clamp and disconnect the hose from the flush water valve.
Note: Water may still remain inside the evaporator. Be sure to drain the water into the
drain pan.
8) Connect the drain pipe to the new flush water valve, and place the valve in position.
9) Connect the hose to the flush water valve, and secure it with the clamp.
158
10) Pour water into the reservoir, and check for water leaks on the flush water valve.
14) Push the stop button, and make sure water is flushing.
IMPORTANT
A single type controller board is supplied as a service board. Some modifications and
adjustment will be required to fit the icemaker models. Do not repair any parts and
electronic devices on the controller board in the field. Replace the whole board with a
new service board.
[a] MODIFICATION
2) Modify the service board referring to the instruction sheet attached (Set the model
number according to “III. 5. [b] SETTING MODEL NUMBER”).
[b] REPLACEMENT
4) Disconnect the connectors and board support from the controller board.
6) Install the new controller board and reassemble the control box in the reverse order of
the removal procedure.
159