FCU TECHNICAL REPORT

SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC12G STWS-ECS-FCU-101 AND
102

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 24.80 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 17.10 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 13.74 °C
Leaving Wet Bulb Temp.** 11.99 °C
Unit Specification
Height: 251 mm Coil Medium Water Fin Length 1318 mm
Depth: 1513 mm Tube Material Copper Tube Diameter 7 mm
Width: 461 mm Fin Material Aluminium Tube Thickness 0.28 mm
Weight 30 kg No of Row 3 Fin Thickness 0.105 mm
Sound Press. Level 40 dBA Tube Height 10 No of Circuits 9
Sound Power dBA FPI 18 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 7.56 kW Total Capacity - kW
Air Flow 980 cfm Sensible capacity 6.22 kW Water Flow rate - L/s
TSP 81 Pa Water Flow rate 0.36 L/s Pressure Drop - kPa
ESP 33 Pa Pressure Drop 20.8 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 200 W Starting Current 1.62 A Fan Absorb power W
Motor size 146 W Motor Efficiency 38.9 % Fan Efficiency 30.1 %
Running Current 0.88 A Motor RPM 1050
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC14G STWS-ECS-FCU-06007
AND 06008

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 24.70 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 17.00 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 13.65 °C
Leaving Wet Bulb Temp.** 12.21 °C
Unit Specification
Height: 363 mm Coil Medium Water Fin Length 891 mm
Depth: 1115 mm Tube Material Copper Tube Diameter 9.52 mm
Width: 660 mm Fin Material Aluminium Tube Thickness 0.33 mm
Weight 34 kg No of Row 3 Fin Thickness 0.11 mm
Sound Press. Level 43 dBA Tube Height 12 No of Circuits 6
Sound Power dBA FPI 14 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 8.20 kW Total Capacity - kW
Air Flow 1130 cfm Sensible capacity 7.20 kW Water Flow rate - L/s
TSP 146 Pa Water Flow rate 0.39 L/s Pressure Drop - kPa
ESP 48 Pa Pressure Drop 15.1 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 307 W Starting Current 2.75 A Fan Absorb power W
Motor size 248 W Motor Efficiency 41.6 % Fan Efficiency 38.6 %
Running Current 1.34 A Motor RPM 875
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC06G STWS-ECS-FCU-06009
AND 06010

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 26.30 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 18.70 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 13.94 °C
Leaving Wet Bulb Temp.** 13.03 °C
Unit Specification
Height: 251 mm Coil Medium Water Fin Length 676 mm
Depth: 873 mm Tube Material Copper Tube Diameter 7 mm
Width: 461 mm Fin Material Aluminium Tube Thickness 0.28 mm
Weight 17.5 kg No of Row 3 Fin Thickness 0.105 mm
Sound Press. Level 38 dBA Tube Height 10 No of Circuits 5
Sound Power dBA FPI 18 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 4.60 kW Total Capacity - kW
Air Flow 500 cfm Sensible capacity 3.56 kW Water Flow rate - L/s
TSP 86 Pa Water Flow rate 0.22 L/s Pressure Drop - kPa
ESP 35 Pa Pressure Drop 26.4 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 106 W Starting Current 0.91 A Fan Absorb power W
Motor size 80 W Motor Efficiency 46.4 % Fan Efficiency 33.9 %
Running Current 0.47 A Motor RPM 1170
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC10G STWS-ECS-FCU-06013
AND 06014

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 25.00 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 17.30 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 13.81 °C
Leaving Wet Bulb Temp.** 12.18 °C
Unit Specification
Height: 251 mm Coil Medium Water Fin Length 1067 mm
Depth: 1262 mm Tube Material Copper Tube Diameter 7 mm
Width: 461 mm Fin Material Aluminium Tube Thickness 0.28 mm
Weight 26 kg No of Row 3 Fin Thickness 0.105 mm
Sound Press. Level 40 dBA Tube Height 10 No of Circuits 8
Sound Power dBA FPI 18 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 6.32 kW Total Capacity - kW
Air Flow 800 cfm Sensible capacity 5.19 kW Water Flow rate - L/s
TSP 82 Pa Water Flow rate 0.30 L/s Pressure Drop - kPa
ESP 33 Pa Pressure Drop 22.9 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 176 W Starting Current 2.09 A Fan Absorb power W
Motor size 140 W Motor Efficiency 43.5 % Fan Efficiency 38.6 %
Running Current 0.77 A Motor RPM 1190
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC08G STWS-ECS-FCU-06019

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 27.80 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 20.60 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 14.39 °C
Leaving Wet Bulb Temp.** 14.04 °C
Unit Specification
Height: 251 mm Coil Medium Water Fin Length 1067 mm
Depth: 1262 mm Tube Material Copper Tube Diameter 7 mm
Width: 461 mm Fin Material Aluminium Tube Thickness 0.28 mm
Weight 26 kg No of Row 3 Fin Thickness 0.105 mm
Sound Press. Level 37 dBA Tube Height 10 No of Circuits 7
Sound Power dBA FPI 18 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 7.43 kW Total Capacity - kW
Air Flow 650 cfm Sensible capacity 5.03 kW Water Flow rate - L/s
TSP 70 Pa Water Flow rate 0.36 L/s Pressure Drop - kPa
ESP 33 Pa Pressure Drop 42.2 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 143 W Starting Current 1.27 A Fan Absorb power W
Motor size 104 W Motor Efficiency 36.4 % Fan Efficiency 39.9 %
Running Current 0.63 A Motor RPM 1080
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC06G STWS-ECS-FCU-06021

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 25.80 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 18.20 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 13.86 °C
Leaving Wet Bulb Temp.** 12.78 °C
Unit Specification
Height: 251 mm Coil Medium Water Fin Length 676 mm
Depth: 873 mm Tube Material Copper Tube Diameter 7 mm
Width: 461 mm Fin Material Aluminium Tube Thickness 0.28 mm
Weight 17.5 kg No of Row 3 Fin Thickness 0.105 mm
Sound Press. Level 38 dBA Tube Height 10 No of Circuits 5
Sound Power dBA FPI 18 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 4.31 kW Total Capacity - kW
Air Flow 500 cfm Sensible capacity 3.44 kW Water Flow rate - L/s
TSP 86 Pa Water Flow rate 0.21 L/s Pressure Drop - kPa
ESP 35 Pa Pressure Drop 23.5 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 106 W Starting Current 0.91 A Fan Absorb power W
Motor size 80 W Motor Efficiency 46.4 % Fan Efficiency 33.9 %
Running Current 0.47 A Motor RPM 1170
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC06G STWS-ECS-FCU-06022

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 26.00 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 18.40 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 13.89 °C
Leaving Wet Bulb Temp.** 12.88 °C
Unit Specification
Height: 251 mm Coil Medium Water Fin Length 676 mm
Depth: 873 mm Tube Material Copper Tube Diameter 7 mm
Width: 461 mm Fin Material Aluminium Tube Thickness 0.28 mm
Weight 17.5 kg No of Row 3 Fin Thickness 0.105 mm
Sound Press. Level 38 dBA Tube Height 10 No of Circuits 5
Sound Power dBA FPI 18 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 4.42 kW Total Capacity - kW
Air Flow 500 cfm Sensible capacity 3.49 kW Water Flow rate - L/s
TSP 86 Pa Water Flow rate 0.21 L/s Pressure Drop - kPa
ESP 35 Pa Pressure Drop 24.6 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 106 W Starting Current 0.91 A Fan Absorb power W
Motor size 80 W Motor Efficiency 46.4 % Fan Efficiency 33.9 %
Running Current 0.47 A Motor RPM 1170
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC18G STWS-ECS-FCU-06023

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 25.00 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 18.60 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 13.45 °C
Leaving Wet Bulb Temp.** 13.08 °C
Unit Specification
Height: 363 mm Coil Medium Water Fin Length 1030 mm
Depth: 1253 mm Tube Material Copper Tube Diameter 9.52 mm
Width: 660 mm Fin Material Aluminium Tube Thickness 0.33 mm
Weight 38 kg No of Row 3 Fin Thickness 0.11 mm
Sound Press. Level 45 dBA Tube Height 12 No of Circuits 7
Sound Power dBA FPI 14 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 12.91 kW Total Capacity - kW
Air Flow 1450 cfm Sensible capacity 9.63 kW Water Flow rate - L/s
TSP 162 Pa Water Flow rate 0.62 L/s Pressure Drop - kPa
ESP 48 Pa Pressure Drop 22.9 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 459 W Starting Current 4.38 A Fan Absorb power W
Motor size 418 W Motor Efficiency 44.9 % Fan Efficiency 34.5 %
Running Current 2 A Motor RPM 1000
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.
FCU TECHNICAL REPORT
SOFTWARE VERSION: 3.7.6.0 Report Date: 4/13/2018

Project Name: Customer:


Address : Selection by:

Unit Naming:
Model: FWC08G FWC08G [18]

Selection Input
Internal Tube Fluid Water Altitude 0 m
Glycol 0 %
Cooling Heating
Indoor Dry Bulb Temp. 30.20 °C Indoor Dry Bulb Temp. - °C
Indoor Wet Bulb Temp. 23.00 °C Water Inlet Temp. - °C
Water Inlet Temp. 7.00 °C Water Temp. Drop - °C
Water Temp. Rise 5.00 °C Leaving Dry Bulb Temp.** - °C
Leaving Dry Bulb Temp.** 14.78 °C
Leaving Wet Bulb Temp.** 14.78 °C
Unit Specification
Height: 251 mm Coil Medium Water Fin Length 1067 mm
Depth: 1262 mm Tube Material Copper Tube Diameter 7 mm
Width: 461 mm Fin Material Aluminium Tube Thickness 0.28 mm
Weight 26 kg No of Row 3 Fin Thickness 0.105 mm
Sound Press. Level 37 dBA Tube Height 10 No of Circuits 7
Sound Power dBA FPI 18 Fin Pattern Slit
Level
Performance Data
Air Flow Data Cooling Capacity Heating Capacity
Selected Fan Speed MED Total Capacity 9.72 kW Total Capacity - kW
Air Flow 650 cfm Sensible capacity 5.78 kW Water Flow rate - L/s
TSP 70 Pa Water Flow rate 0.46 L/s Pressure Drop - kPa
ESP 33 Pa Pressure Drop 69.6 kPa
Face Velocity 0 m/s
Fan And Motor Data*
Motor Data Fan Data
Input Power 143 W Starting Current 1.27 A Fan Absorb power W
Motor size 104 W Motor Efficiency 36.4 % Fan Efficiency 39.9 %
Running Current 0.63 A Motor RPM 1080
*Base on standard rating condition.
** For reference only.
Disclaimer: The results are based on simulation and may not be accurate or reflect the actual condition. While all reasonable attempts have been
made to ensure accuracy, currency and reliability of the content, all information is provided "as is". There is no guarantee as to the completeness,
accuracy, timeliness or the results obtained from the use of this information. Daikin Malaysia Sdn. Bhd. can not be held responsible for the
correctness, completeness or quality of the information provided by this software. Therefore, liability claims regarding any damages caused by
the use of any information provided, including information which is incomplete or incorrect, will be discarded.

You might also like