Iclean-Kitchen Rev-2
A
Hyderabad-Inida. DATE C
I
PROJECT: Iclean Mainplant Kitchen Dining Area DOCUMENT NO. 06.06.2020
T
SUMMARY OF HEAT LOAD CALCULATION FOR HOSPITAL - SHEET Y
Calculated Load Reheat Humidifier
S. F/C height Full Height Fresh air Equipment Lighting load A
Area (Sq.m) Occupancy Cooling Load (TR) AIR QTY (CFM) (KW) LBH/HR
No. (m) (m) (CFM) Load (W) (W) Remarks N
Summer Monsoon Winter Summer Monsoon Winter Monsoon Winter
D

Q
Iclean Mainplant Kitchen U
a) Dining Area 1297.89 3.0 0.00 44006 175 120.00 1297.89 35.16 29791 A
N
Add 5% Margin = 1.76 0.00 0.00 1490 0 0 0.00 0.00 T
I
AHU Total = 36.92 0.00 0.00 31281 0 0 0.00 0.00 T
Y
Iclean - Kitchen Rev-2
Hyderabad-India DATE
PROJECT: Iclean Mainplant Kitchen Dining Area 06.06.2020
Document No.: - SHEET
OVERALL HEAT TRANSFER CO-EFFICIENT CALCULATIONS
U - Factor Calculation for walls - Exposed
S.No Resistance Material Resistance value
1 100 mm puff panel 19.01

Total 19.01
Inverse of resistance is U = 1/R 0.05

U Factor for calculation for walls - Partition walls


S.No Resistance Material Resistance Value
1 0.00
2 0.00
3 0.00
TOTAL 0.00
Inverse of resistance is U = 1/R #DIV/0!

U - Factor calculation for Roof - Insulated


S.No Resistance Material Resistance value
1 Asbestos cement shingles 0.21
2 False Celing 4.35
3 Air gap of 3/4" to 4 1.00
4
Total 5.56
Inverse of resistance ( 1 /R ) = U 0.18

" U " factor for calculation for floor


S.No Resistance material Resistance value
1 Floor tiles 0.20
2 plaster 0.12
3 plaster 0.12
4
5
TOTAL 0.44
Inverse of resistance is U 2.27

" U " factor for calculation for ceiling


S.No Resistance material Resistance value
1 False Ceiling 4.35
2 Air gap of 3/4" to 4 1.00
3 0.00
TOTAL 5.35
Inverse of resistance is U 0.19
Note: Above values are taken from the ISHRAE hand book 1997 -table-8 and inputs from clients
Iclean-Kitchen Rev-2
Hyderabad-Inida. DATE
PROJECT: Iclean Mainplant Kitchen Dining Area 06.06.2020
Document No.: - SHEET
COOLING LOAD TEMPERATURE DIFFERENCE (CLTD) CALCULATION
OUTSIDE AND INSIDE CONDITION
CONDITIONS DBT-0F WBT-0F %RH GR/LB REMARK
OUTSIDE
a) SUMMER 105.0 71.1 18.1 60.23
b) MONSOON 81.9 77.9 73.8 134.56
c) WINTER 79.3 51.3 8.1 11.98
INSIDE 82.0 69.9 55.0 90.45 VALUES ARE TAKEN FROM ASHRAE-2017
HANDBOOK
DIFFERENCE
a) SUMMER 23.0 -30.22
b) MONSOON -0.1 44.11
c) WINTER -2.7 -78.47
OTHER NECESSARY VALUES FOR BARMER TAKEN FROM ISHRAE-1997 HAND BOOK
DAILY RANGE 25 0
F
LATITUTE 28.35 Deg N (CONSIDERED AS 20 DegN)
SOLAR HEAT GAIN THROUGH GLASS
Solar Heat Gain Thru Ordinary
Glass (Sun Gain)
EXPOSURE Btu/(hr) (sqft sash area) REMARK

summer Monsoon Winter


Glass North 33 11 7
Glass Northeast 12 11 7
Glass East 12 11 7
Glass Southeast 12 11 7 Values are taken from Ishrae -1997 Hand Book
Glass South 12 11 74
(Page No.1.9, Table-7) for 20 DEG North Latitute,
4PM of Suntime on June-21, August-24 &
Glass Southwest 73 113 139 December-22.
Glass West 160 165 118
Glass Northwest 144 118 18
Sky Light 121 107 36
Solar & Transmission Heat Gain Through Wall and Roof (Equivalent Temperature Difference)
EQVT TEMP. Correction Equi. Temp. (OF) Actual Eqvt. Temp. Dif (OF)
EXPOSURE REMARK
DIFF. (OF) Summer Monsoon Winter Summer Monsoon Winter
Wall Northeast 14 6 -17 -15 20 -3 -1
Wall East 14 6 -17 -15 20 -3 -1
Wall Southeast 16 6 -17 -15 22 -1 1
Wall South 26 6 -17 -15 32 9 11
Wall Southwest 40 6 -17 -15 46 23 25
Wall West 40 6 -17 -15 46 23 25 #1
Wall Northwest 24 6 -17 -15 30 7 9
Wall North 14 6 -17 -15 20 -3 -1
Roof Sun Exposed 41 6 -17 -15 47 24 26
Roof Shaded 14 6 -17 -15 20 -3 -1
#1 Values are taken from Ishrae-1997 Hand Book (Page No.1.14 & 1.15, Table-9 & 10) for 4PM of Suntime and the weight
of wall 20LB/SQFT.
SELECTION OF CORRECTION EQUIVALENT TEMPERATURE (0F)

CORRECTION EQUIVALENT
OUTDOOR DESIGN - ROOM TEMP 0F
DAILY RANGE 0F TEMPERATURE (0F) REMARK

Summer Monsoon Winter Summer Monsoon Winter


23.0 -0.1 -2.7 25 6 -17 -15 #2
#2 Value is arrived from Ishrae -1997 Hand Book (Page No.1.15, Table -11)
Iclean-Kitchen Hyderabad-Inida. DOCUMENT NO. Rev-2
PROJECT: Iclean Mainplant Kitchen Dining Area - DATE
ROOM Dining Area Prepared Approved 06.06.2020
ROOM SIZE -IN MTR L 51.3 W 25.3 H 3 SNH PSK SHEET
ROOM SIZE 1297.89 m2 13970 ft2 Height = 10.0 ft 264033 ft2
Estimated for SUMMER MONSOON WINTER
CONDITIONS DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB DB-F WB-F %RH GR/LB
OUTSIDE 105.0 71.1 18.1 60.2 81.9 77.9 73.8 134.56 79.3 51.3 8.1 12.0
INSIDE 82.0 69.9 55.0 90.5 82.0 69.9 55.0 90.45 68.0 62.1 71.8 73.7
DIFFERENCE 23.0 -30.22 -0.1 44.11 11.3 -61.72
OCCUPANCY 175 ft2/person 79.8 LIGHTING 1 Watts/m2
VENTILATION 1508.8 CFM BASED ON: People AIR CHANGES SELECTED
175 PEOPLE 15.0 CFM/PER. 10 AC/H 2625 44006 44006
Bypass Factor 0.12 Contact Factor 0.88
SUN GAIN/ TEMP.DIFF. BTU/HR
ITEM AREA ft2 Factor
Summer Monsoon Winter Summer Monsoon Winter

ROOM HEAT LOAD


SOLAR GAIN -GLASS
Glass-N 150 ft2 33 11 7 0.56 2772 924 588
Glass-NE 0 ft2 12 11 7 0.56 0 0 0
Glass-E 0 ft2 12 11 7 0.56 0 0 0
Glass-SE 0 ft2 12 11 7 0.56 0 0 0
Glass-S 150 ft2 12 11 74 0.56 1008 924 6216
Glass-SW 0 ft2 73 113 139 0.56 0 0 0
Glass-W 0 ft2 160 165 118 0.56 0 0 0
Glass-NW 0 ft2 144 118 18 0.56 0 0 0
Sky Light 0 ft2 121 107 36 0.56 0 0 0
SOLAR & TRANS. GAIN - WALLS & ROOF
Wall-NE 0 ft2 20 -3 -1 0.05 0 0 0
Wall-E 0 ft2 20 -3 -1 0.05 0 0 0
Wall-SE 0 ft2 22 -1 1 0.05 0 0 0
Wall-S 1646 ft2 32 9 11 0.05 2634 741 905
Wall-SW 0 ft2 46 23 25 0.05 0 0 0
WALL-W 807 ft2 46 23 25 0.05 1856 928 1009
WALL-NW 0 ft2 30 7 9 0.05 0 0 0
WALL-N 1646 ft2 20 -3 -1 0.05 1646 -247 -82
Roof-Sun 13719 ft2 47 24 26 0.18 116063 59266 64205
Roof-Shaded 0 ft2 20 -3 -1 0.18 0 0 0
TRANS. GAIN-EXCEPT WALLS & ROOF
ALL GLASS 300 ft2 23.0 -0.1 11.3 0.56 3864 -17 1898
PARTITION-GLASS 0 ft2 23.0 -0.1 11.3 0.56 0 0 0
PARTITION-WALL 0 ft 2
26.0 -5.1 6.3 0.00 0 0 0
CEILING 0 ft2 18.0 -5.1 6.3 0.19 0 0 0
FLOOR 0 ft2 18.0 -5.1 6.3 2.27 0 0 0
INFILTRATION & OUTSIDE AIR
INFILTRATION 0 CFM 1.08 0 0 0
OUTSIDE AIR 44006 CFM 23.0 -0.10 11.30 0.12 1.08 131173 -570 64446
INTERNAL HEAT
PEOPLE 175 Nos 270 BTU/P 47250 47250 47250
LIGHTS 1298 Watt 3.4 BTU/Watt 1.0 4413 4413 4413
APPLIANCES 120 Watt 3.4 BTU/Watt 408 408 408
ROOM SENSIBLE HEAT SUB-TOTAL 313087 114020 191256
ADD DUCT HEAT GAIN 1% 3131 1140 1913
ROOM SENSIBLE HEAT SUB-TOTAL 316218 115160 193169
ADD SAFETY FACTOR 5% 15811 5758 9658
EFFECTIVE ROOM SENSIBLE HEAT TOTAL 332029 120918 202827 27.67

ROOM LATENT HEAT Summer Monsoon Winter


INFILTRATION 0 CFM 0 0.68 0 0 0
OUTSIDE AIR 44006 CFM -30.22 44.1 -61.7 0.12 0.68 -108517 158394 -221630
PEOPLE 175 Nos 205 BTU/P 35875 35875 35875
APPLIANCES 0 3.4 BTU/Watt 0 0 0
ROOM LATENT HEAT SUB-TOTAL -72642 194269 -185755

ADD SAFETY FACTOR 5% -3632 9713 -9288

EFFECTIVE ROOM LATENT HEAT -76274 203982 -195043

EFFECTIVE ROOM TOTAL HEAT ( SENSIBLE + LATENT) 255755 324900 7784

OUTSIDE AIR Summer Monsoon Winter


SENSIBLE 44006 CFM 23.00 -0.10 11.30 0.88 1.08 961936 -4182 472603

LATENT 44006 CFM -30.22 44.11 -61.72 0.88 0.68 -795789 1161557 -1625285

GRAND TOTAL HEAT 421902 1482275 -1144898


CAPACITY TR 35.16 123.52 -95.41
SUMMER MONSOON WINTER
TONNAGE 35.16 TR TONNAGE 123.52 TR TONNAGE -95.41 TR
AIR QTY 29791 CFM AIR QTY 27288 CFM AIR QTY -21077 CFM