TECHNICAL DETAILS
General
Type Designation
Governing Standard
Technical Data
System Parameters
Rated Voltage
Service Voltage
Frequency
No. of Poles
Ambient Temperature Range
Operating Data at rated operating
Voltage & rated pressure
Type of Operating Mechanism
Mechanism is mechanically gang
operated
Operating Data
Making
Breaking,
Opening Time
Arcing Time
‘Switching Data
Rated normal current
Rated short circuit breaking current
Rated short time current
Rated short circuit making current
First pole to clear factor
‘Out-of-phase breaking current
Rated line charging breaking current
Rated cable charging breaking current
Rated operating sequence
Basic Insulation Level
mSec.
mSec.
mSec,
Sec,
3AP1 FG
IEC 62271-4100
145 KV
132 kV
50
Three
-30 to +50
Spring Energy Stored
Yes
55 H-8
60
30 +4
25
3150
40
40, (sec)
100
1.5
10
50
160 -
O-0.3sec ~ CO - 3min-CO
Customer: BiharState Power Transmission Corporation Limited.
Project
ay: Date: | Description :-145kV,40kA,3150A,SF6 CB | Sh No,
Sales Ref: Prep
Work := 1
Se oe | J Office Details :- TECHNICAL DETAILS
‘OriginalReplacement for! No.of;
Sh
Replaced by :- fFaa Rated power frequency withstand
voltage (Amin, 50 Hz)
<1 Phase to earth kV. 275
2 Across the open breaker KV 275
3 Between phases kV 275
42 Rated lighting Impulse withsland voltage
(1.250 micro sec.)
A Toearth kVp 650
2 Aeross the open breaker kVp 650
3 Between phases kVp 850
43 Creepage distance
1 Toearh mm — 9626
2 Across the open breaker mm 3625
3 Insulator type . Combination shed
50 Construction
BA Clearance
i Toearth Z mm 1250
2 Aoross the open breaker mm 1200
3 Phase to phase mm 1360
“4 Pole to pole center distance mm 1700
5.2 Arc quenching Medium
4 Nominal pressure SF6 (@20°C) bar rel.
2 Signal ioss of SF6 (@20°C) bar 5.2 rel.
3 General lockout (@20°C) (Tripping) bar 5.0rel.
A Quantity of SF6 gas required per kg 8
breaker
‘8 Qtyofgas being supplied per breaker, kg 1.8
pre filed in the poles.
6 _Inaddition to pre filled gas, gly of gas kg 8
being sent to site in cylinder.
63 Installation Outdoor
54 ‘Approx. weight of breaker with support =—skg_-—«‘1750 approx
structure
60 Structures, Base Frame
64 Material Mild Stee!
62 Surface Treatment Hot Dip Galavanised
70 Control Cubicle
Customer: BiharState Power Transmission Corporation Limited.
Project
ay: __[ Baie: | Description :-145kV,40kA,3150A,SF6 CB.| Sh No.
| Sales Ref. Prep: q :
Ckd = Work :-
i. ce New” [Office _| Details :- TECHNICAL DETAILS
OriginalReplacement ford 2 No.of
Sh
Replaced by =4
2
3
4
6
6
z
72
1
2
7.3
A
2
3
4
7h
Constraction
Material of enclosure CR Sheet Stee!
Thickness of sheet steet mm 25
Painting for control cubicle Epoxy / Polyester paint
External shade 631 as per ISS
Degree of protection of enclosure IP 55
Padlocking facility for cubicle Provided
Giass window to see spring status Provided on control cublole
Wiring
Control wiring
4 Size. 2.5 sq. mm flexible copper conductor
:2 insulation Grey ~ DC, Black - AC 1100V Grade
Earth Wiring
A Size 2.5 sq. mm flexible cooper conductor
2 Insulation Yellow/Green 1100V Grade
Contol Terminals
Type Stud/Pin Type
Make Connectwell / Elmex / Wago or equivalent
Size mat 4
Spare unwired terminat % 10
Aurxiary Supply
Circuit Rated Souree | Range
Voltage
‘Spring Charging Motor 240V ne Extemal - [65 110%
Closing Cot 220V DC External [85 — 720%
Trp Col= 72 220v DC External [70> 120%
Space Heater / Socket 7 BaOV AG extemal |=
(ilumination 2
‘Terminat Connectors: - Single ACSR Zebra. nos per circult breaker.
i . —}
a
Customer: BiharState Power Transmission Corporation Limited.
Project
ay: Date: Description :-145KV,40KA,5150A,SF6 CB] Sh No,
Sales Ref: Prep:
Ckd Work :=
fork A
a cep [Office - TECHNICAL DETAILS
Original/Replacement for/ 7 No.of
Sh
Replaced by » - 3