1 - Steam Turbine Control Basics
1 - Steam Turbine Control Basics
December 2018
(350psi/24bar)
HP Process (165psi/12bar)
IP Process (35psi/2.5bar)
LP Process
Condenser Header
ACTUATOR
PLANT BOILER
ACTUATOR
T&T PT
PT
LOAD:
PUMP
COMPRESSOR
GENERATOR
ETC.
LET DOWN
STATION
PLANT BOILER PT
TO PLANT
STEAM LOADS
ACTUATOR
T&T PT
PT
LOAD:
PUMP
COMPRESSOR
GENERATOR
ETC.
T&T
PLANT BOILER
ACTUATOR PT
LET DOWN
STATION
TO PLANT
STEAM LOADS
ACTUATOR
ACTUATOR
T&T PT
PT
LOAD:
PUMP
COMPRESSOR
GENERATOR
ETC.
LET DOWN
STATION
PT
PLANT BOILER
TO PLANT
STEAM LOADS
LET DOWN PT
STATION
TO PLANT
STEAM LOADS
ACTUATOR
ACTUATOR
ACTUATOR
PT
T&T
PT
LOAD:
PUMP
COMPRESSOR
GENERATOR
ETC.
LET DOWN
STATION
PT
PT
PLANT BOILER
PT
TO PLANT
STEAM LOADS
TO PLANT
STEAM LOADS
TO Condenser
ACTUATOR
ACTUATOR
T&T
PT
LET DOWN
STATION
PT
PLANT BOILER
TO PLANT
STEAM LOADS
Nozzle
Blade
Single-Stage
Multi-Stage
8
6 4 2 1 3 5
7 Staggered lift
Lifting Bar
Poppet Valve
Constant Load
DESIRED SPEED
ACTUAL SPEED
Increased Load
Decreased Load
Apposing
ACTUATOR
Torques on Shaft
PT
LOAD:
PUMP
COMPRESSOR
GENERATOR
ETC.
• Shaft Load
As the load increases, the speed will be reduced
• Inlet steam Conditions
Changes in the inlet pressure or temperature will change the
available energy in the steam
• Exhaust steam conditions
Changes in the backpressure or condenser vacuum will change
the available energy in the steam
• Extraction flow
Changes in the extraction flow and pressure will cause changes in
the speed
Control
Of The
Actual Speed Energy
or Load
Desired Speed or
Load Reference
Force Balance
F(a) = F(d)
Actual Desired
Speed Speed
Force Force
F(a) F(d)
1000 lb 1000 lb
Decrease Increase
Fuel Fuel
PI Actuator
Buffer Springs
& Needle Valves
Gen
Turbine
Turbine
Speed
PID Actuator
Steam
Turbine Gen
Speed
Frequency
to
Speed Converter Magnetic
Pickup
AC Sine Wave
R Digital
Speed Turbine Control
L Setpoint
3000 rpm
0 40% 40%
PID Actuator
3000 rpm
Steam
Turbine Gen
Speed
Frequency
to
Speed Converter Magnetic
Pickup
AC Sine Wave
PID Tutorial
PID Basics
• PID stands for Proportional, Integral, and Derivative
R Speed • A PID amplifier is used to calculate an appropriate
L Setpoint response to the output based on changes to the input
Error Signal
X
P Gain
D Gain
(Rate of Change)
PID Tutorial
PID Tutorial
Integral Gain
Adjustment
Proportional Gain
Adjustment
Derivative Gain
Adjustment
TIME
Industrial Turbomachinery Systems
38
PID Actuator
Effects Loop Effects Loop
Gain Gain
Steam
Turbine Gen
Speed Effects Loop
Gain
Frequency
to
Digital Converter Magnetic
Pickup
AC Sine Wave
Industrial Turbomachinery Systems
41
Linkage Gain
Steam Valve
Steam
Valve
Steam Valve
Actuator
Demand
Steam Valve
Linkage Travel
Allow some over-travel to ensure steam valve
mechanical stops are reached.
0 – 100% Valve Demand must equal 0 – 100% Valve Flow
8
7 Staggered lift
6 4 2 1 3 5
Lifting Bar
Poppet Valve
Valve Rack
Poppet Valve
Steam Chest
Flow Curves
Flow
PID Actuator
Effects Loop Effects Loop
Gain Gain
Steam
Turbine Gen
Speed Effects Loop
Gain
Frequency
to
Speed Converter Magnetic
Pickup
AC Sine Wave
Industrial Turbomachinery Systems
47
ACTUATOR
ACTUATOR
T&T PT
PT
LOAD:
PUMP
COMPRESSOR
GENERATOR
ETC.
LET DOWN
STATION
PT
PLANT BOILER
TO PLANT
STEAM LOADS
LET DOWN PT
STATION
TO PLANT
STEAM LOADS
Extraction Increases
Inlet Valve Opens
Extraction Valve Closes
V1 = K1 * SPout + K2 * EXTout + K3
V2 = K4 * SPout + K5 * EXTout + K6
DV1
K1 =
D HP EXT CONSTANT
D V1
K2 =
D EXT HP CONSTANT
D V2
K4 =
D HP V1 CONSTANT
D V2
K5 =
D EXT HP CONSTANT
Industrial Turbomachinery Systems
53
HSS
N
Speed N 505E
Signals
N LSS Functional
Input AI
Raise Diagram
Lower -
Setpoint +
- PID
Remote AI Remote AI
-
Raise Setpoint +
- PID Speed
Lower E/D
Cascade
Load
AI LSS
Signal
Input AI
AO V1
Raise Limiter
Lower -
Setpoint +
- PID
Remote AI
Auxiliary E/D
Ratio/
Limiter
Input AI HSS
Ext/Adm
Raise
Lower Setpoint +
-
PID
AO V2
-
Limiter
Remote AI
E/D
Raise
Lower Manual
Setpoint
Remote AI
Raise
Lower -
Setpoint +
-
PID
Remote AI
Aux 1
Input AI E/D
Raise
Lower -
Setpoint +
-
PID
Remote AI
Aux 2 HSS
Ratio/
E/D
Limiter AO V2
Limiter
Input AI
Raise P-1
Lower -
Setpoint +
-
PID
Remote AI
Raise
Manual E/D
Lower
Setpoint
Remote AI
HSS
Input AI
Raise P-2 AO V3
Lower - Limiter
Setpoint +
-
PID
AI
Raise
Manual E/D
Lower
Setpoint
AI
Questions????