Safety System Logic Solvers

ProTech-GII, TPS, & SX


and MicroNet Safety Module

June 2014

CONTROLLING the power of ENERGY

This presentation is intended only for the individual or entity to which it is addressed and may contain information that is the Confidential and/or Proprietary Information of Woodward
Governor Company, the disclosure of which may be in violation of applicable law. If you are not the intended recipient, or an employee or agent responsible for delivery to the intended
TM
recipient, you are hereby notified that any dissemination, distribution, or copying of this message is strictly prohibited and you are requested to notify us immediately by telephone.
ProTech Product Line Applications

Applications
• Turbine Overspeed Device
• Turbine Shutdown Systems
• Engine Shutdown Systems
• VFD (Motor) Shutdown Systems
• High Pressure Vessel Safety Systems
• High Level Container Safety Systems

(2)
PROPRIETARY INFORMATION
API-611 5th Edition Requirements

7.4.2.3 Overspeed Shutdown System

(3)
PROPRIETARY INFORMATION
API-612 7th Edition Requirements

API STANDARD 612 Petroleum, Petrochemical and Natural


SEVENTH EDITION, AUGUST 2014 Gas Industries—Steam Turbines—
Special-purpose Applications

(4)
PROPRIETARY INFORMATION
API-670 5th Edition Requirements

API STANDARD 670


MACHINERY PROTECTION SYSTEMS
SEVENTH EDITION, NOV. 2014

(5)
PROPRIETARY INFORMATION
ProTech Product Line
Overview

(6)
PROPRIETARY INFORMATION
Old ProTech203 Application

(7)
PROPRIETARY INFORMATION
Product Feature Matrix
MicroNet
Feature / Function ProTech203 ProTech-GII ProTech-SX ProTechTPS Safety
Module
Front Panel User Interface X X X X X

Architecture 2-O-O-3 2-O-O-3 1-O-O-1 2-O-O-3 2-O-O-3

IEC 61508-SIL Rating SIL - 3 SIL - 2 SIL - 3 SIL - 3

Accepts MPU, Proximity Probes , Eddy Current MPU MPU/PRX/EDY MPU/PRX/EDY MPU/PRX/EDY MPU/PRX/EDY

Response Time (milliseconds) 35 10 10 10 10

Overspeed Trip X X X X X

Acceleration Trip X X X X

Security KEY Passwords Passwords Passwords Passwords

Pre-Start MPU Detection Circuit X X X X

Configurable via Front Panel or Service Tool FP FP or ST FP or ST FP or ST FP or ST

Serial Modbus Interface X X X X

Internal Frequency Generator – Speed Tests X X X X X

Analog Output (Speed Meter Driver) X X X X

(8)
PROPRIETARY INFORMATION
Product Feature Matrix (cont.)
MicroNet
Feature / Function ProTech203 ProTech-GII ProTech-SX ProTechTPS Safety
Module
Emergency Trip Relays – 2-out-of-3 Voted Models 1 or 2 2 2 2 2

Emergency Trip Relays – Independent Voted Models 1 2 2 2 2


Number of Speed Inputs 3 Total 3 Total 2 Total 3 Total 3 Total

Configurable Analog or Discrete Inputs 7 30 Total 30 Total

Configurable Relay Outputs 3 9 Total 9 Total

Periodic Test Routines X X X

Programmable Logic Blocks X X X

Trip and Alarm Logs X X X X

Overspeed Trip and Test Logs X X X X

Trip Cycle Time Logs X X X

Programmable Event Logs X X X

Programmable Test Routines X X X

24 Hour Time Sync (10 millisecond resolution) X X X

IRIG-B Time Sync (1 millisecond resolution) X

Sequence of Events Logging (1 millisecond) X


(9)
PROPRIETARY INFORMATION
ProTech203 versus - GII & TPS

Feature / Function ProTech203 ProTech–GII and TPS


Front-Panel User Interface 2-Line LCD Display 4.2- Color Graphics Display
Mounting Options Bulkhead Bulkhead or Panel Mount
Approx Package Size (Bulkhead) 310 x 445 x 105 mm 330 x 445 x 159 mm
12.24 x 17.5 x 4.13 inches 13 x 17.5 x 6.25 inches
Safety Certifications IEC 61508 SIL-3 Certifiable
(must be applied with IEC 61508 SIL-3 Certified
redundant overspeed device)
Power Supply Architecture 1 Power Supply Input / Module 2 Redundant PS Inputs

Test Functions Manual Speed Test (per module) Temporary OS Setpoint Change Test
Manual OS Test (per module)
Auto OS Test (per module)
Auto Sequenced OS Test (A-B-C)
Periodic Auto Sequenced OS Test (A-B-C)
Auto Custom OS Test (per module – TPS)

(10)
PROPRIETARY INFORMATION
ProTech203 versus - GII & TPS (cont.)

Feature / Function ProTech203 ProTech–GII and TPS


Logging Functions Peak Speed Peak Speed
(Saved in memory even without Peak Acceleration
power) Last 20 OS Events and OS Test Events
Last 50 Trip / Alarm and Test Events
Logged Data No Real Time Clock Real Time Clock Used
(no time or date logged) Logged Information: Time, Date, Speed,
Acceleration, Test Mode

(11)
PROPRIETARY INFORMATION
ProTech Package Improvements

Bulkhead or Panel Mount Packages Available

Ruggedized Enclosure
(Flush Mount or Bulkhead
mount models available)

Improved Front
Panel Display

Improved Keypad for


Monitoring,
Configuration, &
Service

Added Log Screens


& Buttons

(12)
PROPRIETARY INFORMATION
ProTech Package Improvements
Bulkhead Mount Packages Modular design for
easy on-line repair
IP56 (NEMA4x)
based enclosure

Ruggedized
package design
Removable terminal
blocks for ease of Field wiring access
Rated for IP56
wiring & replacement through gland plates locations

(13)
PROPRIETARY INFORMATION
ProTech Package Improvements

Bulkhead Mount Packages

Individual Kernel
assembly

Input & Communications Trip Relay Output


Wiring Terminal blocks terminal blocks

(14)
PROPRIETARY INFORMATION
ProTech Package Improvements
Front panel mounts
Panel Mount Packages flush to cabinet or
enclosure

Removable back
cover for easy access

Easy wiring &


communication Rated for IP56
port access based enclosures
Includes mounting
screws & IP56 rated
Project Gate Review S124 Page 15
gasket
Example ProTech Screens

(16)
PROPRIETARY INFORMATION
Example ProTech Screens

(17)
PROPRIETARY INFORMATION
Programming & Configuration Tool (PCT)

(18)
PROPRIETARY INFORMATION
Default ProTech Program

(19)
PROPRIETARY INFORMATION
Programming & Configuration Tool (PCT)

(20)
PROPRIETARY INFORMATION
Programming with GAP (Optional)
Optionally programmers can use Woodward’s Graphical Application
Programming Environment to program the ProTechTPS, MSM or SX models..

(21)
PROPRIETARY INFORMATION
Programming with GAP (Optional)
Optionally programmers can use Woodward’s Graphical Application
Programming Environment to program the ProTechTPS, MSM or SX models..

(22)
PROPRIETARY INFORMATION
Programming with GAP (Optional)
Optionally programmers can use Woodward’s Graphical Application
Programming Environment to program the ProTechTPS, MSM or SX models..

(23)
PROPRIETARY INFORMATION
Example ProTech Screens

Example Program Logic Monitoring Screens

(24)
PROPRIETARY INFORMATION
ProTech-GII Applications

(25)
PROPRIETARY INFORMATION
ProTech-GII (Generation Two)
• Same basic functionality as ProTech203
 API611, API612 & API670 compliant
• TMR operation (2 out of 3 voting)
• IEC61508 SIL-3 certification
• Accepts redundant power inputs
 18-32Vdc power source
 90-240Vac (100-150Vdc) power source
• Integral trip solenoid test logic
 Automated periodic test routines
• MPU Detection (Circuit Continuity)
• Proximity Probe input (source included)
• Serial Modbus Communications
 Ethernet gateway optional
• High Acceleration Detection
 Overspeed anticipation logic
• Faster response time --10ms (Independent Relay output models)
(26)
• Alarm, Trip & Overspeed Logs (last 50 events)
PROPRIETARY INFORMATION
Single ProTech-GII Module

(27)
PROPRIETARY INFORMATION
ProTech-GII 2-o-o-3 Voted Application

(28)
PROPRIETARY INFORMATION
ProTech-GII Ind. Voted Application

(29)
PROPRIETARY INFORMATION
ProTechTPS Applications

(30)
PROPRIETARY INFORMATION
ProTechTPS (Total Protection System)

• Same basic functionality as ProTech-GII


 API611, API612 & API670 compliant
• TMR operation (2 out of 3 voting)
• IEC61508 SIL-3 certification
• Accepts redundant power inputs
 18-32Vdc power source
 90-240Vac (100-150Vdc) power source
• Integral trip solenoid test logic (TMR Only)
• Trip Valve response monitor with alarm
• MPU Detection (Circuit Continuity)
• Proximity Probe input (source included)
• Serial Modbus Communications
 Ethernet gateway optional
• High Acceleration or Deceleration Detection
 Overspeed anticipation logic
• Faster response time --10ms (Independent Voted output models)
• 10 Programmable Analog or Discrete inputs
 10 inputs per module (30 total)
 Programmable And, Or, Not Logic
 First Out Indication - Real time clock
 1 Millisecond Trip Date & Alarm log
(31)
PROPRIETARY INFORMATION
Single ProTechTPS Module

(32)
PROPRIETARY INFORMATION
ProTechTPS 2-o-o-3 Voted Application

(33)
PROPRIETARY INFORMATION
ProTechTPS Independent Voted Application

(34)
PROPRIETARY INFORMATION
ProTechTPS Gas Turbine Application
Typical ProTechTPS Process Application

(36)
PROPRIETARY INFORMATION
MicroNet Safety Module
Applications

(37)
PROPRIETARY INFORMATION
MicroNet Safety Module

• Same functionality as ProTechTPS


 Programmable
• Same certifications as ProTechTPS
 IEC61508 SIL-3 certified
• Added functions
 1 Millisecond Time Synchronization (via IRIG_B Input)
 Sequence of Events Recorder Function

(38)
PROPRIETARY INFORMATION
SIL-3 MicroNet Application

(39)
PROPRIETARY INFORMATION
SIL-3 MicroNet Application

(40)
PROPRIETARY INFORMATION
ProTech-SX Applications

(41)
PROPRIETARY INFORMATION
ProTech-SX Product Line
Simplex Protection Device
• Same basic functionality as ProTechTPS
• Simplex operation only
• IEC61508 SIL-2 certification
• Accepts 1 or 2 (redundant) Speed Inputs
 MPU or Proximity probe compatible (one channel)
 MPU Detection (Circuit Continuity - both channels)
• Accepts redundant power inputs
 18-32Vdc power source
 90-240Vac (100-150Vdc) power source
• Trip Valve response monitor with alarm
• Serial Modbus Communications
 Ethernet gateway optional
• High Acceleration Detection
 Overspeed anticipation logic
• Fast response time --10ms
• 7 Programmable Analog or Discrete inputs
 Programmable And, Or, Not Logic
 First Out Indication
 10 millisecond logging (sequence of events
(42) recorder)
PROPRIETARY INFORMATION
ProTech-SX Functionality

(43)
PROPRIETARY INFORMATION
ProTech-SX (Turbine) Application

(44)
PROPRIETARY INFORMATION
ProTech-SX (Engine) Application

(45)
PROPRIETARY INFORMATION
ProTech Ordering Information

(46)
PROPRIETARY INFORMATION
ProTech / Competitor Comparison

(47)
PROPRIETARY INFORMATION
New Product Specs
• The following new ProTech documents are
now available on Woodward’s website
• Safety System Brochure = 51483
• ProTech-GII Product Spec. = 03370
• ProTech-GII Manual = 26709v1 & v2
• ProTechTPS Product Spec. = 03371
• ProTechTPS Manual = 26710v1 & v2
• MSM Product Spec. = 03375
• MSM Manual = 26711v1 & v2
• ProTech-SX Product Spec. = 03372
• ProTech-SX Manual = 26546v1 & v2

• Feel free to download these documents from


the Woodward website as needed.
Standards API611 and
API612 Changes

(49)
PROPRIETARY INFORMATION
Woodward’s API-611 5th Edition Solutions

API-611- 5th Edition Requirement ProTech-GII or ProTechTPS Function/Feature

7.4.2.3.2 If specified, a dedicated electronic two-out-of-three


voting trip shall be furnished. This unit shall be separate and - Separate from DCS or governor
independent of any overall system such as a DCS or governor
and if required shall be provided with electrical power by a - Independent 2-out-of-3 voting architecture
purchaser-supplied power source.

7.4.2.3.3 The requirements of 7.4.2.3.45 through 7.4.2.3.7


apply if a dedicated electronic two-out-of-three voting trip - Independent 2-out-of-3 voting architecture
system is supplied.

7.4.2.3.5 The overspeed trip system shall include at least - Accepts 3 speed sensors (MPU or Prox)
three speed sensors dedicated for the trip system. The
speed sensors are not to be shared with the speed - Alarms on failure of speed sensing signal/element
governing system. The failure of any one speed-sensing
element shall initiate an alarm only. The failure of two of - Any two speed sensor failures initiate a shutdown
three speed-sensing elements shall initiate a shutdown.

ProTechG-II or ProTechTPS
(API-611 Compliant Turbine Shutdown System)

(50)
PROPRIETARY INFORMATION
Woodward’s API-611 5th Edition Solutions

API-611- 5th Edition Requirement ProTech-GII or ProTechTPS Function/Feature


7.4.2.3.6 The design of the electronic trip system shall include
the following as a minimum: • Has a configurable trip speed setting range that can be
1. An assignable trip speed range corresponding to 110% of the set for 110% of the machine’s maximum continuous
maximum continuous speed. speed or above
2. Digital speed indication
• Includes a digital speed indication (tachometer)
3. Output(s) to a suitable separate independent trip actuation
device. The use of more than two separate independent • Utilizes two 2-out-of-3 voted trip relay to activate a trip
actuation devices shall be subject to an agreement between device
the user and the supplier. • Includes Manual or Automatic test functions to test the
4. Manually activated override for testing the electronic portion electronic overspeed shutdown system.
of the overspeed shutdown system. • Allows settings to be changed in the field and uses
5. Settings that are field changeable and protected through password security to control access.
controlled access.

7.4.2.3.7 Failure of the overspeed trip system shall • Uses a failsafe architecture and can be configured for
initiate a turbine shutdown. de-energize to trip action.

ProTechG-II or ProTechTPS
(API-611 Compliant Turbine Shutdown System)

(51)
PROPRIETARY INFORMATION
Woodward’s API-612 7th Edition Solutions

API-612- 7th Edition Requirement ProTechTPS Functions/Features

12.3.1.1 A Turbine Shutdown system shall be provided • Functions as a Turbine Shutdown System – performs
overspeed and other shutdown functions

12.3.1.3 Shall include on-line diagnostics, testing functions • Includes on-line diagnostics and testing functions
and be able to be repaired on-line and is on-line repairable

12.3.1.4 If specified shall conform to standards IEC61508


• Is IEC61508 SIL-3 Certified
or IEC61511

ProTechTPS
(API-612 Compliant Turbine Shutdown
System)

(52)
PROPRIETARY INFORMATION
Woodward’s API-612 7th Edition Solutions

API-612- 7th Edition Requirement ProTechTPS Functions/Features

12.3.1.7 The overspeed shutdown function shall be part of • Includes Overspeed Protection
the turbine shutdown system

12.3.2.1 An overspeed detection system based on three • Includes three independent measuring circuits
independent measuring circuits and two-out-three voting
logic in accordance with API std670 shall be supplied

12.3.3.4 If specified shall have a fault tolerant design, that • Includes a two-out-of-three fault tolerant voting
is capable of being tested without defeating the turbine architecture that can be tested without defeating the
shutdown system shutdown system

12.3.3.5 The trip solenoid valves shall be provided with • Includes on-line Trip Solenoid Response Monitoring
facilities to allow testing of the solenoid valve function (logs response time and alarms if time is too long)( 1
while the turbine is in operation millisecond resolution)

ProTechTPS
(API-612 Compliant Turbine Shutdown
System)

(53)
PROPRIETARY INFORMATION
Woodward’s API-612 7th Edition Solutions

API-612- 7th Edition Requirement ProTechTPS Functions/Features

12.3.4.7 The time from the overspeed condition to full • Includes total trip system response monitoring (logs
closure of the trip valve shall not exceed the time response times and alarms if time is too long) (1
calculated by the turbine vendor to meet the millisecond resolution)
requirements of 12.3.1.7. (127% of rated speed). The
calculation methodology shall be in accordance with
Annex D.

12.4.11 With the exception of the steam trip and throttle • Includes on-line self test routines
valve, it shall be possible to test every component of every • Includes on-line trip solenoid response monitoring
shutdown function while the equipment is in operation. • Includes on-line total shutdown system response
monitoring
12.4.13 Unless otherwise specified, the shutdown system • Included First-Out-Indication logs (shutdown and
shall incorporate a first-out indication to display which alarm)
parameter first reached the trip level, in the even that
multiple shutdowns result from a single initial event.

ProTechTPS
(API-612 Compliant Turbine Shutdown
System)

(54)
PROPRIETARY INFORMATION
55

API670 5th Edition Definitions


56

API670 5th Edition Requirements

8 Electronic Overspeed Detection System


57

API670 5th Edition Requirements


ProTech203 Replacement Models
Old ProTech203
Replacement ProTech-GII (Bulkhead Mount)
8200-200 - 24V, Dual Relay, Energize
8237-1596 - HV/LV, Voted Relays
8200-201 - 24V, Dual Relay, De-Energize
8200-202 - 120V, Dual Relay, Energize
8200-203 - 120V, Dual Relay, De-Energize
8237-1597 - HV/HV, Voted Relays
8200-204 - 220V, Dual Relay, Energize
8200-205 - 220V, Dual Relay, De-Energize
8200-206 - 24V, Independent Relays, Energize
8237-1594 - HV/LV, Indepenent Relays
8200-207 - 24V, Independent Relays, De-Energize
8200-208 - 120V, Independent Relays, Energize
8200-209 - 120V, Independent Relays, De-Energize
8237-1595 - HV/HV, Indepenent Relays
8200-210 - 220V, Independent Relays, Energize
8200-211 - 220V, Independent Relays, De-Energize
9905-750 - 220V, Single Relay, De-Energize 8237-1597 - HV/HV, Voted Relays
9905-751 - 24, 24, 120 Single Relay, De-Energize
8237-1596 - HV/LV, Voted Relays
9905-752 - 24, 24, 220 Single Relay, De-Energize
9905-753 - 120, 120, 220 Single Relay, De-Energize 8237-1597 - HV/HV, Voted Relays
9905-754 - 24V, Single Relay, Energize 8237-1596 - HV/LV, Voted Relays
9905-755 - 120V, Single Relay, Energize
8237-1597 - HV/HV, Voted Relays
ProTech-GII
9905-756 - 220V, Single Relay, Energize
Models
9905-869 - 24V, Single Relay, De-Energize 8237-1596 - HV/LV, Voted Relays Old ProTech203
9905-870 - 120V, Single Relay, De-Energize
9905-871 - 220V, Single Relay, De-Energize
8237-1597 - HV/HV, Voted Relays
Models
9905-872 - 24, 24, 120 Single Relay, De-Energize
8237-1596 - HV/LV, Voted Relays
9905-873 - 24, 24, 220 Single Relay, De-Energize
9905-874 - 120, 120, 220 Single Relay, De-Energize 8237-1597 - HV/HV, Voted Relays
9905-875 - 24V, Single Relay, Energize 8237-1596 - HV/LV, Voted Relays
9905-876 - 120V, Single Relay, Energize
8237-1596 - HV/LV, Voted Relays
9905-877 - 220V, Single Relay, Energize
9905-878 - 24V, Single Relay, De-Energize 8237-1596 - HV/LV, Voted Relays
9905-879 - 120V, Single Relay, De-Energize
8237-1597 - HV/HV, Voted Relays
9905-880 - 220V, Single Relay, De-Energize
9905-881 - 24, 24, 120 Single Relay, De-Energize
8237-1596 - HV/LV, Voted Relays
9905-882 - 24, 24, 220 Single Relay, De-Energize
9905-883 - 120, 120, 220 Single Relay, De-Energize 8237-1597 - HV/HV, Voted Relays
9905-884 - 24V, Single Relay, Energize 8237-1596 - HV/LV, Voted Relays
9905-885 - 120V, Single Relay, Energize
8237-1597 - HV/HV, Voted Relays
9905-886 - 220V, Single Relay, Energize
9905-903 - 24V, Dual Relay, De-Energize 8237-1596 - HV/LV, Voted Relays
9905-975 - 24V, Independent Relays, Energize 8237-1594 - HV/LV, Indepenent Relays
(58)
PROPRIETARY INFORMATION
ProTech203 Replacement Models
Old ProTech203 Replacement ProTech-GII (Bulkhead Mount)
9905-976 - 120V, Independent Relays, Energize
8237-1595 - HV/HV, Indepenent Relays
9905-977 - 220V, Independent Relays, Energize
9905-978 - 24V, Independent Relays, De-Energize 8237-1594 - HV/LV, Indepenent Relays
9905-979 - 120V, Independent Relays, De-Energize
8237-1595 - HV/HV, Indepenent Relays
9905-980 - 220V, Independent Relays, De-Energize
9905-981 - 24V, Independent Relays, Energize 8237-1594 - HV/LV, Indepenent Relays
9905-982 - 120V, Independent Relays, Energize
8237-1595 - HV/HV, Indepenent Relays
9905-983 - 220V, Independent Relays, Energize
9905-984 - 24V, Independent Relays, De-Energize 8237-1594 - HV/LV, Indepenent Relays
9905-985 - 120V, Independent Relays, De-Energize
8237-1595 - HV/HV, Indepenent Relays
9905-986 - 220V, Independent Relays, De-Energize
9905-989 - 24V, Single Relay, De-Energize 8237-1596 - HV/LV, Voted Relays
9905-990 - 120V, Single Relay, De-Energize
8237-1597 - HV/HV, Voted Relays
9905-991 - 220V, Single Relay, De-Energize
9905-992 - 24, 24, 120 Single Relay, De-Energize
8237-1596 - HV/LV, Voted Relays
9905-993 - 24, 24, 220 Single Relay, De-Energize
9905-994 - 120, 120, 220 Single Relay, De-Energize 8237-1597 - HV/HV, Voted Relays
9905-995 - 24V, Single Relay, Energize 8237-1596 - HV/LV, Voted Relays
9905-996 - 120V, Single Relay, Energize
8237-1597 - HV/HV, Voted Relays
ProTech-GII
9905-997 - 220V, Single Relay, Energize
Models
9905-998 - 24V, Single Relay, De-Energize
9905-999 - 120V, Single Relay, De-Energize
8237-1596 - HV/LV, Voted Relays
8237-1597 - HV/HV, Voted Relays
Old ProTech203
9907-080 - 24V, Dual Relay, Energize 8237-1596 - HV/LV, Voted Relays Models
9907-081 - 120V, Dual Relay, Energize
8237-1597 - HV/HV, Voted Relays
9907-082 - 220V, Dual Relay, Energize
9907-083 - 24V, Dual Relay, Energize 8237-1596 - HV/LV, Voted Relays
9907-084 - 120V, Dual Relay, Energize
8237-1597 - HV/HV, Voted Relays
9907-085 - 220V, Dual Relay, Energize
9907-146 - 24V, Single Relay, Energize
8237-1596 - HV/LV, Voted Relays
9907-147 - 24V, Single Relay, De-Energize
9907-148 - 120V, Single Relay, Energize
9907-149 - 120V, Single Relay, De-Energize
8237-1597 - HV/HV, Voted Relays
9907-150 - 220V, Single Relay, Energize
9907-151 - 220V, Single Relay, De-Energize
9907-344 - 24V, Dual Relay, Energize
8237-1596 - HV/LV, Voted Relays
9907-345 - 24V, Dual Relay, De-Energize
9907-346 - 24V, Independent Relays, Energize
9907-347 - 24V, Independent Relays, De-Energize
8237-1594 - HV/LV, Indepenent Relays
9907-975 - 24V, Independent Relays, Energize
9907-981 - 24V, Independent Relays, Energize
(59)
PROPRIETARY INFORMATION
Questions????

(60)
PROPRIETARY INFORMATION