Buzzer

Error Display Display


Alarm Text Alarm Definition Possible Cause Action
Code Code(s) Level

Room sensor will display error code


A21/A22/A23/A24 depending on which
heating circuit 1-4 it controls.
A21 A22 No comm. betw. system Poor EMS connection between display and Check both ends of EMS cabling between
1001
A23 A24
Customer
controller and remote control  The Room sensor has first been installed
installer board. the boards.
successfully. Then the EMS bus signal has
gone absent from the parent controller
(display).

Check that accessories for the EMS bus


The local device hasn't received its EMS
No communication via EMS BUS (room control, mixing module, etc.) are
1010 A11 Customer
connection  token from the EMS bus master for 2 Break/disruption in EMS connection.
properly connected. Also check connection
minutes.
between display and installer board.
The alarm can occur in conjunction with
See action for error code 1010.
alarm 1010.
Outside temp. sensor faulty, The EMS communication between the If, in the alarm history, the error code 1037
1037 Customer
heating standby mode active  sensor and the control unit. can be found, but not 1010, there can be a
Replace the installer board.
fault in the microcontroller of the installer
board.
Time/date has not been set. Set the time and date again.
1038 Customer Invalid time/date value  Time/date has not been set.
Extended power outage. Set the time and date again.

The alarm is given if power is lost during


ongoing screed drying program. The
program is automatically resumed when the
Voltage failure during screed
1041 Customer
drying  power is back, unless the interruption Power loss. Check fuses, possible bad connections etc.
outlasts the battery reserve of the control
unit, or if the set maximum time (normally 12
h) has been exceeded.

The module for external room temperature


Under Service menu >> Set heating/cooling
sensor has not been developed. The alarm Incorrect setting in software. Service menu
>> Heating circ. 1, make sure that Ext. room
No communication with external is triggered if the installer still selects this >> Set heating/cooling >> Heating circ. 1 >>
1051 Customer
room temp. sensor module  module to control a heating circuit. The Ext. room temp. sensor, shall always be set
temp. Sensor = No, and that Programming
unit = RC100/CR10. See room sensors'
alarm is delayed by 4 minutes. (Also see to No.
installer guide for more information.
alarm 3091.)

The module for external room temperature


Under Service menu >> Set heating/cooling
sensor has not been developed. The alarm Incorrect setting in software. Service menu
No communication with external >> Heating circ. 2, make sure that Ext. room
is triggered if the installer still selects this >> Set heating/cooling >> Heating circ. 2 >>
1052 Customer room temperature sensor  module to control a heating circuit. The Ext. room temp. sensor, shall always be set
temp. Sensor = No, and that Programming
module unit = RC100/CR10. See room sensors'
alarm is delayed by 4 minutes. (Also see to No.
installer guide for more information.
alarm 3092.)

7
The module for external room temperature Under Service menu >> Set heating/cooling
Incorrect setting in software. Service menu
No communication with external sensor has not been developed. The alarm >> Heating circ. 3, make sure that Ext. room
>> Set heating/cooling >> Heating circ. 3 >>
1053 Customer room temperature sensor  is triggered if the installer still selects this
Ext. room temp. sensor, shall always be set
temp. Sensor = No, and that Programming
module module to control a heating circuit. (Also see unit = RC100/CR10. See room sensors'
to No.
alarm 3093.) installer guide for more information.

The module for external room temperature


Under Service menu >> Set heating/cooling
sensor has not been developed. The alarm Incorrect setting in software. Service menu
No communication with external >> Heating circ. 4, make sure that Ext. room
is triggered if the installer still selects this >> Set heating/cooling >> Heating circ. 4 >>
1054 Customer room temperature sensor  module to control a heating circuit. The Ext. room temp. sensor, shall always be set
temp. Sensor = No, and that Programming
module unit = RC100/CR10. See room sensors'
alarm is delayed by 4 minutes. (Also see to No.
installer guide for more information.
alarm 3094.)
The room sensor for heating circuit 1 has The display unit in the indoor unit is always Configure the room sensor for remote
Two master user interfaces in
1081 Customer
system.  been incorrectly configured as a controller the controller in the system, and more than control "Fb". See room sensors' installation
("CO"/"SC"). one is not allowed. guide for more information.
The room sensor for heating circuit 2 has The display unit in the indoor unit is always Configure the room sensor for remote
Two master remote controls in
1082 Customer
system.  been incorrectly configured as a controller the controller in the system, and more than control "Fb". See room sensors' installation
("CO"/"SC"). one is not allowed. guide for more information.
The room sensor for heating circuit 3 has The display unit in the indoor unit is always Configure the room sensor for remote
Two master remote controls in
1083 Customer
system.  been incorrectly configured as a controller the controller in the system, and more than control "Fb". See room sensors' installation
("CO"/"SC"). one is not allowed. guide for more information.
The room sensor for heating circuit 4 has The display unit in the indoor unit is always Configure the room sensor for remote
Two master remote controls in
1084 Customer
system.  been incorrectly configured as a controller the controller in the system, and more than control "Fb". See room sensors' installation
("CO"/"SC"). one is not allowed. guide for more information.
The circuit for the flow sensor, connected to Bad connection. Check connection.
the mixer module for circuit 1, is either
shorted or broken. The alarm is delayed by
Heating circuit flow temp. sensor 10 s. Disconnect cable from mixer module and
3021 Customer
faulty - standby mode active  Shorted cable / defective sensor.
measure the sensor with a multimeter. If
Standby mode means that the mixing valve shorted (0 Ohm) or broken (infinite
opening position is set to 10%, to ensure resistance), replace sensor.
frost protection.
The circuit for the flow sensor, connected to Bad connection. Check connection.
the mixer module for circuit 2, is either
shorted or broken. The alarm is delayed by
Heating zone 2 supply Disconnect cable from mixer module and
10 s.
3022 Customer temperature sensor fault,  Shorted cable / defective sensor.
measure the sensor with a multimeter. If
standby mode active shorted (0 Ohm) or broken (infinite
Standby mode means that the mixing valve
opening position is set to 10%, to ensure resistance), replace sensor.
frost protection.

8
The circuit for the flow sensor, connected to Bad connection. Check connection.
the mixer module for circuit 3, is either
shorted or broken. The alarm is delayed by
Heating zone 3 supply Disconnect cable from mixer module and
10 s.
3023 Customer temperature sensor fault,  Shorted cable / defective sensor.
measure the sensor with a multimeter. If
standby mode active shorted (0 Ohm) or broken (infinite
Standby mode means that the mixing valve
opening position is set to 10%, to ensure resistance), replace sensor.
frost protection.
The circuit for the flow sensor, connected to Bad connection. Check connection.
the mixer module for circuit 4, is either
shorted or broken. The alarm is delayed by
Heating zone 4 supply Disconnect cable from mixer module and
10 s.
3024 Customer temperature sensor fault,  Shorted cable / defective sensor.
measure the sensor with a multimeter. If
standby mode active shorted (0 Ohm) or broken (infinite
Standby mode means that the mixing valve
opening position is set to 10%, to ensure resistance), replace sensor.
frost protection.
A mixing module has previously been
installed for heating circuit 1, and now the
installer board has been unable to Poor connection or improperly installed EMS
No communication with htg circ.
3061 A11 Customer
module  communicate with the mixing module over cable between installer board and mixing Check EMS cabling.
the EMS bus for the past 4 minutes. The module.
alarm is automatically acknowledged when
communication is re-established.

A mixing module has previously been


installed for heating circuit 2, and now the
installer board has been unable to Poor connection or improperly installed EMS
No communication with heating
3062 A11 Customer
zone module  communicate with the mixing module over cable between installer board and mixing Check EMS cabling.
the EMS bus for the past 4 minutes. The module.
alarm is automatically acknowledged when
communication is re-established.

A mixing module has previously been


installed for heating circuit 3, and now the
installer board has been unable to Poor connection or improperly installed EMS
No communication with heating
3063 A11 Customer
zone module  communicate with the mixing module over cable between installer board and mixing Check EMS cabling.
the EMS bus for the past 4 minutes. The module.
alarm is automatically acknowledged when
communication is re-established.

A mixing module has previously been


installed for heating circuit 4, and now the
installer board has been unable to Poor connection or improperly installed EMS
No communication with heating
3064 A11 Customer
zone module  communicate with the mixing module over cable between installer board and mixing Check EMS cabling.
the EMS bus for the past 4 minutes. The module.
alarm is automatically acknowledged when
communication is re-established.

9
A room sensor has previously been installed
for heating circuit 1, and now the installer
board has been unable to communicate with Poor connection or improperly installed EMS
No communication with remote
3071 A11 Customer
control  the room sensor over the EMS bus for the cable between installer board and room Check EMS cabling.
past 4 minutes. The alarm is automatically sensor.
acknowledged when communication is re-
established.

A room sensor has previously been installed


for heating circuit 2, and now the installer
board has been unable to communicate with Poor connection or improperly installed EMS
No communication with remote
3072 A11 Customer
control  the room sensor over the EMS bus for the cable between installer board and room Check EMS cabling.
past 4 minutes. The alarm is automatically sensor.
acknowledged when communication is re-
established.

A room sensor has previously been installed


for heating circuit 3, and now the installer
board has been unable to communicate with Poor connection or improperly installed EMS
No communication with remote
3073 A11 Customer
control  the room sensor over the EMS bus for the cable between installer board and room Check EMS cabling.
past 4 minutes. The alarm is automatically sensor.
acknowledged when communication is re-
established.

A room sensor has previously been installed


for heating circuit 4, and now the installer
board has been unable to communicate with Poor connection or improperly installed EMS
No communication with remote
3074 A11 Customer
control  the room sensor over the EMS bus for the cable between installer board and room Check EMS cabling.
past 4 minutes. The alarm is automatically sensor.
acknowledged when communication is re-
established.

Ensure that the room sensor refers to the


Configuration error: Remote The room sensor has been configured to The room sensor has been configured to
3081 Customer
control not used  control circuit 1, which is not defined. control circuit 1, which is not defined.
correct heating circuit. Alternatively, check
the configuration for circuit 1.
Ensure that the room sensor refers to the
Configuration error: Remote The room sensor has been configured to The room sensor has been configured to
3082 Customer
control not used  control circuit 2, which is not defined. control circuit 2, which is not defined.
correct heating circuit. Alternatively, check
the configuration for circuit 2.
Ensure that the room sensor refers to the
Configuration error: Remote The room sensor has been configured to The room sensor has been configured to
3083 Customer
control not used  control circuit 3, which is not defined. control circuit 3, which is not defined.
correct heating circuit. Alternatively, check
the configuration for circuit 3.
Ensure that the room sensor refers to the
Configuration error: Remote The room sensor has been configured to The room sensor has been configured to
3084 Customer
control not used  control circuit 4, which is not defined. control circuit 4, which is not defined.
correct heating circuit. Alternatively, check
the configuration for circuit 4.

10
The resistance thermometer inside the room Ensure that the setting Service menu >> Set
sensor for heating circuit 1 is defective. Incorrect configuration of external room
heating/cooling >> Heating circ. 1 >> Ext.
3091 A11 Customer Room temperature sensor faulty  (EMS communication is working.) An sensor. (This will also produce alarm 1051.)
room temp. Sensor = No.
incorrect configuration of the room sensor
will produce the same alarm. Broken room sensor. The room sensor must be replaced.
The resistance thermometer inside the room Ensure that the setting Service menu >> Set
sensor for heating circuit 2 is defective. Incorrect configuration of external room
heating/cooling >> Heating circ. 2 >> Ext.
3092 A11 Customer Room temperature sensor fault  (EMS communication is working.) An sensor. (This will also produce alarm 1052.)
room temp. Sensor = No.
incorrect configuration of the room sensor
will produce the same alarm. Broken room sensor. The room sensor must be replaced.
The resistance thermometer inside the room Ensure that the setting Service menu >> Set
sensor for heating circuit 3 is defective. Incorrect configuration of external room
heating/cooling >> Heating circ. 3 >> Ext.
3093 A11 Customer Room temperature sensor fault  (EMS communication is working.) An sensor. (This will also produce alarm 1053.)
room temp. Sensor = No.
incorrect configuration of the room sensor
will produce the same alarm. Broken room sensor. The room sensor must be replaced.
The resistance thermometer inside the room Ensure that the setting Service menu >> Set
sensor for heating circuit 4 is defective. Incorrect configuration of external room
heating/cooling >> Heating circ. 4 >> Ext.
3094 A11 Customer Room temperature sensor fault  (EMS communication is working.) An sensor. (This will also produce alarm 1054.)
room temp. Sensor = No.
incorrect configuration of the room sensor
will produce the same alarm. Broken room sensor. The room sensor must be replaced.
The alarm is given if a room sensor was The alarm is given if a room sensor was
Run the configuration wizard from Service
Configuration error: Incorrect previously acknowledged, but it is later previously acknowledged, but it is later
3111 A11 Customer
remote control  replaced with another room sensor type with replaced with another room sensor type with
menu / Commissioning. It automatically
identifies the type of room sensor used.
hygrometer - or vice versa. hygrometer - or vice versa.
Check the function of the mixing valve and
The alarm is given by the mixing module
High temperature. mixing module. Check the cut-off threshold
MM100 for circuit 1, if its MC1 input is open.
for the temperature guard.
3121 Customer Temperature limiter triggered  It is possible to install a temperature guard
Intermittent connection in cabling between
which breaks up the connection over MC1
when the temperature is too high. temperature guard and MC1 input of Check the cabling for continuity.
MM100.
Check the function of the mixing valve and
The alarm is given by the mixing module
High temperature. mixing module. Check the cut-off threshold
MM100 for circuit 2, if its MC1 input is open.
for the temperature guard.
3122 Customer Temperature limiter triggered  It is possible to install a temperature guard
Intermittent connection in cabling between
which breaks up the connection over MC1
when the temperature is too high. temperature guard and MC1 input of Check the cabling for continuity.
MM100.
Check the function of the mixing valve and
The alarm is given by the mixing module
High temperature. mixing module. Check the cut-off threshold
MM100 for circuit 3, if its MC1 input is open.
for the temperature guard.
3123 Customer Temperature limiter triggered  It is possible to install a temperature guard
Intermittent connection in cabling between
which breaks up the connection over MC1
when the temperature is too high. temperature guard and MC1 input of Check the cabling for continuity.
MM100.

11
Check the function of the mixing valve and
The alarm is given by the mixing module
High temperature. mixing module. Check the cut-off threshold
MM100 for circuit 4, if its MC1 input is open.
for the temperature guard.
3124 Customer Temperature limiter triggered  It is possible to install a temperature guard
Intermittent connection in cabling between
which breaks up the connection over MC1
when the temperature is too high. temperature guard and MC1 input of Check the cabling for continuity.
MM100.
Sensor for relative humidity is faulty in the Sensor for relative humidity is faulty in the
3141 A21 Customer Humidity sensor faulty  room sensor for circuit 1. room sensor.
Replace room sensor.

Sensor for relative humidity is faulty in the Sensor for relative humidity is faulty in the
3142 A22 Customer Humidity sensor fault  room sensor for circuit 2. room sensor.
Replace room sensor.

Sensor for relative humidity is faulty in the Sensor for relative humidity is faulty in the
3143 A23 Customer Humidity sensor fault  room sensor for circuit 3. room sensor.
Replace room sensor.

Sensor for relative humidity is faulty in the Sensor for relative humidity is faulty in the
3144 A24 Customer Humidity sensor fault  room sensor for circuit 4. room sensor.
Replace room sensor.

Low batt. voltage in radio room The wireless room sensor for circuit 1 Replace the battery in the wireless room
3171 A71 Customer
temp. sensor in heat. circuit 1  reports low battery level.
Low battery level.
sensor.

Low battery level in the wireless room Measure the battery's voltage and replace it
sensor. if the voltage is weak.

The wireless room sensor for circuit 1 has Experiment with placement of the wireless
No signal from radio room temp.
3181 A91 Customer
sensor for heating circuit 1  previously been installed, but it is no longer room sensor. Start by placing it close to the
possible to establish a connection to it. The distance between the room sensor and key, in order to verify the function. If
the key is too long. connection cannot be established in that
situation, the room sensor may be defective
and needs to be replaced.

Warning if the resistance of the outdoor Outdoor sensor T1 has not been installed. Install outdoor sensor.
Info Outside temperature sensor
5201 A01 Installer sensor T1 > 179 kOhm (corresponding to a
T1 open circuit Break on signal cable between installer Check signal cable and connection to
temperature < -50°C).
board and sensor. installer board.
Warning if the resistance of the outdoor
Info Outside temperature sensor
5202 A01 Installer sensor T1 < ~1300 Ohm (corresponding to a Outdoor sensor T1/signal cable shorted. Check signal cable.
T1 short circuit
temperature > 57°C).
See possible causes for the warnings 5201 See possible actions for the warnings 5201
and 5202. and 5202.
Measure the resistance of the temperature
Alarm if 3 error codes are registered withing Outdoor sensor T1 value is out of range (> sensor. If the value is out of range the signal
Alarm Outside temperature 3 hours, or if the circuit for outdoor sensor 179 kOhm or < 824 Ohm). cable may have a break or short. Replace
5203 H01 Customer signal cable or sensor T1 if necessary.
sensor T1 fault T1 is continuously shorted/broken for 30
minutes.
If sensor T1 measures the correct value,
and the same warning (5201/5202) remains
Defective installer board.
when the sensor is connected, replace the
installer board.

12
Info Z1 Flow temperature sensor Warning if the resistance of flow sensor T0 > Break on signal cable between installer Check signal cable and screw terminal on
5204 A01 Installer
T0 open circuit 30 kOhm (<0°C). board and sensor. installer board.
Warning if the resistance of flow sensor T0 <
Info Z1 Flow temperature sensor
5205 A01 Installer 500 Ohm (corresponding to a temperature > Flow sensor T0/signal cable shorted. Check signal cable.
T0 short circuit
110°C).
See possible causes for the warnings 5204 Se possible actions for the warnings 5204
and 5205. and 5205.
Measure the resistance of the temperature
Alarm if 3 errors of type 5204 or 5205 are Flow sensor T0 value is out of range (> 15 sensor. If the value is out of range the signal
Alarm Z1 Flow temperature registered withing 3 hours, or if the circuit for kOhm or < 300 Ohm). cable may have a break or short. Replace
5206 H01 Customer signal cable or sensor T0 if necessary.
sensor T0 fault flow sensor T0 is continuously
shorted/broken for 30 minutes.
If sensor T0 measures the correct value,
and the same warning (5204/5205) remains
Defective installer board.
when the sensor is connected, replace the
installer board.
Screw terminal on installer board not
Check screw terminal for TC1.
properly tightened.
With TC1 disconnected from installer board,
Info Temp. sensor TC1 open Warning if resistance of sensor > 30 kOhm
5207 A01 Installer Heat carrier outlet sensor TC1/signal cable compare measured Ohm value with sensor
circuit (corresponding to a temperature < 0°C).
open circuit. table in documentation. Replace sensor if
necessary.
Defective installer board. Replace installer board.
With TC1 disconnected from installer board,
Warning if the resistance of the sensor < Heat carrier outlet sensor TC1/signal cable compare measured Ohm value with sensor
Info Temperature sensor TC1 shorted. table in documentation. Repair sensor cable
5208 A01 Installer 390 Ohm (corresponding to a temperature >
short circuit or replace sensor if necessary.
180°C).
Defective installer board. Replace installer board.
Alarm if 3 errors of type 5207 or 5208 are
Alarm Temperature sensor TC1 registered within 3 hours, or if the circuit for Se possible causes for error code 5207 och
5209 H01 Customer (x) See actions for alarm codes 5207, 5208.
fault sensor TC1 is continuously broken/shorted 5208.
for more than 30 minutes.
Screw terminal in installer board, for heat
carrier return sensor TC1, not properly Check screw terminal for TC1.
tightened.
Warning if the resistance of heat carrier
Info Z1 Inlet temp. sensor TC0 return-sensor TC0 > 30 kOhm With sensor disconnected from the installer
5213 A01 Installer
open circuit (corresponding to temperature < 0°C). The Heat carrier return sensor TC0/signal cable board, measure the Ohm value and
compressor is stopped. broken. compare it to table value in documentation.
Repair cable or replace sensor if necessary.
Defective installer board. Replace installer board.

13
With sensor TC0 disconnected from the
Warning if the resistance of heat carrier Heat carrier return sensor TC0/signal cable installer board, measure the resistance and
Info Z1 Inlet temp. sensor TC0 return-sensor TC0 < 500 Ohm shorted. compare it to sensor table in documentation.
5214 A01 Installer
short circuit (corresponding to temperature > 110°C). Replace sensor if necessary.
The compressor is stopped.
Defective installer board. Replace installer board.
Alarm if 3 errors of type 5213 or 5214 are
Alarm Z1 Inlet temp sensor TC0 registered within 3 hours, or if the circuit for See possible causes for alarm codes 5213, See possible actions for alarm codes 5213,
5215 H01 Customer x
fault sensor TC0 is continuously broken/shorted 5214. 5214.
for 30 minutes. The compressor is stopped.

Screw terminal for TC1 on pool module is


Check terminal.
not properly tightened.
Warning if the resistance for sensor TP1,
Info Pool temperature sensor which is named TC1 on the pool module, is With sensor TC1 disconnected from the pool
5234 A01 Installer
TP1 open circuit > 32 kOhm (corresponding to a temperature module, measure its resistance and
Defective sensor or broken signal cable.
< 0°C). compare it to sensor table. Repair cable or
replace sensor if necessary.
Defective pool module. Replace pool module.
Screw terminal for TC1 on pool module is
Check terminal.
not properly tightened.
Warning if the resistance for sensor TP1,
With sensor TC1 disconnected from the pool
Info Pool temperature sensor which is named TC1 on the pool module, is
5235 A01 Installer Pool temperature sensor TP1/signal cable module, measure its resistance and
TP1 short circuit < 680 Ohm (corresponding to a temperature
shorted. compare it to sensor table. Repair cable or
> 100°C).
replace sensor if necessary.
Defective pool module. Replace pool module.
Alarm if 3 errors of type 5234 or 5235 are
Alarm Pool temperature sensor registered within 3 hours, or if the circuit for Se trouble-shooting advice for codes 5234,
5236 H01 Customer Se possible causes for codes 5234, 5235.
TP1 fault the sensor is broken/shorted continuously 5235.
for 30 minutes.

Screw terminal for TW1 on installer board


Warning if the domestic hot water sensor Check screw terminal.
not properly tightened.
TW1 < 0°C. Automatically reset if the
temperature > 0°C.
Info DHW temp. sensor TW1
5237 A01 Installer
open circuit
Sensor TW1 has different characteristics With the sensor disconnected from the
depending on the products' brand. See installer board, measure and compare the
sensor table for more information. Sensor TW1 or signal cable is broken.
resistance to sensor table in documentation.
Repair cable or replace sensor if necessary.
Defective installer board. Replace installer board.

14
Warning if the domestic hot water sensor With the sensor disconnected from the
TW1 > 110°C. Automatically reset if the installer board, measure and compare the
Hot water sensor TW1/signal cable shorted.
temperature < 110°C. resistance to sensor table in documentation.
Info DHW temp. sensor TW1 Repair cable or replace sensor if necessary.
5238 A01 Installer
short circ.
Sensor TW1 has different characteristics If the sensor is found to be working and the
depending on the products' brand. See Defective installer board. warning is still triggered, replace the installer
sensor table for more information. board.
Alarm is triggered if 3 errors of type 5237 or
5238, are registered within 3 hours, or if the
Alarm DHW temperature sensor Se possible causes for error codes 5237 See possible actions for error codes 5237
5239 H01 Customer circuit for sensor TW1 is continuously
TW1 fault and 5238. and 5238.
broken/shorted for more than 15 minutes.
The alarm needs manual reset.
Screw terminal for TK1 not properly
Check screw terminal.
tightened.
Sensor TK1 for cooling outlet in the passive
Info Cooling outlet temperature With the sensor disconnected from the
5240 A01 Installatör cooling station < 0°C (i.e. high resistance).
sensor TK1 open circuit terminal, measure and compare the
Automatic reset when TK1 > 0°C. Sensor TK1 or signal cable is broken.
resistance to sensor table in documentation.
Repair cable or replace sensor if necessary.
With the sensor disconnected from the
Sensor TK1 for cooling outlet in the passive
Info Cooling outlet temperature installer board, measure and compare the
5241 A01 Installer cooling station > 110°C (i.e. low resistance). Sensor TK1 or signal cable is shorted.
sensor TK1 short circuit resistance to sensor table in documentation.
Automatic reset when TK1 < 110°C.
Repair cable or replace sensor if necessary.
Alarm is triggered if 3 errors of type 5240 or Se possible causes for error codes 5240 See possible actions for error codes 5240
5241, are registered within 3 hours, or if the and 5241. and 5241.
Alarm Cooling outlet temperature
5242 H01 Customer circuit is continuously broken/shorted for If function of TK1 is verified, the extension
sensor TK1 fault
more than 30 minutes. The alarm needs board in the passive cooling station may be Replace extension board.
manual reset. defective.
Screw terminal for TK2 not properly
Check screw terminal.
Sensor TK2 for frost protection (brine inlet) tightened.
Info Cooling inlet temperature in the passive cooling station <= -20°C (high With the sensor disconnected from the
5243 A01 Installer
sensor TK2 open circuit resistance), for 3 minutes. Automatic reset terminal, measure and compare the
when TK2 > -20°C. Sensor TK2 or signal cable is broken.
resistance to sensor table in documentation.
Repair cable or replace sensor if necessary.
Sensor TK2 for frost protection (brine inlet) With the sensor disconnected from the
Info Cooling inlet temperature in the passive cooling station > 57°C (low installer board, measure and compare the
5244 A01 Installer Sensor TK2 or signal cable is shorted.
sensor TK2 short circuit resistance), for 3 minutes. Automatic reset resistance to sensor table in documentation.
when TK2 < 57°C. Repair cable or replace sensor if necessary.
Alam is triggered if 3 errors of type 5243 or Se possible causes for error codes 5243 See possible actions for error codes 5243
5244, are registered within 3 hours, or if the and 5244. and 5244.
Alarm Cooling inlet temperature
5245 H01 Customer circuit is continuosly broken/shorted for If function of TK2 is verified, the extension
sensor TK2 fault
more than 30 minutes. The alarm needs board in the passive cooling station may be Replace extension board.
manual reset. defective.

15
Reset the overheating protector. Note that
Tripped overheating protector. the button must be pushed hard. A "click" is
heard when reset.
De-air heating system according to
Low system pressure. Air in the heating
instruction in the installer guide. Refill
system.
heating system.
Clogged filterball on heat carrier return pipe. Clean filter ball.
Bad circulation in the heating carrier/heating Check adjustment valves/thermostats for
system. heating system.
Verify breaking temperature (95°C). Replace
Defective overheating protector.
overheating protector if to trips too soon.
Check the alarm log to see if PC0 has
Circulation pump PC0 does not run. PC0 is produced any alarm in conjunction with error
controlled by Modbus and has its own set of code 5246. Note that PC0 cannot produce
Alarm Z1 electric booster heater Alarm is given when the overheating alarms, where for instance error code 5918, an alarm if its supply voltage iss missing.
5246 A01 Customer E2 manual reset high limit (STB) (x) protector of the electrical heater is tripped, is one of them. Therefore this connection needs to be
or pressure switch tripped which happens at 95 degrees. checked as well.
If PC0 has its supply voltage connected and
Defective circulation pump. has not produced any alarms, but still does
not run - replace the circulation pump.

Toggle each electrical heater output, one at


a time, off and on. Measure the
corresponding control circuit voltage and
output voltage for each contactor. Replace
the contactor if activated even with inactive
One of the contactors for the electrical
control voltage. If the control voltage is
heater has become stuck in closed position.
always 0 V in both off and on state, or
always 230 V in both off and on state, it is a
sign the output relay of the installer board is
defective. Replace the installer board in this
case.

Warning is given when heat carrier delta


TC3-TC0 > 13 K. (The condition needs to be
Info Z1 Flow rate betw. outdoor met for 3-10 minutes, depending on the Check and clean the filterball on the return
Bad circulation in the heat carrier/heating
5252 H01 Customer and indoor unit restricted (check operating mode of the heat pump, for the pipe. Check adjustment valves and
system.
filter) message to be triggered.) The heat pump thermostats for the heating system.
continues to run as normal and the message
can be acknowledged by the customer.
Missing CANbus communication between Bad CAN bus connections on installer board
5265 A01 Installer Info Z1 PCB disconnected Check CAN bus connections.
installer board and HP board for 11 s. or HP board.

16
Alarm if error code 5265 is registered 3
times within 3 h, or if the CANbus
5266 H01 Customer Alarm Z1 PCB disconnected See possible causes for warning 5265. See actions for warning 5265.
communication has been continuously
broken for 15 minutes.

Dirt in filter ball on the return line. Clear system filter/filter ball.
Alarm when sensor TC1 > 87°C for 4 s.
Electrical heater operation is blocked. The
alarm is inactivated when TC1 < 80°C. The Poor circulation in heat transfer Check adjustment valves/thermostats for
Alarm Z1 Electric booster heater system/heating system. heating system. Ensure adequate flow.
5269 A01 Customer (x) customer can acknowledge the message,
EE temperature too high
but the alarm remains active until the With TC1 disconnected from the installer
temperature has dropped below the board, compare its measured value to
approved level. Defective TC1 sensor.
sensor table in documentation. Replace
sensor TC1 if necessary.

De-air heating system according to


Low system pressure. Air in the heating
Alarm when sensor T0 > "Max. flow instruction in the installer guide. Refill
system.
temperature" set point value + 5 K. Return heating system.
sensor TC0 is also monitored in case T0
incorrectly measures a too low temperature Clean filter ball on return pipe. Check
(only when DHW production is not active). Low flow in heating system. adjustment valves and thermostats for the
The alarm is triggered with a delay of 0-10 s heating system.
depending on how large the exceedance is.
With sensor disconnected from the installer
Alarm Heating circuit 1 high flow The alarm is blocked for 5 minutes after a
5271 A01 Customer x Defective T0 sensor. board, compare sensor resistance to table
temperature DHW cycle.
values for T0 found in the documentation.
"Max. flow temperature": Service/ Run the 3-way valve in manual mode and
Commissioning/ Max. temp HCx. check that 230 V is available on terminal 53
The system is in heating mode but the (VW1) in DHW mode. If that is the case but
Automatic reset happens when the flow and diverter valve has not switched over to the valve does not switch, replace the
return temperatures drop to acceptable DHW. motor/cable for the diverter valve. If voltage
levels again. is missing during DHW mode, replace the
installer board.

17
De-air heating system according to
Low system pressure. Air in the heating
instruction in the installer guide. Refill
system.
heating system.
Clogged filterball SC1 on return pipe. Clean filter ball SC1.
Bad circulation in the heating carrier/heating Check adjustment valves/thermostats for
system. heating system.
Tripped fuse at distrubution box. Reset/replace fuses at distrubution box.
Ensure that voltage is connected to
circulation pump. Examine if there are
Circulation pump does not run.
Alarm for external additional additional error codes in the alarm log,
Alarm External auxiliary heater heater/overheating protector. Alarm is related to the circulation pump.
5272 A01 Customer
EM is not operational triggered if 230 V is missing on terminal 64
on installer board. Verify breaking temperature (96°C) for the
overheating protector. For instance, raise
Defective overheating protector.
the temperature with Extra DHW program, to
see if it triggers too soon.
Measure control voltage and output voltage
Contactor for electrical heater has got of each contactor to check if it has been
jammed in closed (active) position. jammed. If a contactor is conintuously active
regardless of control voltage, replace it.
If all points above have been checked and
Possible problem with alarm input of installer
the alarm persists, the installer board may
board. Replace installer board.
be defective.

Tripped fuse for the heat pump. Reset fuse in indoor unit.

Check that all phases are properly


Phase/phases missing on terminals for
connected and that each one carries
supply voltage in heat pump.
5273 A01 Customer Alarm Z1 Phase monitoring x Alarm if phase is missing. voltage.
Phase/phases missing on terminals for Check that all phases are available on
supply voltage on EMI filter in the inverter. terminals for EMI filter.
If voltage is present on all phases connected
to the EMI filter, and alarm remains, the Replace inverter.
inverter is broken.

18
The pressure guard is connected to the HP
board's input "I15" [terminal 6, 13] and the Check for leakage and fill up the cold carrier
circuit is normally closed. The pressure circuit. Recommended pressure is 2.5-3.0
guard will break/open the circuit when the bar.
pressure drops below 0.5 (±0.1) bar. The
event is detected immediately (without Leakage or insufficiently filled cold carrier The pressure sensor is mounted right before
delay) and stops the compressor and cold circuit. the circulation pump, in the flow direction.
carrier pump. The block is removed when When the pump starts, it can result in a brief
the pressure guard has been closed for 30 s depressurization which causes the guard to
(pressure just above 0.5 bar). open. For this reason it's wise to follow the
recommendation.
Alarm Z1 Pressure in brine The alarm is produced when the pressure
5276 A01 Customer x
circuit too low guard has tripped 2 times within 30 min, or
the circuit is continuously broken for 15 min.
It then requires manual acknowledgment
before the heat pump is allowed to make
further start attempts.
Broken circuit on input "I15" (factory Check that the guard is working,
If an external pressure guard has been mounted pressure guard), or on the chosen alternatively that the cable is properly
connected (possible since installer board external input (external pressure guard). connected to the input.
v2.02), it is monitored in parallel with the
factory mounted pressure guard when using
v2.02, or instead of the factory mounted
pressure guard when using v2.03.
Water is continuously tapped from the Stop such continuous usage or change
cylinder. (prolong) the time for thermal disinfection.
If the fuse requires the heater to run at
limited power, you may need to allow a
The electrical heaters output power is set
longer time for thermal disinfection. The time
too low in relation to hot water volume.
can be adjusted under [Service menu >>
DHW >> Max. time].

The domestic hot water temperature, sensor Hot water sensor is misplaced, or have Put the hot water sensor in the correct
Info Last thermal disinfection TW1, has not reached 65°C within 180 come loose from the cylinder. position.
5284 A01 Customer
failed minutes. If the warning is triggered a new Air in the heating coil. De-air the heating coil.
attempt is postponed until the next day.
If using hot water circulation, too big losses Make sure that circulation pipes are properly
from the pipes. insulated.
With sensor disconnected from the installer
Incorrect reading from temperature sensor board, measure its resistance and compare
TW1. it to table value in documentation. Replace if
necessary.
Incorrectly connected pipes to hot water
Fix any pipe connection issues.
system.

19
Check the different sensors and compare
Ohm-values to table values in
Defective sensor.
documentation. Replace sensor if sensor if
necessary.
Warning if T0 (flow), TC1 (heat carrier flow)
or TC0 (heat carrier return) < 5°C for 10 Check that 230V is available on terminal
minutes. When the warning is triggered, all Supply voltage (230 V) is missing for PC0 (51, N) on the installer board. If not,
5285 H01 Installer Info Risk of frost in heat. system available heat sources are activated and all circulation pump PC0. also check that the fuse on the installer
mixing valves are opened, in order to heat board is OK.
the system. The warning is reset when all of
Examine if there are additional error codes
the previously mentioned sensors > 25°C. Some other error has been registered in the
in the alarm log, related to the circulation
Modbus controlled pump PC0.
pump.
Defective installer board (does not provide
Replace installer board.
230V for PC0 despite the fuse beeing OK).
The circuit for the dew point
guard/condensate guard MD1 (previously
named MK2) has been closed over terminal
5294 A01 Installer Info condensation guard tripped Short circuit in cable/humidity sensor. Measure the resistance of the circuit.
34,35 on the installer board. The warning is
automatically reset when the circuit has
been open for 60 seconds.
Short circuit in cable/humidity sensor. Measure the resistance of the circuit.
Alarm when warning 5294 has been active Measure voltage on terminal MD1 (34, 35)
Alarm Condensation monitor has
5295 H01 Customer for 30 minutes. The alarm must be manually on installer board, with the humidity sensor
tripped Defective installer board.
acknowledged. disconnected. If voltage is < 2,5V DC,
replace installer board.

20
Dirt in system filter/filterball valve SC1. Clean the filter.

Poor circulation in heat transfer


Ensure sufficient flow.
system/heating system.
Vent the heating system in accordance with
Air in heat transfer system/heating system. instructions in installation manual. Fill up
with water.
Measure the temperatures at the sensor
Warning if condensing temperature JR1 positions with an external thermometer and
exceeds the current envelope limit -1K. Defective sensor TC3, TC0 or T0. compare them to the temperatures shown in
5298 A01 Installer Info Z1 High pressure alarm JR1 Envelope diagram for the compressor is the HMI. Replace sensor if considerable
presented in its own section in the service deviation is found.
manual.
Diverter valve VW1 does not shift from hot Check VW1 position. A=hot water,
water production to heating. B=heating system.
Defective installer board, bad control signal Check that terminal 53 on installer board
for diverter valve. provides 230V in hot water mode only.
Check that the supply voltage is connected
The circulation pump does not run. to the pump. Check if the alarm log contains
any error codes for the circulation pump.
Defective installer board, supply voltage, Measure voltage on terminal 51-N. If no
230 V, missing from circulation pump PC0. voltage, replace installer board.
Alarm Z1 High pressure alarm Alarm if error code 5298 is registered 3
5299 H01 Customer x See possible causes for error code 5298. See actions for felkod 5298.
JR1 times within 2 hours.
At isolated occurences of this error code, the
The temperature of the inverter's recommendation is to restart the appliance
Info Z1 Temperature too high on High ambient temperature, or poor heat
5302 A01 Installer compressor control system exceeds 110°C. with no further action. Should the error code
compressor control system transfer between inverter and cooling coil.
The compressor is stopped. be given more often, see error code 5303 for
more information.

The temperature of the inverters' Check screw mountings for cooling coil and
compressor control system > 110°C. Alarm Poor heat transfer to cooling coil. the aluminum cooling plate. Check thermal
Alarm Z1 Temperature too high paste and contact surfaces.
5303 H01 Customer x is given if error code 5302 is registered more
on compressor control system
than 2 times within 3 h, or if the temperature If repeated alarms, the inverter is likely
continuously > 110°C for 15 minutes. Replace inverter.
defective.
Suction gas overheating too high. The Compare read value from sensor TR5 with
The temperature for discharge temperature suction gas overheating is calculated value of external thermometer. Connect
sensor TR6 exceeds 110-120°C for 60 s. through TR5 - JR0, and controls the position manometer to refrigerant circuit and
(The exact maximum temperature is of the electronic expansion valve. Therefore measure low pressure. Compare
Info Z1 Hot gas temperature too correct readings from these sensors are evaporating tempeature value to read value
5310 A01 Installer dependent on the working point in the
high important. from JR0.
compressor envelope.)
The alarm is blocked if any of the sensors If neither JR0 or TR5 are bad, a possible Use magnet to manually change position of
TR6, JR0 or JR1 is broken. cause could be that the electronic expansion the EEV during operation. This to ensure
valve is not regulating properly. that the valve has not seized.

21
Measure the actual discharge temperature
Defective discharge temperature sensor
with a thermometer and compare it to the
TR6.
value displayed by TR6.
Suction gas overheating too high. The Compare read value from sensor TR5 with
suction gas overheating is calculated value of external thermometer. Connect
through TR5 - JR0, and controls the position manometer to refrigerant circuit and
Alarm Z1 Hot gas temperature Alarm if error code 5310 is registered more of the electronic expansion valve. Therefore measure low pressure. Compare
5311 H01 Customer x correct readings from these sensors are evaporating tempeature value to read value
too high than 2 times within 3 h.
important. from JR0.
If neither JR0 or TR5 are bad, a possible Use magnet to manually change position of
cause could be that the electronic expansion the EEV during operation. This to ensure
valve is not regulating properly. that the valve has not seized.
Lack of refrigerant, either due to insufficient Search for leak and repair if necessary.
filling or due to leak. Refill refrigerant.
Check resistance of sensor TR6 and signal
Warning if the resistance for sensor TR6 > cable and compare to table value in
Info Z1 Hot gas temperature Broken circuit for discharge gas temperature
5314 A01 Installer 364 kOhm (corresponding to a temperature documentation. Measurement is done with
sensor TR6 open circuit sensor TR6.
< -30°C). sensor disconnected from HP board.
Replace sensor if necessary.

Check resistance of sensor TR6 and signal


Shorted circuit (temperature reading > cable and compare to table value in
Info Z1 Hot gas temperature Discharge gas temperature sensor TR6 or
5315 A01 Installer 150°C) for sensor TR6, for more than 1 documentation. Measurement is done with
sensor TR6 short circuit signal cable is shorted.
minute. Compressor operation is halted. sensor disconnected from installer board.
Replace signal cable or sensor if necessary.
Se possible causes for the error codes 5314 See possible actions for the error codes
and 5315. 5314 and 5315.
Alarm Z1 Gaseous refrigerant Alarm if one of the error codes 5314 or 5315
5316 H01 Customer x If the discharge temperature sensor TR6
temperature sensor TR6 fault is registered 3 times within 3 h.
measures correctly, the HP board may be Replace HP board.
defective.
With sensor disconnected from HP board,
Broken condensor outlet sensor TC3/signal measure resistance of sensor/signal cable
Open circuit for sensor TC3 (resistance > cable. and compare to table values in
Info Z1 condenser temp. sensor 32.9 kOhm, corresponding to a temperature documentation.
5320 A01 Installer
TC3 open circuit reading < 0°C). Reset is done automatically Connector not properly seated in HP board. Check connector.
when read temperature exceeds 0°C.
Broken sensor TC3/signal cable. Replace sensor TC3.
Defective HP board. Replace HP board.
Shorted circuit (< 390 Ohm) for condenser With sensor disconnected from HP board,
sensor TC3. measure the resistance of sensor and signal
Broken condenser outlet sensor TC3 or
cable. Compare to table values in
Info Z1 Condenser temp. sensor Shorted circuit for sensor TC3 (resistance < shorted signal cable.
5321 A01 Installer documentation. Repair signal cable or
TC3 short circuit 390 Ohm corresponding to a temperature replace sensor.
reading > 180°C). Reset is done
automatically when read temperature Defective HP board. Replace HP board.
exceeds 180°C.

22
Alarm if any of the error codes 5320 or 5321
Alarm Z1 Condenser See possible causes for error codes 5320, See possible actions for error codes 5320,
5322 H01 Customer x are registered 3 times within 3 hours, or if
temperature sensor TC3 fault 5321. 5321.
any of them is active for more than 30 min.

Warning if more than 20% of data sent to Supply voltage missing to HP board. Check 230 V connection.
Info Z1 Compressor control
5330 A01 Installer the inverter returns with errors (bad reply or
system communication fault Check Modbus cable/connection terminals
no reply). Interference on Modbus.
between HP board and inverter.
Supply voltage missing to HP board. Check 230V connection.
Check Modbus cable/connection terminals
between HP board and inverter. Disconnect
Interference on Modbus, or intermittent
connectors in both ends of the cabling and
Alarm if communication is missing, or more connection in cabling.
Alarm Z1 Compressor control check that the pins are intact. Replace
5331 H01 Customer x than 30% of data sent to inverter returns Modbus cabling if necessary.
system communication fault
with errors (incorrect reply or no reply at all).
Check that 12V DC is available between
Defective HP board. Modbus terminals 31-34 on HP board. If 12V
DC missing, replace HP board.
Defective inverter. Replace inverter.
Low mains voltage. This alarm can also be
registered in the event of a power failure, If repeated warnings, contact the electricity
and is shown when the heat pump is turned supplier.
on again.
Warning if incoming AC voltage to installer
Info Z1 Undervoltage at power board < 170 V. Warning is automatically Bad connection in cable for supply voltage
5347 H01 Installer Ensure proper connection.
supply reset when incoming AC voltage > 190 V for (230 VAC) to installer board.
2 minutes.
If the error code is given constantly while
supply voltage level is approved, there may
Replace the installer board.
be a bad voltage reading caused by
defective installer board.
Measure the voltage. It shall be between
180-253 VAC.
Supply voltage outside of approved range.
Restart the system.
Bad cabling connection between inverter Check cabling/connections between inverter
and compressor. and compressor.
Compressor does not run, locked rotor. (The Liquid in compressor during start attempt. If Make sure that TR1 reads the correct
Info Z1 Control failure on
5350 A01 Installer probability of internal fault inside inverter is the compressor sensor TR1 reads the wrong temperature by measuring the compressor
compressor
low.) value, the compressor start may be granted body with a thermometer and comparing the
before the refrigerant has evaporated. values.
Check that the A- and P-selectors (rotary
encoders) are set according to the wiring
Improper setting of rotary encoders on the
diagram. It's a good idea to double-check
HP board.
these settings if the HP board has previously
been replaced.

23
Alarm if warning 5350 has been registered
more than 2 times within 3 hours, or if the
warning is active for 15 minutes.
Alarm Z1 Control failure on
5351 H01 Customer x Se possible causes for error code 5350. See possible actions for error code 5350.
compressor
The compressor is stopped. Manual
acknowledgment of the alarm is necessary
for new start attempt.

Warning if the inverter registers an Broken/shorted cabling between the inverter Check cabling between inverter and
overcurrent transient to compressor. and compressor. compressor.
Warning is automatically reset after 4
Info Z1 Current consumption at
5354 A01 Installer minutes if the condition is not fulfilled.
compressor too high Measure the supply voltage. It shall be
(The probability of a defective inverter is Supply voltage is not within the approved between 180-253 VAC.
low.) range.
Restart the system.
Broken/shorted cabling between the inverter Check cabling between inverter and
and compressor. compressor.
Alarm after if 3 error codes (error code Defective inverter. Replace inverter.
Alarm Z1 Current consumption
5355 H01 Customer x 5354) are registered within 3 hours, or if the
on compressor too high Measure the resistance between windings
warning is active for 30 minutes.
Electrical fault in compressor. and earth. If resistance < 10 kOhm, replace
the compressor.

Occassional failed start attempts shall be


The most common cause is that the considered normal and does not require
The message is produced if the DC bus compressor fails to start due to internal further actions. If the error code is produced
voltage inside the inverter exceeds 440 VDC characteristics. The inverter then reacts by very often, for instance 4-5 times in a row,
for the 1-phase models and 800 VDC for 3- sending an alarm for overvoltage. blocking the compressor for a longer time,
phase models, for more than 30 s. the problem requires further investigation.

5362 A01 Installer Info Z1 Overvoltage x If the installer board is older than v2.02:
- The message is given on customer level Check main fuses with regard to poor
Intermittent connection in main fuses.
and must be acknowledged in order to allow contact.
a new start attempt. Note. Do not open the inverter to measure
- Se error code 5370 for additional possible the DC bus voltage! Instead measure the
causes and actions. incoming supply voltage to the inverter. It
Too high supply voltage to inverter.
shall be at most 253 VAC for the 1-phase
models and at most 440 VAC for the 3-
phase models.

24
Motor not correctly mounted on electronc
Check motor.
expansion valve.
Check that the electronic expansion valves
Activate test outdoor unit.
open/close in the correct order.
Suction gas overheating < 2 K and
Info Z1 Superheat of refrigerant Measure the resistance between the gray
5366 A01 Installer discharge gas overheating < 20 K for 10
too low cable and orange, red, yellow and black
minutes. Defective expansion valve motor.
cables. 46 kOhm = OK. If broken or shorted
circuit, replace motor.
Expansion valve VR1 opens too much/gets If repeated warnings, replace the expansion
stuck in open position. valve.
Alarm is given if error code 5366 is
registered more than 2 times within 3 h, or if
Alarm Z1 Superheat of
5367 H01 Customer x the warning is continuously active for 15 See possible causes for error code 5366. See possible actions for error code 5366.
refrigerant too low
minutes. The compressor stops. The alarm
requires manual acknowledgement.
TK2 (cold carrier inlet temperature for Intermittent or missing cable connection to
passive cooling station) is more than 1K Check cabling.
mixing valve VK1.
below TB0 (cold carrier return temperature),
The mixing valve motor is incorrectly Check that the motor is correctly mounted
and TB0 < 1°C, despite mixing valve VK1 in
Alarm wrong position on PCS mounted. relative to the valve, so that it can fully close.
5371 H01 Customer the passive cooling station being closed
mixer valve
(from the perspective of the software, i.e.
active closing signal). The alarm is triggered Defective mixing valve motor. Replace the motor on the valve.
when the condition has been met for 15
minutes.
Check screw mountings for cooling coil and
Poor heat transfer to cooling coil. the aluminum cooling plate. Check thermal
Alarm Z1 PFC compressor Alarm if internal temperature sensor in the paste and contact surfaces.
5387 H01 Customer x
control system overheated inverter's PFC module > 110°C.
If repeated alarms, the inverter is likely
Replace inverter.
defective.
Check that the voltage is between 180-253
Bad grid voltage.
VAC.
Check cabling between inverter and
Short-circuit in cabling.
compressor.
Warning is given if inverter registers Incorrect setting on rotary encoder (P-
overcurrent to compressor. selector) on the HP board. An incorrect
Info Z1 Internal compressor Compare P-selection with settinf defined in
5394 A01 Installer setting can result in improper modulation of
control system failure 1 manual.
Warning is automatically reset after 4 the compressor supply voltages, from the
minutes if condition is no longer fulfilled. inverter.
At sporadic occurences of the message,
restart the appliance. Further actions should
High torque in compressor. (Very low
only be necessary if the problem is
probability of error in inverter.)
recurring. See error code 5395 for more
information.

25
See possible causes for error code 5394. See possible actions for error code 5394.
Alarm if 3 error codes (code 5394) are Measure the resistance between the
Alarm Z1 Internal compressor
5395 H01 Customer x registered within 3 hours, or if the warning is Defective compressor. (Very low probability compressor windings and earth. If
control system failure 1
continuously active for 30 minutes. of error in inverter.) resistance < 10 kOhm, replace the
compressor.
Screw terminal on HP board for sensor TR3
Check screw terminal.
has not been tightened properly.
With sensor disconnected from HP board,
Info Z1 Condensate sensor TR3 measure resistance of sensor and compare
5414 A01 Installer Open circuit for temperature sensor TR3. Sensor TR3/signal cable is broken.
heating mode open circuit it to table values in documentation. If
broken, replace sensor.
If the sensor measures correctly but the
Defective HP board. same error code persists, replace the HP
board.
With sensor disconnected from HP board,
measure resistance of sensor and compare
Sensor TR3/signal cable shorted.
it to table values in documentation. If
Info Z1 Condensate sensor TR3 broken, replace sensor.
5415 A01 Installer Shorted circuit for temperature sensor TR3.
heating mode short circuit
Run the system with sensor disconnected
Defective HP board. from the HP board. If the same error code
5415 persists, replace the HP board.
Alarm is given if error code 5414 or 5415 is
registered more than 2 times within 2 h, or if
Alarm Z1 Refrigerant condensate See possible causes for error codes 5414, See possible actions for error codes 5414,
5416 H01 Customer x the circuit for temperature sensor TR3 has
sensor heating mode TR3 fault 5415. 5415.
been continuously shorted/broken for 15
minutes.
Screw terminal on HP board, for sensor
Check screw terminal of HP board.
TR4, is not properly tightened.
With sensor disconnected from HP board,
Info Z1 Condensate sensor TR4 Broken sensor TR4/signal cable. measure its reistance. If broken, replace
5420 A01 Installer Open circuit for temperature sensor TR4.
cooling mode open circuit sensor.
If the sensor measures correctly but the
Defective HP board. same error code persists, replace the HP
board.
With sensor disconnected from HP board,
Sensor TR4/signal cable broken. measure its resistance. If shorted, replace
Info Z1 Condensate sensor TR4 sensor.
5421 A01 Installer Shorted circuit for temperature sensor TR4.
cooling mode short circuit If the sensor measures correctly but the
Defective HP board. same error code persists, replace the HP
board.

26
Alarm is given if any of the error codes 5420
or 5421 are registered more than 2 times
Alarm Z1 Refrigerant condensate See possible causes for error codes 5420, See possible actions for error codes 5420,
5422 H01 Customer x within within 2 hours, or if the circuit for
sensor cooling mode TR4 fault 5421. 5421.
sensor TR4 is continuously broken/shorted
for 15 minutes.
Screw terminal on HP board, for sensor
Check screw terminal on HP board.
TR5, not properly tightened.
With sensor disconnected from HP board,
Info Z1 Suction gas temp. sensor Sensor TR5/signal cable broken. measure its reistance. If broken, replace
5426 A01 Installer Open circuit for temperature sensor TR5.
TR5 open circuit sensor.
If the sensor measures correctly but the
Defective HP board. same error code persists, replace the HP
board.
With the sensor disconnected from HP
Sensor TR5/signal cable shorted. board, measure its resistance. If shorted,
Info Z1 Suction gas temp. sensor replace sensor.
5427 A01 Installer Shorted circuit for temperature sensor TR5.
TR5 short circuit If the sensor measures correctly but the
Defective HP board. same error code persists, replace the HP
board.
Alarm is given if error code 5426 or 5427 is
Alarm Z1 Suction gas registered more than 2 times within 2 h, or if See possible causes for error codes 5426, See possible actions for error codes 5426,
5428 H01 Customer x
temperature sensor TR5 fault the circuit for sensor TR5 is continuously 5427. 5427.
broken/shorted for 15 minutes.
Poor connection in cabling/terminal 17,19 on Check cabling and terminal connections 17,
HP board. 19 on HP board.
Check that 5V DC is available between
terminal 19 and 24 (signal ground), with the
Info Z1 Low pressure sensor JR0 Warning if voltage < 0,5 V DC on terminal Defective HP board.
5432 A01 Installer pressure sensor disconnected. If voltage is
open circuit 17 on HP board. <0.5V, replace the HP board.
Check that 5V DC is available between
Pressure sensor JR0 is defective. terminal 19 and 24 (signal ground). If
voltage is 5V, replace the pressure sensor.
Alarm is given if error code 5432 is
Alarm Z1 Low pressure sensor registered 3 times within 2 h, or if the circuit
5434 H01 Customer x See possible causes for error code 5432. See possible actions for error code 5432.
JR0 fault for JR0 has been continuously open for 15
minutes.

27
Poor connection in cabling/terminal 16,18 on Check cabling and terminal connections 16,
HP board. 18 on HP board.
Check that 5V DC is available between
terminal 18 and 22 (signal ground), with the
Defective HP board.
Info Z1 High pressure sensor Warning if voltage < 0,5 V DC on terminal pressure sensor disconnected. If voltage is
5438 A01 Installer missing or <0.5V, replace the HP board.
JR1 open circuit 16 on HP board.
Check that 5V DC is available between
terminal 18 and 22 (signal ground), with the
Pressure sensor JR1 is defective.
pressure sensor disconnected. If voltage =
5V DC, replace the pressure sensor.
Alarm is given if error code 5438 is
Alarm Z1 High-pressure sensor registered 3 times within 2 h, or if the circuit
5440 H01 Customer x See possible causes for error code 5438. See possible actions for error code 5438.
JR1 fault for JR1 has been continuously open for 15
minutes.
Check refrigerant filling. Note! Activate the
Alarm after 20 minutes if the electronic Too little refrigerant in heat pump. function ”evacuation/fill” function when
Alarm Z1 Refrigerant charge too
5448 H01 Installer expansion valve VR0 has opened 20% more evacuating or filling refrigerant.
low
than calculated value.
Possible leak in refrigerant circuit. Check/repair leak.
Info Z1 Internal fault on
5452 A01 Customer x Alarm for internal fault in inverter. Defective inverter. Replace inverter.
compressor control system
Info Z1 No power supply to Check main fuses with regards to poor
outdoor unit Low or no voltage to outdoor unit.
contact and blown fuses.
Message is given if incoming AC voltage to
("Outdoor unit" is an unfortunate installer board < 165 V for 10 seconds.
5453 A01 Customer x
choice of words, since the Warning is automatically reset after 2 With repeated warnings, contact the
message is applicable for all minutes if the incoming AC voltage > 190 V. Low incoming mains voltage.
electricity supplier.
heat pump types with an installer
board.)
The circuit's own protective thermostat has
Info Underfloor temperature tripped. Alarm is given when the external Protective thermostat for underfloor heating Reset thermostat, adjust heat curve if
5500 A01 Customer x
limiter has tripped input configured for this purpose, on the has been tripped. necessary.
installer board, is closed.
Incorrect cabling/connections. Check cabling/connections.
Poor connection in CAN bus connections on Check CAN bus connections on installer
installer board or power guard. board and power guard.
Interruption/break on CAN bus cable
Info Connection to current Communication between installer board and Replace CAN bus cable.
5503 A01 Installer between installer board and power guard.
monitor faulty power guard is missing for 30 seconds.
Replace to correct type of CAN bus cable.
Incorrect type of CAN bus cable.
Check documentation for more information.
CAN bus cable installed together with/close Separate CAN bus and power cables by at
to supply voltage to heat pump. least 100 mm to prevent interference.

28
Alarm is given if error code 5503 is
Alarm Connection to current registered 3 times within 3 h, or if
5504 A01 Customer See possible causes for error code 5503. See possible actions for error code 5503.
monitor faulty communication with the power guard has
been missing for 30 minutes.

The compressor has not started within 2 Intermittent connection in cabling between
Ensure proper connection.
minutes after start signal has been sent. inverter and compressor.
Alarm Z1 Compressor does not
5506 A01 Installer Automatic acknowledgement happens after
start
2 minutes, whereupon the inverter is allowed Break power to heat pump and turn it on
to make a new start attempt. Temporary malfunction in inverter.
again.
Internal error in inverter. Replace inverter.
The heat carrier flow is too low. The reason
can be long pipe lengths or a heating Try to decrease the pressure drop.
system that is completely or partially closed.
Defective pressure guard, i.e. broken circuit Replace pressure guard if it triggers too
even though the current pressure is below early. Normal breaking pressure is 44 bar
the limit. (R410A).
The circuit for the high pressure guard MR1
5507 A01 Installer Info Z1 MR1 High press. warning Break or poor connection in cabling between Check cabling/connections between MR1
is open. The compressor stops.
MR1 and inverter. and inverter.
Activate function test och check the function
Expansion valve VR0/EEV0 remains closed.
of the expansion valve. If it does not
(Due to the receiver between the two
regulate, first check control cabling between
expansion valves, a high pressure alarm can
HP board and coil, and the coil itself before
be triggered before a ow pressure alarm.)
replacing the complete expansion valve.
Alarm if error code 5507 is registered more
Alarm Z1 MR1 High pressure than 2 times within 3 h, or if the circuit for See possible causes for error code 5507 See possible actions for error code 5507
5508 H01 Customer x
alarm the high pressure guard is continuously above. above.
open for 15 minutes. The compressor stops.
Warning if temperature of JR1 > the The most likely cause is low outdoor
Info Z1 Dew point outside control Too low evaporating temperature in relation
5512 A01 Installer currently allowed envelope, for more than 60 temperature. See diagram in service
range to condensation temperature.
seconds. manual.
Error code 5512 is registered more than 5 The most likely cause is low outdoor
times witin 3 h, or has been continuously Too low evaporating temperature in relation
temperature. See envelope diagram in
active for more than 15 minutes. The to condensation temperature.
5513 H01 Customer Alarm Z1 Dew point too high x service manual.
compressor stops. Manual
acknowledgement is required for new start Too low flow or too high delta on heating
Adjust temperature/flow.
attempt. system.

29
JR0 < minimum allowed evaporating Check function of cold carrier cirkulation
Insufficient flow in cold carrier/brine circuit.
temperature for more than 30 seconds. pump.

Minimum allowed evaporating temperature


Info Z1 Evaporation pressure on
5514 A01 Installer is based on the type of collector used.
JR0 too low Check control cables to expansion valves.
Borehole: -15°C. One of the expansion valves has got stuck
Surface: -15°C. Run test cycle for outdoor unit and check
in its closed position.
Groundwater: -5°C. that the expansion valves are opening.
Exhaust air: -10°C. If any of the voltages are missing, in
Defective HP board. accordance with above, replace the HP
board.

Alarm Indoor and outdoor unit


are incompatible.
If possible, copy setting of old board from
The configuration of the rotary encoder P on Bad combination of P-settings on installer
(Note. The message has been the same appliance. Alternatively, compare
the installer board and HP board board and/or HP board. In many cases it
5522 A01 Customer defined for air/water heat pumps. x the rotary encoder settings with the
respectively, form an unsupported can be that a board has been replaced and
A more correct description is that approved combinations stated in the installer
combination. that the new board has not been configured.
the installer board and HP board guide.
does not work together due to
incorrect addressing.)

One or more incoming phases to the inverter


Check that all phases are connected.
is missing.
Info Z1 Internal fault 3 on
5523 A01 Installer Short circuit in the inverter's PFC circuit. Temporary malfunction. Await possible
compressor control system
Internal error in inverter. alarm in customer level (code 5524), until
applying further actions.
Error code 5523 has been registered more
Alarm Z1 Internal compressor than 2 times within 3 h, or has been
5524 H01 Customer x Internal error in inverter. Replace inverter.
control system fault 3 continuously active for more than 15
minutes.
JR1 > (TC3 + 5°C) and subcooling > (set
Alarm Z1 Too much refrigerant in point value + 5°C). Both conditions needs to Evacuate heat pump and refill with quantity
5527 H01 Customer Heat pump overfilled.
cooling circuit be fulfilled for more than 15 minutes during specifed on type plate.
hot water production, to trigger the alarm.

Bad connection between sensor TR1 and


Check connector.
HP board.
Broken circuit for compressor temperature
sensor TR1. With sensor disconnected from HP board,
Info Z1 Compressor temp. Compressor temperature sensor TR1 or
5531 A01 Installer measure resistance of sensor. If broken
sensor TR1 open circuit signal cable broken.
Operation can continue by the software circuit (infinite resistance), replace sensor.
using discharge temperature TR6-10°C, as
If the sensor demonstrably works but the
a replacement temperature for TR1.
error code is still produced, the HP board Replace HP board.
can be defective.

30
With sensor disconnected from HP board,
Shorted circuit for compressor temperature Compressor sensor TR1/signal cable is
measure resistance of sensor. If shorted,
sensor TR1. shorted.
Info Z1 Compressor temp. replace sensor.
5532 A01 Installer
sensor TR1 short circuit If the sensor demonstrably works but the
Operation can continue by the software
using discharge temperature TR6-10°C, as error code is still produced, the HP board Replace HP board.
a replacement temperature for TR1. can be defective.
One of the error codes 5531 or 5532 is
Alarm Z1 Compressor See possible causes for the error codes See possible actions for the error codes
5533 H01 Customer x active (broken or shorted circuit for TR1), at
temperature sensor TR1 fault 5531, 5532. 5531, 5532.
the same time as sensor TR6 is broken.
Poor connection in CAN bus connections on Check CAN bus connections on installer
installer board or pool module. board and pool module.
Break on CAN bus cable between installer Replace CAN bus cable between installer
board and pool module. board and pool module.
Change to the correct type of cable. More
Alarm Pool module No communication between installer board
5541 H01 Customer Improper type of CAN bus cable. information can be found in the installer
communication failure and pool board for 90 seconds.
guide.
CAN bus cable installed together with/close Separate CAN bus and power cables by at
to supply voltage to heat pump. least 100 mm to prevent interference.
Disconnect/connect cable shield from/to
Improper earthing of CAN bus cable.
earth.
Measure the temperature with an external
Incorrect reading from suction gas thermometer. If the value presented in the
temperature sensor TR5. display does not match the measured valye,
replace the sensor.
Connect manometer check the pressure on
Incorrect reading from low pressure sensor
the low pressure side. Replace the low
Suction gas overheating (TR5 - JR0) JR0.
pressure sensor if the values do not match.
Info Z1 Superheat temperature is exceeds 10 degrees for more than 10
5543 A01 Installer Poor connection of control signal cables for Check that the cabling is properly attached
excessive minutes, where TR5 is the suction gas temp
and JR0 is the low pressure sensor. expansion valve. in both ends.
A suction gas overheating below 6 degrees
for 10 minutes, can be a sign of shortage,
Lack of refrigerant or defective expansion but the symptoms can also be caused by an
valve. expansion valve that doesn't open properly.
Contact local service department for
guidance.
The temperature limit for TB0 may be set
Cold carrier inlet temperature sensor TB0 < Check the set temperature limit for TB0.
lower than necessary.
Info Z1 Brine inlet temperature at set temperature limit - 1K, for 30 s. (Service/
5547 A01 Installer Compare sensor reading to actual
TB0 is too low Heat source settings/ Heat pump/ TB0 brine
temp min. in) Incorrect reading from sensor TB0. temperature. Replace sensor if there is a
deviation.

31
Error code 5547 is registered more than 2
Alarm Z1 Brine inlet temperature times within 3 h, or has been continuously
5549 H01 Customer See possible causes for error code 5547. See possible actions for error code 5547.
TB0 is too low active for 15 minutes. The compressor
stops. Manual acknowledgment is required.
Cold carrier outlet temperature sensor TB1
Compare sensor reading to actual
Info Z1 Brine outlet temperature < set minimum TB0 temperature - 2K, for 30
5551 A01 Installer Incorrect reading from sensor TB1. temperature. Replace sensor if there is a
at TB1 is too low s. (Service/ Heat source settings/ Heat
deviation.
pump/ TB1 brine temp min. out)
Error code 5551 is registered more than 2
Alarm Z1 Brine outlet times within 3 h, or has been continuously
5553 H01 Customer See possible causes for error code 5551. See possible actions for error code 5551.
temperature TB1 is too low active for 15 minutes. The compressor
stops. Manual acknowledgment is required.
Compare sensor reading to actual
Info Z1 Brine inlet temperature at Warning if TB0 > 30°C for 30 s. The
5555 A01 Installer Incorrect reading from sensor TB0. temperature. Replace sensor if there is a
TB0 is too high compressor stops.
deviation.
Error code 5555 is registered more than 2
times within 3 h, or has been continuously
Alarm Z1 Brine inlet temperature
5557 H01 Customer active for more than 15 minutes. The See possible causes for error code 5555. See possible actions for error code 5555.
TB0 is too high
compressor stops. The alarm requires
manual acknowledgment.
Compare sensor reading to actual
Info Z1 Brine outlet temperature Warning if TB1 > 30°C for 30 seconds. The
5559 A01 Installer Incorrect reading from sensor TB0. temperature. Replace sensor if there is a
at TB1 is too high compressor stops.
deviation.

Error code 5559 is registered more than 2


times within 3 h, or has been continuously
active for more than 15 minutes. An Compare sensor reading to actual
Alarm Z1 Brine outlet
5561 H01 Customer additional condition is that the alarm for low Incorrect reading from sensor TB1. temperature. Replace sensor if there is a
temperature TB1 is too high
pressure in the brine circuit is not active at deviation.
the same time. The compressor stops. The
alarm requires manual acknowledgement.
System filter/filterball is clogged. Check filter. Clean if necessary.
De-air brine system according to instruction
Air in brine system.
in manual.
Info Z1 high temperature The temperature difference TB0-TB1 > 10K Test brine pump PB3 using manual
5563 A01 Installer differential between TB0 and for 15 minutes. The alarm is suppressed if Brine circulation pump PB3 is defective.
operation from the display.
TB1 TB1 > 10°C.
Compare displayed values to actual
temperatures measured with an external
Bad reading from brine sensor TB0/TB1.
thermometer. Replace sensor(s) if
deviation(s) found.

32
System filter/filterball is clogged. Check filter. Clean if necessary.

Error code 5563 is registered more than 2 De-air brine system according to instruction
Air in brine system.
times within 3 h, or has been continuously in manual.
Alarm Z1 Temperature difference Test brine pump PB3 using manual
5565 H01 Customer active for more than 15 minutes. The Brine circulation pump PB3 is defective.
between TB0 and TB1 high
compressor stops. Manual operation from the display.
acknowledgement is required.
Compare displayed values to actual
temperatures measured with an external
Bad reading from TB0/TB1.
thermometer. Replace sensor(s) if
deviation(s) found.
With sensor disconnected from HP board,
Defective sensor TB0 or shorted signal
measure resistance of sensor. If shorted,
cable.
Info Z1 Brine inlet temperature replace sensor.
5571 A01 Installer Shorted circuit for temperature sensor TB0.
sensor TB0 short circuit If the sensor demonstrably is working but
the error code is still produced, the HP Replace HP board.
board may be defective.
With sensor disconnected from HP board,
Brine in sensor TB0/signal cable broken. measure resistance of sensor. If broken,
replace sensor.
Info Z1 Brine inlet temperature Screw terminal for brine sensor TB0 not
5573 A01 Installer Broken circuit for temperature sensor TB0. Check screw terminal.
sensor TB0 open circuit properly tightened.
If the sensor demonstrably is working but
the error code is still produced, the HP Replace HP board.
board may be defective.
Error code 5571 or 5573 has been
registered more than 2 times within 2 h, or
Alarm Z1 Brine inlet temperature See possible causes for error codes 5571, See possible actions for error codes5571,
5575 H01 Customer x the circuit for sensor TB0 has been
sensor TB0 fault 5573. 5573.
conintinuously broken or shorted for more
than 15 minutes.
With sensor disconnected from HP board,
Brine out sensor TB1/signal cable is
measure resistance of sensor. If shorted,
shorted.
Info Z1 Brine outlet temp. sensor replace sensor.
5577 A01 Installer Shorted circuit for temperature sensor TB1.
TB1 short circuit If the sensor demonstrably is working but
the error code is still produced, the HP Replace HP board.
board may be defective.

33
With sensor disconnected from HP board,
Brine out sensor TB1/signal cable broken. measure resistance of sensor. If broken,
replace sensor.
Info Z1 Brine outlet temp. sensor Screw terminal for brine sensor TB1 not
5579 A01 Installer Broken circuit for temperature sensor TB1. Check screw terminal.
TB1 open circuit properly tightened.
If the sensor demonstrably is working but
the error code is still produced, the HP Replace HP board.
board may be defective.
Error code 5577 or 5579 has been
Alarm Z1 Brine outlet registered more than 2 times within 2 h, or See possible causes for error codes 5577, See possible actions for error codes 5577,
5581 H01 Customer x
temperature sensor TB1 fault continuous broken or shorted circuit for 5579. 5579.
sensor TB1 for 15 minutes.
Error code 5514 has been registered more
Alarm Z1 Low pressure sensor
5585 H01 Customer x than 2 times within 3 h, or is continuously See possible causes for error code 5514. See possible actions for error code 5514.
detects problems in brine circuit
active for 15 minutes.
Info Pool module communication No communication with pool module for 90 s
5593 A01 Installer EMS cable not connected or broken. Check EMS connection.
failure or more.
Wait two minutes for the appliance to cool
The flow is blocked by valve. down. Check if there is any closed valve
blocking the flow.
TC1 > TC0 + 20K, and T0 < TC0 + 5K. The The flow is blocked because of bad
Ensure that the circulation pump is running.
5594 A01 Customer Alarm Z1 Air in the system (x) condition is monitored for 10 minutes after electrical connection to circulation pump.
activation of electrcal heater. Redo the filling and venting according to
If there is nothing blocking the flow there is described procedure in the documentation.
likely air in the appliance. Ensure that all air is removed from the
appliance and heating system.
Info: Phase loss to compressor One of the phases is not connected between
Connect phase.
inverter and compressor.
// Note that some versions of the The message is given if the inverter detects
5900 H01 Installer
HMI may show the following phase loss to the compressor. Measure the resistance of the compressor
incorrect text: "Internal fault in Broken winding in compressor.
windings.
control device (MCU)"

Measure the voltages. Contact the electricity


Low supply voltage. There shall be at least
5902 A01 Installer Info: Compressor motor overload Current overload for a period of time. supplier for a logged measurement if the
180 VAC betweeen each phase and neutral.
problem is recurring.

Motor control sequencer error (loss of motor Go through the alarm log to see if there are
This alarm often occurs in conjunction with
5903 A01 Installer Info: Fault in compressor motor control). Typically occurs with another higher more inverter-related alarms that might give
other high priority alarm from the inverter.
priority fault from the inverter. clues to what has happened.
Command to stop with fault (from Modbus
5904 A01 Customer Alarm: External fault at inverter? Defective inverter. Replace inverter.
master).
Measure the phases to the inverter. Contact
Alarm: Insufficient supply voltage
5905 A01 Customer x Supply voltage is lower than 180 VAC. Supply voltage is lower than 180 VAC. the electricity supplier if the problem
to inverter control
persists.

34
If the problem keeps appearing several Check the compressor supply. Disconnect
Info: Brief high compr. motor Rapid increase in power load for the
5906 A01 Installer times, it is likely the case that the rotor is the supply and measure the windings of the
overload compressor.
locked. compressor between U-V, V-W, U-W.
Alarm: Inverter control
5908 A01 Customer Initialization error of inverter control. Initialization error. Initialization error.
initialisation fault
Alarm: heat. pump with unknown A pump of unknown function is connected to The pump to general preset address, when Configure the recently connected circulation
5909 A01 Customer
fct. connected to Modbus Modbus. it should not. pump as either PC0 or PC1.
Missing supply voltage to circulation pump. Check supply power to pump.
Alarm: No communication with No communication with heat carrier
5917 A01 Customer x The communicaton cable for Modbus is not Check communicaton cable and
heating pump PC0 circulation pump PC0.
properly connected. connections.
Heat carrier pump PC0 has a PC0 has a
built-in function for flow measurement. PC0
reports low flow if its measurement indicates
Alarm: Flow rate for heating
5918 H01 Customer x less than 50 l/h for 5 s. The alarm invokes Air in system. Check, de-air and fill heating system.
pump PC0 too low
an automated de-airing routine, which runs
for up to 15 minutes. The alarm is reset
automatically when the flow exceeds 60 l/h.
Check filter ball valve and water quality.
Alarm: Heating pump PC0 is Heat carrier pump PC0 reports error for Rotor is blocked by e.g. foreign objects or Remove pump motor from pump housing
5919 A01 Customer x
blocked locked rotor. deposits which prohibit rotation. and remove any dirt from impeller and
housing.
Check line voltage. Check fuses. If the
Alarm: Supply voltage for heating Heat carrier pump PC0 reports error for low The supply voltage for PC0 is lower than voltage is too low, contact the electricity
5920 A01 Customer x
pump PC0 too low supply voltage. 150V. supplier and request a logged measurement
of the voltage.
Break supply voltage to PC0 and turn it on
Alarm: Internal fault in the Heat carrier pump PC0 reports internal
5921 A01 Customer x Internal electrical fault. again. If the error message comes back,
heating pump PC0 electrical fault.
replace the circulation pump.
Check line voltage. Check fuses. If the
Alarm: Supply voltage for heating Heat carrier pump PC0 reports overvoltage voltage is too high, contact the electricity
5922 A01 Customer x Supply voltage to PC0 is too high.
pump PC0 too high on its supply phase. supplier and request a logged measurement
of the voltage.
Alarm: Dry running of heating
5923 A01 Customer x Heat carrier pump PC0 reports dry run. The heating circuit is not properly filled. Fill heating circuit.
pump PC0
Additional circulation pump has been
Info: Flow rate from ext. source A flow is drawn through the heat carrier Check if there is any additional circulation
5937 A01 Installer mounted in the circuit, which is not
by heating pump PC0 pump PC0 by an external source. pump connected in series with PC0.
controlled by the heat pump.

35
The ambient temperature in the installation
room is too high. As recommended in the
Wait for the temperature to drop.
installer guide, the room temperature shall
Info: Temp. in the control device Heat carrier pump PC0 reports an error for not exceed 35°C.
5938 A01 Installer
of heating pump PC0 too high overheated electronics inside its control box.
If the ambient temperature < 25°C and the
error code is still given, the circulation pump Replace circulation pump PC0.
may be defective.
Check line voltage. Check fuses. If the
Info: Supply voltage heating Heat carrier pump PC0 reports error for low The supply voltage for PC0 is lower than voltage is too low, contact the electricity
5939 A01 Installer
pump PC0 too low supply voltage. 195V. supplier and request a logged measurement
of the voltage.
Circulation pump PC0 reports error for
5940 A01 Installer Info: Air in the heating pump PC0 Air in system. Perform de-airing.
presence of air in the heat carrier circuit.
Alarm: PWM signal outside
5980 A01 Customer Configuration error. Configuration error. Replace the inverter.
permissible range
The warning is triggered if the condensing
pressure has not increased by least 0.5 bar
Info: Incorrect running direction in 10 s after run signal was sent fro the Check that the are correctly connected by
5981 A01 Installer Wrong rotation direction in compressor.
of compressor inverter. The compressor is stopped. the compressor (righ phase sequence).
Automatic reset and new start attempt
follows after 2 minutes.

The alarm is produced if error code 5981 is


Alarm: Incorrect running direction registered more than 2 times within 2 h. The
5983 A01 Customer See possible causes for error code 5981. See possible actions for error code 5981.
of compressor compresor stops. Manual acknowledgement
is required for new start attempt.
Detection is made using the pressure
sensors JR0 and JR1, as well as the
No or almost no refrigerant left in the heat Check the accuracy of the sensors with
temperature sensors TB0 and TC0. A
Alarm: No refrigerant in pump. pressure guage and external thermometer.
5984 A01 Customer possibility is that one of the sensors has a
refrigerant circuit measurement error.
Also see error code 5448.
Search for leak and repair if necessary.
Leak in refrigerant circuit.
Refill refrigerant.
Bad connection between inverter and
Check connections.
compressor.
Alarm: Brief high overload for the Very fast increase of compressor motor
5987 A01 Customer Measure the resistance of the compressor
compressor motor load, which usually is a sign of locked rotor.
Damaged windings in the compressor. windings (U-V, V-W, U-W). If shorted or
broken circuit, replace compressor.
Alarm: Fault in the inverter The alarm often occurs in combination with Check the alarm log to see if additional
5988 A01 Customer Loss of motor control.
control MCE other inverter alarm. inverter alarms have been registered.

36
Bad compressor connection. Check connections.
Measure the resistance of the compressor
Alarm: No phase betw. inverter Damaged windings in the compressor. windings (U-V, V-W, U-W). If shorted or
5989 A01 Customer Phase lost to compressor winding.
control and compressor motor broken circuit, replace compressor.
Replace the inverter if none of the possible
Defective inverter.
causes above explains the alarm.
Measure the voltages. Contact the electricity
Alarm: Overload for the Low supply voltage. There shall be at least
5990 A01 Customer Current overload for a period of time. supplier for a logged measurement if the
compressor motor 180 VAC betweeen each phase and neutral.
problem is recurring.
Info: No communication betw. The HP board has lost communication with
5993 A01 Installer Disturbances in Modbus communication. Check Modbus cables.
inv. control and main contr. unit. the inverter.
The pressure guard for the cold carrier Check for leakage and fill up the cold carrier
Leakage or unsufficiently filled cold carrier
5994 A01 Installer Info: Low pressure in brine circuit circuit has tripped (normally open circuit). circuit. Recommended presssure is 2.5-3.0
circuit.
Pressure limit is 0.5 bar. bar.
Invalid configuration of rotary encoder on Compare setting of rotary encoder to
extension board for passive cooling station. documentation.
Alarm: No communication with Check connections. Replace cabling if
No communication with passive cooling Defective CAN wiring.
6212 H01 Customer the passive cooling module necessary.
module. PCM does not resond.
possible If the CAN cabling is intact and properly
Replace extension board for passive cooling
connected, the extension board may be
station.
defective.
Invalid configuration of rotary encoder on Compare setting of rotary encoder to
Info: No communication with the No communication with passive cooling extension board for passive cooling station. documentation.
6213 A01 Installer
passive cooling module possible module. PCM does not resond.
Defective CAN wiring. Check connections.
Info: Signal from upper DHW With the sensor disconnected from the
The circuit for upper DHW sensor TW2 is Defective sensor or short circuit in signal
6216 A01 Installer temp.sens. TW 2 outs. perm. installer board, measure its resistance. If
VKRUWHG 0HDVXUHGWHPSHUDWXUH•ƒ& cable.
range short circuit, replace the sensor.
Poor connection of sensor. Check that the sensor is properly connected.
Info: No signal from upper DHW The circuit for the upper DHW sensor TW2 With the sensor detached from the installer
6217 A01 Installer
temperature sensor TW2 LVEURNHQ 0HDVXUHGWHPSHUDWXUH”ƒ& Defective sensor or break in signal cable. board, measure its resistance. If broken
circuit, replace the sensor.
See possible causes for error code 6216 See possible actions for error code 6216
Error code 6216 or 6217 has been and 6217. and 6217.
Alarm: Signal from upper DHW
registered more than 2 times wihin 3 h,
6218 H01 Customer temp. sensor TW2 outside perm. If the sensor demonstrably is working but
alternatively continuously shorted or broken
range the error code is still produced, the installer Replace the installer board.
sensor for 15 minutes.
board may be defective.

37
When the message is acknowledged on
customer level, it shown a second time after
24 h. New acknowledgement, then a third
The message is displayed when the heat
and last reminder follows after another 24 h.
pump has been in operation for 3 and 5
Info: Maintenance on heat pump When it has been acknowledged there will
6219 H01 Customer years respectively, and seeks to remind the See definition.
due be no more reminders.
customer of warranty service. Error code
6219 and 6220 are given simultaneously.
If technican acknowledges error code 6220
on installer level, further reminders on
customer level are blocked.
The message is displayed when the heat
pump has been in operation for 3 and 5
years respectively, to remind about warranty
service. Error code 6219 and 6220 are given
Acknowledge error code 6220 on installer
simultaneously.
Info: Perform maintenance on level in conjunction with warranty service.
6220 A01 Installer See definition.
heat pump Further reminders on customer level (error
(The run-time timer is located in the installer
code 6219) will be blocked.
board and will therefore be reset if the board
is replaced. Upgrading of software in
existing board does however not affect the
timer.)