C-E Updated After HazOp 12june 01
C-E Updated After HazOp 12june 01
SDV-2000 03106
SDV-2001 03106
PBA-2400 03107
PBA-2600 03107
PBA-2800 03107
SDV-1720A03109
SDV-1720B03109
SSIV-1721 03109
I-1
I-2
LOW ALARM
Bypass Set
Rev System Interlock CAUSE C&E TEST DONE / N.A. Voting TAG No. P&ID Remarks
Note 19
I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A C C T T T C C C 1
I-2 SIF Platform Shutdown Level 2 DONE Note 14 C C T T T C C C 2
Sealine Emergency Shutdown Level 1 A C
Export Pipeline
19 SIS I-1100 Export Pipeline High High Pressure 2oo3 PSH-1723A 03109 2100 PSIG A Y Y X X 17
20 SIS I-1100 Export Pipeline High High Pressure DONE 2oo3 PSH-1723B 03109 2100 PSIG A Y Y X X 18
21 SIS I-1100 Export Pipeline High High Pressure DONE 2oo3 PSH-1723C 03109 2100 PSIG A Y Y X X 19
22 SIS I-1100 Export Pipeline Low Low Pressure DONE 2oo3 Note 1 PSL-1723A 03109 1710 PSIG A A Y Y X X 20
23 SIS I-1100 Export Pipeline Low Low Pressure DONE 2oo3 Note 1 PSL-1723B 03109 1710 PSIG A A Y Y X X 21
24 SIS I-1100 Export Pipeline Low Low Pressure DONE 2oo3 Note 1 PSL-1723C 03109 1710 PSIG A A Y Y X X 22
25 SIS I-1100 Export Pipeline SDV 1720A/B Position Indication DONE ZIC/ZIO-1720 03109 Y Y 28
26 BCS Export Pipeline Pressure DONE PIT-1722 03109 Y Y X X 25
27 BCS PIG Launcher Pressure DONE PIT-1700 03109 Y Y X 26
28 BCS PIG Launcher Incoming Line Pressure DONE PIT-1701 03109 Y Y 27
SIS I-1101 Indication from SCADA_Control Room Handswicth at Onshore Plant HOLD HS-CRXX 03109 A
SIS I-1101 PP1 HAND SWITCH HOLD HS-CRX1 03109 A
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Deleted
ABBREVIATIONS:
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator Note 16: FCV
C =will remainPopen
Close for several seconds
= Permissive untill pump and motor reach
M = Modulate
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. design speed
O = Open R = Reset X = Alarm
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features. Closing procedure to be defined. Note 17: Selection function
S = Start Stpto
= be provided on
Stop Y =MMI
Yes & HMI
Note 4: Permissive to Start. Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 18: Automatic
T = Trip Start/Stop by LIT-2001
A = Activate
Note 5: Permissive to Close. Note 11: C&E Matrix to be developed by Vendor. to a major risk event in the facility.Safety Instrumented Function Level 2: Note 19: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and Set Points Lis
Platform shutdown due to a correctable major risk event in the platform.
ESD/SIS Indications and Alarms
Remarks
03105 2/2
03105 2/2
P&ID
03106
03107
03107
03107
03106
03110
03110
03111
03113
03113
TAG No.
SDV-5500
SDV-5501
SDV-2001
SDV-2000
PBA-2400
PBA-2600
PBA-2800
I-1
I-2
CAUSE & EFFECT DIAGRAM
LOW ALARM
Set
# Rev System Interlock CAUSE C&E TEST DONE / N.A. Voting Bypass TAG No. P&ID Remarks
Note 19
1 I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A T C C C T T T C 1
2 I-2 SIF Platform Shutdown Level 2 DONE Note 14 T C C C T T T C 2
Liquid Accumulator Tank & Pumps
19 SIS I-0900 Liquid Accumulator Tank Level High High HOLD LSH-2002 03106 165" A A Y Y X X 19
20 SIS I-0900 Liquid Accumulator Tank Level High High HOLD LSH-2003 03106 165" A A Y Y X X 20
21 SIS I-0901 Liquid Accumulator Tank Level Low Low DONE LSL-2002 03106 12" T T T C Y Y X X 21
22 SIS I-0901 Liquid Accumulator Tank Level Low Low DONE LSL-2003 03106 12" T T T C Y Y X X 22
23 SIS I-0910A Liquid Accumulator Pump PBA-2400 DONE Note 12 PSL-2402 03107 3.2 PSIG Note 21 T Y Y X X 23
24 SIS I-0910B Liquid Accumulator Pump PBA-2600 DONE Note 12 PSL-2602 03107 3.2 PSIG Note 21 T Y Y X X 24
25 SIS I-0910C Liquid Accumulator Pump PBA-2800 DONE Note 12 PSL-2802 03107 3.2 PSIG Note 21 T Y Y X X 25
26 26
27 27
28 28
RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 12 13 14 15 27 28 29 30 31 32 33 34 35
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Note 13: BD System to be closed in case of Emergency. Note 16: FCV will remainABBREVIATIONS:
open for several seconds until pump and motor reach
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 8: Electric Heaters Auto Reset (when Temperature is restored). Closing procedure to be defined. design speed C = Close P = Permissive M = Modulate
will be displayed and action will be taken by operator Note 9: Interlock to be provided with Auto Reset features. Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 17: Selection function
O =toOpen
be provided on MMI & HMI
R = Reset X = Alarm
Note 3: Deleted Note 10: Deleted to a major risk event in the facility.Safety Instrumented Function Level 2: Note 18: Automatic Start/Stop by LIT-2001
S = Start Stp = Stop Y = Yes
Note 4: Permissive to Start. Note 11: C&E Matrix to be developed by Vendor. Platform shutdown due to a correctable major risk event at the platform. Note 19: Refer to document
T = PERLA.OF.DIEE.51001.SA
Trip A = Activate "Alarms and Set Point List"
Note 5: Permissive to Close. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY Note 20: Manual Start/Stop at MMI & HMI
Note 6: Action linked to "AND" Operator. Override time to be defined by operator Note 21: Pumps will not be able to start at LOW LOW
ESD/SIS Indications and Alarms
033118
03110
03110
03110
03110
03110
03111
03112
03112
03111
P&I
D
9000#1/9
TAG
note 21
note 22
No.
I-1
I-2
SDV-
SDV-
SDV-
SDV-
SDV-
SDV-
SDV-
PBE-
PBE-
3000
3001
3200
3300
3900
4100
4500
4600
4400
9400
DAS
DAS
Emergency Platform Shutdown Level
DiselGenerator
Gas Generator
HIGH ALARM
LOW ALARM
blanketing
1
Rev System Interlock CAUSE Bypass TAG No. P&ID Set Remarks
C&E TEST DONE / N.A. Voting
Note 19
I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A A C C T T C C
I-2 SIF Platform Shutdown Level 2 DONE Note 14 A C C
SIF Fuel Gas skid shut down Level 3 Notes 21, 22 C C C Stp S
Blowdown Scrubber Tank
1 SIS I-1250 Liquid Seal Tank High High Level DONE LSH-3902 03110 28" C Y Y X X 1
2 04 2
3 SIS I-1200 Blowdown Scrubber Tank Level High High DONE LSH-3002 03110 36" A Y Y X X 3
4 SIS I-1200 Blowdown Scrubber Tank Level High High DONE LSH-3003 03110 36" A Y Y X X 4
5 SIS I-1201 Blowdown Scrubber Tank Level Low Low DONE LSL-3002 03110 6" Note 9 C C T T Y Y X X 5
6 SIS I-1201 Blowdown Scrubber Tank Level Low Low DONE LSL-3003 03110 6" Note 9 C C T T Y Y X X 6
7 SIS I-1202 Blowdown Scrubber Pump PBE-3200 Stop Signal DONE AND XS-3200 03110 Note 5 P P Y Y 7
8 SIS I-1202 Blowdown Scrubber Pump PBE-3300 Stop Signal DONE XS-3300 03110 Note 5 P P Y Y 8
9 SIS I-1203 Blowdown Scrubber SDV-3000 Open DONE AND Deleted ZIO-3000 03110 Note 4 P P Y Y 9
10 SIS I-1203 Blowdown Scrubber SDV-3001 Open DONE Deleted ZIO-3001 03110 Note 4 P P Y Y 10
11 BCS Liquid Seal Tank Level Indicator DONE LIT-3900 03110 Y Y X X 11
12 Y Y X X 12
Fuel Gas Skid
30 Deleted 30
31 SIS I-1300 Fuel Gas Scrubber High High Pressure DONE PSH-4401 03112 165 PSIG A Y Y X X 31
32 SIS I-1301 Fuel Gas Scrubber Low Low Pressure HOLD PSL-4401 03112 120 PSIG A Y Y X X 32
33 SIS I-1302 Fuel Gas Filter 1 Pressure Low Low HOLD PSL-4501 03112 120 PSIG C Y Y X X 33
34 SIS I-1303 Fuel Gas Filter 2 Pressure Low Low HOLD PSL-4601 03112 120 PSIG C Y Y X X 34
35 SIS I-1330 Fuel Gas Filter 1 Pressure Low Low HOLD AND PSL-4501 03112 120 PSIG Note 6 A A Y Y X X 35
36 SIS I-1330 Fuel Gas Filter 2 Pressure Low Low HOLD PSL-4601 03112 120 PSIG Note 6 A A Y Y X X 36
37 SIS I-1304 Fuel Gas Scrubber Level High High DONE LSH-4400 03112 14" A A Y Y X X 37
38 SIS I-1305 Fuel Gas Scrubber Level Low Low DONE LSL-4400 03112 6" C Y Y X X 38
39 SIS I-1306 Fuel Gas Filter 1 Level High High DONE LSH-4500 03112 12" C Y Y X X 39
40 SIS I-1307 Fuel Gas Filter 1 Level Low Low DONE LSL-4500 03112 6" C Y Y X X 40
41 SIS I-1308 Fuel Gas Filter 2 Level High High DONE LSH-4600 03112 12" C Y Y X X 41
42 SIS I-1309 Fuel Gas Filter 2 Level Low Low DONE LSL-4600 03112 6" C Y Y X X 42
43 43
1 2 3 4 5 6 7 8 9 10 11 12 13 27 28 29 30 31 32 33 34 35
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator . Note does not apply if running only one filter. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
ABBREVIATIONS:
Note 21: associated SDVs are 9000 (gas gen 1), 9200 (gas gen 2), 6000 (sump tank), 2001 (liq. Acc.), 5600 (methanol), 5300 (corr. Inhib.), 5500 (LDHI)
Note 22: associated pumps are PBH 6100/6200 (sump tank pumps), PBE 3200/3300 (BD scrubber pumps), PBE 5320 /5340 (methanol pumps), PBE 5620/5660 (corr. inhib. pumps), PBE 5520/40/60/80/90 (LDHI pumps)
ESD/SIS Indications and Alarms
Remarks
TAG No. P&ID
03111
03111
03111
03111
03113
SDV-4100
SDV-4400
HAP-4100
HAP-4200
I-2
Emergency Platform Shutdown Level 1
CAUSE & EFFECT DIAGRAM
EFFECT
EFFECT
LOW ALARM
# Rev System Interlock CAUSE Bypass TAG No. P&ID Set Remarks
C&E TEST DONE / N.A. Voting
Note 19
1 I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A C C T T C 1
2 I-2 SIF Platform Shutdown Level 2 DONE Note 14 C C T T C 2
Fuel Gas Scrubber
3 SIS I-1310 Fuel Gas Scrubber High High Temperature DONE TSH-4401 03112 115ºF Note 8 T T Y Y X X 3
SIS I-13XX Electric Fuel Gas Heater 1 High High Temperature HOLD TSH-4501A 03111 T T Y Y
SIS I-13XX Electric Fuel Gas Heater 12High High Temperature HOLD TSH-4502A 03111 T T Y Y
4 4
49 BCS Shell High Temperature Alarm DONE XA-4101A 03111 Y Y X 49
50 BCS Shell High HighTemperature Alarm DONE XA-4101B 03111 Note 23 Y Y X 50
51 BCS Heater HighTemperature Alarm DONE XA-4100A 03111 Y Y X 51
52 BCS Heater High HighTemperature Alarm DONE XA-4100B 03111 Note 23 Y Y X 52
53 BCS Shell High Temperature Alarm DONE XA-4201A 03111 Y Y X 53
54 BCS Shell High HighTemperature Alarm DONE XA-4201B 03111 Note 23 Y Y X 54
55 BCS Heater HighTemperature Alarm DONE XA-4200A 03111 Y Y X 55
56 BCS Heater High HighTemperature Alarm DONE XA-4200B 03111 Note 23 Y Y X 56
RESET
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
ABBREVIATIONS:
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator Note 16:
C =FCV will remain
Close open for several
P = Permissive seconds untill pump and motor reach
M = Modulate
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. designOspeed
= Open R = Reset X = Alarm
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features Closing procedure to be defined. Note 17:
S =Selection
Start function
Stp to be provided
= Stop on MMI & HMI
Y = Yes
Note 4: Permissive to Start Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 18:
T =Automatic
Trip AStart/Stop
= Activateby LIT-2001
Note 5: Permissive to Close Note 11: C&E Matrix to be developed by Vendor to a major risk event in the facility.Safety Instrumented Function Level 2: Note 19: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and Set Point
Platform shutdown due to a correctable major risk event in the platform. Note 20: The
Note 22:amount
Remoteof gas will be in
Permisive given
Autoin MMSCF and the flow rate in MMSC
Note 21: Manual
Note ON/OFF
23: Local Heater
Heater Panel Control
Shutdown
ESD/SIS Indications and Alarms
Remarks
03113-2
03113-2
03113-2
P&ID
PBHM-6600 03114
PBHM-6700 03114
TAG No.
SDV-6000
I-2
EFFECT
LOW ALARM
# Rev System Interlock CAUSE Bypass TAG No. P&ID Set Remarks
C&E TEST DONE / N.A. Voting
Note 22
1 I-1 Emergency Platform Shutdown Level 1 DONE A C T T C C 1
2 I-2 SIF Platform Shutdown Level 2 DONE C C C 2
Sump Tank
3 SIS I-1400 Sump Tank High Level DONE LSH-6001 03113-2 48" A Y Y X X 3
4 SIS I-1400 Sump Tank High Level DONE LSH-6003 03113-2 48" A Y Y X X 4
5 SIS I-1401 Sump Tank Low Level DONE LSL-6001 03113-2 20" C C Y Y X X 5
6 SIS I-1401 Sump Tank Low Level DONE LSL-6003 03113-2 20" C C Y Y X X 6
7 SIS I-1402 Instrument Air Shutdown Valve SDV-6001 Closed DONE AND ZIC-6001 03113-2 Note 5 P Y Y 7
8 SIS I-1404 Instrument Air Shutdown Valve SDV-6002 Closed DONE ZIC-6002 03113-2 Note 5 P
9 SIS I-1403 Sump Tank Blanketing SDV-6000 Open ZIO-6000 03113-2 Note 4 P P Y Y 8
10 BCS Sump Tank Level DONE LIT-6000 03113-2 Y Y X 9
11 BCS Oil Bucket level control DONE LIC-6002 03113-2 Y Y 10
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Note 13: Blowdown System to be isolated in case of Emergency. Note 17: Selection
ABBREVIATIONS:
function to be provided on MMI & HMI
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 8: Electric Heaters Auto Reset (when Temperature is restored). Closing procedure to be defined. C = CloseP
Note 18: Automatic = Permissive
Start/Stop M = Modulate
by LIT-2001
will be displayed and action will be taken by operator Note 9: Interlock to be provided with Auto Reset features. Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 19: Low
O =Alarm
Openactivation
R = Resetlinked toXLY-6002
= Alarm A/B open
Note 3: Deleted Note 10: Deleted to a major risk event in the facility. Safety Instrumented Function Level 2: S = Start to
Note 20: Connected Stp = Stop
SIS Y alarm
but not safe = Yes
Note 4: Permissive to Start. Note 11: C&E Matrix to be developed by Vendor. Platform shutdown due to a correctable major risk event in the platform. T = TripwillAsend
Note 21: PS-3800 = Activate
an alarm to indicate that CO2 has been re
Note 5: Permissive to Close. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY Note 22: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and
Note 6: Action linked to "AND" Operator. Override time to be defined by operator Note 16: FCV will remain open for several seconds untill pump and motor reach Note 23: Manually operated at the MMI and HMI
design speed
ESD/SIS Indications and Alarms
03104 Note 13
03108 Note 13
SDV-7800 03116
CZZM-700003115
CZZM-720003115
PBE-8200 03117
PBE-8000 03117
DAN-9000 03118
SDV-9000 03118
SDV-9001 03118
DAN-9200 03118
SDV-9200 03118
SDV-9201 03118
DAN-9400 03119
I-1
I-2
EFFECT
EFFECT
Gas Generator #2
HIGH ALARM
LOW ALARM
Set
# Rev System Interlock CAUSE C&E TEST DONE / N.A. Voting Bypass TAG No. P&ID Remarks
Note 19
1 I-1 Emergency Platform Shutdown Level 1 DONE A T T T 1
2 I-2 SIF Platform Shutdown Level 2 DONE T T 2
Instrument Air Package
3 SIS I-1800 Instrument Air Header Low Pressure DONE PSL-7807 03116 75 PSIG A A Y Y X X 3
4 SIS I-1801 Instrument Air Receiver Low Pressure DONE PSL-7803 03115 90 PSIG C Y Y X X 4
5 SIS I-1802 Air Compressor Package DONE XS-7000/7200 03115 Note 11 T T Y Y 5
6 04 BCS Air Compressor Package DONE XS-7002A 03115 Note 11 Y Y 6
7 SIS Wet Air Receiver - Level Indication DONE LI-7500 03115 Note 11 Y Y X X 7
8 8
9 BCS Air Compressor Motor - Running / Stopped DONE XI-7000A 03115 Note 11 Y Y 9
10 04 BCS Air Compressor Motor - Fault DONE XA-7000C 03115 Note 11 Y Y 10
11 BCS Air Compressor Motor - Start / Stop DONE XS-7000A 03115 Note 11 Y Y 11
12 BCS Air Compressor Motor - Running / Stopped DONE XI-7200A 03115 Note 11 Y Y 12
13 04 BCS Air Compressor Motor - Fault DONE XI-7200C 03115 Note 11 Y Y 13
14 BCS Air Compressor Motor - Start / Stop DONE XS-7200A 03115 Note 11 Y Y 14
15 BCS Air Compressor Package - Common Alarm DONE XA-7001 03115 Note 11 Y Y X X 15
16 BCS Starting Air Receiver Drain DONE LIT-7800 03115 Note 11 Y Y X 16
17 BCS BCS Remote I/O: Air Compressor Skid DONE RIO-7000A 03115 Note 11 Y Y X X 17
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator P = Permissive
Note 16: FCV will remain open for several seconds untill M = Modulate
pump and motor reach
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. design speed R = Reset X = Alarm
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features. Closing procedure to be defined. Stp= on
Note 17: Selection function to be provided Stop
MMI & HMIY = Yes
Note 4: Permissive to Start. Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due A=Activate
Note 18: Automatic Start/Stop by LIT-2001
Note 5: Permissive to Close. Note 11: C&E Matrix developed by Vendor to be included with this Master Document. to a major risk event in the facility.Safety Instrumented Function Level 2: Note 19: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and Set Points List"
Platform shutdown due to a correctable major risk event in the platform.
ESD/SIS Indications and Alarms
03118
03118
03119
03118
GSH-0101 03902
03902
03902
03902
03902
03902
ESDV9000
ESDV9200
XS-9005
XS-9205
XS-9405
XS-9000
XA-0103
XA-0101
XA-0102
XA-0105
XA-0104
CAUSE & EFFECT DIAGRAM
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
ABBREVIATIONS:
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator C = Close
Note 16: FCV will remain open for several seconds untill pumpP =and
Permissive
motor reach
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. design speed. O = Open R = Reset
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features. Closing procedure to be defined. S = Start Stp= Stop
Note 4: Permissive to Start. Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due T = Trip
Note 17: Selection function to be provided on MMI & HMI A = Activate
Note 5: Permissive to Close. Note 11: C&E Matrix to be developed by Vendor. to a major risk event in the facility. Safety Instrumented Function Level 2: Note 18: Automatic Start/Stop by LIT-2001
M = Modulate
Note 19: MCC gas detectors shall
Platform shutdown due to a correctable major risk event in the platform. trip all generators through XS-9000 X = Alarm Y = Yes
NOT through XS-9005; XS-9205 or
ESD/SIS Indications and Alarms
03118
03118
03119
03118
GSH-0101 03902
03902
03902
03902
03902
03902
ESDV9000
ESDV9200
XS-9005
XS-9205
XS-9405
XS-9000
XA-0103
XA-0101
XA-0102
XA-0105
XA-0104
CAUSE & EFFECT DIAGRAM
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
ABBREVIATIONS:
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator C = Close
Note 16: FCV will remain open for several seconds untill pumpP =and
Permissive
motor reach
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. design speed. O = Open R = Reset
Note 3: Deleted
Note 4: Permissive to Start.
Note 5: Permissive to Close.
Note 9: Interlock to be provided with Auto Reset features.
Note 10: Deleted
Note 11: C&E Matrix to be developed by Vendor.
Nuevo Valor 72 Closing procedure to be defined.
Note 14: Emergency Platform SD Level 1:Total facility shutdown due
to a major risk event in the facility. Safety Instrumented Function Level 2:
S = Start
T = Trip
Note 17: Selection function to be provided
Note 18: Automatic Start/Stop by LIT-2001
on MMI & HMI
M = Modulate
Stp= Stop
A = Activate
PSI. Platform shutdown due to a correctable major risk event in the platform.
Note 19: MCC gas detectors shall
trip all generators through XS-9000 X = Alarm
NOT through XS-9005; XS-9205 or
Y = Yes
SDV-2000 03106
SDV-2001 03106
PBA-2400 03107
PBA-2600 03107
PBA-2800 03107
SDV-1720A03109
SDV-1720B03109
SSIV-1721 03109
I-1
I-2
LOW ALARM
Bypass Set
Rev System Interlock CAUSE C&E TEST DONE / N.A. Voting TAG No. P&ID Remarks
Note 19
I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A C C T T T C C C 1
I-2 SIF Platform Shutdown Level 2 DONE Note 14 C C T T T C C C 2
Sealine Emergency Shutdown Level 1 A C
Export Pipeline
19 SIS I-1100 Export Pipeline High High Pressure 2oo3 PSH-1723A 03109 2100 PSIG A Y Y X X 17
20 SIS I-1100 Export Pipeline High High Pressure DONE 2oo3 PSH-1723B 03109 2100 PSIG A Y Y X X 18
21 SIS I-1100 Export Pipeline High High Pressure DONE 2oo3 PSH-1723C 03109 2100 PSIG A Y Y X X 19
22 SIS I-1100 Export Pipeline Low Low Pressure DONE 2oo3 Note 1 PSL-1723A 03109 1710 PSIG A A Y Y X X 20
23 SIS I-1100 Export Pipeline Low Low Pressure DONE 2oo3 Note 1 PSL-1723B 03109 1710 PSIG A A Y Y X X 21
24 SIS I-1100 Export Pipeline Low Low Pressure DONE 2oo3 Note 1 PSL-1723C 03109 1710 PSIG A A Y Y X X 22
25 SIS I-1100 Export Pipeline SDV 1720A/B Position Indication DONE ZIC/ZIO-1720 03109 Y Y 28
26 BCS Export Pipeline Pressure DONE PIT-1722 03109 Y Y X X 25
27 BCS PIG Launcher Pressure DONE PIT-1700 03109 Y Y X 26
28 BCS PIG Launcher Incoming Line Pressure DONE PIT-1701 03109 Y Y 27
SIS I-1101 Indication from SCADA_Control Room Handswicth at Onshore Plant HOLD HS-CRXX 03109 A
SIS I-1101 PP1 HAND SWITCH HOLD HS-CRX1 03109 A
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Deleted
ABBREVIATIONS:
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator Note 16: FCV
C =will remainPopen
Close for several seconds
= Permissive untill pump and motor reach
M = Modulate
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. design speed
O = Open R = Reset X = Alarm
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features. Closing procedure to be defined. Note 17: Selection function
S = Start Stpto
= be provided on
Stop Y =MMI
Yes & HMI
Note 4: Permissive to Start. Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 18: Automatic
T = Trip Start/Stop by LIT-2001
A = Activate
Note 5: Permissive to Close. Note 11: C&E Matrix to be developed by Vendor. to a major risk event in the facility.Safety Instrumented Function Level 2: Note 19: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and Set Points Lis
Platform shutdown due to a correctable major risk event in the platform.
MOC-0140.
CAMBIO PSL-9814 E IMPLEMENTACIÓN
DE VOTING 2oo3 PSL-0101B/0201B.
JUN-2018.
ESD/SIS Indications and Alarms
Remarks
03105 2/2
03105 2/2
P&ID
03106
03107
03107
03107
03106
03110
03110
03111
03113
03113
TAG No.
SDV-5500
SDV-5501
SDV-2001
SDV-2000
PBA-2400
PBA-2600
PBA-2800
I-1
I-2
CAUSE & EFFECT DIAGRAM
LOW ALARM
Set
# Rev System Interlock CAUSE C&E TEST DONE / N.A. Voting Bypass TAG No. P&ID Remarks
Note 19
1 I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A T C C C T T T C 1
2 I-2 SIF Platform Shutdown Level 2 DONE Note 14 T C C C T T T C 2
Liquid Accumulator Tank & Pumps
19 SIS I-0900 Liquid Accumulator Tank Level High High HOLD LSH-2002 03106 165" A A Y Y X X 19
20 SIS I-0900 Liquid Accumulator Tank Level High High HOLD LSH-2003 03106 165" A A Y Y X X 20
21 SIS I-0901 Liquid Accumulator Tank Level Low Low DONE LSL-2002 03106 12" T T T C Y Y X X 21
22 SIS I-0901 Liquid Accumulator Tank Level Low Low DONE LSL-2003 03106 12" T T T C Y Y X X 22
23 SIS I-0910A Liquid Accumulator Pump PBA-2400 DONE Note 12 PSL-2402 03107 3.2 PSIG Note 21 T Y Y X X 23
24 SIS I-0910B Liquid Accumulator Pump PBA-2600 DONE Note 12 PSL-2602 03107 3.2 PSIG Note 21 T Y Y X X 24
25 SIS I-0910C Liquid Accumulator Pump PBA-2800 DONE Note 12 PSL-2802 03107 3.2 PSIG Note 21 T Y Y X X 25
26 26
27 27
28 28
RESET
1 1
2 2
3 3
4 4
1 2 3 4 5 6 7 8 9 10 11 12 13 12 13 14 15 27 28 29 30 31 32 33 34 35
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Note 13: BD System to be closed in case of Emergency. Note 16: FCV will remainABBREVIATIONS:
open for several seconds until pump and motor reach
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 8: Electric Heaters Auto Reset (when Temperature is restored). Closing procedure to be defined. design speed C = Close P = Permissive M = Modulate
will be displayed and action will be taken by operator Note 9: Interlock to be provided with Auto Reset features. Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 17: Selection function
O =toOpen
be provided on MMI & HMI
R = Reset X = Alarm
Note 3: Deleted Note 10: Deleted to a major risk event in the facility.Safety Instrumented Function Level 2: Note 18: Automatic Start/Stop by LIT-2001
S = Start Stp = Stop Y = Yes
Note 4: Permissive to Start. Note 11: C&E Matrix to be developed by Vendor. Platform shutdown due to a correctable major risk event at the platform. Note 19: Refer to document
T = PERLA.OF.DIEE.51001.SA
Trip A = Activate "Alarms and Set Point List"
Note 5: Permissive to Close. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY Note 20: Manual Start/Stop at MMI & HMI
Note 6: Action linked to "AND" Operator. Override time to be defined by operator Note 21: Pumps will not be able to start at LOW LOW
MOC-0140.
CAMBIO PSL-9814 E IMPLEMENTACIÓN
DE VOTING 2oo3 PSL-0101B/0201B.
JUN-2018.
ESD/SIS Indications and Alarms
033118
03110
03110
03110
03110
03110
03111
03112
03112
03111
P&I
D
9000#1/9
TAG
note 21
note 22
No.
I-1
I-2
SDV-
SDV-
SDV-
SDV-
SDV-
SDV-
SDV-
PBE-
PBE-
3000
3001
3200
3300
3900
4100
4500
4600
4400
9400
DAS
DAS
Emergency Platform Shutdown Level
DiselGenerator
Gas Generator
HIGH ALARM
LOW ALARM
blanketing
1
Rev System Interlock CAUSE Bypass TAG No. P&ID Set Remarks
C&E TEST DONE / N.A. Voting
Note 19
I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A A C C T T C C
I-2 SIF Platform Shutdown Level 2 DONE Note 14 A C C
SIF Fuel Gas skid shut down Level 3 Notes 21, 22 C C C Stp S
Blowdown Scrubber Tank
1 SIS I-1250 Liquid Seal Tank High High Level DONE LSH-3902 03110 28" C Y Y X X 1
2 04 2
3 SIS I-1200 Blowdown Scrubber Tank Level High High DONE LSH-3002 03110 36" A Y Y X X 3
4 SIS I-1200 Blowdown Scrubber Tank Level High High DONE LSH-3003 03110 36" A Y Y X X 4
5 SIS I-1201 Blowdown Scrubber Tank Level Low Low DONE LSL-3002 03110 6" Note 9 C C T T Y Y X X 5
6 SIS I-1201 Blowdown Scrubber Tank Level Low Low DONE LSL-3003 03110 6" Note 9 C C T T Y Y X X 6
7 SIS I-1202 Blowdown Scrubber Pump PBE-3200 Stop Signal DONE AND XS-3200 03110 Note 5 P P Y Y 7
8 SIS I-1202 Blowdown Scrubber Pump PBE-3300 Stop Signal DONE XS-3300 03110 Note 5 P P Y Y 8
9 SIS I-1203 Blowdown Scrubber SDV-3000 Open DONE AND Deleted ZIO-3000 03110 Note 4 P P Y Y 9
10 SIS I-1203 Blowdown Scrubber SDV-3001 Open DONE Deleted ZIO-3001 03110 Note 4 P P Y Y 10
11 BCS Liquid Seal Tank Level Indicator DONE LIT-3900 03110 Y Y X X 11
12 Y Y X X 12
Fuel Gas Skid
30 Deleted 30
31 SIS I-1300 Fuel Gas Scrubber High High Pressure DONE PSH-4401 03112 165 PSIG A Y Y X X 31
32 SIS I-1301 Fuel Gas Scrubber Low Low Pressure HOLD PSL-4401 03112 120 PSIG A Y Y X X 32
33 SIS I-1302 Fuel Gas Filter 1 Pressure Low Low HOLD PSL-4501 03112 120 PSIG C Y Y X X 33
34 SIS I-1303 Fuel Gas Filter 2 Pressure Low Low HOLD PSL-4601 03112 120 PSIG C Y Y X X 34
35 SIS I-1330 Fuel Gas Filter 1 Pressure Low Low HOLD AND PSL-4501 03112 120 PSIG Note 6 A A Y Y X X 35
36 SIS I-1330 Fuel Gas Filter 2 Pressure Low Low HOLD PSL-4601 03112 120 PSIG Note 6 A A Y Y X X 36
37 SIS I-1304 Fuel Gas Scrubber Level High High DONE LSH-4400 03112 14" A A Y Y X X 37
38 SIS I-1305 Fuel Gas Scrubber Level Low Low DONE LSL-4400 03112 6" C Y Y X X 38
39 SIS I-1306 Fuel Gas Filter 1 Level High High DONE LSH-4500 03112 12" C Y Y X X 39
40 SIS I-1307 Fuel Gas Filter 1 Level Low Low DONE LSL-4500 03112 6" C Y Y X X 40
41 SIS I-1308 Fuel Gas Filter 2 Level High High DONE LSH-4600 03112 12" C Y Y X X 41
42 SIS I-1309 Fuel Gas Filter 2 Level Low Low DONE LSL-4600 03112 6" C Y Y X X 42
43 43
1 2 3 4 5 6 7 8 9 10 11 12 13 27 28 29 30 31 32 33 34 35
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator . Note does not apply if running only one filter. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
ABBREVIATIONS:
Note 21: associated SDVs are 9000 (gas gen 1), 9200 (gas gen 2), 6000 (sump tank), 2001 (liq. Acc.), 5600 (methanol), 5300 (corr. Inhib.), 5500 (LDHI)
Note 22: associated pumps are PBH 6100/6200 (sump tank pumps), PBE 3200/3300 (BD scrubber pumps), PBE 5320 /5340 (methanol pumps), PBE 5620/5660 (corr. inhib. pumps), PBE 5520/40/60/80/90 (LDHI pumps)
MOC-0140.
CAMBIO PSL-9814 E IMPLEMENTACIÓN
DE VOTING 2oo3 PSL-0101B/0201B.
JUN-2018.
ESD/SIS Indications and Alarms
Remarks
TAG No. P&ID
03111
03111
03111
03111
03113
SDV-4100
SDV-4400
HAP-4100
HAP-4200
I-2
Emergency Platform Shutdown Level 1
CAUSE & EFFECT DIAGRAM
EFFECT
EFFECT
LOW ALARM
# Rev System Interlock CAUSE Bypass TAG No. P&ID Set Remarks
C&E TEST DONE / N.A. Voting
Note 19
1 I-1 Emergency Platform Shutdown Level 1 DONE Note 14 A C C T T C 1
2 I-2 SIF Platform Shutdown Level 2 DONE Note 14 C C T T C 2
Fuel Gas Scrubber
3 SIS I-1310 Fuel Gas Scrubber High High Temperature DONE TSH-4401 03112 115ºF Note 8 T T Y Y X X 3
SIS I-13XX Electric Fuel Gas Heater 1 High High Temperature HOLD TSH-4501A 03111 T T Y Y
SIS I-13XX Electric Fuel Gas Heater 12High High Temperature HOLD TSH-4502A 03111 T T Y Y
4 4
49 BCS Shell High Temperature Alarm DONE XA-4101A 03111 Y Y X 49
50 BCS Shell High HighTemperature Alarm DONE XA-4101B 03111 Note 23 Y Y X 50
51 BCS Heater HighTemperature Alarm DONE XA-4100A 03111 Y Y X 51
52 BCS Heater High HighTemperature Alarm DONE XA-4100B 03111 Note 23 Y Y X 52
53 BCS Shell High Temperature Alarm DONE XA-4201A 03111 Y Y X 53
54 BCS Shell High HighTemperature Alarm DONE XA-4201B 03111 Note 23 Y Y X 54
55 BCS Heater HighTemperature Alarm DONE XA-4200A 03111 Y Y X 55
56 BCS Heater High HighTemperature Alarm DONE XA-4200B 03111 Note 23 Y Y X 56
RESET
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
ABBREVIATIONS:
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator Note 16:
C =FCV will remain
Close open for several
P = Permissive seconds untill pump and motor reach
M = Modulate
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. designOspeed
= Open R = Reset X = Alarm
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features Closing procedure to be defined. Note 17:
S =Selection
Start function
Stp to be provided
= Stop on MMI & HMI
Y = Yes
Note 4: Permissive to Start Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 18:
T =Automatic
Trip AStart/Stop
= Activateby LIT-2001
Note 5: Permissive to Close Note 11: C&E Matrix to be developed by Vendor to a major risk event in the facility.Safety Instrumented Function Level 2: Note 19: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and Set Point
Platform shutdown due to a correctable major risk event in the platform. Note 20: The
Note 22:amount
Remoteof gas will be in
Permisive given
Autoin MMSCF and the flow rate in MMSC
Note 21: Manual
Note ON/OFF
23: Local Heater
Heater Panel Control
Shutdown
MOC-0140.
CAMBIO PSL-9814 E IMPLEMENTACIÓN
DE VOTING 2oo3 PSL-0101B/0201B.
JUN-2018.
ESD/SIS Indications and Alarms
Remarks
03113-2
03113-2
03113-2
P&ID
PBHM-6600 03114
PBHM-6700 03114
TAG No.
SDV-6000
I-2
EFFECT
LOW ALARM
# Rev System Interlock CAUSE Bypass TAG No. P&ID Set Remarks
C&E TEST DONE / N.A. Voting
Note 22
1 I-1 Emergency Platform Shutdown Level 1 DONE A C T T C C 1
2 I-2 SIF Platform Shutdown Level 2 DONE C C C 2
Sump Tank
3 SIS I-1400 Sump Tank High Level DONE LSH-6001 03113-2 48" A Y Y X X 3
4 SIS I-1400 Sump Tank High Level DONE LSH-6003 03113-2 48" A Y Y X X 4
5 SIS I-1401 Sump Tank Low Level DONE LSL-6001 03113-2 20" C C Y Y X X 5
6 SIS I-1401 Sump Tank Low Level DONE LSL-6003 03113-2 20" C C Y Y X X 6
7 SIS I-1402 Instrument Air Shutdown Valve SDV-6001 Closed DONE AND ZIC-6001 03113-2 Note 5 P Y Y 7
8 SIS I-1404 Instrument Air Shutdown Valve SDV-6002 Closed DONE ZIC-6002 03113-2 Note 5 P
9 SIS I-1403 Sump Tank Blanketing SDV-6000 Open ZIO-6000 03113-2 Note 4 P P Y Y 8
10 BCS Sump Tank Level DONE LIT-6000 03113-2 Y Y X 9
11 BCS Oil Bucket level control DONE LIC-6002 03113-2 Y Y 10
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Note 13: Blowdown System to be isolated in case of Emergency. Note 17: Selection
ABBREVIATIONS:
function to be provided on MMI & HMI
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 8: Electric Heaters Auto Reset (when Temperature is restored). Closing procedure to be defined. C = CloseP
Note 18: Automatic = Permissive
Start/Stop M = Modulate
by LIT-2001
will be displayed and action will be taken by operator Note 9: Interlock to be provided with Auto Reset features. Note 14: Emergency Platform SD Level 1:Total facility shutdown due Note 19: Low
O =Alarm
Openactivation
R = Resetlinked toXLY-6002
= Alarm A/B open
Note 3: Deleted Note 10: Deleted to a major risk event in the facility. Safety Instrumented Function Level 2: S = Start to
Note 20: Connected Stp = Stop
SIS Y alarm
but not safe = Yes
Note 4: Permissive to Start. Note 11: C&E Matrix to be developed by Vendor. Platform shutdown due to a correctable major risk event in the platform. T = TripwillAsend
Note 21: PS-3800 = Activate
an alarm to indicate that CO2 has been re
Note 5: Permissive to Close. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY Note 22: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and
Note 6: Action linked to "AND" Operator. Override time to be defined by operator Note 16: FCV will remain open for several seconds untill pump and motor reach Note 23: Manually operated at the MMI and HMI
design speed
MOC-0140.
CAMBIO PSL-9814 E IMPLEMENTACIÓN
DE VOTING 2oo3 PSL-0101B/0201B.
JUN-2018.
ESD/SIS Indications and Alarms
03104 Note 13
03108 Note 13
SDV-7800 03116
CZZM-700003115
CZZM-720003115
PBE-8200 03117
PBE-8000 03117
DAN-9000 03118
SDV-9000 03118
SDV-9001 03118
DAN-9200 03118
SDV-9200 03118
SDV-9201 03118
DAN-9400 03119
I-1
I-2
EFFECT
EFFECT
Gas Generator #2
HIGH ALARM
LOW ALARM
Set
# Rev System Interlock CAUSE C&E TEST DONE / N.A. Voting Bypass TAG No. P&ID Remarks
Note 19
1 I-1 Emergency Platform Shutdown Level 1 DONE A T T T 1
2 I-2 SIF Platform Shutdown Level 2 DONE T T 2
Instrument Air Package
3 SIS I-1800 Instrument Air Header Low Pressure DONE PSL-7807 03116 75 PSIG A A Y Y X X 3
4 SIS I-1801 Instrument Air Receiver Low Pressure DONE PSL-7803 03115 90 PSIG C Y Y X X 4
5 SIS I-1802 Air Compressor Package DONE XS-7000/7200 03115 Note 11 T T Y Y 5
6 04 BCS Air Compressor Package DONE XS-7002A 03115 Note 11 Y Y 6
7 SIS Wet Air Receiver - Level Indication DONE LI-7500 03115 Note 11 Y Y X X 7
8 8
9 BCS Air Compressor Motor - Running / Stopped DONE XI-7000A 03115 Note 11 Y Y 9
10 04 BCS Air Compressor Motor - Fault DONE XA-7000C 03115 Note 11 Y Y 10
11 BCS Air Compressor Motor - Start / Stop DONE XS-7000A 03115 Note 11 Y Y 11
12 BCS Air Compressor Motor - Running / Stopped DONE XI-7200A 03115 Note 11 Y Y 12
13 04 BCS Air Compressor Motor - Fault DONE XI-7200C 03115 Note 11 Y Y 13
14 BCS Air Compressor Motor - Start / Stop DONE XS-7200A 03115 Note 11 Y Y 14
15 BCS Air Compressor Package - Common Alarm DONE XA-7001 03115 Note 11 Y Y X X 15
16 BCS Starting Air Receiver Drain DONE LIT-7800 03115 Note 11 Y Y X 16
17 BCS BCS Remote I/O: Air Compressor Skid DONE RIO-7000A 03115 Note 11 Y Y X X 17
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator P = Permissive
Note 16: FCV will remain open for several seconds untill M = Modulate
pump and motor reach
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. design speed R = Reset X = Alarm
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features. Closing procedure to be defined. Stp= on
Note 17: Selection function to be provided Stop
MMI & HMIY = Yes
Note 4: Permissive to Start. Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due A=Activate
Note 18: Automatic Start/Stop by LIT-2001
Note 5: Permissive to Close. Note 11: C&E Matrix developed by Vendor to be included with this Master Document. to a major risk event in the facility.Safety Instrumented Function Level 2: Note 19: Refer to document PERLA.OF.DIEE.51001.SA "Alarms and Set Points List"
Platform shutdown due to a correctable major risk event in the platform.
MOC-0140.
CAMBIO PSL-9814 E IMPLEMENTACIÓN
DE VOTING 2oo3 PSL-0101B/0201B.
JUN-2018.
ESD/SIS Indications and Alarms
03118
03118
03119
03118
GSH-0101 03902
03902
03902
03902
03902
03902
ESDV9000
ESDV9200
XS-9005
XS-9205
XS-9405
XS-9000
XA-0103
XA-0101
XA-0102
XA-0105
XA-0104
CAUSE & EFFECT DIAGRAM
REMARKS: Note 1: Interlock provided for future Perla PS4 Installation. Note 6: Action linked to "AND" Operator. Note 12: Start-up Override to be provided. Note 15: Effect on Export Pipeline Subsea Valve to be defined by COMPANY
ABBREVIATIONS:
Note 2: Blowdown Header High High Pressure: PAH-1201 alarm Note 7: Start-Up Override to be provided. SDV to AUTO when pumps are running. Override time to be defined by operator C = Close
Note 16: FCV will remain open for several seconds untill pumpP =and
Permissive
motor reach
will be displayed and action will be taken by operator Note 8: Electric Heaters Auto Reset (when Temperature is restored). Note 13: BD System to be closed in case of Emergency. design speed. O = Open R = Reset
Note 3: Deleted Note 9: Interlock to be provided with Auto Reset features. Closing procedure to be defined. S = Start Stp= Stop
Note 4: Permissive to Start. Note 10: Deleted Note 14: Emergency Platform SD Level 1:Total facility shutdown due T = Trip
Note 17: Selection function to be provided on MMI & HMI A = Activate
Note 5: Permissive to Close. Note 11: C&E Matrix to be developed by Vendor. to a major risk event in the facility. Safety Instrumented Function Level 2: Note 18: Automatic Start/Stop by LIT-2001
M = Modulate
Note 19: MCC gas detectors shall
Platform shutdown due to a correctable major risk event in the platform. trip all generators through XS-9000 X = Alarm Y = Yes
NOT through XS-9005; XS-9205 or
MOC-0140.
CAMBIO PSL-9814 E IMPLEMENTACIÓN
DE VOTING 2oo3 PSL-0101B/0201B.
JUN-2018.