Controller
Commissioning, maintenance
and troubleshooting instructions
TABLE OF CONTENTS
—
17 First commissioning 23
Signage
A note clarifies instructions or other
NOTE information presented in this Reference Section 5 – Door signage.
document. Proper signs and labels shall be applied and maintained on the
Dimensions door per the following ANSI / BHMA standards:
ANSI/BHMA A156.10-2011: Standard for power operated
Unless otherwise specified, all dimensions are given pedestrian doors, paragraph 11, signage.
in both inches (") and millimeters [mm].
Maintenance: If signs have been removed, or
cannot be read, request that signs be replaced by
2 Product overview contacting local Dorma company.
Intended use Building codes and standards
The ESA drive motor assembly core components consist of ESA II controller wiring installation: observe applicable
a gearmotor with encoder, ESA II controller, and DC power national and local building codes.
suppply. This assembly controls door motion of the ESA series ESA II controller commissioning: observe following standard
of sliding doors. and any applicable national or local standards:
ESA II
controller Metallic doors must be grounded per national and
local codes.
Motor gearbox
Encoder
4
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
4 Technical data
Power supply Door functions
AC power 120 VAC ± 10%, 50/60 Hz Close
Fuse 6.6 amp, not replaceable Automatic
Power supply Permanent open
27 VDC, 2 amperes
external accessories Partial open
Power consumption, max. 250 watt Exit
Driving parameters
Parameter and description Units Default Min. Max.
inches/sec. 20* 4 22
Maximum opening speed
cm/sec. 51* 10 56
inches/sec. 12* 4 12
Maximum closing speed
cm/sec. 30* 10 30
1 9
[Opening accel.] Maximum distance for acceleration to opening speed. n/a 7
1 9
[Closing accel.] Maximum distance for acceleration to closing speed. n/a 7
1 9
[Decel. ramp open] Maximum deceleration ramp at end of door opening cycle. n/a 4
1 9
[Decel. ramp close] Maximum deceleration ramp at end of door closing cycle. n/a 4
inches/sec. 2 1 4
[Creep speed open] Maximum creep speed at end of door opening cycle.
cm/sec. 5 2.5 10
inches/sec. 2 1 4
[Creep speed close] Maximum creep speed at end of door closing cycle.
cm/sec. 5 2.5 9
Hold open time, Night/bank – Display value * 0.1 seconds 15* 15 600
[Delayed opening] Delayed opening after Night / Bank pulse was triggered. seconds 0 0 10
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 5
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
5 Door signage – sliding doors
ESA sliding doors are supplied with door sign decals to alert
and instruct pedestrian traffic in operation and function of door.
Method of activation determines combination of decals required.
Not all decals will be used in every application.
Safety signs are specified in ANSI A156.10, American National
Standard for power operated pedestrian doors, paragraph 11.
All swinging, sliding and folding doors 1
AAADM
American Association of Automatic
Door Manufacturers
ANNUAL COMPLIANCE
INSPECTION
INSPECT FOR AND
COMPLIES WITH ANSI
A156.10 ON:
DATE:______________
by AAADM Certified
Inspector
Number:___________
6
6
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
Automatic single slide door with signage for two-way traffic control
O SX SX O
1
1
6 3
2
4
ANNUAL COMPLIANCE
INSPECTION
4
INSPECT FOR AND
COMPLIES WITH ANSI
A156.19 ON
DATE: _____________
by AAADM Certified
Inspector
Number: __________
7
58” ± 5” 60” max.
36” min.
EXTERIOR INTERIOR
INTERIOR
SX Breakaway sliding door
O Fixed sidelight
BRE
AKO
UT
EXTERIOR
Automatic bi-part slide door with signage for two-way traffic control
O SX SX O
1 1
6 3 4
4 3
ANNUAL COMPLIANCE
INSPECTION
INSPECT FOR AND
COMPLIES WITH ANSI
A156.19 ON
DATE: _____________
by AAADM Certified
Inspector
Number: __________
7 2 2
58” ± 5” 60” max.
36” min.
INTERIOR
EXTERIOR
BRE UT
AKO AKO
UT BRE
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 7
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
6 Product description
ESA drive motor assembly ESA drive motor assembly
1. DC power supply
DC Power supply
35 VDC
120 VAC
BK
YE RD N 50/60 Hz
26
27
28
29
30
31
32
33
34
35
36
37
38
L
Gnd
+ 35VDC
Inhibit
ESA II controller
BK
BN
WH Encoder cable Motor cable
1 YE
GN
BN
BL
5 WH
8
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
7
—
DL2842-010
lock Presence 2 Presence 1 Emergency OFF
internal
switch
05/2017
Outputs Battery
DC signal DCW
Isolated relay Service backup
inputs interface
contacts
ESA II system block diagram
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
21
22
23
24
25
26
27
28
30
31
32
33
36
21
29
34
35
37
38
14
15
16
17
18
19
20
10
11
12
13
20
12
10
11
13
14
15
16
17
18
19
39
40
Reamstown, PA 17567
41
+
42
F: 717-336-2106
T: 717-336-3881
COM 1
Interconnection
DIP switch Programming
LON- adapter Dorma Handheld
interface
RJ45 socket
Service
Interface
Key
Key
Key Key
+ Brn + Brn
Service
Interface
Terminal blocks
Wire sizes ESA II Expansion module interconnect cable DX2889-002
Solid and stranded:
59” [1500] +/- 3/4”
26 - 16 AWG [0.14 -1.5 mm2]
Wht Wht
Stranded wire with ferrrule: Yel Yel
24 - 18 AWG [0.25 -1.0 mm2]
Wire strip length: 1/4" [7]
Screw size: M2
Screw head diameter: 5/32" [3.8] Grn Grn
(+) Brn (+) Brn
Screw torque: 2.2 in-lb [0.25 Nm]
10
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
9 ESA II electrical interface diagram
1 14 33 36 Program switches
45 Blk Gnd CLOSE
+35 VDC Power supply AUTO OPEN
DCW FST - Interface
39 Green Automatic
DCW
Battery
backup Brown Permanent Open
48 42
Interconnection ESA II EXIT ONLY
LON - adapter Red Exit
Motor OFF ON
Dorma
Handheld Encoder PARTIAL OPEN
Bottom view
45 Gnd
46 Signal B DCW interface
47 Signal A to ES 200
48 + 27 VDC 4 3/4” [120 mm] DC power supply
1 Close
2 Automatic Grn
3 Exit only Red Program Yellow – Inhibit
4 Partial open Wht switches
5 Permanent open Brn
6 Gnd Blk Black – Gnd
7 Night / Bank Red – +35VDC 6.6A Fuse – not replaceable
8 Gnd 3 pole plug
9 +27 VDC
10 Lock
11 Status ___ Locking
12 Unlock
13 Gnd
14 +27 VDC
Activation
15 Signal
16 Gnd external
17 +27 VDC Activation
18 Signal
internal
19 Gnd
20 +27 VDC
21 Receiver 2
22 +27 VDC Presence 2
23 Transmitter 2 (LED 2)
24 Gnd
25 +27 VDC
26 Receiver 1
+27 VDC Presence 1
27
28 Transmitter 1 (LED 1)
29 Gnd
30 Open source 1.5A Service
31 +27 VDC
32 Breakout-cutoff
33
Jumper if not used switch (optional) ESA drive motor assembly
34 Inhibit Yellow
35 Gnd Black DC power supply
36 +35 VDC Red
Motor encoder
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 11
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
10 ESA II Expansion module
12
ON
DIP switch
22 GND
23 Signal B DCW Interface to ESA II
24 Signal A
25 + 27 V DC
1 2 1 2
ESA II expansion Motor ESA II
ON ON
module DX2889 gearbox controller Power MUST be removed from ESA II controller
before changing DIP switch settings!
1 C OUT 1 Outputs
2 NO
ESA200 header assembly 3 NC
4 C OUT 2 Maximum
Mount ESA II expansion module against back wall of header 5 NO switching
6 NC current
approximately 12" [305] from end of motor gearbox.
7 C OUT 3 1A @ 30VDC
Power MUST be removed from ESA II controller 8 NO 0.5A @125VAC
9 NC 0.3A @ 60VDC
before installing module and connecting cable!
10 C OUT 4
11 NO
Use 3M™ industrial VELCROW® to secure module to header. 12 + 27 V D C
13 IN IN 1
14 GND
15 + 27 V DC
16 IN IN 2
GND DC inputs
17
18 IN +
IN - IN 3
19
12
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
11 ESA II user interface
A Overview
User interface SERV. button
rv.
SEL. button
Se
+ button
+
– button
2 3 4 7
7 segment display
ESA II LED 2 2
2 l.
controller
LED 1 1 5 6 Se
User
interface
–
Motor gearbox
Encoder
11
1 1 _ Sel.
2.1. Error – Displays a flashing "E" with error present.
Error codes can be accessed and acknowledged.
See Section 11 - C. 2 + Serv.
1 _ Sel.
2 Display flashes
3.1. Parameter – Display will show parameter codes as they
are scrolled, and will display selected parameter
(Parameter "C" is closing speed). See Section 11 - D.
2 + Serv.
3 1 _ Sel.
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 13
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
11 ESA II user interface – continued
C. Accessing error codes
Check controller for error codes before powering off
2 + Serv.
controller.
Power off resets all error codes. No error history will
be displayed when controller is powered back on.
Display
Error description
code
Obstruction
1.1 Error present. Display will flash off and on.
Safety beam
_
Incremental encoder
2 1 Sel.
Backup battery test
2.1 Last occuring error will be displayed error
(example is 8 "Breakout operated").
System - CPU, RAM,
2.2 To return to press . Cycle power
Sel. EEPROM, Relay test
If error no longer present, display will clear.
If error still present, error display will continue to flash. Breakout operated
Fixing error with error display present will remove error
display. Learning cycle
parameter error
After 20 seconds, display will revert to .
If error still present, will flash.
Motor fault
in error memory.
DCW
Press to return to menu, or it will revert to this
Sel.
menu after 20 seconds.
Press again to exit menu, or it will revert to operation
Sel.
mode display after 20 seconds.
14
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
D. Accessing parameters
2 + Serv. Menu-
code Menu code description
Error
display
codes
1 1 _ Sel.
Parameter
setting
Menu
1.1 Press to access menu. Parameter code description codes
Sel.
code
See Section
E.
2 + Serv.
Not available
1 _ Sel.
2 Locking mode (Interlock type) 0-3
+
2.1 Press or to scroll through menu to desired para-
meter (hold open time shown as example). Backup battery operation 0-3
3 1 _ Sel.
Sidelight function 0, 1
3.1 Press to access setting codes for parameter – current Opening speed 0 - 9, A - d
Sel.
setting will be displayed (example is "3", which is a 5
second hold open time).
Closing speed 0-4
2 + Serv.
1 _ Sel.
4
+
4.1 Press or to scroll through parameter setting
codes to desired setting (example is "5", which is a 10
second hold open time).
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 15
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
11 ESA II user interface – continued
E. Parameter settings – codes
Not available Hold open time – in seconds
1.5 15
2.5 20
5 25
EXIT ONLY "OFF"
8 30
EXIT ONLY "OFF" and "ON" >30 seconds
via Dorma
Locking device type 10
handheld
No locking device programmer
Sidelight function
Bistable – locking device remains in position
it was in when power was removed. Stop
Bistable – locking device remains in position
it was in when power was removed. Closing cycle
With status signal contact. Opening speed – inches / second
Monostable – fail safe.
4 18
Locking device is locked with power on.
With status signal contact. 6 20
Battery mode
8 22
No battery
10 24
Emergency closing
12 26
Emergency opening
14 28
Battery emergency mode
4 10
2.5 20
6 12
5 25
8
8 30
>30 seconds
via Dorma
10
handheld
programmer
16
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
12 Operating instructions – program switch panel
1.1 Program switch panel is installed in one of the
vertical door jams. Panel contains 3 switches with
following
functions: CLOSE
AUTO OPEN
I O II
Switch Positions
EXIT ONLY
Main Auto Close Open OFF ON
Door operation
Program panel
EXIT ONLY – OFF
switch setting 1
PARTIAL OPEN – OFF
When external or internal activation signal
is received
door will open to full opening width unless
Partial Open switch is ON
Main switch:
AUTO Once door fully open, Hold open time Exit Only switch:
is initiated with no activation, presense or OFF Internal and external activation sensors
safety beam sensors (optional) activated. both active.
5. Simultaneously* set: When main switch is set to OPEN position and Partial
Partial Open switch to ON Open switch is ON, partial open position is not
recognized – door will move to full open position.
Main switch to AUTO:
Dorma Handheld can be used:
*within 1 sec. of each other
For adjustment of partial open width.
6. Door stops, then closes. To disable setting partial open width by program switch
panel. Partial open width setting can only be made via
ESA II controller stores partial open width Dorma Handheld.
position when main switch set to AUTO. See Appendix – Section B.
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 17
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
14 115 VAC power connection at header
Work on 115 VAC electrical equipment and wiring
must be performed only by qualified electricians!
1.1 Customer 115 VAC wiring enters opening on right side Drive motor assembly
of ESA header and terminates in connector at DC power
supply (see 5.1).
Maximum wire size: 12 AWG [4 mm2]. Solid wire
recommended.
DC power
Maximum branch circuit protection: 15 amperes. supply
Install label with branch circuit protective device
panel and protective device identification numbers
ESA header assembly
near, or on ESA header 115 VAC wiring entrance.
1 Entrance for 115 VAC wiring
+27V
35V
OFF
0V
controller
0V
34 36
37
26 28 30 32 38
25 27 29 31 33
DC power supply
plug and cable
3
0V
0V
1 3 5 7
2 4 6 8
Program switch
panel plug and cable
18
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
Electric shock hazard! 115VAC disconnect to branch DC power cable DC power supply
circuit supplying power to ESA must be OFF prior to
start of and during electrical wiring installation!
5.1 Pull out 115 VAC connector with strain relief from 115 VAC connector
connector attached to DC power supply. 115 VAC connector with strain relief
attached to DC
power supply
5
Bottom section
7
10.1 Reinsert 115 VAC connector with attached strain relief DC power
into connector attached to DC power supply. supply
Spring tension
adjustment
Full turns of
Door width Maximum Spring
spring adjuster +
(interior) door weight size
ITS 96
-
2' - 6" 100 8
Clockwise turns increase spring tension.
3' - 0" 125 15 2
3' - 6" 150
4' - 0" 175
-0 º
7º º -0 º
0
12
45º
20
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
5.1 Open breakout assembly to 90º.
Deadstop helps to prevent damage to breakout
assembly by limiting its travel when breakout is
Sweep range 120° - 0º
operated.
Adjust to 90°
Latch range 7° - 0º
Deadstop
block
7.1 Adjust sweep valve for closing speed from 90° to latch
check (7°).
-
7.2 Adjust latch valve for closing speed from 7° to 0°. +
Sweep
3 mm
hex key
-0 º 0 º
7º -
0º
12
Latch
3 mm
hex key
-0 º 0 º
7º -
0º
12
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 21
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
16 Installation requirements prior to commissioning
1.1 ESA door system fully installed, including glass.
22
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
17 First commissioning
Insure areas around door and in door travel path are
ESA II
+27V
free of personnel and obstacles!
controller
0V
0V
0V
1.1 Verify Program switch plug is disconnected from its
receptacle on ESA II controller.
1 3 5 7
1.2 Verify DC power supply plug is disconnected from its 2 4 6 8
receptacle on ESA II controller.
Program switch
panel plug and cable
1
2.1 Presence 1 and 2 test jumper wiring (may be factory
installed): ESA II controller
Presence 2 – jumper at 21 and 23. Power
+27V
STOP
+27V
+27V
+27V
OFF
35V
Presence 1 – jumper at 26 and 28.
0V
0V
0V
2.2 Breakout jumper at terminals 32 and 33: 21 23 26 28 3233
3
4.1 Turn customer 115 VAC power to ESA II ON.
4.2 Plug DC power supply plug into its receptacle on ESA II STOP Power
+27V
+27V
P/O ESA II
35V
OFF
0V
controller.
0V
controller
4.2 As soon as DC power supply has been switched on,
ESA II controller powers up and security checks are
performed.
26 28 30 32 34 36 38
25 27 29 31 33 35 37
DC Power supply
4 cable and plug
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 23
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
18 Perform learning cycle
Activation sensors are disabled during learning cycle. 2 + Serv.
If an interruption or fault should occur, learning cycle
is terminated and must be restarted.
2 1 _ Sel.
3.1 Door will start an opening cycle:
Flashes
twice
4 1 _ Sel.
0V
0V
controller
7.1 Reinstall program switch panel plug.
9 13
7.2 Set program switch panel main switch to AUTO.
7.3 Go to Section 19, Set door parameters. 1 8
7 Program switch plug and cable
24
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
19. Set door parameters
12 26
14 28
16 30
6 12
2.5 20
5 25
8 30
>30 seconds
10 via Dorma
Handheld
4.1 Night/bank hold open time
Set night/bank hold open time parameter , if used.
Night/bank hold open time – in seconds
Factory default : 1.5 sec.
1.5 15
2.5 20
5 25
8 30
>30 seconds
10 via Dorma
Handheld
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 25
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
19. Set door parameters – continued
1.1 Parameter backup battery mode
Backup battery mode
Factory default : No backup battery installed.
No backup battery installed.
if backup battery installed set parameter to
applicable value. Emergency closing
Emergency opening
3
26
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
21 Reset controller to factory settings
If controller has been commissioned, record ESA II controller
parameter settings, including those accessed by STOP Power
+27V
+27V
+27V
+27V
OFF
35V
Dorma handheld programmer, prior to controller
0V
0V
0V
reset!
1.1 Pull out DC power supply plug from ESA II controller 21 23 26 28 32
socket.
4.1 Press and hold in Serv. button. While holding in Serv. + Serv.
2
button, reconnect DC power supply plug.
+27V
+27V
+27V
35V
0V
0V
0V
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 27
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
22 ESA II expansion module – DCW address 48
Additional functions available with expansion module using
DCW address 48: Power
STOP
P/O ESA II
+27V
+27V
35V
OFF
0V
A –Secondary closing edge sensors controller
0V
B –Panic closing function
34 36
C –Door status contacts
37
26 28 30 32 38
System must be disconnected from DC power supply 25 27 29 31 33
while DCW address of expansion module is set!
DC power supply
plug and cable
1.1 Remove DC power supply plug and cable from its socket 1
on ESA II controller.
DIP switch
DCW address 48 DCW address 49
1 2 1 2
ON ON
System must be disconnected from DC power supply
while DCW address of function module is set!
2
A Secondary closing edge sensors
3.1 If a person enters, or an object is placed in detection
range of secondary closing edge presence sensor:
1. While door is open: door will remain open until person
or object is no longer detected. Once hold open time
expires, door will close.
Leading edge
2. Door in process of closing: door will immediately stop
and remain stopped until person or object is no longer
detected. Door will then immediately continue closing
cycle.
Secondary closing edge
IN functions settings can be changed using Dorma IN1 IN2 IN3 IN4
+27V
+27V
Handheld.
0V
0V
5.2 Press panic closing switch to close door: IN1 IN2 IN3 IN4
+27V
+27V
Door closes immediately (will stop an opening cycle).
0V
0V
Door locks in closed position. + +
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 29
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
22 ESA II Expansion module – DCW address 48 – continued
C Door status contacts
6.1 Door status contact 1 (OUT-1):
OUT1 OUT2 OUT3 OUT4
Default is "Door open".
P/O
Relay contact is closed when door: ES200
1 2 3 4 5 6 7 8 9 10 11 12
Performs an opening cycle.
Is in "open position".
Performs a closing cycle. OUT-4
6.2 Door status contact 2 (OUT-2): N.O.
+27V
35V
A – Airlock function.
OFF
0V
controller
0V
37
1.1 Remove DC power supply plug and cable from its socket 26 28 30 32 38
25 27 29 31 33
on ESA II controller.
1
DC power supply
plug and cable
DIP switch
DCW address 48 DCW address 49
1 2 1 2
ON ON
System must be disconnected from power supply
while DCW address of function module is set!
2
30
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
23 ESA II Expansion module – DCW address 49 – continued
A Airlock function
3.1 Disabling airlock function (IN-3)
As soon as airlock function is activated while door is still
closed, both internal and external activation sensors are
blocked.
A door opening or closing cycle cannot be interrupted.
3.2 Airlock door status 1:
OUT 2 contact closed when door 1 is in "closed" position.
Contact disables door 2 (IN 3) during opening cycle of
Door 1 Door 2
door 1.
Internal and external activation sensors are deactivated. 3
Locking function is disabled as soon as door is closed.
3.3 Airlock door status 2:
Airlock door status function settings can be changed
OUT 2 contact closed when door 2 is in "closed" position.
using Dorma Handheld.
Contact disables door 1 (IN 3) during opening cycle of See Appendix – Section B Special Function Parameters.
door 1.
Internal and external activation sensors are deactivated.
Locking function is disabled as soon as door is closed.
4.1 All airlock function connections utilize direct wiring
(no bus connection).
OUT1 OUT2 OUT3 OUT4 IN1 IN2 IN3 IN4 OUT1 OUT2 OUT3 OUT4 IN1 IN2 IN3 IN4
+27V
+27V
+27V
+27V
0V
0V
0V
0V
+ + + +
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Jumper Jumper
WH
WH
OUT-2
BN
GN
BN
GN
YE
YL
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 31
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
24 Functional test
A Activation, presence and safety beam sensors
32
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
24 Functional test – continued
B Door or door and sidelight breakout
1
2.1 ESA300 with breakout sensors.
1. Walk toward SX door to activate a door opening cycle. ESA300 full breakout
2. Push SX door in breakout direction during opening cycle.
Breakout width
Break kout
out Brea
2
Breakout
beam
See Section 25 - F for breakout beam wiring diagram.
Brea
kout kout
Brea
3
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 33
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
C Monitoring of opening and closing forces
+27V
STOP
+27V
+27V
+27V
OFF
35V
1.1 For these test, bypass presence sensor inputs by
0V
0V
0V
installing jumpers at ESA II controller terminals 21 and
23, and at terminals 26 and 28. 21 23 26 28
20 20 24 25 27 29 30 31 34 36
32 33
DC power
Jumper Jumper supply plug
21 - 32 26 - 28
2.1 Door closing force measurement – force limitation during 1 Presence 2 Presence 1
door closing cycle
1. Walk toward door to activate a door opening cycle.
34
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
23 Functional test – continued
D Autolock assembly
Bipart door shown
Autolock assembly
Autolock assembly
Double hook
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 35
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
24 Functional test – continued
E Autolock – fail safe assembly
Bistable
2.1 Autolock –fail-safe installed and wired.
Power is removed: locking device
Operation: remains in its current position.
Electric bolt lock requires +27VDC to move bolt to Bistable
"lock" position. Power is removed: locking device
remains in its current position.
1. Door is closed. In standby / AUTO mode. With status signal contact.
2. Door activation sensor receives signal. Monostable – fail safe or fail secure,
depending on lock type:
3. +27VDC is removed from lock solenoid. Magnetic lock ( by others)
4. Solenoid deenergizes: DORMA fail safe electric bolt lock
assembly.
Bolt lowers to "unlock" position". With status feedback contact.
Switch opens (unlock position). 1
5. Door opens.
36
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
EXIT ONLY
OFF ON OFF
PARTIAL OPEN
OFF ON OFF
0V
0V
0V
1 2 3 4 5 6 7 8
1 3 5 7
2 4 6 8
Night / Bank
switch
3
4.1 Door will unlock and open at set opening speed .
4
5.1 Night-bank hold open time expires.
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 37
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
24 Functional test – continued
G Battery backup functional test overview
Emergency opening
If battery backup is provided, Parameter must
be set to 1, 2, or 3 to prevent damage to door. Battery emergency mode
35V
controller
OFF
35
0V
OF
See Section 19 – Set door parameters for setting of 37 38
Backup
battery backup operation for door. battery
receptacle
4.1 Following loss of 115 VAC power, the following functions Operator interface
will be monitored: 2 + Serv.
Door operation.
Operator interface; display and LEDs 1 and 2.
1 _
Sel.
4
Customer
5 115 VAC wiring
38
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 39
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
23 Functional test – continued
I Battery backup functional test – setting Emergency closing
Set parameter A to – Emergency closing. See Section 11-D – accessing parameters.
40
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
J Battery backup functional test – setting Emergency opening
Set parameter A to –Emergency opening. See Section 11-D – accessing parameters.
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 41
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
25 Wiring diagrams
A Program switch panel
Grn
Blk
Blk
CLOSE
AUTO OPEN
I O II Brn
EXIT ONLY
OFF ON
PARTIAL OPEN
OFF ON
Blk
Red
ESA II
+27V
controller
0V
0V
0V
Term. Wire
Switch Function
1 3 5 7 No. Color
2 4 6 8 2 Grn Main AUTO Wht
Wht
Brn
Blk
Red
Grn
6 Blk Ground
Program switch
panel plug and cable
42
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
B Autolock assembly C Autolock – fail safe assembly
+27V
+27V
0V
0V
9 10 11 12 13
9 10 11 12 13
Wht
Brn
Grn
WHT
Wht
Red
Blk
Cable supplied Red
Cable supplied with switch
BRN Cable supplied
with solenoid Cable supplied
with solenoid with switch
Grn
Brn
Red
Unlock
Lock
Wht
BRN WHT
Red Blk
Lock
Wht
Microswitch
DX0931-010 Bolt position Solenoid wiring
switch
Double hook Solenoid Red 10
Blk
Autolock – fail safe assembly
DS3586-010 Blu
Autolock carrier bracket
Wht 9
Autolock assembly DX900-010
ATTENTION
Bistable
interlock with
status signaling
contact (NO)
ESA II control
lock setting
L=2
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 43
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
25 Wiring diagrams– continued
D Breakout switch – single door or panel E Breakout switches – double doors or panels
STOP STOP
30 31 32 33 30 31 32 33
ESAII ESAII
controller controller
Blk
Red
Blk Red
Red Blk
Wire nut
Magnetic Magnetic
switch Red switch
Red Red
assembly assembly
Blk Blk Blk
DS1234-01 DS1234-01
32 33 32 Wire nut 33
Blk Red Blk Red Blk Red
+27VDC
Recv 2
Trans 2
1 Double beams Single beam
Breakout
Gnd
N.O. relay energizes on N.C. relay de-energizes on
2
detection detection 20 21 22 23 24 32 33
Standard operating range: Reduced operating range:
3
15' 10'
4 Test Default
Wht
Brn
Red
Blk
NC Brn
5 4 3 2 1
Blue Blk ON NO
Breakout beam (optional) Wht
3
Beam B COM
DO NOT CUT CABLES! 1 2 3 4 AC/DC Blk
4 3 2 1
12-24V Red
Cable by BEA
LED Beam B
44
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 45
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
25 Wiring diagrams – continued
G. Activation / safety sensors – BEA IXIO-DT1
Presence 2
Presence 1
Activation
Activation
external
internal
Reference BEA IXIO-DT1 User
Guide for sensor settings.
+27V
+27V
+27V
+27V
+27V
+27V
35V
OFF
made to sensor settings: ESA II controller
0V
0V
0V
0V
0V
Safety contact (IR output):
Energ/NC
Test output: ON
14 16 18 20 22 24 26 28 30 32 34 36
+27VDC 15 17 19 21 23 25 27 29 31 33 35
+27VDC
+27VDC
Recv 2
Trans 2
Signal
Gnd
Gnd
BEA IXIO-DT1 – external
12-35 Red 14 15 16 20 21 22 23 24
Power
VDC Blk
Wht Activation
Activation* Presence 2
Grn external
Safety Brn
Blu
Brn
Red
Blk
Grn
Wht
Pur
+27VDC
+27VDC
Recv 2
Trans 2
Signal
Gnd
Brn
Red
Grn
Wht
Blk
Pur
Cable by BEA
46
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 47
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
25 Wiring diagrams – continued
I. Activation / safety sensors – Optex X-Zone T and i-oneX T
Presence 2
Presence 1
Activation
Activation
external
internal
Reference Optex X-Zone T
installation manual for DIP
switch settings and sensor
setup.
Reference Optex i-oneX T STOP Power
+27V
+27V
+27V
+27V
+27V
+27V
35V
OFF
ESA II controller
0V
0V
0V
0V
0V
installlation manual for DIP
switch settings and sensor
setup.
14 16 18 20 22 24 26 28 30 32 34 36
15 17 19 21 23 25 27 29 31 33 35
+27VDC
+27VDC
+27VDC
Recv 2
Trans 2
Signal
Optex X-Zone T – external
Gnd
Gnd
Optex i-oneX T– external
1
12-30 Gry 14 15 16 20 21 22 23 24
Power 2
VDC Gry
3 Wht Activation
Activation* Presence 2
4 Yel external
5 Wht/Blk
Safety 6 Yel/Blk
Wht/Blk
Yel/Blk
(+) 7
Red
Test input 8 Blk
Red
Gry
Yel
Wht
Gry
Blk
(-)
+27VDC
+27VDC
Recv 1
Trans 1
Signal
Gnd
Optex i-oneX T– internal
1
12-30 Gry 17 18 19 25 26 27 28 29
Power 2
VDC Gry
3 Wht Activation
Activation* internal Presence 1
4 Yel
5 Wht/Blk
Safety 6 Yel/Blk
Yel/Blk
Wht/Blk
(+) 7
Red
Test input 8 Blk
Red
Gry
Yel
Wht
Gry
Blk
(-)
48
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 49
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
26 Maintenance
Startup and yearly system checks
Battery backup:
Check charge level: 2 Battery backup
2 Dorma Handheld- Every three years
Diagnosis- Battery
Operating Hrs
Header end stops:
End stop
Check location and
3 functionality (door At every service check
contacts both end
stops at same time)
Header assembly
Toothed belt
Track rail
5
50
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
Activation -
presence sensor
Sliding
Sliding
Top holding beam door
door
(if required)
Holding beam
cylindrical heads
7
Maintenance intervals – can be adjusted with Dorma Handheld.
Reference: Appendix, Section B.
Activation and presense sensor
Diagnosis parameter 22 (Maintenance interval.):
Enter a time interval in months until next scheduled
maintenance.
Infrared lens
Diagnosis parameter 27 (Maintenance cycle):
8
Enter number of opening cycles until next schedule
maintenance.
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 51
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
27 Troubleshooting
Prior to performing any maintenance, disconnect the DC Power supply plug and the Backup battery plug from ESA II controller.
Fault Possible causes Remedy
Check circuit breaker supplying power
115 VAC power to controller is off.
to DC power supply. If OFF, turn ON.
Remove DC power supply plug to
controller and check for 35VDC.
Defective DC power supply (internal fuse If power not present, fuse may be
may be blown). blown (not interchangeable) or power
supply is defective.
Controller will not power up. Replace DC power supply.
Male connector (with 115 VAC power
wiring) to DC power supply not firmly Check 115 VAC connector installation.
mated to female connector on supply. Check 115 VAC connector wiring.
115 VAC wiring in connector loose.
35VDC is present to controller but
Defective controller controller will not power up.
Replace controller.
Main program switch set to OPEN. Set switch to AUTO or CLOSE.
Adjust sensor pattern away from face
Presence detection from sensor.
of door.
Close the door/panel to operating
Door remains open, will not close. Door breakout.
position.
Check breakout magnet and reed
Breakout switch wiring.
switch on door and header.
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 53
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
APPENDIX
A A156.10_sensors – sliding doors
Content references portions of ANSI / BHMA A156.10.
Refer to this standard, available through BHMA, for
Sliding Sliding
additional information. Reference numbers in brackets
door door
() are paragraph numbers from the standard.
Standard material reprinted with BHMA permission.
** If 43" activating zone length is not practical due to Two - way traffic
physical or environmental conditions, it shall be CL
permissable to be reduced to 30", along with an additional
sign, visible from side the zone has been reduced on,
stating "AUTOMATIC CAUTION DOOR". See Section 5.
Minimum
One-way traffic – (Reference 8.3.3) activating
detection
2.1 Sliding doors used for one-way traffic A
30" zone
Shall be provided with a secondary activating zone [762 mm]
on side not intended for approach.
Slide
2.2 Secondary activating zone minimum width "B" door Max.
8" [204 mm]
Equal to width of clear opening "B" measured at 8" 5" [127 mm]
perpendicular from face of closed door(s).
8" [204 mm] 5" [127 mm]
2.3 Secondary activating zone minimum length "C" Max.
Fixed One - way traffic
Shall extend a minimum of 24" from face of door panel Secondary activating C
and be effective to within 5" from face of door 30" detection zone
measured at center of door opening. [762 mm]
A Non-approach side
2.4 Sensor shall be deactivated when door(s) are within
6" of fully closed position. Minimum
activating
detection
zone
B
2 Reference Fig. A-13
54
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
Bottom location:
Maximum inactive presence area 6" [152 mm] to 28" [711 mm]
28" [711 mm]
Note: Detection zones depicted in the A A A = Maximum distance to activating detection zone
drawing are approximate (not to scale) B B
C B = Maximum distance to presence detection zone
and are for illustration purpose only
C = 43"
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 55
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
APPENDIX
B Parameters – Dorma Handheld
Parameter detail can be found on subsequent pages.
Also refer to DORMA Handheld manual.
56
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
Configuration parameters
Ref- Description Settings & default
No.
Installed locking device:
-No locking device -none
-Bistable locking device -bistable
1 -Bistable locking device with -bistable N.O.
feedback contact (N.O.) contact
-Monostable locking device, fail -monostable
safe design
Number of doors
-single door
2 -Single door
-double door
-Double door
Door weight in pounds determined
3 (.......)
during learning cycle
Program switch (PGS) type -mech.
4
-ESA-PGS
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 57
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
APPENDIX
B Parameters – Dorma Handheld – continued
Special function parameters Special function parameters
Ref. Description Setting Ref. Description Setting
No. No.
Door status 1 -off Airl. door status 2 -off
Potential-free contact OUT 1 at -door open Potential-free contact OUT 3 at -door open
ESA II expansion module (addr. 48): -door closed ESA II expansion module (addr. 49): -door closed
1
Closes when door leaves "open" -malfunction 6 Sends an opening pulse to door 2 -malfunction
position (defaut setting). -closed & -locked (IN1) at end of closing cycle (pulse -closed & -locked
-door locked signal relaying). -door locked signal
Door status 2 -off -disable airlock
Potential-free contact OUT 2 at -door open Panic closing
ESA II expansion module (addr. 48): -door closed Adjustment of panic closing
2
Closes when door leaves "closed" -malfunction function. Door closes immediately
position (default setting). -closed & -locked following signal. Detectors, light -off
7
-door locked signal barriers and blocking recognition -on
Diagnosis Diagnosis
Ref. Description Setting Ref. Description Setting
No. No.
Current error Error DCW list
1 System indicates current error. messages "ENTER" displays first DCW component
0 - 31 (e.g. 2.48).
Error log 1 to error log 9 5 2= FST module (escape route sliding door) LIST ->
Displays errors that have occurred. 48 = ESA II expansion module with address OO
2 (....)
Select "ERROR" to go to error description. 49 = ESA II expansion module with address O1
Select "HELP" to go to help display.
Delete errors Rech. batt. voltage
3 Command -> Measures voltage of rechargeable battery (...) * 0.1V
Press "ENTER" to delete error log. 6
pack (basic module)
DCW reset
4 Press "ENTER" to delete DCW list in Command -> LON adapter r/o
order to delete former DCW components. 7 This interface is used for data transfer to -off
PC via LON. -on
58
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
Diagnosis Diagnosis
Ref. Description Setting Ref. Description Setting
No. No.
Test cycle mmyy
Installation date
Press "ENTER" to start test cycle. 20 (1110 =
Test cycle is designed to detect Date of installation (month year)
Nov. 2010)
malfunctions in the door's driving
mmyy
phase. Last maintenance
21 (1110 =
The door moves at continuous speed. Last maintenance date
Nov. 2010)
The system indicates the current
speed, which decreases in the Maintenance int.
event of a malfunction. Adjustment of time interval until next
8 The handheld creates a table and Command -> maintenance: (0 ... 60)
lists areas where the door moved at Installation date is required mon
22
reduced speed. Enter maintenance interval (mon =
Set program switch to OFF and Enter maintenance date after service months)
move door manually to indicated under menu item "Last maintenance"
position in order to check it (See in order to reset display.
handheld display "Cur door position"). SID no.
The test level is individually 23 Number is used to identify the respective ( ... )
adjustable. system and installation location.
System no.
18 ( ... )
Displays system number.
DORMA prod-No.
19 ( ... )
DORMA production number
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 59
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
APPENDIX
B Parameters – Dorma Handheld – continued
Diagnosis Diagnosis
Ref. Description Setting Ref. Description Setting
No. No.
AUTOMATIC
*Functions referenced in 32 through 36 not used in deactivated
40 Displays input status of main program
ESA II version. activated
switch while set to AUTOMATIC mode.
Service module EXIT ONLY
deactivated
Enabling/disabling of service module at 41 Displays input status of EXIT ONLY
activated
basic module. program switch while set to ON mode.
-To enable service module: enable
1. Adjust "enable" PARTIAL OPEN
deactivated
42 Displays input status of PARTIAL OPEN
2. Perform upload activated
program switch while set to ON mode.
3. Remove service tool
PERMANENT OPEN
4. Wait for 30 seconds deactivated
32* 43 Displays input status of main program
The service module is now enabled. activated
switch while set to OPEN mode.
-To disable service module: disable
1. Adjust "disable" Key switch NB
deactivated
2. Perform upload 44 Displays status of key switch for Night /
activated
Bank function
3. Remove service tool
4. Wait for 30 seconds Light barrier 1 deactivated
45
Displays status of light barrier 1 activated
The service module is now disabled.
System now only indicates error list. Light barrier 2 deactivated
46
Displays status of light barrier 2 activated
Original settings
Only when program switch is Emergency Stop
deactivated
set to CLOSE and when door is 47 Displays status of Emergency Stop
activated
in "closed" position. pushbutton
33* Press "ENTER" to reset system to original Command -> Sec. closing edge 1
deactivated
settings. 48 Secondary closing edge 1, indicates status
activated
The procedure has been completed when at ESA II expansion module.
8 on basic module display blinks twice.
Sec. closing edge 2
Check parameters P, A, r. and L. at basic deactivated
49 Secondary closing edge 2, indicates status
module. activated
at ESA II expansion module.
Learning cycle Main closing edge
Only when program switch is set deactivated
50 Main closing edge, indicates status at ESA
to CLOSE and when door is in activated
II expansion module.
34* "closed" position. Command ->
Press "ENTER" to start learning cycle. Panic closing 1
deactivated
The procedure has been completed when 51 Displays status of panic closing input at
activated
8 on basic module display blinks twice. ESA II expansion module (addr. 48).
60
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
Diagnosis
Ref. Description Setting
No.
Disable Airl.inp.
deactivated
56 Displays input status to disalbe the airlock at
activated
ESA II expansion module (addr. 49).
Status out (1 - 4)
deactivated
57 Displays status of respective output at
activated
ESA II expansion module (addr. 48).
Airlock out (1 -4)
deactivated
58 Displays status of airlock output at ESA II
activated
expansion module (addr. 49).
SST-Out 1
Displays status of relay output for breakout deactivated
59
sliding door (SST) at DIN 18650 function activated
module.
no error
Error 4 diagnosis HSK error
Displays error message 4 in detail. NSK 1 error
60
(NSK = secondary closing edge, HSK = NSK 2 error
main closing edge, LS = light barrier) LS 1 error
LS 2 error
Error message
deactivated
61 Displays error message (status, airlock, or
activated
DIN 18650 function module).
Prog. BM
not OK
62 Displays current processor adjustment for
OK
basic module.
Ambient temp.
63 ( .. ) ºF
Displays ambient temperature.
Motor temp.
64 ( .. ) ºF
Displays motor temperature.
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice 61
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—
APPENDIX
C BEA Microcell One
1.1 Set operation of safety beams with DIP switches in BEA control box DIP switch settings
control box:
DIP ON
When using a single set of beams, connect beams to OFF
Sw.
Beam A connector and set DIP sw. 1 to "OFF". 1 Double beams Single beams
If Microcell is connected to a safety circuit of an
N.O. N.C.
automatic door, it is recommended to place DIP sw. 2 2
Energize on detection De-energize on detection
to "OFF" position, and use the normally closed circuit
(terminals 3 and 5). Standard operating range Reduced operating range
3
15' 10'
4 Test Default
ON
1 1 2 3 4
4 3 2 1
One or both LEDs are ON: corresponding beam (s) is
interrupted. NC
5 4 3 2 1
Neither LED illuminated: there is a power problem.
ON NO
Beam B Relay COM
1 2 3 4 AC/DC
4 3 2 1
12-24V
LED Beam B
2
62
DORMA USA, Inc. 1 Dorma Drive, Drawer AC T: 717-336-3881 Subject to change without notice
DL2842-010 05/2017 Reamstown, PA 17567 F: 717-336-2106
ESA II CONTROLLER COMMISSIONING, MAINTENANCE AND
TROUBLESHOOTING INSTRUCTIONS
—